Quick setup guide

Radar sensor for continuous level measurement of liquids VEGAPULS 64 4 … 20 mA/HART - two-wire Document ID: 51462

VEGAPULS 64 • 4 … 20 mA/HART - two-wire

51462-EN-160111 Contents 1 For your safety 1.1 Authorised personnel ....................................................................................................... 3 1.2 Appropriate use ................................................................................................................ 3 1.3 Warning about incorrect use ............................................................................................. 3 1.4 General safety instructions ............................................................................................... 3 1.5 CE conformity ................................................................................................................... 4 1.6 NAMUR recommendations .............................................................................................. 4 1.7 Radio license for Europe .................................................................................................. 4 1.8 Environmental instructions ............................................................................................... 4 2 Product description 2.1� Configuration .................................................................................................................... 6 3 Mounting 3.1 Mounting preparations, mounting strap ............................................................................ 7 3.2 Mounting instructions ....................................................................................................... 7 4 Connecting to power supply 4.1 Connecting ....................................................................................................................... 9 4.2 Wiring plan, single chamber housing.............................................................................. 10 5 Set up with the display and adjustment module 5.1 Insert display and adjustment module ............................................................................ 12 5.2 Parameter adjustment - Quick setup .............................................................................. 13 5.3 Parameter adjustment - Extended adjustment................................................................ 15 6 Supplement 6.1 Technical data ................................................................................................................ 21 Information: This quick setup guide enables quick setup and commissioning of your instrument. You�can�find�supplementary�information�in�the�corresponding,�more� detailed Operating Instructions Manual as well as the Safety Manual that�comes�with�instruments�with�SIL�qualification.�These�manuals�are� available on the supplied DVD or in the download area of "www.vega. com". Operating instructions VEGAPULS 64 - 4 … 20 mA/HART - two- wire: Document-ID 51141 Editing status of the quick setup guide: 2015-12-04

1 For your safety

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 1 For your safety 1.1 Authorised personnel All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator. During work on and with the device the required personal protective equipment must always be worn. 1.2 Appropriate use VEGAPULS 64 is a sensor for continuous level measurement. You�can�find�detailed�information�about�the�area�of�application�in� chapter "Product description". Operational reliability is ensured only if the instrument is properly used�according�to�the�specifications�in�the�operating�instructions� manual as well as possible supplementary instructions. 1.3 Warning about incorrect use Inappropriate or incorrect use of the instrument can give rise to application-specific�hazards,�e.g.�vessel�overfill�or�damage�to�system� components through incorrect mounting or adjustment. Also the pro- tective�characteristics�of�the�instrument�can�be�influenced.� 1.4 General safety instructions This is a state-of-the-art instrument complying with all prevailing regulations and guidelines. The instrument must only be operated in a technically�flawless�and�reliable�condition.�The�operator�is�responsible� for the trouble-free operation of the instrument. During the entire duration of use, the user is obliged to determine the compliance of the necessary occupational safety measures with the current valid rules and regulations and also take note of new regula- tions. The safety instructions in this operating instructions manual, the na- tional installation standards as well as the valid safety regulations and accident prevention rules must be observed by the user. For safety and warranty reasons, any invasive work on the device beyond that described in the operating instructions manual may be carried out only by personnel authorised by the manufacturer. Arbi- trary�conversions�or�modifications�are�explicitly�forbidden. The safety approval markings and safety tips on the device must also be observed. Depending on the instrument version, the emitting frequencies are in the C, K or W band range. The low emitting frequencies are far below the internationally approved limit values. When used correctly, the device poses no danger to health.

1 For your safety

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 1.5 CE conformity The�device�fulfills�the�legal�requirements�of�the�applicable�EC�guide- lines.�By�affixing�the�CE�marking,�we�confirm�successful�testing�of�the� product. You�can�find�the�CE�Certificate�of�Conformity�in�the�download�section� of our homepage. 1.6 NAMUR recommendations NAMUR is the automation technology user association in the process industry in Germany. The published NAMUR recommendations are accepted�as�the�standard�in�field�instrumentation. The�device�fulfills�the�requirements�of�the�following�NAMUR�recom- mendations: • NE 21 – Electromagnetic compatibility of equipment • NE 43 – Signal level for malfunction information from measuring transducers • NE�53�–�Compatibility�of�field�devices�and�display/adjustment� components • NE�107�–�Self-monitoring�and�diagnosis�of�field�devices For further information see www.namur.de. 1.7 Radio license for Europe The instrument is approved according to EN 302372-1/2 V1.2.1 (2011-02) for use in closed vessels. For operation inside of closed vessels, the following conditions must be�fulfilled: • The instrument must be permanently mounted on a closed vessel made of metal, reinforced concrete, or comparable attenuating materials. • Flanges,�process�fittings�and�mounting�accessories�must�ensure� the microwave impermeability of the vessel and not let the radar signal escape to the outside • If necessary, existing viewing windows in the vessel must be coated with a microwave impermeable material (e.g. electrically conductive coating) • Manholes�and�flanges�on�the�vessel�must�be�closed�and�sealed�to� avoid penetration of the radar signal • The instrument should be preferably mounted on top of the vessel with antenna orientation downward • The instrument must only be installed and maintained by appropri- ately�qualified�staff 1.8 Environmental instructions Protection of the environment is one of our most important duties. That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection.�The�environment�management�system�is�certified�according� to DIN EN ISO 14001.

1 For your safety

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 Please�help�us�fulfill�this�obligation�by�observing�the�environmental� instructions in this manual: • Chapter "Packaging, transport and storage" • Chapter "Disposal"

2 Product description

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 2 Product description 2.1� Configuration The�type�label�contains�the�most�important�data�for�identification�and� use of the instrument: 2 1 12 11 10 9 5 6 4 3 7 8 Fig. 1: Layout of the type label (example) 1 Instrument type 2 Product code 3 License label 4 Power supply and signal output, electronics 5 Protection rating 6 Measuring range 7 Process and ambient temperature, process pressure 8 Material, wetted parts 9 Serial number of the instrument 10 Data-Matrix-Code for smartphone app 11 Symbol of the device protection class 12 Reminder to observe the instrument documentation The type label contains the serial number of the instrument. With it you�can�find�the�following�instrument�data�on�our�homepage: • Product code (HTML) • Delivery date (HTML) • Order-specific�instrument�features�(HTML) • Operating instructions and quick setup guide at the time of ship- ment (PDF) • Order-specific�sensor�data�for�an�electronics�exchange�(XML) • Test�certificate�(PDF)�-�optional Go to www.vega.com "VEGA Tools" and "Instrument search". Enter the serial number. Alternatively, you can access the data via your smartphone: • Download the smartphone app "VEGA Tools" from the "Apple App Store" or the "Google Play Store" • Scan the Data Matrix code on the type label of the instrument or • Enter the serial number manually in the app Type label Serial number - Instru- ment search

VEGAPULS 64 • 4 … 20 mA/HART - two-wire

51462-EN-160111 3 Mounting 3.1 Mounting preparations, mounting strap The mounting strap is supplied unassembled (optionally) and must be screwed to the sensor before setup with three hexagon socket screws M5 x 10 and spring washers. Max. torque, see chapter "Technical data".�Required�tools:�Allen�wrench�size�4. There�are�two�different�variants�of�screwing�the�strap�to�the�sensor,� see following illustration: 1 2 Fig. 2: Mounting strap for screwing to the sensor 1 For angle of inclination in steps 2� For�angle�of�inclination,�infinitely�variable Depending on the selected variant, the sensor can be rotated in the strap: • Single chamber housing – Angle of inclination in three steps 0°, 90° and 180° – Angle�of�inclination�180°,�infinitely�variable • Double chamber housing – Angle�of�inclination�90°,�infinitely�variable – Angle of inclination in two steps 0° and 90° 3.2 Mounting instructions Radar sensors for level measurement emit electromagnetic waves. The�polarization�is�the�direction�of�the�electrical�component�of�these� waves. The�polarization�direction�is�marked�by�a�nose�on�the�housing,�see� following drawing: 1 Fig. 3: Position of the polarisation 1 Nose for marking the direction of polarisation Polarisation

VEGAPULS 64 • 4 … 20 mA/HART - two-wire

51462-EN-160111 Information: When�the�housing�is�rotated,�the�direction�of�polarization�changes� and�hence�the�influence�of�the�false�echo�on�the�measured�value.� Please keep this in mind when mounting or making changes later. When mounting the sensor, keep a distance of at least 200 mm (7.874 in) from the vessel wall. If the sensor is installed in the center of dished or round vessel tops, multiple echoes can arise. However, these can be suppressed by an appropriate adjustment (see chapter "Setup"). If you cannot maintain this distance, you should carry out a false signal storage during setup. This applies particularly if buildup on the vessel wall is expected. In such cases, we recommend repeating the false signal storage at a later date with existing buildup. > 200 mm (7.87") Fig. 4: Mounting of the radar sensor on round vessel tops In vessels with conical bottom it can be advantageous to mount the sensor in the center of the vessel, as measurement is then possible down to the lowest point of the vessel bottom. Fig. 5: Mounting of the radar sensor on vessels with conical bottom Installation position

4 Connecting to power supply

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 4 Connecting to power supply 4.1 Connecting The voltage supply and signal output are connected via the spring- loaded terminals in the housing. Connection to the display and adjustment module or to the interface adapter is carried out via contact pins in the housing. Information: The terminal block is pluggable and can be removed from the electronics. To do this, lift the terminal block with a small screwdriver and pull it out. When reinserting the terminal block, you should hear it snap in. Proceed as follows: 1. Unscrew the housing lid 2. If a display and adjustment module is installed, remove it by turn- ing it slightly to the left. 3. Loosen compression nut of the cable gland and remove blind plug 4. Remove approx. 10 cm (4 in) of the cable mantle, strip approx. 1 cm (0.4 in) of insulation from the ends of the individual wires 5. Insert the cable into the sensor through the cable entry Fig. 6: Connection steps 5 and 6 - Single chamber housing Connection technology Connection procedure

4 Connecting to power supply

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 Fig. 7: Connection steps 5 and 6 - Double chamber housing 6. Insert the wire ends into the terminals according to the wiring plan Information: Solid�cores�as�well�as�flexible�cores�with�wire�end�sleeves�are�insert- ed�directly�into�the�terminal�openings.�In�case�of�flexible�cores�without� end sleeves, press the terminal from above with a small screwdriver, the terminal opening is then free. When the screwdriver is released, the terminal closes again. You�can�find�further�information�on�the�max.�wire�cross-section�under� "Technical data - Electromechanical data" 7. Check the hold of the wires in the terminals by lightly pulling on them 8. Connect the screen to the internal ground terminal, connect the external ground terminal to potential equalisation 9. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable 10. Reinsert the display and adjustment module, if one was installed 11. Screw the housing lid back on The�electrical�connection�is�finished. 4.2 Wiring plan, single chamber housing The following illustration applies to the non-Ex as well as to the Ex-ia version.

4 Connecting to power supply

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 5 1 2 + ( ) (-) 6 7 8 4...20mA 2 3 4 1 Fig. 8: Electronics and terminal compartment, single chamber housing 1 Voltage supply, signal output 2 For display and adjustment module or interface adapter 3 For external display and adjustment unit 4 Ground terminal for connection of the cable screen Electronics and terminal compartment

5 Set up with the display and adjustment module

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 5 Set up with the display and adjustment module 5.1 Insert display and adjustment module The display and adjustment module can be inserted into the sensor and�removed�again�at�any�time.�You�can�choose�any�one�of�four�differ- ent positions - each displaced by 90°. It is not necessary to interrupt the power supply. Proceed as follows: 1. Unscrew the housing lid 2. Place the display and adjustment module on the electronics in the desired position and turn it to the right until it snaps in. 3. Screw housing lid with inspection window tightly back on Disassembly is carried out in reverse order. The display and adjustment module is powered by the sensor, an ad- ditional connection is not necessary. Fig. 9: Installing the display and adjustment module in the electronics compart- ment of the single chamber housing

5 Set up with the display and adjustment module

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 1 2 Fig. 10: Installing the display and adjustment module in the double chamber housing 1 In the electronics compartment 2 In the terminal compartment Note: If�you�intend�to�retrofit�the�instrument�with�a�display�and�adjustment� module for continuous measured value indication, a higher lid with an inspection glass is required. 5.2 Parameter adjustment - Quick setup To quickly and easily adapt the sensor to the application, select the menu item "Quick setup" in the start graphic on the display and adjustment module. Select the individual menu items with the [->] key. Carry out the steps in the below sequence. 1. Measurement loop name In�the�first�menu�item�you�assign�a�suitable�measurement�loop�name.� Permitted are names with max. 19 characters. 2. Medium In this menu item you select the medium. The selection comprises liquids�with�different�properties. Quick setup process

5 Set up with the display and adjustment module

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 3. Application In this menu item you determine the application. 4. Vessel form In this menu item you specify the for of the vessel bottom and top. 5. Vessel height/Measuring range In this menu item you enter the height of the vessel and hence the active measuring range. 6. Max. adjustment In this menu item you carry out the max. adjustment. Enter�the�measuring�distance�for�100�%�filling. 7. Min. adjustment In this menu item you carry out the min. adjustment. Enter�the�measuring�distance�for�0�%�filling. 8. Termination "Quick setup terminated successfully"�is�displayed�briefly. Information: The echo curve of setup was stored automatically during the quick setup. The�quick�setup�is�finished.

5 Set up with the display and adjustment module

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 The return to the measured value indication is carried out through the [->] or [ESC] keys or automatically after 3 s The menu "Extended adjustment" is available for further settings. Im- portant�functions�are�described�in�the�following�chapter.�You�can�find�a� complete description of all functions of the "Extended adjustment" in the operating instructions manual of VEGAPULS 64. 5.3 Parameter adjustment - Extended adjustment The�main�menu�is�divided�into�five�sections�with�the�following�func- tions: Setup: Settings, e.g., for measurement loop name, units, application, adjustment, signal output Display: Settings, e.g., for language, measured value display, lighting Diagnosis: Information, for example, on device status, peak value, simulation, echo curve Additional adjustments: Date/Time, reset, copy function, scaling, current�output,�false�signal�suppression,�linearization,�HART�mode,� special parameters Info: Instrument name, hardware and software version, calibration date, instrument features In the main menu item "Setup", the individual submenu items should be selected one after the other and provided with the correct parameters to ensure optimum adjustment of the measurement. The procedure is described in the following. Since the radar sensor is a distance measuring instrument, the distance from the sensor to the product surface is measured. To indicate the actual level, an allocation of the measured distance to the percentage height must be carried out. To perform the adjustment, enter the distance with full and empty ves- sel, see the following example: Extended adjustment Main menu Setup - Adjustment

5 Set up with the display and adjustment module

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 100% 0% 0,5 m (19.68") 5 m (196.9") 2 1 3 Fig. 11: Parameter adjustment example min./max. adjustment 1 Min. level = max. measuring distance 2 Max. level = min. measuring distance 3 Reference plane If these values are not known, an adjustment with the distances of e.g. 10�%�and�90�%�is�possible.�Starting�point�for�these�distance�specifica- tions�is�always�the�sealing�surface�of�the�thread�or�flange.�You�can�find� specifications�on�the�reference�plane�in�chapter�"Technical data". The actual level is calculated on the basis of these settings. The actual product level during this adjustment is not important, because the min./max. adjustment is always carried out without changing the product level. These settings can be made ahead of time without the instrument having to be installed. The function "Setup" allows the echo curve to be saved at the time of setup. Information: This is generally recommended, however, for use of the Asset Management functions it is absolutely necessary. Saving should be carried out with a very low level. The function "Echo curve memory" allows up to ten individual echo curves to be stored, for example to detect the measurement behav- iour�of�the�sensor�in�different�operating�conditions. With the adjustment software PACTware and the PC, the stored echo curves�can�be�displayed�with�high�resolution�and�used�to�recognize� signal changes over time. In addition, the echo curve saved during setup can also be displayed in the echo curve window and compared with the current echo curve. Diagnostics - Echo curve memory

5 Set up with the display and adjustment module

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 Menu - Setup Menu item Parameter Default setting Measurement loop name Sensor Units Distance in m Temperature in °C Application Medium Water based Application Storage tank Vessel top/Vessel bottom Dished form/Dished form Vessel height/ Measuring range 30 m Adjustment Max. adjustment 0,000 m(d) 100.00 % Min. adjustment 30 m 0.00 % Damping Integration time 0.0 s Current output Current output - Mode Output characteristics 4 … 20 mA Reaction when malfunctions occur ≤�3.6�mA Current output - Min./Max. 3.8 mA 20.5 mA Lock adjustment Released Menu - Display Menu item Default setting Menu language Order-specific Displayed value 1 Filling height in % Displayed value 2 Electronics temperature in °C Backlight Switched on Menu - Diagnosis Menu item Parameter Default setting Sensor status - Peak value Distance - Meas. certainty - Menu and parameter overview

5 Set up with the display and adjustment module

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 Menu item Parameter Default setting Peak values, ad- ditional Temperature - Curve indication Echo curve - False signal sup- pression - Simulation Percent Echo curve memory Percent Menu - Additional adjustments Menu item Parameter Default setting Date/Time Actual date/Actual time Reset - Copy in- strument settings - Scaling Scaling�size Volume in l Scaling format 0 % corresponds to 0 l 100 % corresponds to 0 l Current out- put 1 Current output - Meas. vari- able Lin. percent - Level Current output - Adjustment 0 … 100 % correspond to 4 … 20 mA Current out- put 2 Current output - Meas. vari- able Lin. percent - Level Current output - Adjustment 0 … 100 % correspond to 4 … 20 mA False signal suppression - Linearization Linear HART mode Address 0 Special pa- rameters - Menu - Info Menu item Parameter Device name VEGAPULS 6. Instrument version Hardware and software version Factory calibration date Date Sensor characteristics Order-specific�characteristics

5 Set up with the display and adjustment module

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 The�following�circumstances�cause�interfering�reflections�and�can� influence�the�measurement: • High sockets • Vessel installations such as struts • Agitators • Buildup or welded joints on vessel walls Note: A false signal suppression detects, marks and saves these false signals so that they are no longer taken into account in the level measurement. This should be done with a low level so that all potential interfering reflections�can�be�detected. Proceed as follows: 1. Select with [->] the menu item "False signal suppression" and confirm�with�[OK]. 2.� Confirm�again�with�[OK]. 3.� Confirm�again�with�[OK]. 4.� Confirm�again�with�[OK] and enter the actual distance from the sensor to the product surface. 5. All interfering signals in this section are detected by the sensor and�stored�after�confirming�with�[OK]. Note: Check the distance to the product surface, because if an incorrect (too large) value is entered, the existing level will be saved as a false signal. The level would then no longer be detectable in this area. If a false signal suppression has already been saved in the sensor, the following menu window appears when selecting "False signal suppression": Additional adjustments - False signal suppression

5 Set up with the display and adjustment module

VEGAPULS 64 • 4 … 20 mA/HART - two-wire 51462-EN-160111 Delete: An already created false signal suppression will be com- pletely deleted. This is useful if the saved false signal suppression no longer matches the metrological conditions in the vessel. Extend: is used to extend an already created false signal suppres- sion. This is useful if a false signal suppression was carried out with too high a level and not all false signals could be detected. When selecting "Extend", the distance to the product surface of the created false signal suppression is displayed. This value can now be changed and the false signal suppression can be extended to this range.

VEGAPULS 64 • 4 … 20 mA/HART - two-wire

51462-EN-160111 6 Supplement 6.1 Technical data Electromechanical data - version IP 66/IP 67 and IP 66/IP 68; 0.2 bar Options of the cable entry Ʋ Cable entry M20 x 1.5, ½ NPT Ʋ Cable gland M20 x 1,5; ½ NPT (cable ø see below table) Ʋ Blind plug M20 x 1.5; ½ NPT Ʋ Closing cap ½ NPT Material ca- ble gland Material seal insert Cable diameter 4.5 … 8.5 mm 5 … 9 mm 6 … 12 mm 7 … 12 mm 10 … 14 mm PA NBR – ● ● – ● Brass, nickel- plated NBR ● ● ● – – Stainless steel NBR – ● ● – ● Wire cross-section (spring-loaded terminals) Ʋ Massive wire, stranded wire 0.2 … 2.5 mm² (AWG 24 … 14) Ʋ Stranded wire with end sleeve 0.2 … 1.5 mm² (AWG 24 … 16) Voltage supply Operating voltage UB Ʋ Non-Ex instrument 12 … 35 V DC Ʋ Ex-d instrument 12 … 35 V DC Ʋ Ex ia instrument 12 … 30 V DC Ʋ Ex-d-ia instrument 17 … 35 V DC Operating voltage UB - illuminated display and adjustment module Ʋ Non-Ex instrument 18 … 35 V DC Ʋ Ex-d instrument 18 … 35 V DC Ʋ Ex ia instrument 18 … 30 V DC Ʋ Ex-d-ia instrument Due to the barrier, no lighting possible Reverse voltage protection Integrated Permissible residual ripple - Non-Ex, Ex-ia instrument Ʋ for 12 V< UB < 18 V ≤�0.7�Veff�(16�…�400�Hz) Ʋ for 18 V< UB < 35 V ≤�1.0�Veff�(16�…�400�Hz) Permissible residual ripple - Ex-d-ia instrument Ʋ for 18 V< UB < 35 V ≤�1�Veff�(16�…�400�Hz) Load resistor Ʋ Calculation (UB - Umin)/0.022 A Ʋ Example - Non-Ex instrument with UB= 24 V DC (24�V�-�12�V)/0.022�A�=�545�Ω

All statements concerning scope of delivery, application, practical use and operat-

ing conditions of the sensors and processing systems correspond to the information available at the time of printing. Subject to change without prior notice © VEGA Grieshaber KG, Schiltach/Germany 2016