Radionics D7024 Reference Manual
Text of the manual
© 1997 Radionics, Inc., Salinas, CA, U.S.A. All rights reserved.
™ The Radionics logo is a registered trademark of Radionics, Inc., Salinas CA, U.S.A.
D7024 Reference Guide P/N 31499B
Reference Guide
for the
D7024 Control/Communicator
Radionics, Inc., 1800 Abbott Street
Salinas, CA 93901, U.S.A.
Customer Service: (800) 538-5807
6/20/97
Copyright © 1997 Radionics, Inc.
D7024 Reference Guide
Table of Contents
Notices
3
FCC Compliance Notice
3
FCC Phone Connection to Users
3
Notice
3
1.0 Overview
4
1.1 System Overview
4
1.2 Specifications
4
1.2.1 Enclosure Housing
4
1.2.2 Temperature
4
1.2.3 Power
4
1.2.4 Outputs
4
1.2.5 Zones (Initiating Circuits)
4
1.2.6 Keypads
5
1.2.7 C
D7024 Reference Guide
Copyright © 1997 Radionics, Inc.
Page 3
FCC Compliance Notice
This equipment has been tested and found to comply
with the limits for a Class A digital device, pursuant to
Part 15 of the FCC Rules. These limits are designed
to provide reasonable protection against harmful
interference in a residential installation. This equip-
Copyright © 1997 Radionics, Inc.
D7024 Reference Guide
1.0 Overview
1.1 System Overview
The D7024 Control/Communicator is a fully integrated
hard-wire fire alarm system. It can support 4 input
points (expandable to 8) and 16 individual users. The
control panel has a built-in LCD keypad, however, up
to 4 additional keypads may be used to provide us
D7024 Reference Guide
Copyright © 1997 Radionics, Inc.
Page 5
1.0 Overview (continued)
1.2.6 Keypads
• Maximum # of keypads:
4 D7033 keypads
• Maximum wire length each:
1000 feet
• Maximum wire length total:
4000 feet in system
• Wire type:
4 conductor, unshielded, #22 AWG (0.8 mm)
“Telephone quad” or #18 AWG (1.0 mm) quad
wiring