Indicating and adjustment module PLICSCOM

Document ID: 36433 Indication and adjustment

About this document

1.1 Function. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.2 Target group . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 1.3 Symbolism used. . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 2 For your safety 2.1 Authorised personnel . . . . . . . . . . . . . . . . . . . . . . . . 5 2.2 Appropriate use . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2.3 Warning about misuse . . . . . . . . . . . . . . . . . . . . . . . 5 2.4 General safety instructions . . . . . . . . . . . . . . . . . . . . 5 2.5 CE conformity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6 2.6 Fulfillment of NAMUR recommendations . . . . . . . . . . 6 2.7 Environmental instructions. . . . . . . . . . . . . . . . . . . . . 6 3 Product description 3.1 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 3.2 Principle of operation . . . . . . . . . . . . . . . . . . . . . . . . 7 3.3 Packaging, transport and storage . . . . . . . . . . . . . . . 8 4 Prepare setup 4.1 Insert indicating and adjustment module. . . . . . . . . . . 9 4.2 Adjustment system . . . . . . . . . . . . . . . . . . . . . . . . . . 10 5 Set up - Sensors up to SW 3.99 5.1 Adjustment menu for all signal outputs. . . . . . . . . . . . 11 5.2 Adjustment menu 4 … 20 mA/HART . . . . . . . . . . . . . 18 5.3 Adjustment menu Profibus PA. . . . . . . . . . . . . . . . . . 21 6 Set up - Sensors from HW 2.0.0 and SW 4.0.0 6.1 Adjustment menu for all signal outputs. . . . . . . . . . . . 24 6.2 Adjustment menu 4 … 20 mA/HART . . . . . . . . . . . . . 30 7 Maintenance and fault rectification 7.1 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32 7.2 How to proceed in case of repair. . . . . . . . . . . . . . . . 32 8 Dismount 8.1 Dismounting steps . . . . . . . . . . . . . . . . . . . . . . . . . . 33 8.2 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33 9 Supplement 9.1 Technical data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34 9.2 Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35 2 Indicating and adjustment module PLICSCOM Contents 36433-EN-091104

Safety instructions for Ex areas

Please note the Ex-specific safety information for installation and operation in Ex areas. These safety instructions are part of the operating instructions manual and come with the Ex-approved instruments. Indicating and adjustment module PLICSCOM 3 Contents 36433-EN-091104

1 About this document

1.1 Function This operating instructions manual provides all the information you need for mounting, connection and setup as well as important instructions for maintenance and fault rectification. Please read this information before putting the instrument into operation and keep this manual accessible in the immediate vicinity of the device. 1.2 Target group This operating instructions manual is directed to trained qualified personnel. The contents of this manual should be made available to these personnel and put into practice by them. 1.3 Symbolism used Information, tip, note This symbol indicates helpful additional information. Caution: If this warning is ignored, faults or malfunctions can result. Warning: If this warning is ignored, injury to persons and/or serious damage to the instrument can result. Danger: If this warning is ignored, serious injury to persons and/or destruction of the instrument can result. Ex applications This symbol indicates special instructions for Ex applications. l List The dot set in front indicates a list with no implied sequence. à Action This arrow indicates a single action. 1 Sequence Numbers set in front indicate successive steps in a procedure. 4 Indicating and adjustment module PLICSCOM 1 About this document 36433-EN-091104

2 For your safety

2.1 Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the required personal protective equipment must always be worn. 2.2 Appropriate use The pluggable indicating and adjustment module is used for measured value indication, adjustment and diagnoses with level and pressure sensors. You can find detailed information on the application range in chapter "Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions. 2.3 Warning about misuse Inappropriate or incorrect use of the instrument can give rise to application-specific hazards, e.g. vessel overfill or damage to system components through incorrect mounting or adjustment. 2.4 General safety instructions This is a state-of-the-art instrument that fulfils the prevailing regulations and guidelines. The instrument must only be operated in a technically flawless and reliable condition. The operator is responsible for the trouble-free operation of the instrument. During the entire duration of use, the user is obliged to determine the compliance of the required occupational safety measures with the current valid rules and regulations and also take note of new regulations. The safety instructions in this operating instructions manual, the national installation standards as well as the valid safety regulations and accident prevention rules must be observed by the user. For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbitrary conversions or modifications are explicitly forbidden. The safety approval markings and safety tips on the device must be also observed. Indicating and adjustment module PLICSCOM 5 2 For your safety 36433-EN-091104

The device fulfills the legal requirements of the applicable EC

guidelines. By attaching the CE mark, VEGA provides a confirmation of successful testing. You can find the CE conformity declaration in the download area of www.vega.com. 2.6 Fulfillment of NAMUR recommendations The requirements of the following NAMUR recommendations are fulfilled: l NE 21 - "Electromagnetic Compatiblity Act of the process and laboratory control technology" The sensors as well as the corresponding indicating and adjustment components are generally upward and downward compatible. 2.7 Environmental instructions Protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental protection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observing the environmental instructions in this manual: l Chapter "Packaging, transport and storage" l Chapter "Disposal" 6 Indicating and adjustment module PLICSCOM 2 For your safety 36433-EN-091104

3 Product description

3.1 Configuration This operating instructions manual applies to the following hardware and software versions of the indicating and adjustment module: l Hardware from 1.0.0 l Software from 1.0.0 The indicating/adjustment module consists of a display with full dot matrix as well as four keys for adjustment. A background lighting is optionally integrated and can be adjusted via the adjustment menu. The display can be optionally equipped with heating to ensure good readability at low temperatures down to -40 °C (-40 °F). The scope of delivery encompasses: l Indicating and adjustment module l Documentation - this operating instructions manual - Supplementary instructions manual 31708 "Heating for in- dicating and adjustment module" (optional) 3.2 Principle of operation The indicating and adjustment module is used for measured value indication, adjustment, and diagnostics for the following VEGA plics® sensors: l VEGAPULS series 60 l VEGAFLEX series 60 l VEGASON series 60 l VEGABAR series 50 and 60 l VEGACAL series 60 The indicating and adjustment module is mounted in the sensor housing. After installation, the sensor as well as the indicating and adjustment module are splash-proof, even without housing cover. Another installation possibility is the external indicating and adjustment unit VEGADIS 61. The operation of two indicating and adjustment module in parallel in the sensor and in VEGADIS 61 however is not supported. The functional range of the indicating and adjustment module is determined by the sensr and corresponds to the respective software version of the sensor. Power is supplied directly by the respective sensor or by VEGADIS 61. An additional connection is not necessary. Scope of the operating instructions manual Instrument versions Scope of delivery Application area Functional range Power supply Indicating and adjustment module PLICSCOM 7 3 Product description 36433-EN-091104

The backlight is also powered by the sensor or via VEGADIS 61.

Prerequisite for this is a supply voltage at a certain level. The exact voltage specifications can be found in the operating instructions manual of the respective sensor. The optional heating requires its own power supply. You can find further details in the supplementary instructions manual "Heating for indicating and adjustment module". 3.3 Packaging, transport and storage Your instrument was protected by packaging during transport. Its capacity to handle normal loads during transport is assured by a test according to DIN EN 24180. The packaging of standard instruments consists of environment- friendly, recyclable cardboard. For special versions, PE foam or PE foil is also used. Dispose of the packaging material via specialised recycling companies. Transport must be carried out under consideration of the notes on the transport packaging. Nonobservance of these instructions can cause damage to the device. The delivery must be checked for completeness and possible transit damage immediately at receipt. Ascertained transit damage or concealed defects must be appropriately dealt with. Up to the time of installation, the packages must be left closed and stored according to the orientation and storage markings on the outside. Unless otherwise indicated, the packages must be stored only under the following conditions: l Not in the open l Dry and dust free l Not exposed to corrosive media l Protected against solar radiation l Avoiding mechanical shock and vibration l Storage and transport temperature see chapter "Supplement - Technical data - Ambient conditions" l Relative humidity 20 … 85 % Packaging Transport Transport inspection Storage Storage and transport temperature 8 Indicating and adjustment module PLICSCOM 3 Product description 36433-EN-091104

4 Prepare setup

4.1 Insert indicating and adjustment module The indicating and adjustment module can be inserted into the sensor and removed again at any time. It is not necessary to interrupt the power supply. Proceed as follows: 1 Unscrew the housing cover 2 Place the indicating and adjustment module in the desired position on the electronics (you can choose any one of four different positions - each displaced by 90°) 3 Press the indicating and adjustment module onto the electronics and turn it to the right until it snaps in. 4 Screw housing cover with inspection window tightly back on Removal is carried out in reverse order. The indicating and adjustment module is powered by the sensor, an additional connection is not necessary. Fig. 1: Insert indicating and adjustment module Note: If you intend to retrofit the instrument with an indicating and adjustment module for continuous measured value indication, a higher cover with an inspection glass is required. Mount/Dismount indica- ting and adjustment mo- dule Indicating and adjustment module PLICSCOM 9 4 Prepare setup 36433-EN-091104

Fig. 2: Indicating and adjustment elements

1 LC display 2 Adjustment keys l [OK] key: - Move to the menu overview - Confirm selected menu - Edit parameter - Save value l [->] key: - Presentation change measured value - list entry - Select editing position l [+] key: - Change value of the parameter l [ESC] key: - interrupt input - Jump to next higher menu The sensor is adjusted via the four keys of the indicating and adjustment module. The LC display indicates the individual menu items. The functions of the individual keys are shown in the above illustration. Approx. 10 minutes after the last pressing of a key, an automatic reset to measured value indication is triggered. Any values not confirmed with [OK] will not be saved. Key functions Adjustment system 10 Indicating and adjustment module PLICSCOM 4 Prepare setup 36433-EN-091104

5 Set up - Sensors up to SW 3.99

5.1 Adjustment menu for all signal outputs With the parameter adjustment, the instrument is adapted to the application conditions. The parameter adjustment is carried out via an adjustment menu. Information: In this operating instructions, all general parameters are described. Additional instrument-specific parameters are described in the operating instructions of the respective sensor. The following presentations are available in the measured value display: l Level as digital value, sensor TAG l Level as digital value and bar graph, sensor TAG l Only with pressure transmitters: Level or pressure as digital value, temperature value With [->] you select the different presentations of the measured value. You can reach the menu overview from any presentation with [OK]. With [ESC] you return from the menu overview to the measured value display. The main menu is divided into five areas with the following functions: ▶ Basic adjustment Display Diagnostics Service Info To damp process-dependent measured value fluctuations, you have to set an integration time of 0 … 999 s in this menu item. Depending on the sensor type, the factory setting is 0 s or 1 s. Damping 0 s In this menu item you select the linearization curve: l linear l Horizontal cylindrical tank l Spherical tank Measured value indica- tion Main menu Basic adjustment/Dam- ping Basic adjustment/Li- nearization curve Indicating and adjustment module PLICSCOM 11 5 Set up - Sensors up to SW 3.99 36433-EN-091104

User programmable means: Switching on a linearization curve

programmed via PC and PACTware A linearization is necessary for all vessels in which the vessel volume does not increase linearly with the level - e. g. in a horizontal cylindrical or spherical tank - and the indication or output of the volume is required. Corresponding linearization curves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume. The linearisation applies to the measured value indication and the current output. By activating the appropriate curve, the volume percentage of the vessel is displayed correctly. If the volume should not be displayed in percent but e.g. in l or kg, a scaling can also be set in the menu item "Display". Factory setting is linear. Linearisation curve linear Caution: Note the following, if the respective sensor is used as part of an overfill protection system according to WHG: If a linearisation curve is selected, the measuring signal is no longer compulsorily linear proportional to the level. This must be taken into consideration by the user, particularly when adjusting the switching point on the level switch. In the menu item "Sensor-TAG" you edit a 12-digit measurement loop name. An unambiguous designation can hence be assigned to the sensor, e.g. the measurement loop name or the tank or product designation. In digital systems and in the documentation of larger plants, a singular designation should be entered for exact identification of individual measuring sites. The available digits comprise: l Letters from A … Z l Numbers from 0 … 9 l Special characters +, -, /, - Factory setting is "Sensor". Sensor-TAG Sensor Basic adjustment/Sen- sor TAG 12 Indicating and adjustment module PLICSCOM 5 Set up - Sensors up to SW 3.99 36433-EN-091104

An integrated background lighting can be adjusted via the adjustment

menu. The function depends on the height of the supply voltage, see operating instructions of the respective sensor. In the default setting, the lightning is switched off. Min. and max. measured values are saved in the sensor. The values are displayed in the menu item "Peak values". l Min. and max. distance in m(d): Radar, guided microwave, ultrasonic sensors l Min. and max. pressure: pressure transmitter1) l Min. and max. temperature: ultrasonic sensors, pressure trans- mitters Pointer When non-contact level sensors are used, the measurement can be influenced by the respective process conditions. In this menu item, the measurement reliability of the level echo is displayed as dB value. The measurement reliability equals signal strength minus noise. The higher the value, the more reliable the measurement. With a functioning measurement, the values are > 10 dB. In this menu item, the device status is displayed. If the sensor detects a fault, "OK" will be displayed. If a fault is detected, a flashing failure message is outputted sensor-specifically, e.g. "E013". The fault is also displayed in clear text, e.g. "No measurement value". Information: The fault message as well as the clear text indication are also carried out in the measured value display. Meas. reliability Sensor status 1) Pressure: -50 … +150 % of the nominal pressure range; temperature: -50 … +150 °C. Display/Lighting Diagnosis/Pointer Diagnosis/Measurement reliability Diagnosis/Device status Indicating and adjustment module PLICSCOM 13 5 Set up - Sensors up to SW 3.99 36433-EN-091104

With ultrasonic and radar sensors as well as sensors with guided

microwave, the "Echo curve" represents the signal strength of the echoes over the measuring range. The units of the signal strength are "dB" (ultrasonic and radar) and "Volt" (guided microwave). The signal strength enables the assessment of the quality of the measurement. With ultrasonic and radar sensors, the "False echo curve" represents the saved false echoes (see menu "Service") of the empty vessel with signal strength in "dB" over the measuring range. Up to 3000 measured values are recorded (depending on the sensor) when starting a "Trend curve". Then the values can be displayed on a time axis. The oldest measured values are always deleted. In the menu item "Choose curve", the respective curve is selected. Curve selection Echo curve ▼ Information: The trend recording is not activated when being shipped. It must be started by the user via the menu item "Start trend curve". A comparison of echo and false echo curve allows a more detailled specification on the measurement reliability. The selected curve is updated permanently. With the [OK] key, a submenu with zoom functions is opened. The following functions are available with "Echo and false echo curve": l "X-Zoom": Zoom function for the meas. distance l "Y-Zoom": 1, 2, 5 and 10-fold signal magnification in "dB" l "Unzoom": Reset the presentation to the nominal measuring range with single magnification In the menu item "Trend curve" the following are available: l "X-Zoom": Resolution - 1 minute - 1 hour - 1 day l "Stop/Start": Interrupt a recording or start a new recording l "Unzoom": Reset the resolution to minutes As default setting, the recording pattern has 1 minute. With the adjustment software PACTware, this pattern can be also set to 1 hour or 1 day. Diagnosis/Curve selec- tion Diagnosis/Curve pre- sentation 14 Indicating and adjustment module PLICSCOM 5 Set up - Sensors up to SW 3.99 36433-EN-091104

In this menu item you simulate a user-defined level or pressure value

via the current output. This allows you to test the signal path, e.g. through connected indicating instruments or the input card of the control system. The following simulation variables are available: l Percent l Current l Pressure (with pressure transmitters) l Distance (with radar and guided microwave) With Profibus PA sensors, the selection of the simulated value is made via the "Channel" in the menu "Basic adjustments". How to start the simulation: 1 Push [OK] 2 Select the requested simulation variable with [->] and confirm with [OK] 3 Set the requested numerical value with [+] and [->]. 4 Push [OK] The simulation is now running, with 4 … 20 mA/HART a current is outputted and with Profibus PA or Foundation Fieldbus a digital value. How to interrupt the simulation: à Push [ESC] Information: The simulation is terminated automatically 10 minutes after the last key has been pushed. Simulation Start simulation? With the reset function, modified values are reset. Three subfunctions are available: l Basic adjustment - Reset the values modified with the indicating and adjustment module to the sensor-specific basic setting l Factory setting Service/Simulation Service/Reset Indicating and adjustment module PLICSCOM 15 5 Set up - Sensors up to SW 3.99 36433-EN-091104

As basic adjustment, but also reset of special parameters to

the default values2) l Peak values measured value and temperature3) - Reset of the min./max. values of pressure, level and temper- ature to the current values Information: Because the reset values are nearly sensor-specifc, they are listed in the operating instructions manual of the respective sensor. Reset Select reset? In this menu item you select the internal arithmetic unit of the sensor. With radar, guided microwave and ultrasonic sensors this is m(d) or ft(d). For pressure transmitters more comprehensive units are available. They are described in the operating instructions manual of the respective sensor in the menu "Basic adjustments". Unit of measurement m(d) The sensor is already set to the ordered national language. In this menu item you can change the language. The following languages are available, e.g. in software version 3.50: l Deutsch l English l Français l Espanõl l Pycckuu l Japanese l Italiano l Netherlands l Japanese l Chinese 2) Special parameters are parameters which are set customer-specifically on the service level with the adjustment software PACTware. 3) Temperature only with pressure transmitters and ultrasonic sensors. Service/Adjustment unit Service/Language 16 Indicating and adjustment module PLICSCOM 5 Set up - Sensors up to SW 3.99 36433-EN-091104

With this function

l Load parameter adjustment data from the sensor into the indicating and adjustment module l Write parameter adjustment data from the indicating and adjust- ment module into the sensor The data are permanently saved in an EEPROM memory in the indicating and adjustment module and remain there even in case of power failure. From there, they can be written in one or several sensors or kept as backup for a probable sensor exchange. Kind and volume of the copied data depend on the respective sensor. Information: Before writing the data into the sensor, it is checked if the data fit the sensor. If data do not fit, a fault signal is triggered or the function is blocked. When writing data into the sensor, you will see from which instrument type the data originate and which TAG-no. this sensor had. The following items are checked: l Software version l WHG approval l SIL activated l Measuring principle l Radar C-band/K-band l Radar measuring range < 30 m or > 30 m l Signal output l Pressure measuring range Copy sensor data Copy sensor data? In this menu item, the PIN is activated/deactivated permanently. Entering a 4-digit PIN protects the sensor data against unauthorized access and unintentional modifications. If the PIN is activated permanently, it can be deactivated temporarily (i.e. for approx. 60 min.) in any menu item. The instrument is delivered with the PIN set to 0000. Service/Copy sensor data Service/PIN Indicating and adjustment module PLICSCOM 17 5 Set up - Sensors up to SW 3.99 36433-EN-091104

Only the following functions are permitted with activated PIN:

l Select menu items and show data l Read data from the sensor into the indicating/adjustment module. In this menu item the most important sensor information can be displayed: l Instrument type l Serial number: 8-digit number, e.g. 12345678 Instrument type Serial number 12345678 l Date of manufacture: Date of the factory calibration, e.g. 10. January 2008 l Software version: Edition of the sensor software, e.g. 3.50 Date of manufacture 10. January 2008 Software version 3.50 l Date of last change using PC: Date of the last change of sensor parameters via PC, e.g. 10. January 2008 Last change using PC 10. January 2008 l Sensor details, e.g. approval, process fitting, seal, measuring cell, measuring range, electronics, housing, cable entry, plug, cable length etc. Sensor characteristics Display now? 5.2 Adjustment menu 4 … 20 mA/HART In the menu item "Display" you can define how the measured value should be presented on the display. Info/Info Display/Display 18 Indicating and adjustment module PLICSCOM 5 Set up - Sensors up to SW 3.99 36433-EN-091104

The following values can be displayed:

l Height l Pressure (only with pressure transmitters) l Distance (only with radar, guided microwave, ultrasonics) l Current l Scaled l Percent l Lin. percent l Temperature (only with pressure transmitters). The selection "scaled" opens the menu items "Display unit" and "Scaling". In "Display unit" there are the following options: l Height l Mass l Flow l Volume l Without unit Depending on selection, the different units are in turn available. In the menu item "Scaling", the requested numerical value with decimal point is entered for 0 % and 100 % of the measured value. There is the following relation between the indication value in the menu "Display" and the adjustment unit in the menu "Basic adjustment": l With radar, guided microwave and ultrasonics, displayed value "Distance" means: presentation of the measured value in the selected adjustment unit, e.g. m(d) l With pressure, displayed value "Pressure" or "Height" means: presentation of the measured value in the selected adjustment unit, e.g. bar or m. Displayed value Scaled ▼ Display unit Volume ▼ l ▼ Scaling 0 % = 0.0 l 100 % = 100.0 l In the menu item "Current output" you determine the behaviour of the current output during operation and in case of failure. The following options are available: Service/Current output Indicating and adjustment module PLICSCOM 19 5 Set up - Sensors up to SW 3.99 36433-EN-091104

4 … 20 mA

20 … 4 mA Failure mode4) Hold value 20.5 mA 22 mA < 3.6 mA Min. current5) 3.8 mA 4 mA Max. current6) 20 mA 20.5 mA The values in bold font represent the data of the factory setting. In HART multidrop mode, the current is constantly 4 mA. This value does not change even in case of failure. Current output Output mode: 4-20 mA ▼ Failure mode: 22 mA ▼ Min. current 3.8 mA ▼ The functional safety is already activated Ex factory for instruments with SIL qualification. For instruments Ex factory without SIL qualification, the functional safety must be activated by the user for applications according to SIL via the indicating and adjustment module. The SIL factory setting cannot be deactivated by the user. The activation of SIL has the following impact: l In the menu item "Failure mode" under "Current output", the parameters "Hold value" and "20.5 mA" are blocked l In the menu item "HART mode", the function "Multidrop" is blocked Note: For such applications, it is absolutely necessary to take note of "Safety Manual". HART offers standard and multidrop mode. The mode standard with the fixed address 0 means output of the measured value as 4 … 20 mA signal. 4) Value of the current output in case of failure, e.g. if no valid measured value is delivered. 5) This value is not underrun during operation. 6) This value is not exceeded during operation. Service/Functional safe- ty (SIL) Service/HART mode 20 Indicating and adjustment module PLICSCOM 5 Set up - Sensors up to SW 3.99 36433-EN-091104

In Multidrop mode, up to 15 sensors can be operated on one two-wire

cable. An address between 1 and 15 must be assigned to each sensor.7) In this menu item you determine the HART mode and enter the address for multidrop. HART mode Standard Address 0 The default setting is standard with address 0. 5.3 Adjustment menu Profibus PA Level and pressure sensors operate as slaves on the Profibus PA. To be identified as a bus participant, each sensor must have a unique address. Each instrument is delivered with address 126. With this address, it can at first be connected to an existing bus. However, the address must be changed. This can be done in this menu item. Sensor address 126 The channel is the input selector switch for function block (FB) of the sensor. Within the function block, additional scalings (Out-Scale) are carried out. In this menu item, the value fir the function block is selected: l SV1 (Secondary Value 1): - Percent with radar, guided microwave and ultrasonic sensors - Pressure or height with pressure transmitters l SV2 (Secondary Value 2): - Distance with radar, guided microwave and ultrasonic sensors - Percent with pressure transmitters l PV (Primary Value): - Linearised percentage value Channel PV lin. value 7) The 4 … 20 mA signal of the HART sensor is switched off. The sensor consumes a constant current of 4 mA. The measuring signal is transmitted exclusively as digital HART signal. Basic adjustment/Sen- sor address Channel Indicating and adjustment module PLICSCOM 21 5 Set up - Sensors up to SW 3.99 36433-EN-091104

Radar, guided microwave and ultrasonic sensors deliver the following

measured values: l SV1 (Secondary Value 1): Percentage value after the adjustment l SV2 (Secondary Value 2): Distance value before the adjustment l PV (Primary Value): Linearised percentage value l PA-Out (value after passing the function block): PA output A pressure transmitter delivers the following measured values: l SV1 (Secondary Value 1): Pressure or height value before adjustment l SV2 (Secondary Value 2): Percentage value after the adjustment l PV (Primary Value): Linearised percentage value l PA-Out (value after passing the function block): PA output l Temperature In the menu item "Display" you can define which measured value should be presented on the display. Displayed value PA-Out Profibus transmits two values cyclically. The first value is determined in the menu item "Channel". The selection of the additional cyclical value is made in the menu item "Additional PA value". The following values are available with radar, guided microwave and ultrasonic sensors: l SV1 (Secondary Value 1): Percentage value after the adjustment l SV2 (Secondary Value 2): Distance value before the adjustment l PV (Primary Value): Linearised percentage value With pressure transmitters the following values are available: l SV1 (Secondary Value 1): Pressure or height value before adjustment l SV2 (Secondary Value 2): Percentage value after the adjustment l PV (Primary Value): Linearised percentage value Additional PA value Display/Display Service/Additional PA value 22 Indicating and adjustment module PLICSCOM 5 Set up - Sensors up to SW 3.99 36433-EN-091104

Here, you determine the unit and scaling for PA-Out. These settings

also apply to the values displayed on the indicating and adjustment module if in the menu item "Displayed value" PA-Out was selected. The following displayed values are available in "Out-Scale unit": l Pressure (only with pressure transmitters) l Height l Mass l Flow l Volume l Others (no unit, %, mA) In the menu item "PV-Out-Scale", the requested numerical value with decimal point is entered for 0 % and 100 % of the measured value. Out-Scale-Unit Service/Determine Out- Scale Indicating and adjustment module PLICSCOM 23 5 Set up - Sensors up to SW 3.99 36433-EN-091104

6 Set up - Sensors from HW 2.0.0 and SW 4.0.0

6.1 Adjustment menu for all signal outputs With the parameter adjustment, the instrument is adapted to the application conditions. The parameter adjustment is carried out via an adjustment menu. Information: In this operating instructions, all general parameters are described. Further, instrument-specific parameters are described in the operating instructions of the respective sensor. The following presentations are available in the measured value display: l Level as digital value, sensor TAG l Level as digital value and bar graph, sensor TAG With [->] you select the different presentations of the measured value. You can reach the menu overview from any presentation with [OK]. With [ESC] you return from the menu overview to the measured value display. The main menu is divided into five areas with the following functions: Setup: Contains settings for medium, application, vessel, adjustment, signal output as well as device TAGs Display: Contains language changeover, settings to the indicated measured value as well as for lighting Diagnosis: Contains information on pointer, reliability, echo curve and simulation Additional settings: Contains false signal suppression, linearization curve, sensor length, reset, adjustment unit, SIL function, HART mode Info: Shows instrument type, serial number, software version, last change, sensor characteristics Measured value indica- tion Main menu 24 Indicating and adjustment module PLICSCOM 6 Set up - Sensors from HW 2.0.0 and SW 4.0.0 36433-EN-091104

In the menu item "Sensor-TAG" you edit a 12-digit measurement loop

name. An unambiguous designation can hence be assigned to the sensor, e.g. the measurement loop name or the tank or product designation. In digital systems and in the documentation of larger plants, a singular designation should be entered for exact identification of individual measuring sites. The available digits comprise: l Letters from A … Z l Numbers from 0 … 9 l Special characters +, -, /, - To damp process-dependent measured value fluctuations, you have to set an integration time of 0 … 999 s in this menu item. Depending on the sensor type, the factory setting is 0 s or 1 s. In the delivery status, the sensor is set to the ordered national language. This menu item enables the setting of another national language. The optionally integrated background lighting can be adjusted via the adjustment menu. The function depends on the height of the supply voltage, see operating instructions of the respective sensor. The lighting is switched off in the delivery status. Setup/Measurement loop name Setup/Damping Display/Language Display/Lighting Indicating and adjustment module PLICSCOM 25 6 Set up - Sensors from HW 2.0.0 and SW 4.0.0 36433-EN-091104

In this menu item, the device status is displayed.

Min. and max. measured values are saved in the sensor. The values are displayed in the menu item "Peak values". In this menu item, the electronics temperature is displayed. In this menu item you simulate measured values via the current output. This allows the signal path to be tested, e.g. via connected indicating instruments or the input card of the processing system. Information: With Profibus PA sensors, the selection of the simulated value is made via the "Channel" in the menu "Basic adjustments". How to start the simulation: 1 Push [OK] 2 Select the requested simulation variable with [->] and confirm with [OK] 3 Set the requested numerical value with [+] and [->]. 4 Push [OK] The simulation is now running, with 4 … 20 mA/HART a current is outputted and with Profibus PA or Foundation Fieldbus a digital value. Diagnosis/Device status Diagnosis/Pointer Diagnosis/Electronics temperature Diagnosis/Simulation 26 Indicating and adjustment module PLICSCOM 6 Set up - Sensors from HW 2.0.0 and SW 4.0.0 36433-EN-091104

How to interrupt the simulation:

à Push [ESC] Information: The simulation is terminated automatically 10 minutes after the last key has been pushed. In this menu item, you select the measured variable of the system. A linearization is necessary for all vessels in which the vessel volume does not increase linearly with the level - e. g. in a horizontal cylindrical or spherical tank - and the indication or output of the volume is required. Corresponding linearization curves are preprogrammed for these vessels. They represent the correlation between the level percentage and vessel volume. The linearisation applies to the measured value indication and the current output. By activating the appropriate curve, the volume percentage of the vessel is displayed correctly. If the volume should not be displayed in percent but e.g. in l or kg, a scaling can be also set in the menu item "Display". Caution: Note the following, if the respective sensor is used as part of an overfill protection system according to WHG: If a linearisation curve is selected, the measuring signal is no longer compulsorily linear proportional to the level. This must be taken into consideration by the user, particularly when adjusting the switching point on the level switch. Additional settings/De- vice settings Further settings/Linear- ization Indicating and adjustment module PLICSCOM 27 6 Set up - Sensors from HW 2.0.0 and SW 4.0.0 36433-EN-091104

In this menu item, the PIN is activated/deactivated permanently.

Entering a 4-digit PIN protects the sensor data against unauthorized access and unintentional modifications. If the PIN is activated permanently, it can be deactivated temporarily (i.e. for approx. 60 min.) in any menu item. The instrument is delivered with the PIN set to 0000. Caution: With active PIN, the adjustment via PACTware/DTM as well as other systems is also blocked. Only the following functions are permitted with activated PIN: l Select menu items and show data l Read data from the sensor into the indicating/adjustment module. In delivery status, the PIN is "0000". The instrument has an internal clock. With this function the sensor settings are copied. The following functions are available: l Store data from the sensor into the indicating/adjustment module. l Store data from the indicating and adjustment module in the sensor The following data or settings for adjustment of the indicating and adjustment module are saved: l All data of the menu "Setup" and "Display" l In the menu "Additional settings" the items "Distance unit, temperature unit and linearization" l The values of the user programmable linearization curve Additional settings/PIN Further settings/Date and time Further settings/Copy sensor settings 28 Indicating and adjustment module PLICSCOM 6 Set up - Sensors from HW 2.0.0 and SW 4.0.0 36433-EN-091104

The copied data are permanently saved in an EEPROM memory in the

indicating and adjustment module and remain there even in case of power failure. From there, they can be written into one or more sensors or kept as backup for a possible sensor exchange. Kind and volume of the copied data depend on the respective sensor. Note: Before the data are stored in the sensor, a check is carried out to determine if the data fit the sensor. If the data do not fit, a fault signal is triggered or the function is blocked. When data are being written into the sensor, the display shows which instrument type the data originate from and which TAG-no. this sensor had. In this menu, you read out the instrument name and the instrument serial number: In this menu item, the hardware and software version of the sensor is displayed. In this menu item, the date of factory calibration of the sensor as well as the date of the last change of sensor parameters are displayed via the indicating and adjustment module or via the PC. Info/Instrument type Info/Sensor version Info/Calibration date Indicating and adjustment module PLICSCOM 29 6 Set up - Sensors from HW 2.0.0 and SW 4.0.0 36433-EN-091104

In this menu item, the features of the sensor such as approval, process

fitting, seal, measuring range, electronics, housing and others are displayed. 6.2 Adjustment menu 4 … 20 mA/HART In the menu item "Current output mode" you determine the output characteristics and the fault mode of the current output. In the menu item "Current output Min./Max.", you determine the reaction of the current output during operation and in case of failure. In this menu item, you define how the measured value is displayed. There is the following relationship between the indication value in the menu "Display" and the adjustment unit in the menu "Device settings": Sensor characteristics Setup/Current output mode Setup/Current output Min./Max. Display/Displayed value 30 Indicating and adjustment module PLICSCOM 6 Set up - Sensors from HW 2.0.0 and SW 4.0.0 36433-EN-091104

With radar, guided microwave and ultrasonic sensors, displayed

value "Distance" means: presentation of the measured value in the selected adjustment unit, e.g. m(d) l With pressure transmitters, displayed value "Pressure" or "Height" means: presentation of the measured value in the selected adjustment unit, e.g. bar or m. In this menu item, you define the scaling of the measured value on the display. In the menu item "Scaling", the requested numerical value with decimal point is entered for 0 % and 100 % of the measured value. In this menu item, you define the scaling of the measured value on the display. The sensor offers the HART modes standard and Multidrop. In this menu item you determine the HART modes and enter the address with Multidrop. The mode standard with the fixed address 0 means output of the measured value as 4 … 20 mA signal. In Multidrop mode, up to 63 sensors can be operated on one two-wire cable. An address between 1 and 126 must be assigned to each sensor.8) The default setting is standard with address 0. 8) The 4 … 20 mA signal of the HART sensor is switched off. The sensor consumes a constant current of 4 mA. The measuring signal is transmitted exclusively as digital HART signal. Display/Scaling size Display/Scaling Further settings/HART mode Indicating and adjustment module PLICSCOM 31 6 Set up - Sensors from HW 2.0.0 and SW 4.0.0 36433-EN-091104

7 Maintenance and fault rectification

7.1 Maintenance When the device is used correctly, no maintenance is required in normal operation. 7.2 How to proceed in case of repair If a repair is necessary, please proceed as follows: You can download a return form (23 KB) from our Internet homepage www.vega.com under: "Downloads - Forms and certificates - Repair form". By doing this you help us carry out the repair quickly and without having to call back for needed information. l Print and fill out one form per instrument l Clean the instrument and pack it damage-proof l Attach the completed form and, if need be, also a safety data sheet outside on the packaging l Please ask the agency serving you for the address of your return shipment. You can find the respective agency on our website www.vega.com. 32 Indicating and adjustment module PLICSCOM 7 Maintenance and fault rectification 36433-EN-091104

Before dismounting, be aware of dangerous process conditions such

as e.g. pressure in the vessel, high temperatures, corrosive or toxic products etc. Take note of chapters "Mounting" and "Connecting to power supply" and carry out the listed steps in reverse order. 8.2 Disposal The instrument consists of materials which can be recycled by specialised recycling companies. We use recyclable materials and have designed the electronics to be easily separable. WEEE directive 2002/96/EG This instrument is not subject to the WEEE directive 2002/96/EG and the respective national laws. Pass the instrument directly on to a specialised recycling company and do not use the municipal collecting points. These may be used only for privately used products according to the WEEE directive. Correct disposal avoids negative effects to persons and environment and ensures recycling of useful raw materials. Materials: see chapter "Technical data" If you have no possibility to dispose of the old instrument professionally, please contact us concerning return and disposal. Indicating and adjustment module PLICSCOM 33 8 Dismount 36433-EN-091104

approx. 150 g (0.33 lbs)

Ambient conditions Ambient temperature -15 … +70 °C (+5 … +158 °F) Storage and transport temperature -40 … +80 °C (-40 … +176 °F) Indicating and adjustment module Voltage supply and data transmission through the sensor Indication LC display in dot matrix Adjustment elements 4 keys Protection rating - unassembled IP 20 - mounted into the sensor without cover IP 40 Materials - Housing ABS - Inspection window Polyester foil Display light Power supply through the sensor, voltage range see sensor operating instructions manual 34 Indicating and adjustment module PLICSCOM 9 Supplement 36433-EN-091104

Fig. 3: Dimensions PLICSCOM

Indicating and adjustment module PLICSCOM 35 9 Supplement 36433-EN-091104

Industrial property rights

VEGA product lines are global protected by industrial property rights. Further information see http://www.vega.com. Only in U.S.A.: Further information see patent label at the sensor housing. VEGA Produktfamilien sind weltweit geschützt durch gewerbliche Schutzrechte. Nähere Informationen unter http://www.vega.com. Les lignes de produits VEGA sont globalement protégées par des droits de propriété intellectuelle. Pour plus d'informations, on pourra se référer au site http://www.vega.com. VEGA lineas de productos están protegidas por los derechos en el campo de la propiedad industrial. Para mayor información revise la pagina web http://www.vega.com. Линии продукции фирмы ВЕГА защищаются по всему миру правами на интеллектуальную собственность. Дальнейшую информацию смотрите на сайте http://www.vega.com. VEGA系列产品在全球享有知识产权保护。 进一步信息请参见网站。 9.4 Trademark All the brands as well as trade and company names used are property of their lawful proprietor/originator. 36 Indicating and adjustment module PLICSCOM 9 Supplement 36433-EN-091104

Additional PA value

- Primary Value 22 - Secondary Value 22 Adjustment system 10 Application area 7 C Channel with Profibus PA 21 Copy sensor data 17 Copy sensor settings 28 Current output 19 Current output Min./Max. 30 D Damping 11, 25 Date of manufacture 29 Date/Time 28 Display 18 Display with Profibus PA 22 Displayed value 30 E Echo curve 14 Electronics temperature 26 F Functional range 7 Functional safety (SIL) 20 H HART mode - Multidrop 20, 31 - Standard 20, 31 I Info 18 Instrument type 29 Instrument versions 7 K Key function 10 L Language 16, 25 Lighting 13, 25 Linearisation 27 Linearisation curve 11 M Main menu 11, 24 Meas. reliability 13 Measured value indication 11, 24 Measured value presentation 18 Measured variable of the system 27 Measurement loop name 25 O Out-Scale with Profibus PA 23 P PIN 17, 28 Pointer 13, 26 Power supply 7 R Reset 15 S Scaling measured value for display 31 Scaling of the measured value for display 31 Sensor address Profibus PA 21 Sensor characteristics 30 Sensor status 13, 26 Sensor version 29 Sensor-TAG 12 Simulation 15, 26 U Unit of measurement 16 Indicating and adjustment module PLICSCOM 37 Index 36433-EN-091104

VEGA Grieshaber KG

Am Hohenstein 113 77761 Schiltach Germany Phone +49 7836 50-0 Fax +49 7836 50-201 E-mail: [email protected] www.vega.com Printing date: ISO 9001� All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing systems correspond to the information avail- able at the time of printing. © VEGA Grieshaber KG, Schiltach/Germany 2009 Subject to change without prior notice 36433-EN-091104