DSE 7420 Installation Instructions
Text of the manual
ACCESSING THE FRONT PANEL CONFIGURATION EDITOR.
•
Ensure the engine is at rest and the module is in STOP mode by pressing the Stop/Reset
button.
•
Press the Stop/Reset
and Info
buttons simultaneously.
•
If a module security PIN has been set, the PIN number request is then
shown :
•
Press the
button the first digit will flash to enable the pin to be entered.
•
Press
(up) or
(down to adjust it to the correct value)
•
Press
(right) when the first digit is correctly entered. The digit you have just entered will now
show ‘#’ for security.
•
Repeat this process for the other digits of the PIN number. You can press (left) if you need to move
back to adjust one of the previous digits.
•
When
is pressed after editing the final PIN digit, the PIN is checked for validity. If the number is
not correct, you must re-enter the PIN.
•
If the PIN has been successfully entered (or the module PIN has not been
enabled), the editor is displayed :
EDITING A PARAMETER
•
Enter the editor as described above.
•
Press the
or
to cycle to the section you wish to view/change. Then press
or
to cycle to the parameter within the section you have chosen.
•
To edit the parameter, press
to enter edit mode. The parameter begins to flash to indicate that
you are editing the value.
•
Press the up or down buttons to change the parameter to the required value.
•
Press
to save the value. The parameter ceases flashing to indicate that it has been saved.
•
To exit the editor at any time, press and hold the
or
button.
D E E P S E A E L E C T R O N I C S
7 4 2 0 I NST AL L AT I O N I N ST RU CT I O N S
053-088
ISSUE 2
TYPICAL WIRING DIAGRAM
A larger diagram is available in the operators manual.
Deep Sea Electronics Plc.
Tel:+44 (0)1723 890099
Fax: +44 (0)1723 893303
Email: [email protected]
Web: www.deepseaplc.com
Deep Sea Electronics inc.
Phone: +1 (815) 316-8706
Fax: +1 (815) 316- 8708
TOLL FREE (USA only) : Tel: 1 866 636 9703
Email: [email protected]
Web: www.deepseausa.com
NOTE: When the editor is visible, it is automatically exited after 5 minutes of inactivity to
ensure security.
NOTE: The PIN number is automatically reset when the editor is exited (manually or
automatically) to ensure security.
NOTE: More comprehensive module configuration is possible using the 86xx series PC
configuration software. Please contact us for further details
NOTE: The contents of the tables overleaf may differ depending on the actual module
configuration.
DIMENSIONS AND MOUNTING
For flat surface mounting in a Type 1 enclosure.
DIMENSIONS
240.0mm x 181.1mm x 41.7mm (9.4” x 7.1” x 1.6”)
PANEL CUTOUT:
220mm x 160mm (8.7” x 6.3”)
Front Panel Configuration Editor
Section
Parameter as shown on display
Values
Display
Contrast
53%
Language
English, others.
Current Date and Time
hh:mm
Timers
LCD Page Timer
5m
Scroll Delay
2s
Engine Pre Heat Timer
0s
Engine Crank Duration
10s
Engine Crank Rest Time
10s
Engine Safety On Delay
10s
Engine Smoke Limiting
0s
Engine Smoke Limiting Off
0s
Engine Warm Up Time
0s
Engine Cool Down Time
1m
Engine Speed Overshoot Delay
0s
Engine Failed To Stop
30s
Battery Under Voltage Warning Delay
1m
Battery Over Voltage Warning Delay
1m
Return Delay
30s
Generator Transient Delay
0s
Mains Transient Delay
2s
Mains transfer time
0.7s
Mains
Mains Under Voltage Alarm
184v
Mains Over Voltage Alarm
277v
Mains Under Frequency Alarm
45Hz
Mains over Frequency Alarm
55Hz
Mains Transient Delay
2s
CT Primary
600A
CT Secondary
5A
Mains kW Rating
345kW
Mains kVar Rating
258kW
Generator
Under Voltage Shutdown
184v
Under Voltage Pre-Alarm
196v
Nominal Voltage
230v
Over Voltage Pre-Alarm
265v
Over Voltage Shutdown
277v
Under Frequency Shutdown
40Hz
Under Frequency Pre-Alarm
42Hz
Nominal frequency
50Hz
Over Frequency Pre-Alarm
54Hz
Over Frequency Shutdown
57Hz
Full Load Rating
500A
kW Overload Trip
100%
Delayed Over current
Active
Delayed Over Current
100%
AC System
3 Phase 4 Wire
CT Primary
600A Power Cycle After Exit
CT Secondary
5A Power Cycle After Exit
Short Circuit Trip
200%
Earth CT Primary
500A
Earth Fault Trip
Active
Earth Fault Trip
10%
Transient Delay
0s
Gen Reverse Power Delay
2s
Gen Reverse Power
35kW
Engine
Oil Pressure Low shutdown
1.03bar
Oil Pressure Low Pre-Alarm
1.24bar
Coolant Temp High Pre-Alarm
90ºC
Coolant Temp High Electrical Trip
92ºC (When Enabled)
Coolant Temp High Shutdown
95ºC
Start Delay Off load
5s
Start Delay on load
5s
Start Delay Telemetry
5s
Pre Heat Timer
0s
Crank Duration
10s
Crank rest Time
10s
Safety On Delay
10s
Smoke Limiting
0s
Smoke limiting off
0s
Warm Up Time
0s
Cool Down Time
1m
Speed Overshoot Delay
0s
Speed Overshoot
0%
Fail To Stop Delay
30s
Battery Under Volts Warning
Active
Battery Under Volts Warning Delay
1m
Battery Under Volts Warning
10v
Battery Over Volts Warning
Active
Battery Over Volts Warning Delay
1m
Battery Over Volts Warning
30v
Charge Alternator Failure Warning
Active
Continued Overleaf
Front Panel Configuration Editor (continued)
Section
Parameter as shown on display
Values
Engine (continued)
Charge Alternator Failure Warning
6.0v
Charge Alternator Warning Delay
5s
Charge Alternator Failure Shutdown
Inactive
Charge Alternator Failure Shutdown
4.0v (When Enabled)
Charge Alternator Shutdown Delay
5s (When Enabled)
Droop %
Active, Inactive. Electronic engines only when
droop is enabled.
Scheduler
Scheduler
Active, Inactive
Schedule On Load
Active , Inactive (Only Available When
Scheduler Is Active)
Schedule Period
Weekly, Monthly (Only Available When
Scheduler Is Active)
Schedule Time & Date Selection (1-16)
Press
to begin editing then
or
when selecting the different
parameters in the scheduler.
ACCESSING THE ‘RUNNING’ CONFIGURATION EDITOR
•
The ‘running’ editor can be entered while the engine is running. All protections remain active if the
engine is running while the running editor is entered.
•
Press and hold the
button to enter the running editor.
ADJUSTABLE PARAMETERS (Running editor)
•
Enter the editor as described above.
•
Press the up
or down
buttons to cycle to the section you wish to view/change.
•
To Edit the parameter press the
button to enter edit mode. The parameter begins to flash to
indicate that you are editing the value.
•
Press the up
or down
buttons to change the parameter to the required value.
•
Press the
button to save the value. The parameter ceases flashing to indicate that it has been
saved.
•
To exit the editor at any time , press and hold the
button.
Running Editor
Section
Parameter as shown on display
Factory Settings
DISPLAY
Contrast
53%
Language
English