Pipe Freeze Protection
and Flow Maintenance
This step-by-step design guide provides the tools necessary to design a Raychem XL-Trace
pipe freeze protection or flow maintenance system. For other applications or for design
assistance, contact your Tyco Thermal Controls representative or phone Tyco Thermal
Controls at (800) 545-6258. Also, visit our web site at www.tycothermal.com.
Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
How to Use this Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Safety Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
System Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
XL-Trace Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Self-Regulating Heating Cable Construction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Pipe Freeze Protection Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Typical Pipe Freeze Protection System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
General Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Fire Sprinkler Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Flow Maintenance Applications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Typical Flow Maintenance System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Greasy Waste Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Fuel Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Pipe Freeze Protection and Flow Maintenance Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Design Step by Step . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Step 1 Determine design conditions and pipe heat loss . . . . . . . . . . . . . . . . . . . . . 13
Step 2 Select the heating cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Step 3 Determine the heating cable length . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Step 4 Determine the electrical parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Step 5 Select the connection kits and accessories . . . . . . . . . . . . . . . . . . . . . . . . 26
Step 6 Select the control system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Step 7 Select the power distribution . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Step 8 Complete the Bill of Materials . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
XL-Trace System Pipe Freeze Protection and Flow Maintenance Design Worksheet . . . . . . 37
Introduction
Raychem XL-Trace is designed for pipe freeze protection and flow maintenance in the
following applications:
•� Freeze protection of general water piping (aboveground and buried)
•� Freeze protection of fire sprinkler systems (aboveground and buried supply pipes)
•� Flow waste lines (aboveground and buried)
•� Flow maintenance of fuel lines (aboveground)
XL-Trace System
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
2 of 44
www.tycothermal.com
H55838 2/12
This guide does not cover applications in which any of the following conditions exist:
•� Hazardous locations, as defined in the national electrical codes
•� Pipe temperature other than specified in Table 1 on page 3
•� Pipe maintenance temperatures above 150°F (65°C)
•� Supply voltage other than 120 V or 208–277 V
If your application conditions are different, or if you have any questions, contact your
Tyco Thermal Controls representative or contact Tyco Thermal Controls directly
at (800) 545-6258 .
How to Use this Guide
This design guide presents Tyco Thermal Controls’ recommendations for designing an XL-Trace
pipe freeze protection or flow maintenance system . It provides design and performance data,
electrical sizing information, and application configuration suggestions . Following these
recommendations will result in a reliable, energy-efficient system .
OTHER REquIRED DOCuMEnTS
This guide is not intended to provide comprehensive installation instructions . For complete
XL-Trace pipe freeze protection and flow maintenance system installation instructions, please
refer to the following additional required documents:
•� XL-Trace System Installation and Operation Manual (H58033)
•� Additional installation instructions are included with the connection kits, thermostats,
controllers, and accessories
If you do not have these documents, you can obtain them from the Tyco Thermal Controls
web site at www .tycothermal .com .
For products and applications not covered by this design guide, please contact your Tyco
Thermal Controls representative or call Tyco Thermal Controls directly at (800) 545-6258 .
Safety Guidelines
As with any electrical equipment, the safety and reliability of any system depends on the
quality of the products selected and the manner in which they are installed and maintained .
Incorrect design, handling, installation, or maintenance of any of the system connection kits
could damage the system and may result in inadequate performance, overheating, electric
shock, or fire . To minimize these risks and to ensure that the system performs reliably, read
and carefully follow the information, warnings, and instructions in this guide .
This symbol identifies important instructions or information .
This symbol identifies particularly important safety warnings that must be followed .
WARnInG: To minimize the danger of fire from sustained electrical arcing if the
heating cable is damaged or improperly installed, and to comply with the requirements of
Tyco Thermal Controls, agency certifications, and national electrical codes, ground-fault
equipment protection must be used on each heating cable branch circuit . Arcing may not
be stopped by conventional circuit protection .
3 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
System Overview
Warranty
Tyco Thermal Controls’ standard limited warranty applies to all products .
An extension of the limited warranty period to ten (10) years from the date of installation is
available if a properly completed online warranty form is submitted within thirty (30) days
from the date of installation . You can access the complete warranty on our web site at
www .tycothermal .com .
System Overview
The XL-Trace system provides freeze protection and flow maintenance for aboveground
and buried pipe applications . The XL-Trace system is based on self-regulating heating cable
technology . Tyco Thermal Controls offers the option of three self-regulating heating cables
with the XL-Trace system: 5XL, 8XL, and 12XL (208–277 V only) for applications using 120 and
208–277 V power supplies . The cable’s output is reduced automatically as the pipe warms,
so there is no possibility of failure due to overheating .
An XL-Trace system includes the heating cable, power connection, splice, tee connections,
controls, contactors, power distribution panels, accessories, and the tools necessary
for a complete installation .
XL-Trace Applications
Identify which of the standard XL-Trace applications below pertain to your installation .
Proceed to the appropriate design sections that follow .
Table 1 XL-Trace Applications
Application
Description
Specific application
requirements
Pipe freeze protection
General water piping
Freeze protection (40°F [4°C]
minimum) of insulated, metal or
plastic water piping
“Aboveground piping,” page 6
“Buried piping,” page 7
Sprinkler piping
Freeze protection (40°F [4°C]
minimum) of standpipes up to
20", supply pipes and branch lines
with sprinklers
“Standpipes, supply pipes, and
branch lines with sprinklers” on
page 8 . Also see “XL-Trace
System for Fire Sprinkler Freeze
Protection Design Guide” (H58489) .
Flow maintenance
Greasy waste lines
Flow maintenance (110°F [43°C]
minimum) for insulated greasy
waste lines
“Aboveground piping” on page 10
“Buried piping” on page 11
Fuel lines
Flow maintenance (40°F [4°C]
minimum) for insulated metal
piping containing #2 fuel oil
“For aboveground piping only,”
page 12
note: If your application does not fit these guidelines, contact your local Tyco Thermal
Controls representative or call (800) 545-6258 .
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
4 of 44
www.tycothermal.com
H55838 2/12
Self-Regulating Heating Cable Construction
Raychem XL-Trace self-regulating heating cables are comprised of two parallel nickel-coated
bus wires in a cross-linked polymer core, a tinned copper braid, and a fluoropolymer or
polyolefin outer jacket . These cables are cut to length, simplifying the application design and
installation .
Fig. 1 XL-Trace heating cable construction
With self-regulating technology, the number of electrical paths between bus wires changes in
response to temperature fluctuations . As the temperature surrounding the heater decreases,
the conductive core contracts microscopically . This contraction decreases electrical resis-
tance and creates numerous electrical paths between the bus wires . Current flows across
these paths to warm the core .
As the temperature rises, the core expands microscopically . This expansion increases
electrical resistance and the number of electrical paths decreases . The heating cable
automatically reduces its output .
At low temperature,
there are many
conducting paths,
resulting in high output
and rapid heat-up. Heat
is generated only when it
is needed and precisely
where it is needed.
At high temperature,
there are few conducting
paths and output is
correspondingly lower,
conserving energy
during operation.
At moderate temperature,
there are fewer conducting
paths because the heating
cable efficiently adjusts by
decreasing output, eliminating
any possibility of overheating.
The following graphs illustrate the response of self-regulating heating cables to
changes in temperature. As the temperature rises, electrical resistance increases,
and our heaters reduce their power output.
Temperature
Resistance
Power
Temperature
Constant wattage
Constant wattage
Self-regulating
Self-regulating
Fig. 2 Self-regulating heating cable technology
Nickel-plated copper bus wire
Self-regulating conductive core
Modified polyolefin inner jacket
Tinned-copper braid
Polyolefin or
fluoropolymer outer jacket
5 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection Applications
Pipe Freeze Protection Applications
A pipe freeze protection system is designed to maintain water temperature at a minimum of
40°F (4°C) to prevent freezing .
Typical Pipe Freeze Protection System
A typical pipe freeze protection system includes the XL-Trace self-regulating heating cables,
connection kits, ambient temperature control, and power distribution .
Fig. 3 Typical XL-Trace pipe freeze protection system
Lighted End Seal
Heating Cable
End Seal Kit
Tee Kit
Power Distribution Panel
Power Connection Kit
Splice Kit
Cross Kit
Ambient RTD
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
6 of 44
www.tycothermal.com
H55838 2/12
General Water Piping
General water piping is defined as metal or plastic water piping located in nonhazardous
locations .
AbOvEGROunD PIPInG
Fig. 4 Typical aboveground piping system
Application Requirements
The system complies with Tyco Thermal Controls requirements for aboveground general
water piping when:
•� The heating cable is permanently secured to insulated metal pipes with GT-66 glass tape,
or to plastic pipes using AT-180 aluminum tape .
•� A 30-mA ground-fault protection device (GFPD) is used .
•� The heating cable is installed per manufacturer’s instructions with approved Raychem
connection kits . See Table 13 on page 27 and the XL-Trace System Installation and
Operation Manual (H58033) .
Cable Selection
See “Other Required Documents” page 14 .
Approvals
UL Listed, FM Approved, and c-CSA-us Certified for nonhazardous locations .
RayClic-PC
power connection
Junction
box
XL-Trace
heating cable
RayClic-S
splice
RayClic-T
tee
Insulation
RayClic-LE
lighted end seal
(optional)
RayClic-E
end seal
DigiTrace C910
Electronic controller
5XL1-CR, -CT
5XL2-CR, -CT
8XL1-CR, -CT
8XL2-CR, -CT
5XL1-CR, -CT
5XL2-CR, -CT
8XL1-CR, -CT
8XL2-CR, -CT
12XL2-CR, -CT
-w
7 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection Applications
buRIED PIPInG
Fig. 5 Typical buried piping system
Application Requirements
The system complies with Tyco Thermal Controls requirements for use on buried insulated
metal or plastic pipe when:
•� The pipeline is buried at least 2 feet deep .
•� All heating cable connections (power, splice, tee, and end termination) are made above-
ground . no buried or in-conduit splices or tees are allowed .
•� The heating cable has a fluoropolymer outer jacket (-CT) .
•� The power connection and end seal are made in UL Listed and CSA Certified junction
boxes above grade .
•� The heating cable is protected from the pipe to the power connection box in UL Listed
and CSA Certified water-sealed conduit (minimum 3/4-inch diameter) suitable for the
location .
•� A 30-mA ground-fault protection device (GFPD) is used .
•� Closed-cell, waterproof thermal insulation with fire-retardant, waterproof covering is used .
•� The heating cable is installed per manufacturer’s instructions with approved Tyco Thermal
Controls connection kits . See Table 15 on page 29 and the XL-Trace System Installation
and Operation Manual (H58033) .
Cable Selection
See “Pipe Heat Loss Calculations,” page 14 .
Approvals
UL Listed, FM Approved, and c-CSA-us Certified for nonhazardous locations .
RTD10CS
Insulation
Conduit
XL-Trace
heating cable
with -CT jacket
Ground
Alternate
power connection
Alternate
end seal
Ground
Wall
RayClic-LE*
RayClic-PC*
Junction box
RayClic-E
end seal
Conduit
Wall
with wall
mounting
bracket
with wall
mounting
bracket
FTC-XC
power
connection
*To protect the heating cable run it inside
Convolex tubing between the conduit and
the RayClic connection kits.
DigiTrace C910
Electronic controller
Conduit for
temperature
sensor
5XL1-CT
5XL2-CT
8XL1-CT
8XL2-CT
5XL1-CT
5XL2-CT
8XL1-CT
8XL2-CT
12XL2-CT
-w
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
8 of 44
www.tycothermal.com
H55838 2/12
Fire Sprinkler Systems
XL-Trace is designed to maintain fire suppression system standpipes, supply piping, mains,
feeders, branch lines and sprinklers at 40°F (4°C) in areas subject to freezing .
STAnDPIPES, SuPPLy PIPES, AnD bRAnCH LInES WITH SPRInkLERS
Fig. 6 Standard sprinkler standpipe heating system layout
Refer to the Fire Sprinkler System Freeze Protection Design Guide (H58489) for detailed in-
structions to design XL-Trace heating cable circuits to freeze protect aboveground or buried
supply pipe, feeders, mains standpipes, branch lines and sprinklers .
Approvals
The 2007 edition of nFPA 13 (Standard for the Installation of Sprinkler Systems) allows List-
ed electrical heat tracing to freeze protect fire suppression systems including supply lines,
standpipes and branch lines containing sprinklers . XL-Trace is c-CSA-us Certified for use on
fire suppression systms under CSA C22 .2 no . 130-03 for Canada and Ieee 515 .1-2005 for
the US . The system covered in this manual includes supply lines, standpipes, branch lines
and sprinkler heads .
XL-Trace systems are also UL and ULC Listed for freeze-protecting sprinkler supply lines,
standpipes up to 20 inches in diameter and branch lines not containing sprinklers .
Standpipe
Thermal insulation
Control valves
in heated enclosure
RayClic-PC
power connection
RayClic-S splice
RayClic-LE
lighted end seal
Ambient sensing RTD
Ground
XL-Trace
Power
distribution
panel
Fire
alarm
panel
DigiTrace C910
electronic
controller
Refer to Branch
Lines with
Sprinkler section
for information on
heat tracing
sprinkler heads.
Line sensing RTD
5XL1-CR, -CT
5XL2-CR, -CT
8XL1-CR, -CT
8XL2-CR, -CT
5XL1-CR, -CT
5XL2-CR, -CT
8XL1-CR, -CT
8XL2-CR, -CT
12XL2-CR, -CT (not for branch lines
with sprinklers and sprinkler heads)
-w
9 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Flow Maintenance Applications
Flow Maintenance Applications
A flow maintenance system is designed to maintain cooking greasy waste lines and #2 fuel
oil lines above the temperature at which the viscosity inhibits fluid flow .
Typical Flow Maintenance System
A typical flow maintenance system includes the XL-Trace self-regulating heating cables with
a fluoropolymer outer jacket, connection kits, line-sensing temperature control and power
distribution .
Splice Kit
Powered Tee Kit
Heating Cable
Lighted End Seal
Power Distribution Panel
Grade
Electronic Controller
RTD
Fig. 7 Typical XL-Trace flow maintenance system
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
10 of 44
www.tycothermal.com
H55838 2/12
Greasy Waste Lines
Greasy waste lines are defined as piping used for the disposal of waste oils and fats created in
the cooking process . Typical applications include greasy waste lines from commercial
restaurants . A grease-line flow maintenance system is designed to maintain a 110°F (43°C)
minimum fluid temperature .
AbOvEGROunD PIPInG
Fig. 8 Typical aboveground piping system
Application Requirements
The system complies with Tyco Thermal Controls requirements for aboveground greasy
waste lines when:
•� The heating cable is permanently secured to metal pipes with GT-66 glass tape, or to
plastic pipes using AT-180 aluminum tape .
•� The heating cable must have a fluoropolymer outer jacket (-CT) .
•� A 30-mA ground-fault protection device (GFPD) is used .
•� Tees and splices are installed using pipe mounting brackets, not in direct contact with
piping .
•� The heating cable is installed per manufacturer’s instructions with approved Tyco Thermal
Controls connection kits . See Table 13 on page 27 and the XL-Trace System Installation
and Operation Manual (H58033) .
Cable Selection
See “Pipe Heat Loss Calculations,” page 14 .
Approvals
XL-Trace systems (-CT only) are UL Listed, FM Approved, and c-CSA-us Certified for
nonhazardous locations .
RayClic-PC
power
connection
Junction
box
RayClic-S
splice
Insulation
RayClic-LE
lighted end seal
RayClic-E
Alternate
end seal
XL-Trace
heating cable
with -CT jacket
RayClic-SB-04
pipe mounting bracket
DigiTrace C910
Electronic controller
RTD10CS
5XL1-CT
5XL2-CT
8XL1-CT
8XL2-CT
5XL1-CT
5XL2-CT
8XL1-CT
8XL2-CT
12XL2-CT
-w
11 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Flow Maintenance Applications
buRIED PIPInG
Fig. 9 Typical buried greasy waste line
Application Requirements
The system complies with Tyco Thermal Controls requirements for buried greasy waste lines
when:
•� The heating cable is permanently secured to metal pipes with GT-66 glass tape, or to
plastic pipes using AT-180 aluminum tape .
•� The heating cable must have a fluoropolymer outer jacket (-CT) .
•� The pipeline is buried at least 2 feet deep .
•� All heating cable splices or tees are made aboveground . no buried or in-conduit splices
or tees are allowed .
•� The power connection and end seal are made in UL Listed and CSA Certified junction
boxes above grade .
•� The heating cable is protected from the pipe to the power connection box in UL Listed
and CSA Certified conduit (minimum 3/4-inch diameter) suitable for the location .
•� A 30-mA ground-fault protection device (GFPD) is used .
•� Closed-cell, waterproof thermal insulation with fire-retardant, waterproof covering is used .
•� The heating cable is installed per manufacturer’s instructions with approved Tyco Thermal
Controls connection kits . See Table 15 on page 29 and the XL-Trace System Installation
and Operation Manual (H58033) .
Cable Selection
See “Heating Cable Catalog number” on page 18 .
Approvals
XL-Trace systems (-CT only) are UL Listed, FM Approved, and c-CSA-us Certified for
nonhazardous locations .
RTD10CS
Insulation
Conduit
XL-Trace
heating cable
with -CT jacket
Ground
Alternate
power connection
Alternate
end seal
Ground
Wall
RayClic-LE*
RayClic-PC*
Junction box
RayClic-E
end seal
Conduit
Wall
with wall
mounting
bracket
with wall
mounting
bracket
FTC-XC
power
connection
*To protect the heating cable run it inside
Convolex tubing between the conduit and
the RayClic connection kits.
DigiTrace C910
Electronic controller
Conduit for
temperature
sensor
5XL1-CT
5XL2-CT
8XL1-CT
8XL2-CT
5XL1-CT
5XL2-CT
8XL1-CT
8XL2-CT
12XL2-CT
-w
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
12 of 44
www.tycothermal.com
H55838 2/12
Fuel Lines
Fuel lines are defined as those carrying #2 fuel oil . A fuel line flow maintenance system is
designed to maintain a 40°F (4°C) minimum fluid temperature to maintain flow .
FOR AbOvEGROunD PIPInG onLy
Fig. 10 Typical aboveground piping system
Application Requirements
The system complies with Tyco Thermal Controls requirements for aboveground #2 fuel oil
piping when:
•� The heating cable is permanently secured to metal pipes with GT-66 glass tape, or to
plastic pipes using AT-180 aluminum tape .
•� The heating cable must have a fluoropolymer outer jacket (-CT) .
•� Tees and splices are installed using pipe mounting brackets, not in direct contact with
piping .
•� A 30-mA ground-fault protection device (GFPD) is used .
•� The heating cable is installed per manufacturer’s instructions with approved Tyco Thermal
Controls connection kits . See Table 13 on page 27 and the XL-Trace System Installation
and Operation Manual (H58033) .
Cable Selection
See “Pipe Heat Loss Calculations,” page 14 .
Approvals
XL-Trace systems (-CT only) are UL Listed, FM Approved, and c-CSA-us Certified for
nonhazardous locations .
RayClic-S
splice
XL-Trace
heating cable
with -CT jacket
RTD10CS
RayClic-LE
lighted end seal
Junction
box
Insulation
RayClic-PC
power
connection
RayClic-SB-04
pipe mounting bracket
DigiTrace C910
Electronic controller
5XL1-CT
5XL2-CT
8XL1-CT
8XL2-CT
5XL1-CT
5XL2-CT
8XL1-CT
8XL2-CT
12XL2-CT
-w
13 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection and Flow Maintenance Design
Pipe Freeze Protection and Flow Maintenance Design
This section details the design steps necessary to design your application . The examples
provided in each step are intended to incrementally illustrate the project parameter output for
two sample designs from start to finish . As you go through each step, use the “XL-Trace System
Pipe Freeze Protection and Flow Maintenance Design Worksheet,” page 37, to document your
project parameters, so that by the end of this section you will have the information you need
for your Bill of Materials .
XL-erate, the commercial pipe freeze protection and flow maintenance design software is
available at http://www .tycothermal .com to assist with your design .
Design Step by Step
Your system design requires the following essential steps .
�Determine design conditions and pipe heat loss
�Select the heating cable
Determine the heating cable length
Determine the electrical parameters
Select the connection kits and accessories
Select the control system
Select the power distribution
Complete the Bill of Materials
Pipe Freeze Protection
and Flow Maintenance
1. Determine design
conditions and heat
loss
2. Select the heating
cable
3. Determine the
heating cable length
4. Determine the
electrical parameters
5. Select the
connection kits and
accessories
6. Select the control
system
7. Select the power
distribution
8. Complete the Bill of
Materials
Step Determine design conditions and pipe heat loss
Collect the following information to determine your design conditions:
•� XL-Trace application (from Table 1Location
–
Indoors
–
Outdoors
–
Aboveground
–
Buried
•� Maintain temperature (Tm)
•� Maximum system temperature (Tmax)
•� Minimum ambient temperature (Ta)
•� Pipe diameter and material
•� Pipe length
•� Thermal insulation type and thickness
•� Supply voltage
Example: Pipe Freeze Protection – Water Piping
Location
Aboveground, outdoor
Maintain temperature (Tm)
40°F (4°C)
Maximum system temperature (Tmax)
80°F (27°C)
Minimum ambient temperature (Ta)
–20°F (–29°C)
Pipe diameter and material
2-inch plastic
Pipe length
300 ft (91 m)
Thermal insulation type and thickness
1-inch fiberglass
Supply voltage
120 V
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
14 of 44
www.tycothermal.com
H55838 2/12
Example: Pipe Freeze Protection – Greasy Waste Line
Location
Buried
Maintain temperature (Tm)
110°F (43°C)
Maximum system temperature (Tmax)
125°F (52°C)
Minimum ambient temperature (Ta)
50°F (10°C) (soil temperature)
Pipe diameter and material
4-inch metal
Pipe length
200 ft (61 m)
Thermal insulation type and thickness
1-inch rigid cellular urethane
Supply voltage
208 V
PIPE HEAT LOSS CALCuLATIOnS
To select the proper heating cable you must first determine the pipe heat loss . To do this you
must first calculate the temperature differential (DT) between the pipe maintain temperature
and the minimum ambient temperature .
Fig. 11 Pipe heat loss
Calculate temperature differential DT
To calculate the temperature differential (DT), use the formula below:
DT = Tm – Ta
Example: Pipe Freeze Protection – Water Piping
Tm
40°F (4°C)
Ta
–20°F (–29°C)
DT = 40°F – (–20°F) = 60°F
DT = 4°C – (–29°F) = 33°C
Example: Flow Maintenance – Greasy Waste Line
Tm
110°F (43°C)
Ta
50°F (10°C)
DT = 110°F – (50°F) = 60°F
DT = 43°C – (10°C) = 33°C
Determine the pipe heat loss
Match the pipe size, insulation thickness, and temperature differential (DT) from Table 2 to
determine the base heat loss of the pipe (Qb) .
Example: Pipe Freeze Protection – Water Piping
Pipe diameter
2 inch
20
40
60
80
−40
−20
0
+20
+40
Maintain
temperature
°F
°F
Minimum
ambient
temperature
Thermal insulation thickness
Pipe or
tubing
diameter
15 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection and Flow Maintenance Design
Insulation thickness 1 inch
DT
60°F (33°C)
Heat loss (Qb) for 60°F must be calculated through interpolation between DT at 50°F and DT
at 100°F from Table 2 . For difference between the DT of 50°F and the DT of 100°F:
Qb-50
3 .2 W/ft (from Table 2)
Qb-100
6 .8 W/ft (from Table 2)
DT interpolation
DT 60°F is 20% of the distance between DT 50°F and DT 100°F
Qb-60
Qb-50 + [0 .20 x (Qb-100 – Qb-50)] = 3 .2 + [0 .20 x (6 .8 – 3 .2)] = 3 .9 W/ft
Pipe heat loss (Qb)
3.9 W/ft @ Tm 40°F (12.9 W/m @ Tm 4°C)
Example: Flow Maintenance – Greasy Waste Line
Pipe diameter
4 inch
Insulation thickness 1 inch
DT
60°F (33°C)
Qb for 60°F must be calculated through interpolation between DT at 50°F and DT at 100°F
from Table 2 . For difference between the DT of 50°F and the DT of 100°F:
Qb-50
5 .4 W/ft (from Table 2)
Qb-100
11 .2 W/ft (from Table 2)
DT interpolation
DT 60°F is 20% of the distance between DT 50°F and DT 100°F
Qb-60
Qb-50 + [0 .20 x (Qb-100 – Qb-50)] = 5 .4 + [0 .20 x (11 .2 – 5 .4)] = 6 .6 W/ft
Pipe heat loss Qb
6.6 W/ft @ Tm 110°F (21.5 W/m @ Tm 43°C)
Compensate for insulation type and pipe location
The base heat loss is calculated for a pipe insulated with thermal insulation with a k-factor
ranging from 0 .2 to 0 .3 BTU/hr–°F-ft2/in (fiberglass or foamed elastomer) in an outdoor, or
buried application . To get the heat loss for pipes insulated with alternate types of thermal
insulation and for pipes installed indoors, multiply the base heat loss of the pipe (Qb) from
Step 3 by the insulation multiple from Table 4 and the indoor multiple from Table 3 to
get the corrected heat loss:
Qcorrected = Qb x Insulation multiple x Indoor multiple
Example: Pipe Freeze Protection – Water Piping
Location
Aboveground, outdoor
Thermal insulation thickness and type 1-inch fiberglass
Pipe heat loss Qb
3 .9 W/ft @ Tm 40°F (12 .9 W/m @ Tm 4°C)
Qcorrected
3 .9 W/ft x 1 .00 x 1 .00 = 3.9 W/ft @ Tm 40°F
(12.9 W/m @ Tm 4°C)
Example: Flow Maintenance – Greasy Waste Line
Location
Buried
Thermal insulation type and thickness 1-inch rigid cellular urethane
Pipe heat loss Qb =
6 .6 W/ft @ Tm 110°F (21 .5 W/m @ Tm 43°C)
Qcorrected =
6 .6 W/ft x 0 .6 x 1 .00 = 4.0 W/ft @ Tm 110°F
(13.1 W/m @ Tm 43°C)
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
16 of 44
www.tycothermal.com
H55838 2/12
Table 2 Pipe Heat Loss (qb) for Outdoor or buried Pipe (W/ft) for 1/2 to 3-1/2 inches
Insulation thickness
(DT)
Pipe diameter (IPS) in inches
(in)
°F
°C
1/2
3/4
1
1-1/4
1-1/2
2
2-1/2
3
3-1/2
0 .5
20
11
1 .0
1 .2
1 .4
1 .6
1 .8
2 .2
2 .5
3 .0
3 .4
50
28
2 .5
2 .9
3 .5
4 .1
4 .6
5 .5
6 .5
7 .7
8 .6
100
56
5 .2
6 .1
7 .2
8 .6
9 .6
11 .5
13 .5
16 .0
18 .0
150
83
8 .1
9 .5
11 .2
13 .4
14 .9
17 .9
21 .1
25 .0
28 .1
1 .0
20
11
0 .6
0 .7
0 .8
1 .0
1 .1
1 .3
1 .5
1 .7
1 .9
50
28
1 .6
1 .9
2 .2
2 .5
2 .8
3 .2
3 .8
4 .4
4 .9
100
56
3 .4
3 .9
4 .5
5 .2
5 .8
6 .8
7 .8
9 .1
10 .2
150
83
5 .3
6 .1
7 .0
8 .2
9 .0
10 .6
12 .2
14 .2
15 .9
1 .5
20
11
0 .5
0 .6
0 .7
0 .8
0 .8
1 .0
1 .1
1 .3
1 .4
50
28
1 .3
1 .5
1 .7
1 .9
2 .1
2 .4
2 .8
3 .2
3 .6
100
56
2 .8
3 .1
3 .5
4 .0
4 .4
5 .1
5 .8
6 .7
7 .4
150
83
4 .3
4 .8
5 .5
6 .3
6 .9
8 .0
9 .1
10 .5
11 .6
2 .0
20
11
0 .5
0 .5
0 .6
0 .6
0 .7
0 .8
0 .9
1 .0
1 .1
50
28
1 .1
1 .3
1 .4
1 .6
1 .8
2 .0
2 .3
2 .6
2 .9
100
56
2 .4
2 .7
3 .0
3 .4
3 .7
4 .2
4 .8
5 .5
6 .0
150
83
3 .7
4 .2
4 .7
5 .3
5 .8
6 .6
7 .5
8 .5
9 .4
2 .5
20
11
0 .4
0 .5
0 .5
0 .6
0 .6
0 .7
0 .8
0 .9
1 .0
50
28
1 .0
1 .2
1 .3
1 .4
1 .6
1 .8
2 .0
2 .3
2 .5
100
56
2 .2
2 .4
2 .7
3 .0
3 .3
3 .7
4 .2
4 .7
5 .2
150
83
3 .4
3 .7
4 .2
4 .7
5 .1
5 .8
6 .5
7 .4
8 .1
3 .0
20
11
0 .4
0 .4
0 .5
0 .5
0 .6
0 .6
0 .7
0 .8
0 .9
50
28
1 .0
1 .1
1 .2
1 .3
1 .4
1 .6
1 .8
2 .0
2 .2
100
56
2 .0
2 .2
2 .4
2 .7
2 .9
3 .3
3 .7
4 .2
4 .6
150
83
3 .1
3 .4
3 .8
4 .3
4 .6
5 .2
5 .8
6 .6
7 .1
4 .0
20
11
0 .3
0 .4
0 .4
0 .5
0 .5
0 .5
0 .6
0 .7
0 .7
50
28
0 .9
0 .9
1 .0
1 .1
1 .2
1 .4
1 .5
1 .7
1 .8
100
56
1 .8
2 .0
2 .1
2 .4
2 .5
2 .9
3 .2
3 .5
3 .8
150
83
2 .8
3 .0
3 .4
3 .7
4 .0
4 .4
4 .9
5 .5
6 .0
note: Multiply the W/ft heat loss values by 3 .28 for W/m .
17 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection and Flow Maintenance Design
Table 1.2 continued Pipe Heat Loss (qb) for Outdoor or buried Pipe (W/ft) for 4 to 20 inches
Insulation thickness
(DT)
Pipe diameter (IPS) in inches
(in)
°F
°C
4
6
8
10
12
14
16
18
20
0 .5
20
11
3 .8
5 .3
6 .8
8 .4
9 .9
10 .8
12 .2
13 .7
15 .2
50
28
9 .6
13 .6
17 .4
21 .4
25 .2
27 .5
31 .3
35 .0
38 .8
100
56
20 .0
28 .4
36 .3
44 .6
52 .5
57 .4
65 .2
73 .0
80 .8
150
83
31 .2
44 .3
56 .6
69 .6
81 .9
89 .5
101 .7
113 .8
126 .0
1 .0
20
11
2 .1
2 .9
3 .7
4 .5
5 .3
5 .8
6 .5
7 .3
8 .0
50
28
5 .4
7 .5
9 .4
11 .5
13 .5
14 .7
16 .6
18 .6
20 .5
100
56
11 .2
15 .6
19 .7
24 .0
28 .1
30 .6
34 .7
38 .7
42 .8
150
83
17 .5
24 .3
30 .7
37 .4
43 .8
47 .8
54 .1
60 .4
66 .7
1 .5
20
11
1 .5
2 .1
2 .6
3 .2
3 .7
4 .0
4 .5
5 .0
5 .5
50
28
3 .9
5 .3
6 .7
8 .1
9 .4
10 .2
11 .5
12 .9
14 .2
100
56
8 .1
11 .1
13 .9
16 .8
19 .6
21 .3
24 .0
26 .8
29 .5
150
83
12 .7
17 .3
21 .6
26 .2
30 .5
33 .2
37 .5
41 .8
46 .1
2 .0
20
11
1 .2
1 .7
2 .1
2 .5
2 .9
3 .1
3 .5
3 .9
4 .3
50
28
3 .1
4 .2
5 .2
6 .3
7 .3
7 .9
8 .9
9 .9
10 .9
100
56
6 .6
8 .8
10 .9
13 .1
15 .2
16 .5
18 .6
20 .7
22 .8
150
83
10 .2
13 .8
17 .0
20 .5
23 .8
25 .8
29 .0
32 .3
35 .5
2 .5
20
11
1 .1
1 .4
1 .7
2 .1
2 .4
2 .6
2 .9
3 .2
3 .5
50
28
2 .7
3 .6
4 .4
5 .2
6 .1
6 .6
7 .4
8 .2
9 .0
100
56
5 .6
7 .4
9 .1
10 .9
12 .6
13 .7
15 .3
17 .0
18 .7
150
83
8 .7
11 .6
14 .2
17 .0
19 .7
21 .3
23 .9
26 .5
29 .1
3 .0
20
11
0 .9
1 .2
1 .5
1 .8
2 .0
2 .2
2 .5
2 .7
3 .0
50
28
2 .4
3 .1
3 .8
4 .5
5 .2
5 .6
6 .3
7 .0
7 .6
100
56
4 .9
6 .5
7 .9
9 .4
10 .8
11 .7
13 .1
14 .5
15 .9
150
83
7 .7
10 .1
12 .4
14 .7
16 .9
18 .3
20 .5
22 .6
24 .8
4 .0
20
11
0 .8
1 .0
1 .2
1 .4
1 .6
1 .7
1 .9
2 .1
2 .3
50
28
2 .0
2 .5
3 .1
3 .6
4 .1
4 .4
5 .0
5 .5
6 .0
100
56
4 .1
5 .3
6 .4
7 .5
8 .6
9 .3
10 .3
11 .4
12 .4
150
83
6 .4
8 .3
10 .0
11 .8
13 .4
14 .5
16 .1
17 .8
19 .4
note: Multiply the W/ft heat loss values by 3 .28 for W/m .
Table 3 Indoor Pipe Heat Loss Multiples
Fiberglass thickness (in)
Indooor multiple
0 .5
0 .79
1
0 .88
1 .5
0 .91
2
0 .93
2 .5
0 .94
3
0 .95
4
0 .97
Table 4 Insulation Heat Loss Multiples
k factor at 50°F (10°C) (bTu/hr–°F-ft2/in)
Insulation multiple
Examples of preformed pipe insulation
0 .1–0 .2
0 .6
Rigid cellular urethane (ASTM C591)
0 .2–0 .3
1 .0
Glass fiber (ASTM C547)
Foamed elastomer (ASTM C534)
0 .3–0 .4
1 .4
Cellular glass (ASTM C552)
Mineral fiber blanket (ASTM C553)
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
18 of 44
www.tycothermal.com
H55838 2/12
Pipe Freeze Protection
and Flow Maintenance
2. Select the heating
cable
3. Determine the
heating cable length
4. Determine the
electrical parameters
5. Select the
connection kits and
accessories
6. Select the control
system
7. Select the power
distribution
8. Complete the Bill of
Materials
1. Determine design
conditions and heat
loss
Step Select the heating cable
To select the appropriate XL-Trace heating cable for your application, you must determine
your cable supply voltage, power output, and outer jacket . Once you select these, you will be
able to determine the catalog number for your cable .
HEATInG CAbLE CATALOG nuMbER
Before beginning, take a moment to understand the structure underlying heating cable cata-
log numbers . You will refer to this numbering convention throughout the product selection
process . Your goal is to determine the catalog number for the product that best suits your
needs .
Fig. 12 Heating cable catalog number
Select the heating cable from Fig . 13 that provides the required power output to match the
corrected heat loss for your application . Fig . 13 shows the power output for the heating
cables on metal pipe at 120/208 volts . To correct the power output for other applied voltage
or plastic pipes multiply the power output at the desired maintain temperature by the factors
listed in Table 5 . If the pipe heat loss, Qcorrected, is between the two heating cable power
output curves, select the higher-rated heating cable .
5XL1-CR and 5XL1-CT (120 V)
5XL2-CR and 5XL2-CT (208 V)
8XL1-CR and 8XL1-CT (120 V)
8XL2-CR and 8XL2-CT (208 V)
12XL2-CR and 12XL2-CT (208 V)
Pipe temperature
Power W/ft
50
(10)
30
(–1)
40
(5)
60
(15)
70
(21)
80
(27)
90
(32)
100
(38)
110
(43)
120
(49)
130
(54)
°F
(°C)
10
8
14
12
6
4
2
0
Fig. 13 Heating cable power output on metal pipe
Catalog number: 5, 8 or 12 XL 1 or 2 -CR -CT
Power output (W/ft)
Product family
Voltage
1 = 120 V (only available for 5 or 8)
2 = 208, 240, 277 V (available for 5, 8, or 12)
Jacket type: Polyolefin
Fluoropolymer (required for buried pipes, grease and fuel lines)
or
19 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection and Flow Maintenance Design
Table 5 Power Output Correction Factors
voltage correction factors
5XL1
8XL1
5XL2
8XL2
12XL2
120 V
1 .00
1 .00
–
–
–
208 V
–
–
1 .00
1 .00
1 .00
240 V
–
–
1 .12
1 .12
1 .14
277 V
–
–
1 .29
1 .27
1 .30
Plastic pipe correction factor
(With AT-180 Aluminum tape)
0 .75
0 .75
0 .75
0 .75
0 .75
Confirm that the corrected power output of the heating cable selected is greater than the
corrected pipe heat loss (Qcorrected) . If Qcorrected is greater than the power output of the
highest-rated heating cable, you can:
•� Use two or more heating cables run in parallel
•� Use thicker insulation to reduce heat loss
•� Use insulation material with a lower k factor to reduce heat loss
Example: Pipe Freeze Protection – Water Piping
Pipe maintain temperature (Tm)
40°F (4°C) (from Step 1)
Qcorrected
Qcorrected = 3 .9 W/ft @ Tm 40°F (13 .1 W/m @ Tm 4°C)
Supply voltage
120 V (from Step 1)
Pipe material
Plastic (from Step 1)
Select heating cable:
Qb = 3 .9 W/ft @ Tm 40°F (from Step 1)
5XL1= 5 .6 W/ft @ 40°F (from Fig. 13)
Supply voltage correction factor
1 .00 (from Table 5)
Pipe material correction factor
Plastic = 0 .75 (from Table 5)
Corrected heating cable power
5 .6 W/ft x 1 .00 x 0 .75 = 4 .2 W/ft
Selected heating cable
5XL1
Example: Flow Maintenance – Greasy Waste Line
Pipe maintain temperature (Tm)
110°F (43°C) (from Step 1)
Qcorrected
3 .9 W/ft @ Tm 110°F (13 .1W/m @ Tm 43°C)
Supply voltage
208 V (from Step 1)
Pipe material
Metal (from Step 1)
Select heating cable:
Qb = 3 .9 W/ft @ Tm 110°F (from Step 1)
12XL2= 7 .0 W/ft @110°F (from Fig. 13)
Supply voltage correction factor
1 .00 (from Table 5)
Pipe material correction factor
Metal = 1 .00
Corrected heating cable power
7 .0 x 1 .00 x 1 .00 = 7 .0 W/ft
Selected heating cable
12XL2
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
20 of 44
www.tycothermal.com
H55838 2/12
COnFIRM EXPOSuRE TEMPERATuRE RATInG FOR THE HEATInG CAbLE
Refer to Table 6 to verify that the maximum system temperature does not exceed the expo-
sure temperature of the selected heating cable .
Table 6 Heating Cable Temperature Ratings
5XL1
5XL2
8XL1
8XL2
12XL2
Maximum maintain temperature (Tm)
150°F
(65°C)
150°F
(65°C)
150°F
(65°C)
150°F
(65°C)
150°F
(65°C)
Maximum exposure temperature (Texp)
150°F
(65°C)
150°F
(65°C)
150°F
(65°C)
150°F
(65°C)
185°F
(85°C)
Example: Pipe Freeze Protection – Water Piping
Maximum system temperature (Tmax)
80°F (27°C) (from Step 1)
Selected heating cable
5XL1 (from previous step)
Maximum heating cable exposure temperature (Texp) 150°F (65°C) (from Table 6)
Tmax < Texp
yes
Example: Flow Maintenance - Greasy Waste Line
Maximum system temperature (Tmax)
125°F (52°C) (from Step 1)
Selected heating cable
12XL2 (from previous step)
Maximum heating cable exposure temperature (Texp) 185°F (85°C)(from Table 6
Tmax < Texp
yes
SELECT OuTER JACkET
Select the appropriate heating cable outer jacket for the application . Jacket options are:
-CR Compatible with most XL-Trace applications
-CT Required for grease and fuel line flow maintenance; may be used in other XL-Trace
applications for improved mechanical strength and chemical resistance .
Example: Pipe Freeze Protection – Water Piping
Selection:
5XL1-CR
Example: Flow Maintenance - Greasy Waste Line
Selection:
12XL2-CT
Pipe Freeze Protection
and Flow Maintenance
2. Select the heating
cable
3. Determine the
heating cable length
4. Determine the
electrical parameters
5. Select the
connection kits and
accessories
6. Select the control
system
7. Select the power
distribution
8. Complete the Bill of
Materials
1. Determine design
conditions and heat
loss
Step Determine the heating cable length
In Step 2 you selected the appropriate heating cable and the number of runs of heating cable
required for the pipe . Multiply the length of the pipe by the number of heating cable runs for
the heating cable length .
Additional heating cable will be required for heat sinks and connection kits . Use Table 7
and Table 8 to determine the additional footage required for heat sinks (valves, flanges, and
pipe supports) . You will determine the additional heating cable for connection kits in Step 5 .
Round up fractional lengths to ensure heating cable lengths are sufficient .
Heating cable length = Pipe length x No. heating cable runs
Total heating cable
length required
(Pipe length x No.
heating cable runs)
Additional heating cable
for heat sinks (valves, pipe
supports, and flanges)
=
+
21 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection and Flow Maintenance Design
Table 7 Additional Heating Cable for valves
Pipe diameter (IPS) (inches)
Heating cable (feet (meters))
1/2
0 .8
(0 .24)
3/4
1 .3
(0 .4)
1
2 .0
(0 .6)
1-1/4
3 .3
(1 .1)
1-1/2
4 .3
(1 .3)
2
4 .3
(1 .3)
3
4 .3
(1 .3)
4
4 .3
(1 .3)
6
5 .0
(1 .5)
8
5 .0
(1 .5)
10
5 .6
(1 .7)
12
5 .9
(1 .9)
14
7 .3
(2 .2)
18
9 .4
(2 .9)
20
10 .5
(3 .2)
Table 8 Additional Heating Cable for Pipe Supports and Flanges
Support
Additional cable
Pipe hangers (insulated)
no additional heating cable
Pipe hangers noninsulated
and U-bolt supports
Add 2x pipe diameter
Welded support shoes
Add 3x the length of the shoe
Flanges
Add 2x pipe diameter
note: For applications where more than one heating cable is required per foot of pipe, this
correction factor applies for each cable run .
Example: Pipe Freeze Protection – Water Piping
Pipe length
300 ft (91 m) (from Step 1)
Pipe diameter
2-inch plastic (from Step 1)
number of heating cable runs
1 (from Step 2)
Valves
3 gate valves
4 .3 ft x 3 gate valves = 12 .9 ft (3 .9 m)
Pipe supports
5 pipe hangers with U-bolts
2-inch pipe diameter = 2 / 12 = 0 .17 ft
[0 .17 ft pipe diameter x 2] x 5 pipe supports
= 1 .7 ft (0 .5 m)
Flanges
0
Total heating cable for heat sinks
12 .9 ft (3 .9 m) + 1 .7 ft (0 .5 m) = 14 .6 ft (4 .4 m)
Rounded up to 15 ft (5 m)
Total heating cable length required 300 ft (91 m) x 1 run + 15 ft = 315 ft (96 m) of 5XL1-CR
(note: AT-180 Aluminum tape is required for installing
heating cable on plastic pipe .)
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
22 of 44
www.tycothermal.com
H55838 2/12
Example: Flow Maintenance – Greasy Waste Line
Pipe length
200 ft (61 m) (from Step 1)
Pipe diameter
4-inch metal (from Step 1)
number of heating cable runs
1 (from Step 2)
Valves
2 gate valves
[4 .3 ft x 2 gate valves] x 1 run = 8 .6 ft (2 .6 m)
Pipe supports
2 non-insulated hangers
4-inch pipe diameter = 4 /12 = 0 .33 ft
[(0 .33 ft pipe diameter x 2) x 2 pipe supports] x 1 run
= 1 .3 ft (0 .4 m)
Flanges
2
4-inch pipe diameter = 4 /12 = 0 .33 ft
[(2 x 0 .33 ft (pipe diameter)) x 2 flanges] x 1 run
= 1 .3 ft (0 .4 m)
Total heating cable for heat sinks
8 .6 ft (2 .6 m) + 1 .3 ft (0 .4 m) + 1 .3 ft (0 .4 m)
= 11 .2 ft (2 .2 m)
Rounded up to 12 ft (3 m)
Total heating cable length required 200 ft x 1 run + 12 ft = 212 ft (65 m) of 12XL2-CT
Pipe Freeze Protection
and Flow Maintenance
2. Select the heating
cable
3. Determine the
heating cable length
4. Determine the
electrical parameters
5. Select the
connection kits and
accessories
6. Select the control
system
7. Select the power
distribution
8. Complete the Bill of
Materials
1. Determine design
conditions and heat
loss
Step Determine the electrical parameters
To determine the electrical requirements for your application, you must determine the
number of circuits and calculate the transformer load .
DETERMInE nuMbER OF CIRCuITS
To determine the number of circuits, you need to know:
•� Total heating cable length
•� Supply voltage
•� Minimum start-up temperature
Use Table 9 to determine the maximum circuit length allowed . If the total heating cable length
exceeds the maximum circuit length for the expected start-up temperature, more than one
circuit will be required .
number of circuits =
Heating cable length required
Maximum heating cable circuit length
Important: Select the smallest appropriate ground-fault circuit breaker size .
WARnInG: To minimize the danger of fire from sustained electrical arcing if the heat-
ing cable is damaged or improperly installed, and to comply with the requirements of Tyco
Thermal Controls, agency certifications, and national electrical codes, ground-fault equip-
ment protection must be used on each heating cable branch circuit . Arcing may not be
stopped by conventional circuit protection .
23 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection and Flow Maintenance Design
Table 9 Maximum Circuit Length in Feet
40°F / 110°F Maintain*
Start-up
temperature (°F)
Cb size
(A)
5XL1
8XL1
5XL2
8XL2
12XL2
120 v
120 v
208 v
240 v
277 v
208 v
240 v
277 v
208 v
240 v
277 v
–20°F
15
101
76
174
178
183
131
138
146
111
114
117
20
134
101
232
237
245
175
184
194
148
151
156
30
201
151
349
356
367
262
276
291
223
227
234
40
270
201
465
474
478
349
368
388
297
303
312
0°F
15
115
86
199
203
209
149
157
166
120
122
126
20
153
115
265
271
279
199
209
221
160
163
168
30
230
172
398
406
419
298
314
331
239
244
252
40
270
210
470
490
530
370/399
390/420
420/443
319
326
336
20°F
15
134
100
232
237
244
173
182
192
126
129
133
20
178
133
309
315
325
231
243
257
169
172
177
30
270
200
464
473
488
346
365
385
253
258
266
40
270
210
470
490
530
370/462
390/486
420/513
340/349
344
355
40°F
15
160
119
278
283
292
206
217
229
142
145
150
20
214
159
370
378
390
275
290
306
190
194
200
30
270
210
470
490
530
370/416
390/438
420/462
285
291
300
40
270
210
470
490
530
370/554
390/584
420/616
340/398
360/406
380/419
50°F
(buried)
15
–
–
–
–
–
228
240
254
152
155
160
20
–
–
–
–
–
304
320
338
203
207
213
30
–
–
–
–
–
457
481
507
304
310
320
40
–
–
–
–
–
609
641
676
405
414
427
65°F
(indoors grease)
15
–
–
–
–
–
272
286
302
169
172
178
20
–
–
–
–
–
362
381
402
225
230
237
30
–
–
–
–
–
543
572
603
338
345
356
40
–
–
–
–
–
610
660
720
430
460
490
* When maximum circuit length is listed in:
•�black�type,�the�value�is�for�applications�with�a�40°F�maintain
•�red italic type, the value is for applications with a 110°F maintain
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
24 of 44
www.tycothermal.com
H55838 2/12
Table 10 Maximum Circuit Length in Meters
4°C / 43°C Maintain*
Start-up
temperature (°C)
Cb size
(A)
5XL1
8XL1
5XL2
8XL2
12XL2
120 v
120 v
208 v
240 v
277 v
208 v
240 v
277 v
208 v
240 v
277 v
–29°C
15
31
23
53
54
56
40
42
44
34
35
36
20
41
31
71
72
75
53
56
59
45
46
48
30
61
46
106
108
112
80
84
89
68
69
71
40
82
61
142
145
149
106
112
118
90
92
95
–18°C
15
35
26
61
62
64
45
48
51
36
37
38
20
47
35
81
83
85
61
64
67
49
50
51
30
70
52
121
124
128
91
96
101
73
74
77
40
82
64
143
149
162
113/122
119/128
128/135
97
99
102
–7°C
15
41
31
71
72
74
53
56
59
39
39
41
20
54
41
94
96
99
70
74
78
51
52
54
30
82
61
141
144
149
106
111
117
77
79
81
40
82
64
143
149
162
113/141
119/148
128/156
104/106
105
108
4°C
15
49
36
85
86
89
63
66
70
43
44
46
20
65
48
113
115
119
84
88
93
58
59
61
30
82
64
143
149
162
113/127
119/134
128/141
87
89
91
40
82
64
143
149
162
113/169
119/178
128/188
104/121
110/124
116/128
10°C
(buried grease)
15
–
–
–
–
–
70
73
77
46
47
49
20
–
–
–
–
–
93
98
103
62
63
65
30
–
–
–
–
–
139
147
155
93
95
98
40
–
–
–
–
–
186
195
206
124
126
130
18°C
(indoors grease)
15
–
–
–
–
–
83
87
92
52
53
54
20
–
–
–
–
–
110
116
123
69
70
72
30
–
–
–
–
–
166
174
184
103
105
108
40
–
–
–
–
–
186
201
220
131
140
149
* When maximum circuit length is listed in:
•�black�type,�the�value�is�for�applications�with�a�4°C�maintain
•�red italic type, the value is for applications with a 43°C maintain
Example: Pipe Freeze Protection – Water Piping
Total heating cable length
315 ft of 5XL1-CR (from Step 3)
Supply voltage
120 V (from Step 1)
Minimum start-up temperature
–20°F (–29°C) (from Step 1)
number of circuits
315 ft / (210 ft max CL) = 1 .8 circuits
Round up to 2 circuits
Example: Flow Maintenance – Greasy Waste Line
Total heating cable length
223 ft of 12XL2-CT (from Step 3)
Supply voltage
208 V (from Step 1)
Minimum start-up temperature
50°F (10°C) (from Step 1)
number of circuits
223 ft / 428 ft = 0 .8 circuits
Round up to 1 circuit
25 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection and Flow Maintenance Design
DETERMInE TRAnSFORMER LOAD
Transformers must be sized to handle the load of the heating cable . Use the following tables
to calculate the total transformer load .
Table 11 Transformer Sizing (Amperes/foot)
Minimum start-up
temperature (°F)
5XL1
8XL1
5XL2
8XL2
12XL2
120
120
208
240
277
208
240
277
208
240
277
–20
0 .119
0 .159
0 .069
0 .067
0 .065
0 .092
0 .087
0 .082
0 .108
0 .106
0 .102
0
0 .105
0 .139
0 .060
0 .059
0 .057
0 .080
0 .076
0 .072
0 .100
0 .098
0 .095
20
0 .090
0 .120
0 .052
0 .051
0 .049
0 .069
0 .066
0 .062
0 .095
0 .093
0 .090
40
0 .075
0 .101
0 .043
0 .042
0 .041
0 .058
0 .055
0 .052
0 .084
0 .083
0 .080
50
–
–
–
–
–
0 .053
0 .050
0 .047
0 .079
0 .077
0 .075
65
–
–
–
–
–
0 .044
0 .042
0 .040
0 .072
0 .070
0 .067
Table 12 Transformer Sizing (Amperes/meter)
Minimum start-up
temperature (°C)
5XL1
8XL1
5XL2
8XL2
12XL2
120
120
208
240
277
208
240
277
208
240
277
–20
0 .391
0 .521
0 .226
0 .221
0 .215
0 .301
0 .286
0 .270
0 .354
0 .347
0 .336
–18
0 .343
0 .457
0 .198
0 .194
0 .188
0 .264
0 .251
0 .238
0 .329
0 .322
0 .312
–7
0 .294
0 .394
0 .170
0 .166
0 .161
0 .227
0 .216
0 .205
0 .311
0 .305
0 .296
4
0 .246
0 .331
0 .142
0 .139
0 .135
0 .191
0 .181
0 .172
0 .276
0 .271
0 .263
10
–
–
–
–
–
0 .172
0 .164
0 .155
0 .259
0 .254
0 .246
18
–
–
–
–
–
0 .145
0 .138
0 .130
0 .233
0 .228
0 .221
Use Table 11 or Table 12 to determine the applied voltage and the maximum A/ft (A/m) at the
minimum start up temperature to calculate the transformer load as follows:
Example: Pipe Freeze Protection – Water Piping
Total heating cable length
315 ft of 5XL1-CR (from Step 3)
Minimum start-up temperature
–20°F (–29°C) (from Step 1)
Circuit breaker sizing
30 A
1000
= Transformer
load (kW)
Max A/ft at minimum start-up temperature x Heating cable length (ft)
x Supply voltage
= (0.119 A/ft x 315 ft x 120 V) / 1000
= 4.5 kW
Transformer load (kW)
1000
Max A/ft at –20°F x Total feet
x Supply voltage
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
26 of 44
www.tycothermal.com
H55838 2/12
Example: Flow Maintenance – Greasy Waste Line
Total heating cable length
212 ft of 12XL2-CT (from Step 3)
Supply voltage
208 V
Minimum start-up temperature
50°F (10°C) (from Step 1)
Maximum circuit length
Tm = 110°F, 304 ft
Pipe Freeze Protection
and Flow Maintenance
2. Select the heating
cable
3. Determine the
heating cable length
4. Determine the
electrical parameters
5. Select the
connection kits and
accessories
6. Select the control
system
7. Select the power
distribution
8. Complete the Bill of
Materials
1. Determine design
conditions and heat
loss
Step Select the connection kits and accessories
All XL-Trace systems require a power connection and end seal kit . Splice and tee kits are
used as required . Use Table 13 on page 27 (for aboveground applications) and
Table 15 on page 29 (for buried applications) to select the appropriate connection kits .
note: Add extra cable on your Bill of Materials for power connections, tees, and end
seals . See Table 13 on page 27, Table 15 on page 29, and Table 16 on page 30 for
more information .
WARnInG: Approvals and performance are based on the use of Tyco Thermal
Controls-specified parts only . Do not substitute parts or use vinyl electrical tape .
AbOvEGROunD PIPInG
Fig. 14 RayClic connection system
Use the following table for general piping, standpipe sprinkler piping, and greasy waste and
fuel lines . Develop a bill of materials from the connection kits listed in this table .
note: Connection kits must be off the pipe when installed on greasy waste, fuel oil, or
pipes exceeding 150°F (65°C) .
= (0.079 A/ft x 212 ft x 208 V) / 1000
= 3.5 kW
Transformer load (kW)
1000
Max A/ft at 50°F x Total feet
x Supply voltage
RayClic-PT
powered
tee
RayClic-PC
powered connection
RayClic-S
splice
RayClic-X
cross tee
RayClic-T
tee
RayClic-PS
powered
splice
RayClic-LE
lighted end seal
RayClic-E
end seal
Alternate
lighted end seal
Alternate
connection kits
XL-Trace
heating cable
27 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection and Flow Maintenance Design
Table 13 Connection kits and Accessories for Aboveground Piping
Catalog number
Description
Standard
packaging
usage
Heating cable
allowance1
Connection kits
RayClic-PC
Power connection and end seal (RayClic-SB-04
pipe mounting bracket included)
1
1 per circuit
2 ft (0 .6 m)
RayClic-PS
Powered splice and end seal (RayClic-SB-04
pipe mounting bracket included)
1
1 per circuit
4 ft (1 .2 m)
RayClic-PT
Powered tee and end seal (RayClic-SB-04
pipe mounting bracket included)
1
1 per circuit
6 ft (1 .8 m)
FTC-P2
Power connection and end seal
note: FTC-P is required for circuits requiring
40 A circuit breakers .
1
1 per circuit
3 ft (0 .9 m)
RayClic-S
Splice
1
As required
2 ft (0 .6 m)
RayClic-T
Tee kit with end seal
1
As required
3 ft (0 .9 m)
R
RayClic-X
Cross connection to connect four heating
cables
1
As required
8 ft (2 .4 m)
FTC-HST3
Low-profile splice/tee
2
As required
3 ft (0 .9 m)
RayClic-Le
Lighted end seal (RayClic-SB-04 pipe
mounting bracket included)
1
Alternate end seal
2 ft (0 .6 m)
RayClic-e
extra end seal
1
Additional end seal
0 .3 ft (0 .1 m)
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
28 of 44
www.tycothermal.com
H55838 2/12
Table 13 Connection kits and Accessories for Aboveground Piping
Catalog number
Description
Standard
packaging
usage
Heating cable
allowance1
Accessories
RayClic-SB-04
Pipe mounting bracket
1
As required
–
RayClic-SB-02
Wall mounting bracket
1
As required
–
eTL
“electric-Traced” label
1
1 label per 10 feet
(3 m) of pipe
–
GT-66
Glass cloth adhesive tape
66 ft (20 m)
See Table 14
–
GS-54
Glass cloth adhesive tape
54 ft (20 m)
See Table 14
–
AT-180
Aluminum tape - required for installing
heating cable on plastic pipe
180 ft
(55 m)
1 ft/ft [0 .3 m/m] of
heating cable
–
1 Allow extra heating cable for ease of component installation .
2 Junction box not included .
3 One RayClic-e end seal is required for each FTC-HST used as a tee kit .
Table 14 quantity of Glass Cloth Adhesive Tape Required (attach at 1-foot intervals)
Pipe size (in)
<2
3
4
6
8
10
Feet of pipe per GT-66 roll
60 (18 m)
50 (15 m)
40 (12 m)
25 (8 m)
20 (6 m)
15 (5 m)
Feet of pipe per GS-54 roll
49 (15 m)
41 (13 m)
33 (10 m)
20 (6 m)
16 (5 m)
12 (4 m)
(Continued)
29 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection and Flow Maintenance Design
buRIED PIPInG
Fig. 15 Typical buried piping system
Use the following for buried water piping and greasy waste lines . note that all connections
must be aboveground and that no splices/tees are allowed . Develop a bill of materials from
the connection kits in this table .
Table 15 Connection kits and Accessories for buried Piping
Catalog number
Description
Standard
packaging
usage
Heating cable
allowance1
RayClic-PC
Power connection and end seal
(RayClic-SB-04 pipe mounting bracket
included)
1
1 per circuit
2 ft (0 .6 m)
FTC-XC
The FTC-XC power connection and end
seal kit is for use with XL-Trace heating
cable that is run through conduit to a junc-
tion box . Materials for one power connec-
tion and end seal is included in the kit .
note: FTC-XC is required for circuits
requiring 40 A circuit breakers .
1
1 per circuit
2 ft (0 .6 m)
RayClic-Le
Lighted end seal (RayClic-SB-04 pipe
mounting bracket included)
1
Alternate end seal
2 ft (0 .6 m)
RayClic-e
extra end seal
1
Additional end seal
0 .3 ft (0 .1 m)
RTD10CS
Insulation
Conduit
XL-Trace
heating cable
with -CT jacket
Ground
Alternate
power connection
Alternate
end seal
Ground
Wall
RayClic-LE*
RayClic-PC*
Junction box
RayClic-E
end seal
Conduit
Wall
with wall
mounting
bracket
with wall
mounting
bracket
FTC-XC
power
connection
*To protect the heating cable run it inside
Convolex tubing between the conduit and
the RayClic connection kits.
DigiTrace C910
Electronic controller
Conduit for
temperature
sensor
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
30 of 44
www.tycothermal.com
H55838 2/12
Table 15 Connection kits and Accessories for buried Piping
Catalog number
Description
Standard
packaging
usage
Heating cable
allowance1
Accessories
RayClic-SB-04
Pipe mounting bracket
1
As required
–
RayClic-SB-02
Wall mounting bracket
1
As required
–
eTL
“electric-Traced” label
1
1 label per 10 feet
(3 m) of pipe
–
GT-66
Glass cloth adhesive tape
66 ft (20 m)
See Table 16
–
GS-54
Glass cloth adhesive tape
54 ft (20 m)
See Table 16
–
AT-180
Aluminum tape - required for installing
heating cable on plastic pipe
180 ft (55 m)
1 ft/ft [0 .3 m/m] of
heating cable
–
1 Allow extra heating cable for ease of component installation .
Table 16 quantity of Glass Cloth Adhesive Tape Required (attach at 1-foot intervals)
Pipe size (in)
<2
3
4
6
8
10
Feet of pipe per GT-66 roll
60 (18 m)
50 (15 m)
40 (12 m)
25 (8 m)
20 (6 m)
15 (5 m)
Feet of pipe per GS-54 roll
49 (15 m)
41 (13 m)
33 (10 m)
20 (6 m)
16 (5 m)
12 (4 m)
(Continued)
31 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection and Flow Maintenance Design
Pipe Freeze Protection
and Flow Maintenance
2. Select the heating
cable
3. Determine the
heating cable length
4. Determine the
electrical parameters
5. Select the
connection kits and
accessories
6. Select the control
system
7. Select the power
distribution
8. Complete the Bill of
Materials
1. Determine design
conditions and heat
loss
Pipe Freeze Protection
and Flow Maintenance
Step Select the control system
Temperature controls save energy by ensuring that the system is energized only when
necessary . Tyco Thermal Controls offers a wide variety of monitoring and control options,
including:
•� Mechanical thermostats provide a cost effective control solution .
•� electronic thermostats provide higher accuracy of the heating cable circuit with
thermistor sensors .
•� electronic controllers provide superior accuracy with RTD temperature sensors, built-in
ground-fault protection, monitoring and alarm output .
•� Modbus® protocol communication over RS-485 system is supported using DigiTrace
Protonode multi-protocol gateways .
note: Fire sprinkler standpipe freeze protection requires DigiTrace C910, DigiTrace
C910-485 or ACCS-30 controllers with alarm relays connected to the fire control panel .
note: Greasy waste flow maintenance requires line sensing controllers such as the
DigiTrace eC-TS or DigiTrace C910, or the DigiTrace ACCS-30 .
Use the following table to identify the control system suitable for your application . Contact
your Tyco Thermal Controls representative or contact Tyco Thermal Controls directly at
(800) 545-6258 for more information .
Table 17 Temperature Control Options
Application
Electronic
thermostat
Electronic controllers
Single-point
Multipoint
EC-TS
DigiTrace C910*
ACCS-30
Ambient sensing
x
x
x
Line sensing
x
x
x
Buried pipe
x
x
x
Fire sprinklers
–
x
x
Sensor
Thermistor
See data sheet
See data sheet
Sensor length
–
10 ft
"
Set point range
30°F to 110°F
(–1°C to 43°C)
–76°F to 1058°F
(–60°C to 570°C)
"
enclosure
neMA 4X
neMA 4X
"
Differential
3°F (1 .6°C)
3°F (1 .6°C)
"
Set point repeatability
3°F (1 .6°C)
3°F (1 .6°C)
"
enclosure limits
–40°F to 140°F
(–40°C to 60°C)
–40°F to 140°F
(–40°C to 60°C)
"
Switch rating
30 A
30 A
"
Switch type
SPST
DPST
"
electrical rating
100–277 V
100–277 V
"
Approvals
c-UL-us
c-CSA-us
"
Ground-fault
protection
–
20 mA to 250 mA
"
Alarm outputs
"
AC relay
–
100–277 V, 0 .75 A
max .
"
Dry contact relay
–
48 Vac/dc, 500 mA
max .
"
* The C910-485 is available to provide RS-485 communication capability . Connect to the
BMS using DigiTrace Protonode multi-protocol gateways
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
32 of 44
www.tycothermal.com
H55838 2/12
Table 18 Control Systems
Catalog number
Description
Electronic Thermostats and Accessories
eC-TS
electronic thermostat housed in a neMA 4X enclosure with 2 x 1/2-in conduit entries for
power and one gland entry for the sensor . The temperature set point and LeD indicators
for alarm, power, and heating cable status can be visually checked through the clear lid .
electrical rating is 30 A at 100–277 V, 50–60 Hz, SPST switch . eC-TS includes a 25 ft
(7 .6 m) sensor .
SB-110
Pipe mounting bracket for eC-TS
Electronic Controllers and Sensors
C910
C910-485
The C910 is a compact, full-featured microprocessor-based single-point heat-trace control-
ler . The C910 provides control and monitoring of electrical heat-tracing circuits for both
freeze protection and temperature maintenance, and can be set to monitor and alarm for
high and low temperature, high and low current, ground-fault level, and voltage . The
DigiTrace C910 controller is available with an electromechanical relay (eMR) for use in
ordinary areas . The C910-485 comes with an RS-485 communication module .
ACCS-UIT2
ACCS-PCM2-5
The DigiTrace ACCS-30 Advanced Commercial Control System is a multipoint electronic
control and monitoring system for heat-tracing used in commercial freeze protection and
flow maintenance applications . The DigiTrace ACCS-30 system can control up to 260 circuits
with multiple networked ACCS-PCM2-5 panels, with a single ACCS-UIT2 user interface ter-
minal . The ACCS-PCM2-5 panel can directly control up to 5 individual heat-tracing circuits
using electromechanical relays rated at 30 A up to 277 V .
By FieldServer Technologies
www.ProtoCessor.com
PROTOCESSOR
SERIAL ETHERNET
PROTONODE
FRAME GND
- PWR
+PWR
RS 485+
RS 485 -
RS 485 GND
S3
S2
S1
S0
B3
B2
B1
B0
A7
A6
A5
A4
A3
A2
A1
A0
Protonode-LeR
Protonode-ReR
The DigiTrace Protonode is an external, high performance multi-protocol gateway for
customers needing protocol translation between Building Management Systems (BMS) and
the DigiTrace ACCS-30 or C910-485 controllers .
The Protonode-LeR is for LonWorks® systems; and the Protonode-ReR is for BACnet® or
Metasys® n2 systems .
RTD-200
RTD3CS
RTD10CS
Three-wire RTD (Resistance Temperature Device) used with DigiTrace C910 and ACCS-30
controllers .
RTD-200: 6-ft (1 .8 m) fluoropolymer with 1/2-in nPT bushing
RTD3CS: 3-ft (0 .9 m) flexible armor with 1/2-in nPT bushing
RTD10CS: 10-ft (3 m) flexible armor with 1/2-in nPT bushing
33 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection and Flow Maintenance Design
2. Select the heating
cable
3. Determine the
heating cable length
4. Determine the
electrical parameters
5. Select the
connection kits and
accessories
6. Select the control
system
7. Select the power
distribution
8. Complete the Bill of
Materials
Pipe Freeze Protection
and Flow Maintenance
1. Determine design
conditions and heat
loss
Pipe Freeze Protection
and Flow Maintenance
Step Select the power distribution
Once the heating cable circuits have been defined, you must select how to provide power to
them . Power to the XL-Trace heating cables can be provided in several ways: directly through
the temperature control, through external contactors, or through HTPG power distribution
panels .
SInGLE CIRCuIT COnTROL
Heating cable circuits that do not exceed the current rating of the selected temperature
control device shown in Table 18 can be switched directly (see Fig . 16) .
GROuP COnTROL
If the current draw exceeds the switch rating, or if the controller will activate more than one
circuit (group control, an external contactor must be used (see Fig . 16 on page 33) .
Large systems with many circuits should use an HTPG power distribution panel . The HTPG
is a dedicated power-distribution, control, ground-fault protection, monitoring, and alarm
panel for freeze protection and broad temperature maintenance heat-tracing applications .
This enclosure contains an assembled circuit-breaker panelboard . Panels are equipped with
ground-fault circuit breakers with or without alarm contacts . The group control package al-
lows the system to operate automatically in conjunction with an ambient-sensing thermostat,
individual electronic, or duty cycle controller .
Fig. 16 Single circuit and group control
Single circuit control
Group control
Temperature
controller
1-pole
GFEP breaker
1
N
G
Heating
cable
ø
ø supply
C
Temperature
controller
Contactor
1-pole
GFEP breaker
N
G (Typ 3)
ø2
ø1
ø3
3-phase 4-wire
supply (WYE)
3-pole main
breaker
ø
ø
1 supply
N
Heating cable
sheath, braid
or ground
Heating cable
sheath, braid
or ground
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
34 of 44
www.tycothermal.com
H55838 2/12
Fig. 17 HTPG power distribution panel
Fig. 18 HTPG power schematic
A
COMMON ALARM
PUSH TO ACKNOWLEDGE
HAND/OFF/AUTO
1
2
3
4
5
6
7
8
9
10
11
12
Main circuit
breaker
Main
contactor
Distribution
panelboard
Fuse holder
C
POWER ON
TB 1
TB 2
AR
R
Ground
bus bar
Selector switch
Alarm relay
(optional)
Terminals
(optional)
Push button for
light testing
Alarm horn (optional)
Alarm option shown above
Door
disconnect
(optional)
N
Ø1
Three-pole main
circuit breaker
Panel
energized
Contactor
coil
C
NC
External controller/
thermostat*
Hand
Auto
Off
Three-pole main
contactor
Ø3
Ø2
Power
connection
Heating cable
One-pole with 30-mA
ground-fault trip
(120/277 Vac)
Two-pole with 30-mA
ground-fault trip
(208/240 Vac)
Alarm
remote
annunciation
(with alarm
option)
Heating
cable
circuit
Heating
cable
circuit
G
End seal
Heating cable shealth, braid or ground
Three-phase, 4 wire supply (Wye)
35 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
Pipe Freeze Protection and Flow Maintenance Design
Table 19 Power Distribution
Catalog number
Description
Power Distribution
A
COMMON ALARM
PUSH TO ACKNOWLEDGE
HAND/OFF/AUTO
C
POWER ON
HTPG
Heat-tracing power distribution panel with ground-fault and monitoring for group control .
Contactors
e104
Three-pole, 100 Amp per pole, 600 V maximum contactor housed in UL Listed, CSA
Certified, neMA 4X enclosure with two 1-inch conduit entries . When ordering, select coil
voltage (110–120, 208–240, 277 V) .
enclosure dimensions: 13-1/2 in x 9-1/5 in x 6-11/16 in (343 mm x 234 mm x 170 mm) .
e304
Three-pole, 40 Amp per pole, 600 V maximum contactor housed in UL Listed, CSA Certified
neMA 4X enclosure with two 1-inch conduit entries . When ordering, select coil voltage
(110–120, 208–240, 277 V) .
enclosure dimensions: 9-1/2 in x 7-1/5 in x 6-11/16 in (241 mm x 183 mm x 170 mm) .
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
36 of 44
www.tycothermal.com
H55838 2/12
2. Select the heating
cable
3. Determine the
heating cable length
4. Determine the
electrical parameters
5. Select the
connection kits and
accessories
6. Select the control
system
7. Select the power
distribution
8. Complete the Bill of
Materials
Pipe Freeze Protection
and Flow Maintenance
1. Determine design
conditions and heat
loss
Pipe Freeze Protection
and Flow Maintenance
Step Complete the bill of Materials
If you used the Design Worksheet to document all your design parameters, you should have
all the details necessary complete your Bill of Materials .
37 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
XL-Trace System Pipe Freeze Protection and Flow Maintenance Design Worksheet
XL-Trace System Pipe Freeze Protection and Flow Maintenance Design Worksheet
Step Determine design conditions and pipe heat loss
Design conditions
XL-Trace
application
Location
Maintain
temp.
(Tm)
Max.
system
temp.
(Tmax)
Min.
ambient
temp.
(Ta)
Pipe diameter
and material
Pipe length
Thermal insulation
type and thickness
Pipe freeze protection
Water piping
Indoors
Outdoors
Aboveground
Buried
______
______
______
____ in
Metal
Plastic
_____ ft (m)
Fiberglass
________ ____ in
Sprinkler piping
Indoors
Outdoors
Aboveground
Buried
______
______
______
____ in
Metal
Plastic
_____ ft (m)
Fiberglass
________ ____ in
Flow maintenance
Greasy waste
lines
Indoors
Outdoors
Aboveground
Buried
______
______
______
____ in
Metal
Plastic
_____ ft (m)
Fiberglass
________ ____ in
Fuel lines
Indoors
Outdoors
Aboveground
Buried
______
______
______
____ in
Metal
Plastic
_____ ft (m)
Fiberglass
________ ____ in
Example:
0 Water piping
0 Aboveground
0 Outdoor
40°F
80°F
–20°F
2 in
0 Plastic
300 ft
0 Fiberglass
1 in
Pipe heat loss
Calculate temperature differential DT
Pipe maintain temperature (TM)
°F (°C)
Ambient temperature (TA)
°F (°C)
TM
∆T
−
=
Example: Pipe Freeze Protection − Water Piping
TA
Pipe maintain temperature (TM)
°F
(from Step 1)
(from Step 1)
Ambient temperature (TA)
°F
TM
∆T
40 °F
40 °F
−20 °F
−20 °F
60 °F
−
=
TA
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
38 of 44
www.tycothermal.com
H55838 2/12
Determine the pipe heat loss: See Table 2 for the base heat loss of the pipe (Qb) . If the DT for your system is not listed, interpolate between the two
closest values .
QB-50 ∆T1
W/ft (W/m)
QB-100 ∆T2
W/ft (W/m)
QB
W/ft (W/m)
in
in
°F (°C)
W/ft (W/m)
W/ft (W/m)
Example: Pipe Freeze Protection − Water Piping
Pipe diameter
2 in
1 in
60°F
Insulation thickness
3.2 W/ft
6.8 W/ft
∆T
QB-50
QB-100
Pipe diameter
Insulation thickness
∆T
QB-50
QB-50
∆T 60°F is 20% of the distance between ∆T 50°F and ∆T 100°F
QB-50 + [0.20 x (QB-100 − QB-50)]
∆T interpolation
3.2 + [0.20 x (6.8 − 3.2)] = 3.9 W/ft
QB-60
3.9 W/ft @ TM 40°F
Pipe heat loss (QB-60)
39 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
XL-Trace System Pipe Freeze Protection and Flow Maintenance Design Worksheet
Compensate for insulation type and pipe location
See Table 2 for the pipe heat loss (Qb) . If the DT for your system is not listed, interpolate between the two closest values .
See Table 3 for indoor multiple
See Table 4 for insulation multiple
QB
QCORRECTED
QB
x
=
W/ft (W/m)
Insulation multiple
Indoor multiple (if applicable)
Location
Insulation thickness and type
Insulation multiple
x
Indoor multiple
(if applicable)
Example: Pipe Freeze Protection − Water Piping
Location
Aboveground, indoor
1-in fiberglass
Thermal insulation thickness and type
3.9 W/ft @ TM 40°F
Indoor multiple
1.00
Insulation multiple
N/A
3.9 W/ft
1.00
3.9 W/ft @ TM 40°F
QCORRECTED
QB
x
==
=
Insulation multiple
QB
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
40 of 44
www.tycothermal.com
H55838 2/12
Step Select the heating cable
Power output data: See Fig . 13
Power output correction factors: See Table 5
Heating cable temperature ratings: See Table 6
Select outer jacket
-CR
-CT
Example: Pipe Freeze Protection – Water Piping
5XL1-CR
Power at rated V factor
x
Pipe maintain temperature (TM)
(from Step 1)
(from Step 1)
(from Step 1)
(from Step 1)
(from Step 1)
(from Step 1)
(from Step 1)
(from Step 1)
Corrected heat loss (QCORRECTED)
Supply voltage
Pipe material (metal or plastic)
XL-Trace application (water, fuel oil, or greasy waste)
Pipe freeze protection: general water piping, sprinkler piping
Flow maintenance: greasy waste lines, fuel lines
Maximum system use temperature (TMAX)
Plastic pipe correction factor
=
Corrected power
Heating cable selected
Power at TM (120/208 V)
Power output correction factor
Plastic pipe correction factor
If No, then design with additional runs of heating cable or thicker thermal insulation.
EYes
No
E
Maintain temperature (TM)
40°F
3.9 W/ft @ TM 40°F
120 V
plastic
QB = 3.9 W/ft @ TM 40°F
Select curve C: 5XL1 = 5.6 W/ft @ 40°F
Power output correction factor: 120 V = 1.00
Pipe material correction factor: Plastic = 0.75
Corrected heating cable power: 5.6 @/ft x 1.00 x 0.75 = 4.2 W/ft
Select: 5XL1
Maximum system temperature (TMAX): 80°F
Maximum heating cable exposure temperature (TEXP): 150°F
TMAX < TEXP: Yes
Corrected heat loss (QCORRECTED)
Supply voltage
Pipe material (metal or plastic*)
(*AT-180 aluminum tape required for
installing heating cable on plastic pipes)
Example: Pipe Freeze Protection − Water Piping
CORRECTED
41 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
XL-Trace System Pipe Freeze Protection and Flow Maintenance Design Worksheet
Step Determine the heating cable length
For additional heating cable allowance for valves: See Table 7 .
For additional heating cable allowance for pipe supports and flanges: See Table 8 .
Pipe length
(
)
x
+
Total heating cable
length required
Number of heating
cable runs
Total heating cable length
Heat sinks
=
Additional cable for valves,
pipe supports, and flanges
Type of valves
x
Total heating cable
for valves
How many
=
Additional heating cable
Type of pipe supports
x
Total heating cable
for pipe supports
How many
=
Additional heating cable
*2-in pipe diameter = 0.17 ft
Type of flanges
x
Total heating cable
for flanges
How many
=
Additional heating cable
Total heating cable for heat sinks:
Pipe length
(
)
x
+
Total heating cable
length required
300 ft
1
15 ft
315 ft
Number of heating
cable runs
Total heating cable length
Heat sinks
=
Additional cable for valves,
pipe supports, and flanges
Type of valves
x
Total
Gate valves
3
4.3 ft
12.9 ft
How many
=
Additional heating cable
Example:
Type of pipe supports
x
Total
Pipe hangers noninsulated
and U-bolt supports
5
(0.17 ft* x 2 = 0.34 ft)
1.7 ft
How many
=
Additional heating cable
*2-in pipe diameter = 0.17 ft
Type of flanges
x
Total
n/a
0
0
0 ft
How many
=
Additional heating cable
14.6 ft rounded up to 15 ft
Total:
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
42 of 44
www.tycothermal.com
H55838 2/12
Step Determine the electrical parameters
Determine maximum circuit length and number of circuits
See Table 9 and Table 10 .
Determine transformer load
See Table 11 and Table 12 .
201 ft
315 ft
1.6 circuits, round up to 2
315 ft of 5XL1-CR
−20°F
201 ft
/
=
Number of circuits
Maximum heating cable circuit length
Total heating cable length required
T 120 V T 208 V
T 240 V T 277 V
Total heating cable length required
Supply voltage:
T 15 A T 20 A
T 30 A T 40 A
Circuit breaker size:
Minimum start-up temperature
Maximum circuit length
/
=
Number of circuits
Maximum heating cable circuit length
Total heating cable length required
T 120 V T 208 V
T 240 V T 277 V
Total heating cable length required
Supply voltage:
T 15 A T 20 A
T 30 A T 40 A
Circuit breaker size:
Minimum start-up temperature
Maximum circuit length
Example:
9
9
x
/ 1000 =
Transformer
load (kW)
0.119 A/ft
315 ft
120 V
4.5 kW
Max A/ft at minimum start-up temperature
Heating cable length
x
Supply voltage
Example:
x
/ 1000 =
Transformer
load (kW)
Max A/ft at minimum start-up temperature
Heating cable length
x
Supply voltage
43 of 44
2. Fire Sprinkler
System Freeze
Protection
1. Pipe Freeze
Protection and
Flow Maintenance
3. Roof and Gutter
De-Icing
4. Surface Snow
Melting – MI
5. Surface Snow
Melting and Anti-
Icing – ElectroMelt
6. Freezer Frost
Heave Prevention
7. Floor Heating
8. Technical Data
Sheets
XL-Trace System Pipe Freeze Protection and Flow Maintenance Design Worksheet
Step Select the connection kits and accessories
See Table 13 .
Connection kits – Aboveground
Description
quantity
Heating cable allowance
RayClic-PC
RayClic-PS
RayClic-PT
FTC-P
RayClic-S
RayClic-T
RayClic-X
FTC-HST
RayClic-Le
RayClic-e
Power connection and end seal
Power splice and end seal
Powered tee and end seal
Power connection and end seal
Splice
Tee kit with end seal
Cross connection
Low-profile splice/tee
Lighted end seal
extra end seal
____________
____________
____________
____________
____________
____________
____________
____________
____________
____________
__________________
__________________
__________________
__________________
__________________
__________________
__________________
__________________
__________________
__________________
Connection kits – buried
Description
quantity
Heating cable allowance
RayClic-PC
FTC-XC
RayClic-Le
RayClic-e
Power connection and end seal
Power splice and end seal
Lighted end seal
extra end seal
____________
____________
____________
____________
__________________
__________________
__________________
__________________
Accessories – Aboveground and buried
Description
quantity
RayClic-SB-04
RayClic-SB-02
eTL
GT-66
GS-54
AT-180
Pipe mounting bracket
Wall mounting bracket
“electric-Traced” label
Glass cloth adhesive tape
Glass cloth adhesive tape
Aluminum tape (for plastic pipes)
_____________
_____________
_____________
_____________
_____________
_____________
+
=
Total heating cable
length required
Total heating cable allowance for connection kits
Total heating cable length
Total heating cable
allowance for connection kits
PIPe FReeze PROTeCTIOn AnD FLOW MAInTenAnCe
44 of 44
www.tycothermal.com
H55838 2/12
Step Select the control system
See Table 18 .
Thermostats, controllers
and accessories
Description
quantity
eC-TS
SB-110
DigiTrace C910
ACCS-UIT2
ACCS-PCM2-5
Protonode-LeR
Protonode-ReR
RTD3CS
RTD10CS
RTD-200
electronic thermostat with 25-ft sensor
Pipe mounting bracket for eC-TS
Microprocessor-based single-point heat-tracing controller
ACCS-30 user interface terminal
ACCS-30 power control panel
Multi-protocol gateway
Multi-protocol gateway
Resistance temperature device
Resistance temperature device
Resistance temperature device
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
_____________
Step Select the power distribution
See Table 19 .
Power distribution
Description
quantity
HTPG
Heat-tracing power distribution panel for group control
_____________
Contactors
Description
quantity
e104
e304
Three-pole, 100 Amp per pole contactor
Three-pole, 40 Amp per pole contactor
_____________
_____________
Step Complete the bill of Materials
Use the information recorded in this worksheet to complete the Bill of Materials .
© 2012 Tyco Thermal Controls LLC
Important: All information, including illustrations, is believed to be reliable. Users, however, should independently evaluate the
suitability of each product for their particular application. Tyco Thermal Controls makes no warranties as to the accuracy or
completeness of the information, and disclaims any liability regarding its use. Tyco Thermal Controls' only obligations are those
in the Tyco Thermal Controls Standard Terms and Conditions of Sale for this product, and in no case will Tyco Thermal Controls
or its distributors be liable for any incidental, indirect, or consequential damages arising from the sale, resale, use, or misuse of
the product. Specifications are subject to change without notice. In addition, Tyco Thermal Controls reserves the right to make
changes—without notification to Buyer—to processing or materials that do not affect compliance with any applicable specification.
Worldwide Headquarters
Tyco Thermal Controls
7433 Harwin Drive
Houston, TX 77036
USA
Tel: 800-545-6258
Tel: 650-216-1526
Fax: 800-527-5703
Fax: 650-474-7711
[email protected]
www.tycothermal.com
Europe, Middle East, Africa
Tyco Thermal Controls
Romeinse straat 14
3001 Leuven
België / Belgique
Tel: +32 16 213 511
Fax: +32 16 213 603
Canada
Tyco Thermal Controls
250 West St.
Trenton, Ontario K8V 5S2
Canada
Tel: 800-545-6258
Fax: 800-527-5703
Tel: 613-392-6571
Fax: 613-392-3999
Latin America
Tyco Thermal Controls
Al. Araguaia, 2044 – Sala.1101,
Bloco B
Edificio CEA – Alphaville
Barueri – Sao Paulo – Brasil
06455-000
Tel: +55 11 2588 1400
Fax: +55 11 2588 1410
Asia Pacific
Tyco Thermal Controls
20F, Innovation Building,
1009 Yi Shan Rd,
Shanghai 200233, P.R.China
Tel: +86 21 2412 1688
Fax: +86 21 5426 2937 / 5426 3167
Tyco, Alliance Integrated Systems, AMC, AutoMatrix, AutoSol, BTV, CapaciSense, Chemelex, DHSX, DigiTrace, DigiTrace logo,
DigiTrace Supervisor, Duoterm, ElectroMelt, EM2XR, FHSM, FHSC, FlexFit, FlexiClic, Flowguard, FreezeTrace, FreezGard,
Frostex, Frostex Plus, Frostguard, FroStop, FSE, Gardian, HAK, Handvise, HBTV, HCCL, HotCap, HQTV, HTPG, HTPI, HWAT, HXTV,
IceStop, Interlock, JBM, JBS, K-Flex, K-Flex logo, KHE, KHH, KHL, KHP, KTV, Labsafe, LBTV, LHC, LHFV, LHRV, Metabond, Mini
WinterGard, Miser WinterGard, MoniTrace, Multi-plus, NGC, PetroTrace, PLI, PolyMatrix, Pyro CiC, PyroFLX, Pyromaster, Pyropak,
Pyrosil, PyroSizer, Pyrotenax, Pyrotenax Designer, Pyrotenax logo, QTVR, QuickNet, QuickNet logo, QuickStat, QuickTerm,
RayClic, RaySol, RayStat, Retro WinterGard, RHS, RHSC, RHSM, RMM2, SBF, SBV, SC, SHC, Sheathmaster, ShowerGuard, SLBTV,
Smart Heat for Comfort and Safety, SnoCalc, SnoCalc logo, STS, System 500, System 1850, System 1850-SE, System 2000,
System 2200, T2, T2 logo, T2Blue, T2QuickNet, T2Red, T2Reflecta, TankCalc Plus, TempBus, Thermoheat, ThermoLimit, Thermo-
Line, Total Care in Heat-tracing, Touch, Trac-Loc, Trac Calc, TraceCalc Net, TraceCalc Net logo, TraceCalc Pro logo, TraceGuard 277,
TraceMaster, Tracer, Tracer logo, TRACERLYNX, TRACERLYNX logo, TraceStat, TraceTek, TraceTek logo, TruckPak, VLBTV, VLKTV, VPL,
We manage the heat you need, WinterGard, WinterGard logo, WinterGard Plus, WinterGard Wet, XL-ERATE, XL-ERATE logo, XL-Trace,
XTV and Zero EMI are registered and/or unregistered trademarks of Tyco Thermal Controls LLC or its affiliates.
All other trademarks are the property of their respective owners.