Regin Regio Midi Manual
Read Online
Read the Regin Regio Midi Manual online using the built-in PDF viewer.
Text of the manual
The information in this manual has been carefully checked and is believed to be correct. Regin however, makes no
warranties as regards the contents of this manual and users are requested to report errors, discrepancies or ambiguities to
Regin, so that corrections may be made in future editions. The information in this document is subject to change
without prior notification.
The software described in this document is supplied under license by Regin and may be used or copied only in
accordance with the terms of the license. No part of this document may be reproduced or transmitted in any form, in any
fashion, electronically or mechanically, without the express, written permission of Regin.
COPYRIGHT
© AB Regin. All rights reserved.
TRADEMARKS
Some product names mentioned in this document are used for identification purposes only and may be the registered
trademarks of their respective companies.
February 2018
Document revision: 1.7
The functions described in this manual are handled using Regio tool© version 1.6
Table of contents
CHAPTER 1 ABOUT THE MANUAL ..................................................................................... 5
Terms ................................................................................................................................ 5
More information ............................................................................................................. 5
CHAPTER 2 INTRODUCTION TO REGIO .............................................................................. 6
REGIO ZONE CONTROLLERS............................................................................................................ 6
REGIO MIDI ............................................................................................................................... 7
Application examples ....................................................................................................... 7
CHAPTER 3 MODELS ......................................................................................................... 8
Model overview ................................................................................................................ 8
Design ............................................................................................................................... 9
CHAPTER 4 TECHNICAL DATA ......................................................................................... 10
DIMENSIONS .................................................................................................................. 10
COMMUNICATION ......................................................................................................... 10
Accessories for Regio Midi ............................................................................................. 11
CHAPTER 5 INSTALLATION PREPARATIONS ..................................................................... 12
DIFFERENT VERSIONS OF TERMINALS AND PINS ................................................................................ 12
USING LABELS ........................................................................................................................... 12
CONFIGURATION ....................................................................................................................... 13
Configuration using Regio tool© ..................................................................................... 13
Setting of DIP switches (models without display) .......................................................... 14
CALIBRATION ........................................................................................................................... 14
TROUBLESHOOTING ................................................................................................................... 14
CHAPTER 6 INSTALLATION .............................................................................................. 15
MOUNTING ............................................................................................................................. 15
WIRING .................................................................................................................................. 15
Measurement and testing during installation ................................................................ 17
Wiring for basic models with 3 universal outputs (RC-C3H, RC-C3, RC-C3O) ................ 18
Wiring for model for CO2 control (RC-C3DOC) ............................................................... 21
Wiring for model with built-in CO2 sensor (RCC-C3DOCS) .............................................. 23
Wiring for models for CO2 control and fan control (RC-C3DFOC) .................................. 25
Wiring for models for fan control (RC-CF, RC-CFO, RC-CDFO) ........................................ 27
Wiring for models for three-point control (RC-CTH, RC-CT, RC-CTO, RC-CDTO) ............ 30
CHAPTER 7 CONTROL MODES ......................................................................................... 32
DIFFERENT CONTROL MODES ....................................................................................................... 32
ADDITIONAL FEATURES ............................................................................................................... 38
CHAPTER 8 OPERATING MODES ..................................................................................... 42
DIFFERENT OPERATING MODES .................................................................................................... 42
ACTIVATION OF THE DIFFERENT OPERATING MODES .......................................................................... 44
CHAPTER 9 SETPOINT CALCULATION .............................................................................. 47
CHAPTER 10 ACTUATORS ............................................................................................... 49
CHAPTER 11 FAN CONTROL ............................................................................................ 51
CHAPTER 12 SPECIAL FUNCTIONS ................................................................................... 55
CHANGE-OVER FUNCTION ........................................................................................................... 55
FORCED VENTILATION ................................................................................................................ 55
CONDENSATION SENSOR ............................................................................................................. 56
FROST PROTECTION................................................................................................................... 56
HIGH/LOW ROOM TEMPERATURE ALARM ...................................................................................... 56
LIGHTING CONTROL................................................................................................................... 56
CHAPTER 13 INDICATIONS .............................................................................................. 57
CHAPTER 14 DISPLAY HANDLING .................................................................................... 58
DISPLAY INDICATIONS ................................................................................................................ 58
PARAMETER MENU ................................................................................................................... 59
CHAPTER 15 MEMORY FUNCTION ON POWER FAILURE ................................................... 66
CHAPTER 16 MODBUS SIGNAL TYPES .............................................................................. 67
CHAPTER 17 MODBUS SIGNALS....................................................................................... 69
DISCRETE INPUTS ...................................................................................................................... 69
COIL STATUS REGISTER ............................................................................................................... 70
INPUT REGISTER ....................................................................................................................... 71
HOLDING REGISTER ................................................................................................................... 72
CHAPTER 18 BACNET SIGNAL TYPES ................................................................................ 83
CHAPTER 19 BACNET SIGNALS ........................................................................................ 84
ANALOGUE INPUTS ................................................................................................................... 84
ANALOGUE VALUES ................................................................................................................... 84
BINARY INPUTS ........................................................................................................................ 86
BINARY VALUES ........................................................................................................................ 86
LOOP ..................................................................................................................................... 87
MULTISTATE INPUTS ................................................................................................................. 87
MULTISTATE VALUES ................................................................................................................. 87
DEVICE ................................................................................................................................... 88
Regio Midi manual
Chapter 1 About the manual
5
Chapter 1 About the manual
This manual describes the Regio Midi range of controllers.
Terms
Term used in the manual:
FS
Factory setting
More information
More information about Regio Midi can be found in:
•
Regio tool© Manual – Manual of how to configure the controllers
The information is available for download from Regin’s website, www.regincontrols.com.
The document Regio in EXO Projects, containing information on how to use Regio in the
EXO system, can be downloaded from Regin’s FTP server. It is intended for our system
customers who need to share files with us, e.g. at technical support. Contact one of our sales
engineers to get access to the FTP server.
Chapter 2 Introduction to Regio
Regio Midi manual
Chapter 2 Introduction to Regio
Regio zone controllers
Regio is a wide series of room controllers which handle everything from heating, cooling and
ventilation to lighting, humidity, CO2 monitoring and blinds. Regio can be used for creating
everything from stand-alone systems for managing the functions in one room, to large,
integrated systems with a comprehensive SCADA-system.
Applications
The Regio controllers have a discrete design and are easy to use. They are suitable in buildings
where you want optimal comfort and low energy consumption, for example offices, schools,
shopping centres, airports, hotels and hospitals.
Mounting
The modular design with a separate bottom plate for wiring makes the whole Regio series easy
to install and commission. The controllers are mounted directly on the wall or on a wall box.
Regio Midi manual
Chapter 2 Introduction to Regio
7
Regio Midi
Communication
The controllers can be connected to a central SCADA-system via RS485 (EXOline, BACnet*
or Modbus) and configured for a particular application using the configuration tool Regio
tool©,
which
can
be
downloaded
free
of
charge
from
Regin’s
homepage
www.regincontrols.com. See the manual for Regio tool© for more information.
* BACnet is only available in models with display
Control modes
The controllers can be configured for different control modes/control sequences:
•
Heating
•
Heating or cooling via the change-over function
•
Heating/Heating
•
Heating/Cooling
•
Heating/ Cooling with VAV-control and forced supply air function
•
Heating/Cooling with VAV-control
•
Cooling
•
Cooling/Cooling
•
Heating/Cooling/VAV (only available in …3-models, except C3DFOC)
•
Heating/Heating or Cooling via change-over (only available in …F-models)
•
Change-over with VAV- function
Application examples
Chapter 3 Models
Regio Midi manual
Chapter 3 Models
There are 12 different Midi room controllers. They can be divided according to type of control
in basic models, models for fan control and models for three-point control.
Model overview
RC…
Basic models control analogue actuators, thermal actuators or On/Off actuators with spring
return.
RCC…
Basic models with built-in CO2 sensor. The units control analogue actuators, thermal actuators
or On/Off actuators with spring return.
…-C-models
Models with communication. Communication via EXOline, Modbus or BACnet. Note that
BACnet communication only is available for models with display.
…D-models
Models with display.
…F-models
Like basic models, models for fan control (…F-models) control analogue, thermal and spring
return actuators. With the exception of RC-C3DFOC, they also have a button/fan switch and
three digital outputs for control of a three-speed fan (fan coil, etc.). RC-C3DFOC has EC fan
control on analogue output UO3.
…H-models
Models with hidden setpoint
…O-models
Models with occupancy button
…T-models
Models for three-point control (…T-models) have four digital outputs for control of two three-
point actuators.
…C-models
C at the end. Models with input for external CO2 sensor.
…3-models
The …3-models have an additional output for control of either an On/Off damper, analogue
forced ventilation damper, an analogue EC-fan or an analogue third damper.
Models
Display
Occupancy button
Fan control
3-point control
Setpoint knob
Hidden setpoint
EC fan control (AO)
follow cooling/heating
Control of a third
sequence (damper)
Input for CO2 sensor
CO2 sensor (built in)
Basic models
without fan
control/three-
point control
(…3-models)
RC-C3H
●
●
●
RC-C3
●
●
●
RC-C3O
●
●
●
●
RC-C3DOC
●
●
●
●
●
RCC-C3DOCS
●
●
●
●
●
●
Models for fan
control
(…F-models)
RC-CF
●
●
RC-CFO
●
●
●
RC-CDFO
●
●
●
RC-C3DFOC
●
●
●
●
●
Models for
three-point
control (…T-
models)
RC-CTH
●
●
RC-CT
●
●
RC-CTO
●
●
●
RC-CDTO
●
●
●
Table 1. The Midi models and their functions
Regio Midi manual
Chapter 3 Models
9
Design
RC-C3H, RC-CTH
RC-C3, RC-CT
RC-C3O, RC-CTO
RC-CDTO, RC-C3DOC, RCC-C3DOCS
RC-CF
RC-CFO
RC-CDFO, RC-C3DFOC
Chapter 4 Technical data
Regio Midi manual
Chapter 4 Technical data
Supply voltage ...................................................................................... 18...30 V AC, 50...60 Hz
Internal consumption ........................................................................................................ 2.5 VA
Ambient temperature ...................................................................................................... 0...50°C
Ambient humidity.................................................................................................. Max 90 % RH
Storage temperature .................................................................................................... -20...+70°C
Terminal blocks ......................................................... Lift type for cable cross-section 2.1 mm2
Protection class ..................................................................................................................... IP20
Material casing ............................................................................................... Polycarbonate, PC
Colour
Cover ...................................................................................................... Polar white RAL9010
Bottom plate .............................................................................................................. Light gray
Weight ................................................................................................................................. 110 g
Dimensions
Models without setpoint knob .......................................................................... 95 x 95 x 28 mm
Models with setpoint knob ............................................................................... 95 x 95 x 31 mm
Communication
Type ................................. RS485 (EXOline or Modbus with automatic detection or BACnet*)
Communication speed ................... 9600, 19200, 38400 bps (EXOline, Modbus and BACnet*)
...................................................................................................... or 76800 bps (BACnet* only)
Functions as ...................................................................................................................................
Modbus ..................................................................................................................... RTU Slave
BACnet ........................................................................................................................... MS/TP
Modbus ........................................................ 8 bits, 1 or 2 stop bits. Odd, even (FS) or no parity
Galvanically isolated port ....................................................................................................... No
* BACnet is only available in models with display
Memory
Non-volatile (EEPROM) ...................................... All settings and configurations are preserved
See also Chapter 15, Memory function on power failure.
Built-in temperature sensor
Type .................................................................................................. NTC, linearised, 15 kOhm
Measuring range ............................................................................................................. 0...50°C
Accuracy ...................................................................................................... ± 0.5°C at 15...30°C
Built-in CO2 sensor
Temperature dependance .... 5 ppm per °C or 5 % of the reading per °C (whichever is greater)
Long term stability ..................................... < 2 % of FS over life of a sensor (15 years typical)
Response time ................................................................... < 3 min. for 90 % step change typical
Warm-up time .......................................... < 2 min. (operational), 10 min. (maximum accuracy)
Measuring principle ............................................. NDIR (Non-Dispersive Infrared Technology)
Measuring range CO2 ............................................................................................. 0…5000 ppm
Accuracy .......................................................... 400…5000 ppm ± 25 ppm ± 3 % of the reading
Signal update ...................................................................................................... Every 5 seconds
Regio Midi manual
Chapter 4 Technical data
11
Models with display
Display type ......................................................................... LCD with background illumination
EMC emission and immunity standard
This product conforms to the requirements of the EMC Directive 2014/35/EU through product
standards EN 61000-6-1 and EN 61000-6-3.
RoHS
This product conforms to the Directive 2011/65/EU of the European Parliament and of the
Council.
Inputs
AI1 ........................................................................... PT1000-sensor, 0...50°C, accuracy ± 0.1°C
UI .....................................................................AI: PT1000-sensor, 0...100°C, accuracy ± 0.2°C
............................................................................................................................ or AI2: 0…10 V
....................................................................................................................... or DI: see DI below
CI .................................................................................... Regin’s condensation sensor, KG-A/1
DI ..................................................... Closing potential-free contact connected to +C in one end
Outputs
DO ............................................................................................................... 24 V AC, max 0.5 A
UO ..................................................... DO:24 V AC, max 2.0 A or AO:0...10 V DC, max 5 mA
+C, power output for DI only .............................. 24 V DC, max 10mA, short circuit protected
For more information about inputs and outputs, see the chapter Wiring.
Accessories for Regio Midi
External temperature sensors ........................ TG-R5/PT1000,TG-UH/PT1000,TG-A1/PT1000
Occupancy detector .......................................................................................................... IR24-P
Relay module for -F-models .................................................................................................. RB3
Change-over .........................................................................................................TG-A1/PT1000
Condensation sensor ........................................................................................................ KG-A/1
CO2 transmitter ................................................................................................................ CO2RT
Service adapter for Regio Midi ................................................................................... RC-TEST
Connection plates ................................................................................................... RC-CONN:10
The accessories are available from Regin. For more information, see the product sheets and
instructions for each product, search via www.regincontrols.com.
Chapter 5 Installation preparations
Regio Midi manual
Chapter 5 Installation preparations
Different versions of terminals and pins
In the summer of 2008, a new terminal type was introduced in the Regio controllers. The old
terminal type is dark grey and intended for 1.3 mm pins. The new terminal type is light grey
and intended for 1.1 mm pins. Confusion between a new and old bottom plate may lead to
deficient contact. Therefore, it is important to use an old electronics unit together with an old
bottom plate and a new electronics unit together with a new bottom plate. From the end of
2017 the bottom plate will be white instead of grey.
Figures 1 and 2 show an example of the difference between the old and current terminal types
(the number of terminals depends on the Regio model).
Figure 1. Old terminal type (1.3 mm pins)
Figure 2. Current terminal type (1.1 mm pins)
Using labels
On the back of the electronics cassette, there is a set of labels which makes it easier to install
large numbers of Midi controllers. By using the labels as carriers of information for the
installation engineer, much time will be saved and you can keep wiring errors at a minimum.
Figure 3. Label on the back of the controller
The three-piece label can be split and the parts can be fastened to the installation drawing and
the bottom plate of the controller. The label carries information on the communication address
etc., and has a note area where you can enter a reference number to the connection diagram.
The address on the sticker has a different meaning depending on what communication protocol
is used.
Model and address
Field for new address or reference to connection diagram
Field for room number
Regio Midi manual
Chapter 5 Installation preparations
13
Example 1
If the address on the sticker is 191:183 the following addresses are valid for the different
communication protocols:
EXOline: PLA=191, ELA=183
Modbus: address=183
BACnet: device ID=191183 (low 4 figures=1183, high 3 figures=19), MS/TP MAC
address=83*
Example 2
If the address on the sticker is 10:001 the following addresses are valid for the different
communication protocols:
EXOline: PLA=10, ELA=1
Modbus: address=1
BACnet: device ID=10001 (low 4 figures=1, high 3 figures=1), MS/TP MAC address=1*
* BACnet is only available in models with display
Configuration
If you want to configure the unit, it is normally better to do this before sending the electronic
cassette to the installation site. The bottom plates with location and wiring information can be
sent separately in advance to the installation site for electric installation.
The controllers are normally configured using Regio tool©.
Models with a display can be configured via the parameter menu in the display, but the easiest
way to set parameters is via Regio tool©. See Configuration using Regio tool© below and the
chapter Display handling.
Models without a display have DIP switches for configuration. See the section DIP switches
below.
Configuration using Regio tool©
1. Download Regio tool© to your computer from www.regincontrols.com.
2. Connect the computer to the back of the Regio cassette with an E-cable-USB or
equivalent.. The E-cable-USB is connected to terminals 42(A) and 43(B). Use a 24 V AC
transformer for supply voltage of the Regio cassette on terminals 10 and 11.
3. Go to the Device manager on your computer and check which communication port that
the cable has been assigned.
4. Open Regio tool© on your computer. The passwords in Regio tool© for the various access
levels are 1111 (log in as administrator) and 3333 (log in as operator). For more
information, see the manual for Regio tool©.
5. Go to the Tools menu in Regio tool© and choose Communication Settings and the
Communication Channels window will open up. Check that the Default port is the same
as assigned on the computer, otherwise change the port name in Regio tool©.
6. Each controller has a unique PLA- and ELA-address on delivery. If the PLA:ELA address
is unknown, go to the Tools menu and choose Search For Controllers. This function will
search through all the possible addresses until the Regio unit is detected.
7. Set the controller address under the Configuration menu. The controller address should
be entered instead of the Regio tool© default address (254:30).
The computer and the Regio unit should now be in contact with each other.
8. Start setting parameters and functions for the Regio. See the manual for Regio tool© for
more information.
Chapter 5 Installation preparations
Regio Midi manual
Setting of DIP switches (models without display)
Models without display have eight DIP switches (SW1-8) for setting basic functions. They are
found on the back of the electronics cassette.
Figure 4. DIP switches
SW1-2
Basic setpoint (°C)
SW1
SW2
20
OFF
OFF
22 (FS)
OFF
ON
24
ON
OFF
26
ON
ON
Table 3. Setting of basic heating setpoint with DIP switch SW1 and SW2
See also the chapter Setpoint calculation for setting of SW1-2.
SW3
Occupied is the pre-set operating mode, SW3: OFF (FS). If you want the pre-set operating
mode to be Stand-by, set SW3 in mode ON. For more information, see the chapter Operating
modes.
SW4-8
Follow the tables in the chapter Installation for setting SW4-8.
Calibration
Calibration of a measured room temperature should be done under stable conditions.
Troubleshooting
The Manual/Auto function in Regio tool© makes it possible to test outputs. The output itself is
not affected; only the software object that controls the output. This means that the built-in
safety functions will not be disregarded.
The controllers have different indications which can be used for troubleshooting. See the
section Indications.
Regio Midi manual
Chapter 6 Installation
15
Chapter 6 Installation
Mounting
Place the controller in a location that has a temperature representative for the room. A suitable
location is approx. 1.6 m above floor level in a place with unobstructed air circulation. Remove
the frame by pressing the locking tab in the lower edge of the cover with a screwdriver. See
figure 5.
Next, gently lift the electronics cassette out, See figure 6. Be careful not to damage the
electronics.
Figure 5.
Figure 6.
The bottom plate with terminals has several fixing hole combinations. Select suitable holes
and screw the bottom plate onto the wall or connection box, so that the arrows on the bottom
plate point upwards. Do not tighten the screws too hard!
With surface-mounted cabling, break out suitable holes from the marks in the plastic.
Wiring
All units that share the same transformer and communication loop must use the same
transformer-pole for G (terminal 10) and G0 (terminal 11). On the communication loop the A-
terminal (terminal 42) should only be connected to another A-terminal and the B-terminal
(terminal 43) to another B-terminal. Otherwise, the communication will not work.
Chapter 6 Installation
Regio Midi manual
The communication cable must be a screened twisted pair cable. The shield must be connected
to G0 on one (and only one) Midi controller in each separate power supply loop with 24 V
AC. If the length of the loop exceeds 300 m, a repeater is required. See figure 7.
Figure 7.
The figure below shows the location of the terminals. The connection diagrams and tables on
the following pages show the wiring for basic models, the model for CO2 control, the model
with built in CO2 sensor, models for fan control and models for three-point control.
Figure 8. Examples of bottom plate with terminals
For detailed information on connection of a communication cable to the Midi-controllers, see
the manual Regio in EXO Projects.
Regio Midi manual
Chapter 6 Installation
17
Measurement and testing during installation
In order to make measurements and test the inputs/outputs of a Regio room controller during
installation, Regin’s RC-TEST service adapter may be used.
Simply align the pins at the bottom of the RC-TEST with the terminals contained in the
controller’s socket and then plug the Regio electronics cassette into the terminals at the top of
the device. Testing takes place via a standard multimeter.
Chapter 6 Installation
Regio Midi manual
Wiring for basic models with 3 universal outputs (RC-C3H, RC-C3,
RC-C3O)
Figure 9. Connection diagrams for basic models with 3 universal outputs
Terminal
Designation
Operation
10
G
Supply voltage 24 V AC
11
G0
Supply voltage 0 V
12-14
No function.
20
GDO
24 V AC out common for DO. Internally connected to terminal 10, G.
21
G0
0 V common for UO. Internally connected to terminal 11, G0.
22
UO3
For VAV control
alternatively
For forced ventilation. 24 V AC output, max. 2.0 A. 24 V actuator is
connected between terminal 22 and terminal 20, GDO.
alternatively
For 0…10 V DC damper control/EC-fan. The damper actuator/EC-fan
0…10 V control signal terminal is connected to terminal 22, and its
supply terminals to terminals 10 and 11. Make sure that the reference
pole G0 is connected to the correct terminal on the actuator.
alternatively
Lighting control On/Off
RDAB5-24
Regio Midi manual
Chapter 6 Installation
19
Terminal
Designation
Operation
23
UO1
Control of heating (FS) cooling or heating/cooling via change-over.
For 0...10 V DC valve actuators, max 5 mA (FS). The valve actuator's
0…10 V control signal terminal is connected to terminal 23 and its
supply terminals to terminals 10 and 11. Make sure that the reference
pole G0 is connected to the correct terminal on the actuator.
alternatively
For a 24 V AC thermal actuator, max 2.0 A. The thermal actuator is
connected between terminals 23 and 20, GDO. Using DIP-switch SW8,
the output can be set to suit actuator type NO or NC.
N.B.: when UO1 has been set for use with thermal actuators for 24 V AC
(digital output function) the controller utilizes time-proportional control
to give a smooth control of the connected actuator. The output signal for
UO1 can be set to NC (normally closed) or NO (normally open) by
changing the position of DIP-switch SW8 for models without display
and by changing parameter 73 for models with display. This setting
refers to which type of actuator, NC or NO, it is intended for.
For choice of output function, analogue or digital, see Table 5, SW5. On
models with display, go into the parameter menu and change parameter
20 to thermal actuator.
alternatively
For a 24V AC actuator with spring return, max. 2.0 A. The actuator is
connected between terminals 23 and 20. This can be configured either
through the display or through Regio tool©. The output signal for UO1
can be set to NC (normally closed) or NO (normally open).
24
UO2
Control output heating or cooling (FS).
For a 0...10 V DC valve actuator, max 5 mA (FS). The valve actuator’s
0…10 V control signal terminal is connected to terminal 24 and its
supply terminals to terminals 10 and 11. Make sure that the reference
pole G0 is connected to the correct terminal on the actuator.
alternatively
For a 24 V AC thermal actuator, max 2.0 A. The thermal actuator is
connected between terminals 24 and 20, GDO.
For choice of output function, analogue or digital, see Table 5, SW6. On
models with display, go into the parameter menu and change parameter
21 to thermal actuator.
alternatively
For a 24V AC actuator with spring return, max. 2.0 A. The actuator is
connected between terminals 24 and 20. This can be configured either
through the display or through Regio tool©.
30
AI1
For an external room sensor, PT1000 or supply air temperature limitation
sensor. Measuring range 0...50°C. The sensor is connected between
terminals 30 and 41, AGnd.
See Table 5, SW7.
31
UI1
For switching between heating and cooling on a two-pipe system
(change-over).
A PT1000-sensor is connected between terminals 31 and 41, AGnd.
Measuring range: 0...100°C.
alternatively
For a potential-free contact. A potential-free contact is connected
between terminals 31 and 40, +C.
32
DI1
Occupancy detector. A potential-free contact is connected between
terminals 32 and 40, +C. Closed contact corresponds to occupancy.
alternatively
Window contact (DI). A potential-free contact is connected between
terminals 33 and 40, +C. Closed contact indicates closed window.
See also the section Occupancy detector in the chapter Operating modes.
Chapter 6 Installation
Regio Midi manual
Terminal
Designation
Operation
33
DI2/CI
Regin’s condensation sensor, KG-A/1 (FS). The sensor is connected
between terminals 33 and 41, AGnd.
alternatively
Window contact (DI). A potential-free contact is connected between
terminals 33 and 40, +C. Closed contact indicates closed window.
alternatively
Run indication from e.g. an air handling unit. A potential-free contact is
connected between terminals 33 and 40, +C.
See Table 5, SW4.
40
+C
24 V DC out common for DI and UI (with digital function)
41
AGnd
Analogue ground, reference for AI and UI (with analogue function)
42
A
RS485-communication A
43
B
RS485-communication B
Table 4. I/O connection terminals for basic models with 3 analogue outputs
DIP switches (only models without display)
The ON-position is marked on the DIP switch.
ON
OFF
Comment
SW4
DI, window contact.
Closed contact indicates
closed window.
CI, Regin’s condensation
sensor, KG-A/1 (FS).
Function terminal 33,
DI2/CI.
SW5
Digital output for 24 V
AC thermal actuator.
Analogue output for
0...10 V DC valve
actuator (FS).
Function terminal 23,
UO1.
SW6
Digital output for 24 V
AC thermal actuator.
Analogue output for
0...10 V DC valve
actuator (FS).
Function terminal 24,
UO2.
SW7
External, PT1000-sensor. Internal NTC-sensor
(FS).
Temperature sensor.
SW8
NO
NC (FS)
Function terminal 23,
UO1
Choosing NC (FS) gives direct action on output UO1, i.e. increasing signal
(longer pulses) on increasing control output. This setting is used when UO1 is
connected to a thermal actuator of type Regin RTAM-24 (NC). In the event of a
power cut the valve will close.
Choosing NO gives reverse action on output UO1, i.e. decreasing signal
(shorter pulses) on increasing control output. This setting is used when UO1 is
connected to a thermal actuator of type Regin RTAOM-24 (NO). In the event
of a power cut the valve will open.
Table 5. DIP switches SW4-SW8
Regio Midi manual
Chapter 6 Installation
21
Wiring for model for CO2 control (RC-C3DOC)
Figure 10. Connection diagrams for model for CO2 control
Terminal
Designation
Operation
10
G
Supply voltage 24 V AC
11
G0
Supply voltage 0 V
12-14
No function.
20
GDO
24 V AC out common for DO. Internally connected to terminal 10, G.
21
G0
0 V common for UO. Internally connected to terminal 11, G0.
22
UO3
Output for VAV or EC-fan.
For forced ventilation. 24 V AC output, max. 2.0 A. 24 V actuator is
connected between terminal 22 and terminal 20, GDO.
alternatively
For 0…10 V DC damper control/EC-fan. The damper actuator/EC-fan
0…10 V control signal terminal is connected to terminal 22 and its supply
terminals to terminals 10 and 11. Make sure that the reference pole G0 is
connected to the correct terminal on the actuator.
alternatively
Lighting control On/Off.
RDAB5-24
Chapter 6 Installation
Regio Midi manual
Terminal
Designation
Operation
23
UO1
Control output heating (FS), cooling or heating or cooling via change-over.
For a 0...10 V DC valve actuator, max 5 mA (FS). The valve actuator’s
0…10 V control signal terminal is connected to terminal 23 and its supply
terminals to terminals 10 and 11. Make sure that the reference pole G0 is
connected to the correct terminal on the actuator.
alternatively
For a 24 V AC thermal actuator, max 2.0 A. The thermal actuator is
connected between terminals 23 and 20, GDO.
alternatively
For a 24V AC actuator with spring return, max. 2.0 A. The actuator is
connected between terminals 23 and 20. This can be configured either
through the display or through Regio tool©. The output signal for UO1 can
be set to NC (normally closed) or NO (normally open).
24
UO2
Control output heating or cooling (FS).
For a 0...10 V DC valve actuator, max 5 mA (FS). The valve actuator’s
0…10 V control signal terminal is connected to terminal 24 and its supply
terminals to terminals 10 and 11. Make sure that the reference pole G0 is
connected to the correct terminal on the actuator.
alternatively
For a 24 V AC thermal actuator, max 2.0 A. The thermal actuator is
connected between terminals 24 and 20, GDO.
alternatively
For a 24V AC actuator with spring return, max. 2.0 A. The actuator is
connected between terminals 24 and 20. This can be configured either
through the display or through Regio tool©.
30
AI1
For an external room sensor or supply air temperature, PT1000. Measuring
range 0...50°C. The sensor is connected between terminals 30 and 41,
AGnd.
31
AI2
For a 0…10 V CO2 sensor
alternatively
Flow input
alternatively
0…10 V input
32
DI1
Occupancy detector. A potential-free contact is connected between
terminals 32 and 40, +C. Closed contact corresponds to occupancy.
alternatively
Window contact (DI). A potential-free contact is connected between
terminals 33 and 40, +C. Closed contact indicates closed window.
alternatively
Change-over.
33
DI2/CI
Regin’s condensation sensor, KG-A/1 (FS). The sensor is connected
between terminals 33 and 41, AGnd.
alternatively
Window contact (DI). A potential-free contact is connected between
terminals 33 and 40, +C. Closed contact indicates closed window.
alternatively
Change-over.
alternatively
Run indication from e.g. an air handling unit. A potential-free contact is
connected between terminals 33 and 40, +C.
40
+C
24 V DC out common for DI and UI (with digital function)
41
AGnd
Analogue ground, reference for AI and UI (with analogue function)
42
A
RS485-communication A
43
B
RS485-communication B
Table 6. I/O connection terminals for model for CO2 control
Regio Midi manual
Chapter 6 Installation
23
Wiring for model with built-in CO2 sensor (RCC-C3DOCS)
Figure 11. Connection diagrams for model with built-in CO2 sensor
Terminal
Designation
Operation
10
G
Supply voltage 24 V AC
11
G0
Supply voltage 0 V
12-14
No function.
20
GDO
24 V AC out common for DO. Internally connected to terminal 10, G.
21
G0
0 V common for UO. Internally connected to terminal 11, G0.
22
UO3
Output for VAV or EC-fan.
For forced ventilation. 24 V AC output, max. 2.0 A. 24 V actuator is
connected between terminal 22 and terminal 20, GDO.
alternatively
For 0…10 V DC damper control/EC-fan. The damper actuator/EC-fan
0…10 V control signal terminal is connected to terminal 22 and its supply
terminals to terminals 10 and 11. Make sure that the reference pole G0 is
connected to the correct terminal on the actuator.
alternatively
Lighting control On/Off.
23
UO1
Control output heating (FS), cooling or heating or cooling via change-over.
For a 0...10 V DC valve actuator, max 5 mA (FS). The valve actuator’s
0…10 V control signal terminal is connected to terminal 23 and its supply
terminals to terminals 10 and 11. Make sure that the reference pole G0 is
connected to the correct terminal on the actuator.
alternatively
For a 24 V AC thermal actuator, max 2.0 A. The thermal actuator is
connected between terminals 23 and 20, GDO.
alternatively
For a 24V AC actuator with spring return, max. 2.0 A. The actuator is
connected between terminals 23 and 20. This can be configured either
through the display or through Regio tool©. The output signal for UO1 can
be set to NC (normally closed) or NO (normally open).
Chapter 6 Installation
Regio Midi manual
Terminal
Designation
Operation
24
UO2
Control output heating or cooling (FS).
For a 0...10 V DC valve actuator, max 5 mA (FS). The valve actuator’s
0…10 V control signal terminal is connected to terminal 24 and its supply
terminals to terminals 10 and 11. Make sure that the reference pole G0 is
connected to the correct terminal on the actuator.
alternatively
For a 24 V AC thermal actuator, max 2.0 A. The thermal actuator is
connected between terminals 24 and 20, GDO.
alternatively
For a 24V AC actuator with spring return, max. 2.0 A. The actuator is
connected between terminals 24 and 20. This can be configured either
through the display or through Regio tool©.
30
AI1
For an external room sensor or supply air temperature, PT1000. Measuring
range 0...50°C. The sensor is connected between terminals 30 and 41,
AGnd.
31
AI2
For a 0…10 V CO2 sensor
alternatively
Flow input
alternatively
0…10 V input
32
DI1
Occupancy detector. A potential-free contact is connected between
terminals 32 and 40, +C. Closed contact corresponds to occupancy.
alternatively
Window contact (DI). A potential-free contact is connected between
terminals 33 and 40, +C. Closed contact indicates closed window.
33
DI2/CI
Regin’s condensation sensor, KG-A/1 (FS). The sensor is connected
between terminals 33 and 41, AGnd.
alternatively
Window contact (DI). A potential-free contact is connected between
terminals 33 and 40, +C. Closed contact indicates closed window.
alternatively
Run indication from e.g. an air handling unit. A potential-free contact is
connected between terminals 33 and 40, +C.
40
+C
24 V DC out common for DI and UI (with digital function)
41
AGnd
Analogue ground, reference for AI and UI (with analogue function)
42
A
RS485-communication A
43
B
RS485-communication B
Table 7. I/O connection terminals for model with built in CO2 sensor
Regio Midi manual
Chapter 6 Installation
25
Wiring for models for CO2 control and fan control (RC-C3DFOC)
Figure 12. Connection diagrams for models for CO2 control and fan control
Terminal
Designation
Operation
10
G
Supply voltage 24 V AC
11
G0
Supply voltage 0 V
12-14
No function.
20
GDO
24 V AC out common for DO. Internally connected to terminal 10, G.
21
G0
0 V common for UO. Internally connected to terminal 11, G0.
22
UO3
Control EC fan, 0…10 V DC.
23
UO1
Control output heating (FS), cooling or heating or cooling via change-over.
For a 0...10 V DC valve actuator, max 5 mA (FS). The valve actuator’s 0…10
V control signal terminal is connected to terminal 23 and its supply terminals to
terminals 10 and 11. Make sure that the reference pole G0 is connected to the
correct terminal on the actuator.
alternatively
For a 24 V AC thermal actuator, max 2.0 A. The thermal actuator is connected
between terminals 23 and 20, GDO.
alternatively
For a 24V AC actuator with spring return, max. 2.0 A. The actuator is
connected between terminals 23 and 20. This can be configured either through
the display or through Regio tool©. The output signal for UO1 can be set to NC
(normally closed) or NO (normally open).
Chapter 6 Installation
Regio Midi manual
Terminal
Designation
Operation
24
UO2
Control output heating, cooling (FS) or heating or cooling via change-over.
For a 0...10 V DC valve actuator, max 5 mA (FS). The valve actuator’s 0…10
V control signal terminal is connected to terminal 24 and its supply terminals to
terminals 10 and 11. Make sure that the reference pole G0 is connected to the
correct terminal on the actuator.
alternatively
For a 24 V AC thermal actuator, max 2.0 A. The thermal actuator is connected
between terminals 24 and 20, GDO.
alternatively
For a 24V AC actuator with spring return, max. 2.0 A. The actuator is
connected between terminals 24 and 20. This can be configured either through
the display or through Regio tool©.
30
AI1
For an external room sensor or supply air temperature limitation sensor,
PT1000. Measuring range 0...50°C. The sensor is connected between terminals
30 and 41, AGnd.
31
AI2
For a 0…10 V CO2 sensor
alternatively
Flow input
alternatively
0…10 V input
32
DI1
Occupancy detector. A potential-free contact is connected between terminals 32
and 40, +C. Closed contact corresponds to occupancy.
alternatively
Window contact (DI). A potential-free contact is connected between terminals
33 and 40, +C. Closed contact indicates closed window.
alternatively
Change-over.
33
DI2/CI
Regin’s condensation sensor, KG-A/1 (FS). The sensor is connected between
terminals 33 and 41, AGnd.
alternatively
Window contact (DI). A potential-free contact is connected between terminals
33 and 40, +C. Closed contact indicates closed window.
alternatively
Change-over.
alternatively
Run indication from e.g. an air handling unit. A potential-free contact is
connected between terminals 33 and 40, +C.
40
+C
24 V DC out common for DI and UI (with digital function)
41
AGnd
Analogue ground, reference for AI and UI (with analogue function)
42
A
RS485-communication A
43
B
RS485-communication B
Table 8. I/O connection terminals for CO2 control and fan control
Regio Midi manual
Chapter 6 Installation
27
Wiring for models for fan control (RC-CF, RC-CFO, RC-CDFO)
Figure 13. Connection diagrams for models for fan control
Terminal
Designation
Operation
10
G
Supply voltage 24 V AC
11
G0
Supply voltage 0 V
12
DO1
For fan control, low speed. 24 V AC output, max 0.5 A. A 24 V AC relay
is connected between terminal 12 and terminal 20, GDO.
13
DO2
For fan control, medium speed. 24 V AC output, max 0.5 A. A 24 V AC
relay is connected between terminal 13 and terminal 20, GDO.
14
DO3
For fan control, high speed. 24 V AC output, max 0.5 A. A 24 V AC relay
is connected between terminal 14 and terminal 20, GDO.
20
GDO
24 V AC out common for DO. Internally connected to terminal 10, G.
21
G0
0 V common for UO. Internally connected to terminal 11, G0.
22
DO4
For forced ventilation. 24 V AC output, max 0.5 A. A 24 V AC actuator is
connected between terminal 22 and terminal 20, GDO.
RDAB5-24
Chapter 6 Installation
Regio Midi manual
Terminal
Designation
Operation
23
UO1
Control of heating (FS), cooling or heating/cooling via change-over.
For a 0...10 V DC valve actuator, max 5 mA (FS). The valve actuator's
0…10 V control signal terminal is connected to terminal 23 and its supply
terminals to terminals 10 and 11. Make sure that the reference pole G0 is
connected to the correct terminal on the actuator.
alternatively
For a 24 V AC thermal actuator, max 2.0 A. The thermal actuator is
connected between terminals 23 and 20, GDO. Using DIP-switch SW8, the
output can be set to NO or NC.
N.B: when UO1 has been set for use with thermal actuators for 24 V AC
(digital output function) the controller utilizes time-proportional control to
give a smooth control of the connected actuator. The output signal for UO1
can be set to NC (normally closed) or NO (normally open) by changing the
position of DIP-switch SW8 for models without display and by changing
parameter 73 for models with display. This setting refers to which type of
actuator, NC or NO, it is intended for.
For choice of output function, analogue or digital, see Table , SW5. On
models with display, go into the parameter menu and change parameter 20
to thermal actuator.
alternatively
For a 24V AC actuator with spring return, max. 2.0 A. The actuator is
connected between terminals 23 and 20. This can be configured either
through the display or through Regio tool©. The output signal for UO1 can
be set to NC (normally closed) or NO (normally open).
24
UO2
Control of heating, cooling (FS) or heating/cooling via change-over.
For a 0...10 V DC valve actuator, max 5 mA (FS). The valve actuator’s
0…10 V control signal terminal is connected to terminal 24 and its supply
terminals to terminals 10 and 11. Make sure that the reference pole G0 is
connected to the correct terminal on the actuator.
alternatively
For a 24 V AC thermal actuator, max 2,0 A. The thermal actuator is
connected between terminals 24 and 20, GDO.
For choice of output function, analogue or digital, see Table , SW6. On
models with display, go into the parameter menu and change parameter 21
to thermal actuator.
alternatively
For a 24V AC actuator with spring return, max. 2.0 A. The actuator is
connected between terminals 24 and 20. This can be configured either
through the display or through Regio tool©.
30
AI1
For an external room sensor or supply air temperature limitation sensor,
PT1000. Measuring range 0...50°C. The sensor is connected between
terminals 30 and 41, AGnd.
See Table , SW7.
31
UI1
For switching between heating and cooling on a two-pipe system (change-
over).
A PT1000-sensor is connected between terminals 31 and 41, AGnd.
Measuring range: 0...100°C.
alternatively
For a potential-free contact. A potential-free contact is connected between
terminals 31 and 40, +C.
32
DI1
Occupancy detector. A potential-free contact is connected between
terminals 32 and 40, +C. Closed contact corresponds to occupancy.
alternatively
Window contact (DI). A potential-free contact is connected between
terminals 32 and 40, +C. Closed contact indicates closed window.
See also the section Occupancy detector in the chapter Operating modes.
Regio Midi manual
Chapter 6 Installation
29
Terminal
Designation
Operation
33
DI2/CI
Regin’s condensation sensor, KG-A/1 (FS). The sensor is connected
between terminals 33 and 41, AGnd.
alternatively
Window contact (DI). A potential-free contact is connected between
terminals 33 and 40, +C. Closed contact indicates closed window.
alternatively
Run indication from e.g. an air handling unit. A potential-free contact is
connected between terminals 33 and 40, +C.
See Table , SW4.
40
+C
24 V DC out common for DI and UI (with digital function)
41
AGnd
Analogue ground, reference for AI and UI (with analogue function)
42
A
RS485-communication A
43
B
RS485-communication B
Table 9. I/O connection terminals for models for fan control
DIP switches (only models without display)
The ON-position is marked on the DIP switch.
ON
OFF
Comment
SW4
DI, window contact.
Closed contact indicates
closed window.
CI, Regin’s condensation
sensor, KG-A/1 (FS).
Function terminal 33,
DI2/CI.
SW5
Digital output for 24 V
AC thermal actuator.
Analogue output for
0...10 V DC valve
actuator (FS).
Function terminal 23,
UO1.
SW6
Digital output for 24 V
AC thermal actuator.
Analogue output for
0...10 V DC valve
actuator (FS).
Function terminal 24,
UO2.
SW7
External, PT1000-sensor. Internal NTC-sensor
(FS).
Temperature sensor.
SW8
NO
NC (FS)
Function terminal 23,
UO1
Choosing NC (factory setting) gives direct action on output UO1, i.e.
increasing signal (longer pulses) on increasing control output. This setting is
used when UO1 is connected to a thermal actuator of type Regin RTAM-24
(NC). In the event of a power cut the valve will close.
Choosing NO gives reverse action on output UO1, i.e. decreasing signal
(shorter pulses) on increasing control output. This setting is used when UO1 is
connected to a thermal actuator of type Regin RTAOM-24 (NO). In the event
of a power cut the valve will open.
Table 10. DIP switches SW4-SW8
Chapter 6 Installation
Regio Midi manual
Wiring for models for three-point control (RC-CTH, RC-CT, RC-CTO,
RC-CDTO)
Figure 14. Connection diagrams for models for three-point control
Terminal
Designation
Operation
10
G
Supply voltage 24 V AC
11
G0
Supply voltage 0 V
12
DO1
For forced ventilation. 24 V AC output, max 0.5 A. A 24 V AC actuator is
connected between terminal 12 and terminal 20, GDO.
13
DO2
For a three-point actuator, heating increase. 24 V AC output, max 0.5 A.
The actuator’s terminal for opening signal is connected to terminal 13. The
common pole on the actuator is connected to terminal 20, GDO.
14
DO3
For a three-point actuator, heating decrease. 24 V AC output, max 0.5 A.
The actuator’s terminal for closing signal is connected to terminal 14.
20
GDO
24 V AC out common for DO. Internally connected to terminal 10, G.
21
G0
0 V common for DO. Internally connected to terminal 11, G0.
22
DO4
For a three-point actuator, cooling increase. 24 V AC output, max 0.5 A.
The actuator’s terminal for opening signal is connected to terminal 22. The
common pole on the actuator is connected to terminal 20, GDO.
23
DO5
For a three-point actuator, cooling decrease. 24 V AC output, max 0.5 A.
The actuator’s terminal for closing signal is connected to terminal 23.
24
No function.
30
AI1
For an external room sensor or supply air temperature limitation sensor,
PT1000. Measuring range 0...50°C. The sensor is connected between
terminals 30 and 41, AGnd.
See Table 1, SW7.
RDAB5-24
Regio Midi manual
Chapter 6 Installation
31
Terminal
Designation
Operation
31
UI1
For switching between heating and cooling on a two-pipe system (change-
over).
A PT1000-sensor is connected between terminals 31 and 41, AGnd.
Measuring range: 0...100°C.
alternatively
For a potential-free contact. A potential-free contact is connected between
terminals 31 and 40, +C.
32
DI1
Occupancy detector. A potential-free contact is connected between
terminals 32 and 40, +C. Closed contact corresponds to occupancy.
alternatively
Window contact (DI). A potential-free contact is connected between
terminals 32 and 40, +C. Closed contact indicates closed window.
See also the section Occupancy detector in the chapter Operating modes.
33
DI2/CI
Regin’s condensation sensor, KG-A/1 (FS). The sensor is connected
between terminals 33 and 41, AGnd.
alternatively
Window contact (DI). A potential-free contact is connected between
terminals 33 and 40, +C. Closed contact indicates closed window.
alternatively
Run indication from e.g. an air handling unit. A potential-free contact is
connected between terminals 33 and 40, +C.
See Table 1, SW4.
40
+C
24 V DC out common for DI and UI (with digital function)
41
AGnd
Analogue ground, reference for AI and UI (with analogue function)
42
A
RS485-communication A
43
B
RS485-communication B
Table 11. I/O connection terminals for models for three-point control
DIP switches (only models without display)
The ON-position is marked on the DIP switch.
ON
OFF
Comment
SW4
DI, window contact.
Closed contact indicates
closed window.
CI, Regin’s condensation
sensor, KG-A/1 (FS).
Function terminal 33,
DI2/CI.
SW5
DO5 activated (FS).
Not permitted.
Shall be ON.
SW6
Not used.
SW7
External, PT1000-sensor. Internal NTC-sensor
(FS).
Temperature sensor.
SW8
NO
NC (FS)
Function terminal 23, UO1
Choosing NC (factory setting) gives direct action on output UO1, i.e. increasing
signal (longer pulses) on increasing control output. This setting is used when UO1
is connected to a thermal actuator of type Regin RTAM-24 (NC). In the event of a
power cut the valve will close.
Choosing NO gives reverse action on output UO1, i.e. decreasing signal (shorter
pulses) on increasing control output. This setting is used when UO1 is connected
to a thermal actuator of type Regin RTAOM-24 (NO). In the event of a power cut
the valve will open.
Table 12. DIP switches SW4-SW8
Chapter 7 Control modes
Regio Midi manual
Chapter 7 Control modes
Different control modes
The controllers can be configured for different control modes/control sequences. Depending
on which control mode is active, one, both or all three of the universal outputs, UO1, UO2 and
UO3, are used. See Table 13 below for a summary.
Control mode
UO1*
UO2*
UO3**
Heating
Heating
-
Forced ventilation
(digital), Lighting
control,
Analogue, 0...10 V
(VAV damper),
EC fan
Heating/Heating (split output signal)
Heating
Heating
Heating or cooling via change-over
Heating or cooling
-
Heating/Cooling
Heating
Cooling
Heating/Cooling with VAV-control and
forced supply air function
Heating
Cooling
Heating/Cooling with VAV-control
Heating
Cooling
Cooling
Cooling
Cooling
Cooling/Cooling (split output signal)
Cooling
Cooling
Heating/Cooling/VAV
(only available in -C3- models, except
C3DFOC)
Heating
Cooling
Heating/Heating or Cooling via change-
over (only available in fan models)
Heating
Cooling
Change over with VAV-function
Heating or cooling
Cooling
Table 13. Control modes
* Not available in …T-models.
** Only available in …3-models.
Control mode 0: Heating
In control mode Heating, the unit is always a heating controller and controls according to the
heating setpoint plus/minus the setpoint adjustment. The setpoint can be adjusted in the display
or via the setpoint knob.
Control mode 1: Heating/Heating
Split output signal
In control mode Heating/Heating, the controller is always a heating controller and controls
according to the basic heating setpoint plus the setpoint adjustment. The control signal is
divided between the two outputs with a deadband in between. The first output (UO1) works
between 0...48 % of the control signal. When the control signal reaches 52 %, UO2 starts to
operate and will be 10 V when the control signal is 100 %. See the figure below:
Regio Midi manual
Chapter 7 Control modes
33
Output signal
Heating 2
Heating 1
0 %
100 %
100 %
48 %
52 %
Heating demand
Control mode 2: Heating or cooling via change-over
This control mode is used for installations with 2-pipe systems. It makes it possible to use the
same pipe for both heating and cooling, depending on whether heating or cooling is required.
Switching between heating and cooling mode can be performed either by using a digital or an
analogue input. Only one output is used to control the actuator (UO1). See more in the chapter
Change-over function.
Control mode 3: Heating/Cooling
In control mode Heating/Cooling, the controller functions as a heating controller when the
room temperature is lower than the basic heating setpoint plus half the neutral zone. The
neutral zone is the difference in temperature between the heating setpoint and the cooling
setpoint. When the room temperature exceeds this limit, the controller becomes a cooling
controller. There is a hysteresis of 0.1°C when the controller changes from heating to cooling
controller and vice versa. When the controller is heating, it regulates according to the basic
heating setpoint plus the setpoint adjustment, and when it is cooling according to the basic
cooling setpoint plus the setpoint adjustment.
Output signal
Cooling
Heating
0 %
Temp (°C)
100 %
SP
heating
SP
cooling
Neutral zone
Control mode 4: Heating/Cooling with VAV-control and
forced supply air function
Like control mode Heating/Cooling but the cooling output is controlling a supply air damper
(sub-tempered supply air). When the ventilation is forced (See Chapter 12, Special functions),
the cooling output is set to full cooling (full supply air volume), regardless of what the
controller output signal is.
For VAV control, several basic flows exist for supply air depending on the current running
mode.
Chapter 7 Control modes
Regio Midi manual
Factory settings:
•
Presence (Occupied): 20 %
•
Standby and no presence (Unoccupied): 10 %
•
Off: 0 %
A max limitation for cooling is available for Heating/Cooling with VAV-control and forced
supply air function.
The max limitation is configured 0...100 %, where 0 means the damper is entirely closed and
100 that the damper is entirely open. The function is activated by configuring the appropriate
parameter to a value less than 100. The cooling limitation is present in control modes 4, 5 and
8.
Control mode 5: Heating/Cooling with VAV-control
Heating and cooling are controlled in the same way as in the VAV-control above. The damper
cannot be forced like above. There is also a function that opens the supply air damper on
heating demand. This is normally always required if the heater is placed in the supply air duct,
to carry the heat to the room. A maximum limit is set for the opening of the damper on heating
demand. The factory setting is zero, which means that the function to open the damper on
heating demand is not active. The basic flow can also be set separately.
For VAV control, several basic flows exist for supply air depending on the current running
mode.
Factory settings:
•
Presence (Occupied): 20 %
•
Standby and no presence (Unoccupied): 10 %
•
Off: 0 %
A max limitation for both cooling and heating is available for Heating/Cooling with VAV-
control.
The max limitation is configured 0...100 %, where 0 means the damper is entirely closed and
100 that the damper is entirely open. The function is activated by configuring the appropriate
parameter to a value less than 100. The cooling limitation is present in control modes 4, 5 and
8. The heating limitation is present in control modes 5 and 8.
Max airflow on
heating demand
(settable)
Output signal
Cooling
Heating
0 %
Temp (°C)
100 %
Basic airflow
(settable)
Heating output
Cooling output
Increasing airflow on
heating demand
SP
heating
SP
cooling
Control mode 6: Cooling
In control mode Cooling, the unit is always a cooling controller and controls according to the
basic cooling setpoint plus the setpoint adjustment.
Regio Midi manual
Chapter 7 Control modes
35
Control mode 7: Cooling/Cooling
Split output signal
In control mode Cooling/Cooling, the controller always functions as a cooling controller and
controls according to the basic cooling setpoint plus the setpoint adjustment. The control signal
is divided between the two outputs with a deadband in between. The first output (UO1) works
between 0...48 % of the control signal. When the control signal reaches 52 %, UO2 starts to
operate and will be 10 V when the control signal is 100 %. See the figure below:
Output signal
Cooling 2
Cooling 1
0 %
100 %
100 %
48 %
52 %
Cooling demand
Control mode 8: Heating/Cooling/VAV
This control mode offers the possibility to control three analogue outputs: heating, cooling and
VAV. When the controller is in cooling mode, the control signal is split between cooling and
VAV (this control mode is only available in …C3 models, except RC-C3DFOC), see figure
below:
To avoid Y2 and Y3 opening and closing frequently during switch-over, a saddle point is
implemented. Y2 will output 0…10 V (linear) when the controller output is 0…48 % and Y3
will output 0…10 V (linear) when the controller output is 52…100 %. In the saddle point, the
outputs will always be 100 % for Y2 and 0 % for Y3.
As an addition to the function described above, it is possible to connect a CO2 sensor to RC-
C3DOC or use the built-in CO2 sensor in RCC-C3DOCS. The output on Y3 will then be
affected by either cooling demand or by the CO2 level rising too high. The output from the
CO2 function is linear between two user-defined setpoints (see figure below).
A max limitation for both cooling and heating is available for Heating/Cooling/VAV-control.
The max limitation is configured 0...100 %, where 0 means the damper is entirely closed and
100 that the damper is entirely open. The function is activated by configuring the appropriate
parameter to a value less than 100. The cooling limitation is present in control modes 4, 5 and
8. The heating limitation is present in control modes 5 and 8.
Chapter 7 Control modes
Regio Midi manual
The variable for the min. limit of the VAV-damper is the same as for the VAV-damper in the
VAV control applications on Y2. Default is 20 % min. limit.
Reversed sequence
In some applications, e.g. free cooling, it may be desirable to reverse the sequence of Y2 and
Y3 (i.e., to open Y3 before Y2). This function is a configuration of the control mode
Heating/Cooling/VAV. When the function is active, the sequence of Y2 and Y3 will be
reversed, i.e. Y3 will open 0…100 % when controller output is in the range of 0…48 % and
Y2 will open 0…100 % when the controller output is 52…100 %. See the figure below:
At forced ventilation, Y3 will open fully as before, and Y2 will control depending on
temperature. However, Y2 will not give any output unless the controller output is above
52 %.
Regio Midi manual
Chapter 7 Control modes
37
This function is only valid for models with Y3 output.
For VAV control, several basic flows exist for supply air depending on the current running
mode. Factory settings:
•
Presence (Occupied): 20 %
•
Standby and no presence (Unoccupied): 10 %
•
Off: 0 %
Control mode 9: Heating/Heating or cooling via change-
over
For models offering fan functionality (excluding RC-C3DFOC), a function for control of a
heating battery on UO1 in sequence with change-over on UO2 is available. When this has been
performed, the start sequence of UO1/UO2 is changed along with the limits for fan start.
The change-over function will be used to switch between summer and winter mode. UO2 will
be used as a cooling actuator in summer mode and as a heating actuator in winter mode.
In summer mode, Regio will function as a regular heating/cooling controller.
In winter mode, Regio will function as a heating/heating controller. UO2 will initiate first and
UO1 second. The electrical heating battery connected to UO1 will start only if the ordinary
heat battery on UO2 cannot meet the heating demand. When a heating demand exists, the
output of UO2 is 0…100 % linear to the heating demand 0…48 % and UO1 0…100 % to the
heating demand 52…100 %. When the heating demand is 48…52 % UO2 will always output
100 % and UO1 0 %.
Chapter 7 Control modes
Regio Midi manual
As the electrical heater is connected to UO1, and since an electrical heater may become very
hot, a fan stop delay has been implemented into the system. The fan stop delay will only be
activated in heating mode, and then only if the fan has been running prior to the stop. When
the heat output has been set to 0 %, the fan will continue to run for an additional 120 s, at the
same speed it had prior to stopping.
It is very important to note that Regio does not have any built-in function for monitoring when
the fan is running or if the heat battery is overheating. This function must instead be provided
by a supervisory system.
Control mode 10: Change-over with VAV function
This control mode is used when room temperature is controlled via VAV and the same duct is
used for both warm and under-tempered air. Change-over takes place on UO1. Min/max
limitations are active. CO2 control is also active and operates according to a linear function.
For the system to function properly, the change-over sensor must be used to measure duct air
temperature.
For more information see chapter 12: Change-over.
Min and max supply air limitation
Analogue input 1 (AI1) can be configured for use with a supply air temperature limitation
sensor. The controller will then automatically switch to cascade control. There are four values
for min and max limitation. The settable range is 10...50°C. The default setting is:
Control mode
Min limitation
Max limitation
Heating
24°C
35°C
Cooling
12°C
24°C
A room controller will then work together with a supply air temperature controller using
cascade control, resulting in a calculated supply air temperature maintaining the room
temperature setpoint.
The cascade factor consists of the supply air controller being faster than the room controller.
The cascade factor in Regio Midi acts as a divisor which affects both the P-band and I-time.
Example: If the cascade factor is 3 and the room controller has a P-band of 10°C and an I-
time of 300 s, the supply air controller will receive a P-band of 3°C and an I-time of 100 s.
The supply air controller will therefore be 3 times as fast as the room controller.
Additional features
CO2 sensor and VAV control (RC-C3DOC, RCC-
C3DOCS, RC-C3DFOC)
RC-C3DOC, RCC-C3DOCS and RC-C3DFOC can be set to all of the above control modes.
When RC-C3DOC, RCC-C3DOCS or RC-C3DFOC are set to VAV control, the control mode
is combined with a CO2 control function.
In control mode Heating/Cooling with VAV-control, the CO2 concentration in the room will
make the VAV damper, cooling output UO2, open. The function is linear and the damper
works between the configured min. flow (FS=20 %) and 100 %, depending on the CO2
concentration in the room. If the CO2 concentration drops below the configured min. limit, the
damper will stay on the minimum allowed air flow. When the CO2 concentration rises, the
damper will open linearly until reaching the configured CO2 max. value, at which point it will
be 100 % open.
Regio Midi manual
Chapter 7 Control modes
39
Minimum limit on analogue 0…10 V actuators
The minimum limitation on the analogue output is only active in Bypass, Occupied and
Standby. If the operating mode is Unoccupied or Off, the damper will be closed (0 V on the
analogue output). See table below:
Operating mode
Min. limit
VAV output (Y2)
Bypass
20 %
2 V
Occupied
20 %
2 V
Standby
20 %
2 V
Unoccupied
20 %
0 V
Off
20 %
0 V
Many damper actuators have a working range of 2...10 V. This means that to set a minimum
limitation of 20 %, the min. limitation in the Regio will have to be set to 36 % .
Forced ventilation depending on the heating/cooling
output
At 100 % heating or cooling output, forced ventilation can be activated. The function is
intended to be used when the heater or cooler is located in the ventilation duct and the system
is struggling to reach the setpoint. When the cooling or heating output reaches 100 %, the
controller will switch to control mode Bypass.
The controller will remain in forced ventilation throughout the set Bypass time (FS=2h).
Three different alternatives can be selected for setting the function forced ventilation:
•
Not active (FS)
•
Forced ventilation at 100% heating or cooling output
•
Forced ventilation at 100% cooling output
Chapter 7 Control modes
Regio Midi manual
Presence detection depending on the CO2
concentration
This function is not active when the controller is configured for Heating/Cooling with VAV-
control.
When the CO2 concentration exceeds the set value for activation of presence, UO3 will switch
to forced ventilation if the presence operating mode is set to Bypass. It will stay there until the
concentration drops below the set value (FS=800ppm) minus the hysteresis (FS=160ppm).
When the concentration drops below this value, the controller will remain in presence mode
for the duration of the configured occupancy off-delay (FS=10min).
Minimum limit for the heating output
In some applications, it is desirable to set a minimum limit for the heating output in order to
prevent, for instance, downdraughts under windows. In general, this function works in a way
similar to the minimum limit for the cooling output. However, there is a difference between
the minimum limit for the heating and cooling output as the minimum limit for the latter still
remains active after the controller enters heating mode. In addition, the minimum limitation
for the heating output functions in all control modes.
Regio Midi manual
Chapter 7 Control modes
41
Features for RC-C3DOC, RCC-C3DOCS, C3DFOC
0…10 V input
The 0…10 V input used as a CO2 input for RC-C3DOC, RCC-C3DOCS and RC-C3DFOC
supports a general 0…10 V signal. This input is not connected to any function but only acts as
a read-out for the signal. To configure this option, parameter 81 is set to option 7, “0…10 V”.
Flow input
AI2 may be configured as a flow calculation input. A flow corresponding to 0 V and one
corresponding to 10 V is set, and the flow is then calculated linearly between these two end
points. To configure the flow calculation, Parameter 81 has the additional option 8, “Flow
calculation”.
The calculated flow value may be shown in the display by setting parameter 42 to option 9.
Chapter 8 Operating modes
Regio Midi manual
Chapter 8 Operating modes
Different operating modes
The Regio controllers have the following operating modes:
•
0 = Off
•
1 = Unoccupied
•
2 = Stand-by
•
3 = Occupied (FS)
•
4 = Bypass
Off
Operating mode Off means that the controller is not heating or cooling, and the fans are
stopped. However, the temperature must not drop below the set minimum temperature
(FS=8°C). If it does, the controller will start heating, and (if a fan is used) start the fan whether
it has been manually stopped or not.
For controllers with display the background lighting is not lit, and only OFF is shown in the
display.
Unoccupied
Operating mode Unoccupied means that the room where the controller is placed is not used
for an extended period of time, for example during holidays or long weekends. Both heating
and cooling are disconnected and the fans are stopped within a temperature interval with
configurable min/max temperatures (FS min=15°C, max=30°C).
For controllers with display the background lighting is not lit, but the current room temperature
(or setpoint depending on the configuration) is shown in the display. OFF is also shown in the
display.
Stand-by
Operating mode Stand-by means that the room is in an energy save mode and is not used at
the moment. This can be during nights, weekends, evenings etc. The controller is prepared to
change operating mode to Occupied (comfort) if someone enters the room (presence). The
room temperature is controlled around the applicable heating and cooling setpoints, with an
extended temperature interval (FS= ± 3°C). For example, if the heating setpoint=22°C and the
cooling setpoint=24°C, the controller will allow the temperature in the room to be between
19°C and 27°C. The setpoints can also be adjusted ± 3°C via the setpoint knob or the display.
For controllers with display the background lighting is lit (dimmed). STANDBY and the
current room temperature (or setpoint depending on the configuration) are shown in the
display.
Regio Midi manual
Chapter 8 Operating modes
43
Occupied
Operating mode Occupied means that the room is in use and is therefore in a comfort mode.
The controller regulates the room temperature around a heating setpoint and a cooling setpoint
(FS heating setpoint=22°C, cooling setpoint=24°C). The setpoints can also be adjusted ± 3°C
locally via the setpoint knob or in the display, or via a central command.
For controllers with display the background lighting is lit (dimmed), and the occupancy
indication is shown (see the chapter Display handling). The current room temperature (or
setpoint depending on the configuration) is also shown in the display.
Bypass
Operating mode Bypass means that the controller controls the room temperature in the same
way as in operating mode Occupied. The output for forced ventilation is also active. After a
configurable time (FS=2 hours) in Bypass, the controller automatically returns to the pre-set
operating mode. Bypass is normally activated when the Occupancy button is pressed, via an
occupancy detector, a central command or the CO2 level. The operating mode is useful for
example in conference rooms, where many people are present at the same time for a certain
period of time.
For controllers with display the background lighting is lit (dimmed). The occupancy indication
and the symbol for forced ventilation are shown (see the chapter Display handling). The
current room temperature (or setpoint depending on the configuration) is shown in the display.
The bypass timer can be set to work as a switch-off delay, determining the time that “Bypass”
should be active (FS=120 min). Alternatively, a settable timer can be configured via the
display. In this case, each press of the occupancy button will change the timer as follows: Off
1h 2h 3h 4h 5h Off.
Control modes
Depending on various settings and values, the controller will be set to different control modes
using different setpoints:
Chapter 8 Operating modes
Regio Midi manual
Activation of the different operating modes
Pre-set operating mode The pre-set operating mode is configured to Occupied by default. On models without display
the pre-set mode can be changed to Stand-by using DIP switch SW3. OFF (FS): Occupied,
ON: Stand-by. On models with display, this is configured in the parameter menu in the display,
parameter 45.
The operating mode is changed at the following events:
•
When the Occupancy button is pressed (if the controller has an Occupancy button).
•
Activation/deactivation of an occupancy detector on the digital input.
•
Activation/deactivation of presence by CO2 level (for model with CO2 detection)
•
Via central control, for example central time control, central booking system etc.
Occupancy button
For models without fan control, the occupancy button push time for Shutdown is 5 s as a
default. It is configurable via Regio tool©.
When pressing the occupancy button, the controller is set to forced ventilation. If the button is
pressed again when forced ventilation is active, the controller will switch to the default running
mode which can be configured either to Off, Unoccupied, Standby or Occupied.
When the Occupancy button is held depressed for more than 5 seconds, the controller will
change its operating mode to Shutdown (Off/Unoccupied), regardless of the present operating
mode. Via the display or Regio tool©, it is possible to configure which operating mode (Off or
Unoccupied) should be activated upon Shutdown (FS=Unoccupied).
Shutdown
If the Occupancy button is pressed for less than 5 seconds when the controller is in its pre-set
operating mode or in Shutdown, the controller will change to Bypass. If the button is then
depressed for less than 5 seconds, the controller will return to the pre-set operating mode.
After a configurable period of time in Bypass (FS=2 hours), the controller will return to the
pre-set operating mode.
For models with fan control (RC-CF/CFO/CDFO/C3DFOC), the Occupancy button Shutdown
push time is 0 s as a default. This value is configurable via Regio tool©.
Because of the default 0 s setting, switching operating modes by depressing the Occupancy
button functions differently: If the Occupancy button is pressed when the controller is in the
pre-set operating mode or in Bypass mode, the controller will change to Shutdown. If the
Occupancy button is pressed in Shutdown mode, the controller will switch to Bypass. After a
configurable period of time in Bypass (FS=2 hours), the controller will return to the pre-set
operating mode.
Regio Midi manual
Chapter 8 Operating modes
45
For handling of the Occupancy button in combination with central control, please see the
section entitled Central control, below.
Occupancy detector
For local control of the operating mode between the pre-set operating mode and Bypass or
Occupied, an occupancy detector is connected.
When occupancy is indicated, the controller changes operating mode to Bypass or Occupied.
If you want to be able to enter the room temporarily without activating Presence (to, for
example, pick something up) it is possible to configure a power-up delay. This means that
Presence is not activated until the power-up delay has expired. The Presence delay can be set
to a value between 0 and 60 minutes (FS=0 min).
In Bypass on presence, there is a switch-off timer, which means that if there is no occupancy
indication during this time (FS=10 min), the controller will return to the pre-set operating
mode.
Chapter 8 Operating modes
Regio Midi manual
Central control
Central control of the operating mode is also possible. By changing the variable
RegioRemoteState, you can control the operating mode centrally according to the following
table (there is a variable list for central control in Part IV of this manual):
RegioRemoteState
Description
0
Central operating mode Off
1
Central operating mode Unoccupied
2
Central operating mode Standby
3
Central operating mode Occupied
4
(Not used)
5 (FS)
No central control
Table 14. The variable RegioRemoteState
The occupancy button When using central control (i. e. RegioRemoteState <> 5) and you press the Occupancy button,
the controller will change to Bypass and stay in this mode for as long time as you have
configured. If you press the Occupancy button again when the controller is in Bypass, the
controller will change to Stand-by, regardless of what has been set in the central control
(RegioRemoteState).
When the controller is in Bypass and the Bypass time has run out, the controller will change
to the operating mode given by RegioRemoteState. If RegioRemoteState equals 5 it will
change to the pre-set operating mode.
If the controller is in Stand-by and the central control is changed, the controller will change to
this new operating mode.
Occupancy detector
When central control is used and the occupancy detector is activated, the controller will go to
Bypass for a configurable time, and thereafter return to the central operating mode.
Central command
Via central commands from a comprehensive system, for example EXO4, you can handle the
controller in the same way as you handle it locally via the Occupancy button, i. e. you can
change its operating mode to Off/Unoccupied (Shutdown) or Bypass.
Central commands should be regarded as events and can be changed locally via the Occupancy
button.
Off/Unoccupied
Bypass
Command Bypass
Command ”Shutdown”
Regio Midi manual
Chapter 9 Setpoint calculation
47
Chapter 9 Setpoint calculation
Basic setpoint
There are two basic setpoints, one basic heating setpoint (FS=22°C) and one basic cooling
setpoint (FS=24°C). Units without display have DIP switches to change the setpoints (see
Table 3). The basic cooling setpoint is automatically changed at the same time. Therefore, the
difference between the basic heating setpoint and the basic cooling setpoint is always the same.
On models with display, the basic setpoint is set in the display.
On all models, you can also configure the setpoints via a central system or Regio tool©. When
the model has DIP switches, the latest setpoint change will be valid.
Setpoint offset
On all models, except RC-C3H and RC-CTH, the setpoint value can be adjusted up and down
from the basic setpoint value, via the setpoint knob or the display. How much the value can be
adjusted can be configured in Regio tool© or in the parameter menu in the display (FS= ± 3°C).
In models with display, you use the INCREASE button to increase the current setpoint in steps
of 0.5°C to the max. limit, and the DECREASE button to decrease the current setpoint in steps
of 0.5°C to the min. limit.
RC-C3H and RC-CTH have neither display nor setpoint knob. On these models, the setpoint
is adjusted from the back of the electronics cassette with a small screwdriver.
Calculation of the active setpoint
What setpoint value the controller should control according to depends on the operating mode,
the control mode and the current setpoint offset.
Off
In operating mode Off or on open window the controller is a heating controller, and controls
according to the frost protection setpoint (FS=8°C), regardless of the setpoint adjustment.
Unoccupied
In operating mode Unoccupied, it controls according to the heating setpoint (FS=15°C) if a
control mode with heating has been set and the room temperature is lower than this setpoint.
If the room temperature is higher than the cooling setpoint (FS=30°C) and a control mode with
cooling has been set, the unit is a cooling controller and controls according to the cooling
setpoint. The active setpoint changes in the middle of the neutral zone with a hysteresis of
0.1°C. A setpoint adjustment is not active in this operating mode.
Stand-by
In operating mode Stand-by the controller controls according to the basic heating setpoint or
the basic cooling setpoint plus/minus a settable neutral zone (FS=3°C). The setpoint can also
be adjusted via the setpoint knob or display. This means that the factory setting for the heating
setpoint is 19°C ± 3°C (local adjustment) and the cooling setpoint is 27°C ± 3°C (local
adjustment). On heating demand the unit will control according to the heating setpoint, and on
cooling demand it will control according to the cooling setpoint. The setpoint change takes
place halfway between the setpoints with a hysteresis of 0.1°C.
Occupied/Bypass
In operating modes Occupied and Bypass the unit controls according to the basic heating
setpoint or the basic cooling setpoint. The setpoint can also be adjusted via the setpoint knob
or display. The setpoint change takes place halfway between the setpoints with a hysteresis of
0.1°C.
Chapter 9 Setpoint calculation
Regio Midi manual
Setpoint display at
setpoint adjustment
Parameter 74 is used to set what is shown in the display when the setpoint is adjusted.
0 = The added adjustment is shown in the display. Example: +1.5°C. The adjustment is added
to both the heating and cooling setpoints.
1 = The sum of the control setpoint and the adjustment is shown in the display. Example: The
control setpoint is 22°C and the added adjustment is +1.5°C. This means that the value
23.5°C will be shown in the display. ”HEAT” or ”COOL” will flash depending on which
of the setpoint values is the control setpoint when you enter the setpoint menu, i.e.
depending on which setpoint you are changing. The adjustment is added to both the
heating and cooling setpoints.
2 = The sum of the heating setpoint and the adjustment is shown in the display. The
adjustment is added to both the heating and cooling setpoints.
3 = The sum of the cooling setpoint and the adjustment is shown in the display. The
adjustment is added to both the heating and cooling setpoints.
Regio Midi manual
Chapter 10 Actuators
49
Chapter 10 Actuators
Regio can be used with four types of actuators:
•
Analogue 0…10 V actuators
•
Thermal actuators
•
3-point actuators (Increase/Decrease actuators)
•
On/Off spring return actuators
On units without display, it is possible to select if thermal or analogue actuators will be used
via the DIP switches. For other actuators and Regio models, the actuator type is set via Regio
tool© or, for controllers with a display, in the parameter menu.
Analogue actuators
The following output signals can be set for analogue actuators:
•
0…10 V (FS)
•
2…10 V
•
10…2 V
•
10…0 V
Thermal actuators
When thermal actuator control has been selected, it is controlled digitally with time
proportional pulses via output UO1 and UO2. By pulsing, the opening degree of the actuator
(and its valve) is varied. The period time (in seconds) is the sum of the on and off output times
on the output. The period time is FS=60s. The controller varies the on and off output times
proportionally depending on the output signal demand to the actuator.
3-point actuators
For 3-point actuators (increase/decrease actuators, -T-models), two digital outputs are used for
controlling one actuator, one output to open the actuator and one to close it. You can configure
the run time (in seconds) for the different actuators (FS=120 s). The program calculates the
position of the actuator (0…100 %) and sends an increase or decrease signal when the
controller output signal deviates more than the set neutral zone (FS=2 %) from the calculated
position.
In order not to subject the actuator motor to unnecessary wear, it is possible to configure the
outputs for 3-point actuators so that they will close after a control period of one minute plus
run time, at either 0 % or 100 %. This takes place via Modbus (Coil status register 23) or using
Regio tool©.
On/Off actuators
On/Off actuators can be used in control modes 0-8.
Control mode:
0 = Heating
1 = Heating/Heating
Chapter 10 Actuators
Regio Midi manual
2= Heating or Cooling via change-over function
3 = Heating/Cooling
6 = Cooling
7 = Cooling / Cooling
The actuators operate using a hysteresis (FS=2K), as depicted below.
In control mode 1 and 7, the actuators are controlled in sequence.
When in heating mode, the temperature is permitted to fall below the setpoint minus the
hysteresis before opening the actuator. The actuator will then remain open until the
temperature has reached the setpoint. In cooling mode, the opposite will occur.
Actuator exercise
All actuators are exercised. The exercise takes place at set intervals in hours (FS=23 hours
interval). An opening signal is sent to the actuator for as long as the configured run time. Then
a closing signal corresponding to the length of the run time is sent and the exercise is finished.
On units with a display, the exercise can be inactivated by setting parameters 36 and 37 to zero
(0).
Regio Midi manual
Chapter 11 Fan control
51
Chapter 11 Fan control
In controllers for fan control (…F-models) it is possible to control a fan at the following
speeds: Off, Low speed, Medium speed, High speed, Auto. The fan speed in the Auto position
depends on the controller output signal and the settings for each speed.
Fan speed control
Manual control
The fan can be manually controlled to work at any speed. On models with display, you press
the fan button once and a fan symbol is lit for 5 seconds in the display. As long as the symbol
is lit, you can change the fan speed by repeatedly pressing the fan button. Models without
display have a fan switch.
Figure 15. Fan button on models with display
Figure 16. Fan switch on models without display
The controller has the following positions:
Auto =
Automatic control of the fan speed to maintain desired room temperature
0
=
Manual off
I
=
Manual position with low speed
II
=
Manual position with medium speed
III
=
Manual position with high speed
Manual setting of speed I-III means that the speed of the fan in operating modes Stand-by,
Occupied and Bypass is always the set speed. In the other operating modes, the fan is demand
controlled.
Auto control
In auto mode, you can configure if the fan should be controlled by the heating output, the
cooling output, or both the heating and cooling outputs. When the selected output exceeds the
start value that has been set for each speed (FS speed 1=20 %, speed 2=60 %, speed 3=100
%), the fan is activated. It stops when the controller output signal drops below the set value
minus the set hysteresis (FS=5 %).
When the fan speed changes, there is always a minimum delay (2-3 s) between the inactivation
of the output for the current speed and the activation of the output for the new speed. Only one
fan speed output is defined at a time.
Fan stopped
In operating modes Off and Unoccupied, the fan is stopped, regardless of the position of the
fan switch or the setting in the display, on condition that the temperature is within the set
temperature limits. If the temperature is not within the set temperature limits, the fan will be
started in the corresponding Auto position, regardless of the settings.
Chapter 11 Fan control
Regio Midi manual
No fan stop
Models RC-CF/CFO and CDFO contain an option in which the fan will never stop in operating
modes Bypass, Occupied and Standby but instead continue to run at fan speed 1. This function
uses parameter number 41. The factory setting for this option is 0, meaning that the function
is disabled. This function will only work if the fan is in Auto mode; if the fan is set to manual
mode, the manual setting will instead be applied.
EC fan control
Models RC-C3/C3H/C3O/C3DOC and C3DFOC offer an added function for the control of EC
fans. When this function is active, Y3 will follow Y1 and Y2, respectively. As for …F models
with fan control, it is possible to select whether the fan will run in Heating or Cooling, or in
both Heating and Cooling. This setting is made using the same parameter (P50) as for other
fan models.
The function is activated by setting UO3 to Control of EC fan (P22). It may be activated in
control modes Heating, Heating/Heating, Heating or Cooling via change-over,
Heating/Heating or Cooling via change-over, Heating/Cooling, Cooling/Cooling and Cooling.
The function will add a minimum limit to UO3, so that the fan will have sufficient supply
voltage.
Regio Midi manual
Chapter 11 Fan control
53
For model RC-C3DFOC, the fan button will control the EC fan output to pre-set speeds and
then offer feedback to the user through the fan segment displayed. This takes place in the same
way as for other …F models.
When the fan button is pressed, it will step through the configured fan levels:
NOTE: Regio tool© contains the text "Controller output for fan speed”. For an EC fan, this
signifies the output level for fan speed 1, 2 and 3. When in auto mode, the output is fully step
less.
Prevent manual fan control
This function prevents manual control of the fan when it is not desirable for it to be affected
by the Cooling/Heating output signal. If the fan is not activated and set to follow the
Cooling/Heating signal, it should not be possible to alter the fan speed manually. Please note
that if the fan configuration is set to not follow the cooling or heating signal and this function
is simultaneously active, the fan will not be controllable using the fan button.
This function works as described below:
Parameter 91 setting
Is manual fan control available?
If heating signal
If cooling
signal
0 = The fan is controlled neither by heating nor
cooling demand
No
No
1 = The fan is controlled by heating demand
Yes
No
2 = The fan is controlled by cooling demand
No
Yes
3 = The fan is controlled by both cooling and heating
demand
Yes
Yes
If the controller has a fan button (only applies to models with a display), fan control will return
to auto mode when the controller changes control mode from cooling to heating or vice versa.
If the controller has a fan switch (only applies to models without a display), fan control will
instead return to the current fan speed mode.
Chapter 11 Fan control
Regio Midi manual
Fan boost function
If there is a great difference between the room setpoint and current room temperature, or if one
simply wishes to hear the fan start, a boost function can be activated to make the fan run at top
speed for a set duration. An extra controller is then running in the background, using a P-band
for fan control separate from that of the ordinary controller. The controller with the highest
value will be outputted to the fan. The P-band is fixed and cannot be changed. When this
function is active, the fan will initially run at full speed for 10 s and then decrease to the speed
set by the extra controller for the remainder of the time set for the boost function.
The boost function has a higher priority than the manually set fan speed.
Fan kickstart
When using today’s energy-saving EC fans, there is always a risk the fan will not start due to
the low control voltage preventing the fan from exceeding its starting torque. The fan will
then remain at a standstill while power still flows through it, which may give rise to damage.
The kickstart function ensures fan output is set to 100 % for a set time (1...10 s) thereby
making sure the starting torque is exceeded. Kickstart is activated when the lowest fan speed
is selected. The function is also active during manual fan control. After the set time (1-10 s)
has elapsed, the fan will return to its original speed.
Regio Midi manual
Chapter 12 Special functions
55
Chapter 12 Special functions
Change-over function
Change-over is a function for installations with 2-pipe systems. It makes it possible to use the
same pipe for both heating and cooling, depending on requirements during for example the
summer (cooling output) and the winter (heating output).
Control modes
To activate the change-over function, control modes "Heating or Cooling via change-over" or
"Heating/Heating or Cooling via change over" needs to be configured.
All controllers in the Regio series have an input for change-over. To be able to configure the
control mode "Heating/Heating or Cooling via change-over", it is necessary to have a Regio
Midi controller with fan function. The input can be either of the type analogue PT1000-sensor
or a closing contact connected to a digital input (FS=PT1000-input).
Change-over digital
When using a digital signal input (potential-free contact), closing the contact will activate the
change-over function and set the heating output, UO1 alt. DO2/DO3 (-T-models), to cooling.
On open contact, the change-over function will set the heating output to heating.
Change-over analogue
There are two different analogue change-over modes, simple and advanced. In both cases, a
temperature sensor must be connected to an analogue input to measure the media temperature.
Change-over simple
In simple mode, the change-over state is set to cooling when the change-over temperature goes
below the low limit. It is set to heating when the change-over temperature exceeds the high
limit.
Change-over advanced In advanced mode, the change-over function will measure the difference between the room
and media temperature. As long as the heat valve is more than 20 % open, or every time a
valve exercise is performed, the difference between the media and room temperature will be
calculated. If the temperature difference is greater than the configured value (differs for
Heating and Cooling mode), the control mode will change. The factory settings for the
difference between Heating and Cooling change-over are:
•
Change from Heating to Cooling = 4K
•
Change from Cooling to Heating = 3K
This setting may be changed using parameters number 9 and 10.
Forced ventilation
All Regio midi controllers have functionality for forced ventilation. All controllers except RC-
C3DFOC have a digital output for controlling a forcing damper to increase the airflow to the
room. This output is always activated in operating mode Bypass.
When control mode “Heating/Cooling with VAV-control and forced supply air function” is
active, the cooling output is used to control the forcing damper. When forced ventilation is
active, the cooling output is set to full cooling, regardless of what the controller output signal
is.
Models RC-C3/RC-C3H/RC-C3O/RC-C3DOC/RCC-C3DOCS can select whether the forced
ventilation output should be a 0…10 V analogue output or a 24 V digital output (parameter
22).
Chapter 12 Special functions
Regio Midi manual
Condensation sensor
Special input CI
There is a special input (CI) on all Regio controllers. This input is intended for Regin’s
condensation sensor, KG-A/1, and functions internally as a digital input, i. e. condensation or
no condensation.
When the condensation sensor is activated, the cooling control is blocked and the controller is
set in neutral position. When condensation ceases, the controller will start controlling from the
neutral position.
Window contact
When window contact has been configured, the controller is set to normal mode on closed
window. On open window, the controller is set to off mode, the heating and cooling outputs
are set to 0 V and the frost protection function is activated.
Run indication, DI2
Digital input 2 (DI2) can be configured for run indication of e.g. an air handling unit. This
indication can then be read in EXOline and Modbus. The change is made in parameter 18.
Frost protection
Regio has built-in frost protection, which is activated when the controller is not in use. The
frost protection prevents the temperature from dropping below 8°C. Return to normal fan speed
and control occurs automatically when the room temperature exceeds 8°C.
High/low room temperature alarm
High/low temperature alarm is a function to indicate if the room temperature is too high or too
low.
The high room temperature alarm will trigger when the room temperature exceeds the
configured high temp limit (FS=40°C).
The low room temperature alarm will trigger when the room temperature falls below the
configured low temp limit (FS=15°C).
The alarms are implemented as points that trigger when the temperature either exceeds or falls
below the limits, and return as soon as the temperature returns. There is no advanced alarm
handling, incorporating blocking or acknowledging or so forth. There is only an indication for
faulty temperatures. All other alarm and alarm handling functions must be handled by a
supervisory system.
Lighting control
UO3/DO4/DO1 can be used for lighting control. When UO3/UO4/DO1 is configured for
lighting control, the following applies:
Digital input 1
UO3/UO4/DO1 is activated when presence is detected via DI1. The output then remains active
for as long as presence is detected. The Standby/Occupied/Bypass operating modes are active
as usual.
Off mode
If the controller is in Off-mode (Off/Unoccupied), the occupancy input (DI1) will be active if
UO3/DO4/DO1 is configured for lighting control.
Occupancy button
This button still controls On/Off and forced ventilation. If UO3/DO4/DO1 is configured for
lighting control, the output will not be activated if a button is pressed.
Regio Midi manual
Chapter 13 Indications
57
Chapter 13 Indications
LED
All controllers without a display, except RC-CH and RC-CTH, have a LED shaped like a
thermometer on the front. A red indication is shown when heating control is functional and a
blue indication is shown when cooling control is active. When there is something wrong with
the controller or if a setting is incorrect, the LED will flash red and blue.
Figure 17. The LED
The occupancy button
In models without a display, the occupancy button has the following indications:
•
Occupied: Fixed green indication
•
Standby: Flashing green indication
•
Bypass: Fixed green indication with a short flash
•
Off and Unoccupied: No indication
For each of the above running modes, indications can be configured to behave in the following
ways using Regio tool©:
•
Off = 0
•
Flashing = 1
•
Fixed light = 2
•
Fixed with short flash = 3
Figure 18. The occupancy button
On Regio models with a display, these indications are shown in the display. See the chapter
Display handling.
Communication LED
When the frame has been removed, a LED is visible in the right edge of the controller. It lights
up green when the controller is sending information.
Chapter 14 Display handling
Regio Midi manual
Chapter 14 Display handling
The Midi models RC-C3DO/RC-C3DFOC/RC-CDFO, RC-CDTO and RCC-C3DOCS have a
display instead of a setpoint knob.
These models also have an Occupancy button, as well as an INCREASE button and a
DECREASE button to increase and decrease the setpoint.
Figure 19. Buttons for display handling
Display indications
The display has the following indications (indications marked with an asterisk (*) are only
available on -F-models):
Figure 20. Indications in the display
INCREASE button
Occupancy button
DECREASE button
AUTO/MAN*: Auto/Man indication on the fan
Occupancy indication
Open window
Fan*
Setpoint
Changeable value
Forced ventilation
COOL/HEAT: Shows if the unit controls according to
the heating or cooling setpoint
SERVICE: Is shown when parameters are set, flashes when
there is something wrong with the controller
Fan speed*: Current fan speed (0, 1, 2, 3)
Current room temperature
in °C to one decimal point
OFF: Unoccupied (the
temperature is shown) or Off-
indication (only OFF is
shown)
STANDBY: Standby indication
Indoor / outdoor temp.
Regio Midi manual
Chapter 14 Display handling
59
Parameter menu
It is possible to set different parameter values in a parameter menu. The parameter menu is
accessed by simultaneously holding the INCREASE and DECREASE buttons pressed for
about 5 seconds and then pressing the INCREASE button twice. The Service indication will
be displayed.
The display will initially show the parameter number “1”. Use the INCREASE and
DECREASE buttons to scroll between parameters.
Press the Occupancy button to select the desired parameter. The parameter number will be
replaced by the parameter value. The value can be changed using the INCREASE and
DECREASE buttons. If a button is held depressed the value will start scrolling, first slowly
and then with increasing speed in 3 – 4 steps with 2 – 3 seconds between steps.
Acknowledge/Regret
To acknowledge and store a set parameter value, press the Occupancy button again, the display
then returns to showing the parameter number. To retrieve the original value, i.e. the value
before change, press the INCREASE and DECREASE buttons at the same time. The original
value is shown on the display.
Return
After a certain time, about 1 minute, or when the INCREASE and DECREASE buttons are
pressed at the same time while in the menu, the display returns to the normal view. Exit is
shown on the display after the last parameter. The parameter menu is exited by pressing the
Occupancy button while in Exit. Pressing on INCREASE goes to the first parameter and
pressing on DECREASE goes to the last parameter.
Blocking of buttons
To prevent unauthorised users from accessing important functions, Regio controllers have a
built-in function for blocking button access. As seen in the below tables, blocking may take
place in different ways. The INCREASE/DECREASE buttons are always blocked/unblocked
simultaneously. If the INCREASE/DECREASE buttons are blocked, the parameter menu can
still be reached normally. Parameter 108 is used for configuration.
For models without a fan button and configuration options 4-6, the function remains the same
as for options 0-3.
Configuration options
Button function
0
No button is active
1
Only Occupancy button active
2
Only INCREASE/DECREASE buttons active
3
Occupancy and INCREASE/DECREASE buttons active
4
Only fan button active
5
Occupancy and fan buttons active
6
INCREASE/DECREASE and fan buttons active
7
All buttons active
Configuration
options
Occupancy
button active
INCREASE/DECREASE
buttons active
Fan button
active
0
1
X
2
X
3
X
X
4
X
5
X
X
6
X
X
7
X
X
X
Chapter 14 Display handling
Regio Midi manual
Configuration menu blocking
This function prevents unauthorised access to the configuration menu using the buttons on the
front of the device. When the function is active, all buttons will function normally except for
the configuration menu no longer being accessible when INCREASE and DECREASE are
pressed simultaneously. The function can be activated via the display, Regio tool© and
Modbus. Please note that if the function is activated via the display, re-entering the parameter
list via the display will be prevented. The function must then be deactivated using Regio tool©.
Parameter list
The following parameters can be changed in the parameter menu (FS = Factory setting):
Parameter
number
Description
FS
1
Basic heating setpoint
22°C
2
Basic cooling setpoint
24°C
3
Neutral zone at standby,
Heating setpoint = Basic sp. heating-3 by default
Cooling setpoint = Basic sp.cooling+3 by default
3°C
4
Heating setpoint at Unoccupied
15°C
5
Cooling setpoint at Unoccupied
30°C
6
Frost protection setpoint
8°C
7
P-band for room controller
10°C
8
I-time for room controller
300 s
9
The difference between the temperature in the room and the media
temperature for change-over to cooling
3K
10
The difference between the temperature in the room and the media
temperature for change-over to heating
4K
11
Control mode:
0=Heating
1= Heating / Heating
2= Heating or Cooling via change-over
3= Heating / Cooling
4= Heating / Cooling with VAV-control and forced ventilation
5= Heating / Cooling with VAV-control
6= Cooling
7= Cooling / Cooling
8= Heating / Cooling/VAV (C3-models, except RC-C3DFOC)
9=Heating / Heating or Cooling via change-over (only available on models
with fan control)
10 = Change-over with VAV function
3
12
Time in Bypass mode
120 min
13
Disconnect timer with Occupancy/Unoccupancy
10 min
14
Switch-on delay for Occupancy
0 min
15
State connected sensor on AI1:
0=Internal sensor
1=External room sensor
2=Change-over sensor (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC)
3-10 = No function
11 = Supply air temperature limitation sensor
0
16
State connected sensor on UI1: (All models except RC-C3DOC,
RCC-C3DOCS, RC-C3DFOC )
0=None
1=Change-over digital
2=Change-over analogue
2
17
State connected sensor on DI1:
0=Not active
1=Window contact
2= No function
3= Presence detector
4=Change-over sensor (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC )
5-6=No function
1
Regio Midi manual
Chapter 14 Display handling
61
Parameter
number
Description
FS
18
State connected sensor on DI2:
1=Window contact
2=Condensation sensor
3=No function
4=Change-over sensor (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC )
5 = No function
6 = No function
7 = Run indication
2
20
State connected function on UO1:
0=None
1=Thermal actuator heat
2= None
3=Heating actuator 0...10 V
4= None
5=On/off actuator heat
6= None
3
21
State connected function on UO2:
0= None
1= None
2=Thermal actuator cool
3= None
4=Cooling actuator 0…10 V
5= None
6=On/off actuator cool
4
22
State connected function on UO3:
0= None
1=Forced vent. digital
2=Analogue output (OEM)
3 = Lighting control
4 = Analogue output
5=Control of EC fan (RC-C3-models)
1
24
Y3 output in manual mode (only if Y3 is configured as an analogue output;
not available for RC-C3DFOC)
0 %
28
State output signal range for Y3-actuators:
0=0…10 V
1=2…10 V
2=10…2 V
3=10…0 V
0
29
State output signal range for heating actuators:
0=0…10 V
1=2…10 V
2=10…2 V
3=10…0 V
0
30
State output signal range for cooling actuators:
0=0…10 V
1=2…10 V
2=10…2 V
3=10…0 V
0
31
Period time for heating actuators with thermal actuator
60 s
32
Period time for cooling actuators with thermal actuator
60 s
33
Run time for heating actuators with increase/decrease actuators
120 s
34
Run time for cooling actuators with increase/decrease actuators
120 s
35
Neutral zone for increase/decrease actuators
2%
36
Time in hours between exercise of heating actuators
23h
37
Time in hours between exercise of cooling actuators
23h
38
Hysteresis for on/off actuators and heating
2K
39
Hysteresis for on/off actuators and cooling
2K
40
Minimum limit for the heat output
20 %
41
The fan will never stop
0=OFF
1=ON
0
Chapter 14 Display handling
Regio Midi manual
Parameter
number
Description
FS
42
Select if setpoint or actual value is to be shown in the display.
0=Actual value
1=Heat setpoint
2=Cool setpoint
3=Average value of heating and cooling setpoint
4=Only setpoint offset
5= CO2 concentration in the room in ppm (RC-C3DOC, RCC-C3DOCS,
RC-C3DFOC)
6=Heating setpoint +setpoint offset
7=cooling setpoint+setpoint offset
8=Average of heating and cooling setpoint+setpoint offset
9=The calculated flow in the duct in l/s (RC-C3DOC, RCC-C3DOCS,
RC-C3DFOC)
0
43
Highest permitted setpoint adjustment upwards
3°C
44
Highest permitted setpoint adjustment downwards
3°C
45
Pre-set operating mode:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied. Forced ventilation is not set in Occupied mode.
3
46
State operating mode by pressing the occupancy button for 5 s:
0=Off
1=Unoccupied.
1
47
Select operating mode for central control:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
5=No central control
5
48
Min flow at cool output when control mode Heating/Cooling with VAV-
control is selected
Min flow at Y3 output when control mode Heating/Cooling/VAV is selected
20 %
49
Max flow on Y3 output when control mode Heating/Cooling/VAV is selected
and in heating mode
0 %
50
Configuration of fan control:
0=No control
1=Fan is controlled by heating demand
2=Fan is controlled by cooling demand
3=Fan is controlled by both heating and cooling demand
3
51
Start signal in % for fan speed 1 on heating or cooling control
5%
52
Start signal in % for fan speed 2
60%
53
Start signal in % for fan spped 3
100%
54
Hysteresis for start/stop of fans
5%
55
State number of speeds for the fan (1, 2 or 3)
3
56
Temperature compensation on AI1
0°C
57
Temperature compensation on UI1
0°C
58
Temperature compensation on internal room sensor
0°C
59
Filter factor for analogue temperature inputs
0,2
60
State NO/NC digital input 1:
0=NO (Normally open)
1=NC (Normally closed)
0
61
State NO/NC digital input 2:
0=NO (Normally open)
1=NC (Normally closed)
1
62
State NO/NC universal input 1:
0=NO (Normally open)
1=NC (Normally closed)
0
63
Manual/Auto Heating output:
0=Off
1=Manual
2=Auto
2
64
Manual/Auto cooling output:
0=Off
1=Manual
2=Auto
2
Regio Midi manual
Chapter 14 Display handling
63
Parameter
number
Description
FS
65
Manual/Auto Y3 forced ventilation output:
0=Off
1=Manual
2=Auto
For C3 models (except C3DFOC), manual mode means that Y3 puts out what
is stated in parameter 24 if Y3 is configured as an analogue output.
When Y3 is configured as a Digital output (including for C3 models) or does
not exist, this parameter constitutes the Manual/Auto mode for the forced
ventilation.
2
66
Manual/Auto control of change over mode:
0=Heat control
1=Cool control
2=Automatic change over depending on analogue sensor input or digital
input
2
67
Heating output in manual mode
0 %
68
Cooling output in manual mode
0 %
69
Controller Modbus address
Factory set
70
Parity bit Modbus communication:
0=No parity
1=Odd parity
2=Even parity
3 = No parity, 1 stop bit
2
71
Modbus time out for character (t1.5), in ms. Should be 1,5 times a character,
i.e. at least 2 ms.
3 ms
72
Answer delay in Modbus (t3.5), in ms. Should be 3,5 times a character, i.e. at
least 5 ms.
5 ms
73
Selection of heating output function (NO/NC):
0=NC (Normally closed)
1=NO (Normally opened)
0
74
Setpoint display at setpoint adjustment.:
0=The offset is shown in the display
1=The active setpoint + offset is shown in the display. Heat or Cool is shown
depending on whether heat or cool is active when entering the menu
2=Heat setpoint + offset is shown in the display
3=Cooling setpoint + offset is shown in the display
0
75
Sequence order for Y2 and Y3:
0=Y2 activates before Y3
1=Y3 activates before Y2
0
76
Forced ventilation, control function:
0=Not active
1=Forced ventialtion at 100% output of heat or cool
2=Forced ventilation at 100% Cool output
0
77
Operating mode at presence detection:
3=Occupied
4=Bypass
4
78
EXOline PLA-address
Factory set
79
EXOline ELA-address
Factory set
80
Selection of cooling output functions (NO/NC):
0=NC
1=NO
0
81
State the connected sensor at AI2: (Only RC-C3DOC, RCC-C3DOCS,
RC-C3DFOC)
0=None
1– 4=No function
5= CO2-sensor
6=No function
7=0…100% (OEM-function)
8=Flow calculation
9=0…10 V
5
82
Flow at 0 V input in AI2
0 l/s
83
Flow at 10 V input in AI2
100 l/s
84
Minimum runtime when calculating for change over
600s
86
Alarm limit for high room temperature
40°C
87
Alarm limit for low room temperature
15°C
Chapter 14 Display handling
Regio Midi manual
Parameter
number
Description
FS
91
Function to prevent user from setting manual fan speed if fan should not run
due to cooling/heating output according to parameter 50.
0 = Not active
1 = Active
0
92
Fan boost function. Activation time:
0 = Not active
1-10 = The function is active for 10 s.
10-600 = Total activation time
0
93
Boost function, configuration:
0 = Heating mode only
1 = Cooling mode only
2 = Both heating and cooling mode
1
94
Fan kickstart. The fan will run 100 % when starting up for the set time.
0 = Not active
1-10 = Active for set time (seconds)
0 seconds
97
Activate presence if CO2 level is higher (RC-C3DOC, RCC-C3DOCS,
RC-C3DFOC)
800ppm
98
Deactivate presence if the CO2 level is lower than the limit minus this
hysteresis (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC)
160ppm
100
Filter factor for CO2-input (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC)
0.2
101
Offset for internal CO2 sensor reading
0ppm
104
CO2-level at 0 V (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC)
0ppm
105
CO2-level at 10 V (RC-C3DOC, RCC-C3DOCS, RC-C3DFOC)
2000ppm
108
Button function configuration:
0 = No button is active
1 = Only Occupancy button active
2 = Only INCREASE/DECREASE buttons active
3 = Occupancy and INCREASE/DECREASE buttons active
4 = Only fan button active
5 = Occupancy and fan buttons active
6 = INCREASE/DECREASE and fan buttons active
7 = All buttons active
7
109
Activate parameter menu access via display:
0 = Not active
1 = Active
NOTE: Activating this function via the display will prevent re-entry! If so,
parameter menu access may be activated again using Regio tool©.
0
110
Activate manual bypass timer setting. When the function is active, the user
may step through bypass time in 1 hour increments.
0 = Not active
1 = Active
0
112
Min limit for VAV-damper at CO2-control (RC-C3DOC, RCC-C3DOCS,
RC-C3DFOC)
600ppm
113
Max limit for VAV-damper at CO2-control (RC-C3DOC, RCC-C3DOCS,
RC-C3DFOC)
800ppm
114
This parameter defines the protocol to be used:
0=EXOline/Modbus
1=BACnet MS/TP
0
115
BACnet MS/TP MAC address:
0-127=master address
128-254=slave address
Factory set (00-
99)
116
Low 4 figures of the BACnet device ID. 0-9999
Factory set
117
High 3 figures of the device ID.
Factory set
118
BACnet MS/TP Max master.
127
119
COMbus speed:
0=9600
1=19200
2=38400
3=76800 (only BACnet)
0
120
COMbus reset.
When activated (1) it resets the communication to default settings
0 (deactivated)
121
Min limit for EC fan (%)
10 %
Regio Midi manual
Chapter 14 Display handling
65
Parameter
number
Description
FS
122
EC fan max limitation (V)
10
123
VAV-damper max limitation (%), control modes 5, 6 and 9
100 %
122
Max limit for EC fan (%)
100 %
125
Model
Factory set
(read only)
126
Version Major
Factory set
(read only)
127
Version Minor
Factory set
(read only)
128
Version Branch
Factory set
(read only)
129
Revision
Factory set
(read only)
132
Basic flow, Standby
10 %
133
Basic flow when no presence (Unoccupied)
10 %
134
Basic flow, Off
0 %
144
Period time for VAV-actuators with thermal actuators
60 s.
145
Select VAV-actuator function (NO/NC)
0 = NC (normally closed)
1 = NO (normally open)
0
146
Supply air max limitation for cascade control and heating control
35°C
147
Supply air min limitation for cascade control and heating control
24°C
148
Supply air max limitation for cascade control and cooling control
24°C
149
Supply air min limitation for cascade control and cooling control
12°C
150
Cascade factor between room controller and supply air controller
3°C
151
Frost protection temperature for supply air when supply air temperature
limitation is active
8°C
152
Activate supply air temperature limitation for:
0 = Heating control
1 = Cooling control
2 = Both heating and cooling control
1
153
Select simple or advanced analog change-over function
0 = Simple
1 = Advanced
1
154
Use valve exercise
0 = Never
1 = Regularly
2 = Regularly and at power-up
3 = Regularly, at power-up and when changing state to Occupied
1
Table 15. Parameter list
Chapter 15 Memory function on power failure
Regio Midi manual
Chapter 15 Memory function on power
failure
On power failure, settings and configurations are preserved in the controller in a so-called non-
volatile memory (EEPROM). All changes made to the settings and configuration is saved in
the memory, which means that the latest values are always stored. Measured values, as well as
other variables that change often, are not stored.
Values can be saved up to approximately 100 000 times in the non-volatile memory. Therefore,
changed values should not systematically and very often be sent to the controller via network
communication. Normal changes may still be sent via the network; for example if the operating
mode is changed a few times per day.
Disable autosave
There is a function to disable the automatic saving to EEPROM. We recommend to use this
function when huge amount of changes are sent to the unit via network communication.
Save now to EEPROM This function saves all settings right now to the EEPROM. If autosave is disabled, it is highly
recommended to save all settings to the EEPROM after configuring the unit for all settings to
be kept after any type of power failure or restart of the unit.
Example
Activation of Bypass is not stored in the memory. Instead, the controller will return to the pre-
set operating mode after power failure. However, the set operating mode will be saved if
central control is being used (parameter 47).
Regio Midi manual
Chapter 16 Modbus signal types
67
Chapter 16 Modbus signal types
EXOL Types
The EXOL types of the signals:
R = Real (-3.3E38 - 3.3E38)
I = Integer (-32768 - 32767)
X = Index (0 - 255)
L = Logic (0/1)
Modbus Type
The Modbus types of the signals (types in the list below):
1 = Coil Status Register (Modbus function = 1, 5 and 15)
2 = Discrete Input (Modbus function = 2)
3 = Holding Register (Modbus function = 3, 6 and 16)
4 = Input Register (Modbus function = 4)
Supported Modbus functions:
1 = Read Coils
2 = Read Discrete Input
3 = Read Holding Register
4 = Read Input Register
5 = Write Single Coil
6 = Write Single Register
15 = Write Multiple Coils
16 = Write Multiple Registers
Scale factor Modbus
”Discrete Inputs” and ”Coil status register” always have scale factor 1. For ”Input register”
and ”Holding register”, see variable list in chapter ”Modbus signals”.
EXOline/Modbus
The Midi controller automatically switches between EXOline and Modbus depending on the
present communication type, without any communication error.
Modbus wiring etc.
A protocol such as Modbus consists of several layers (OSI-model). The bottom layer
is always the physical layer, number of wires and signal levels. The next layer
describes the communication digits (number of data bits, stop-bits, parity etc). Then
come the layers describing the Modbus specific functions (number of digits per
message, the meaning of different messages etc).
For Modbus, the bottom layer can be RS485, RS422 or RS232.
RS485 contra RS422
RS485 and RS422 are the electric part of the protocol, i. e. the physical layer.
RS485 has two connections, A and B. Often there is also a protective earth (N on EXO
controllers). RS485 units are connected A A and B B. You may have to shift A and B in
order for Modbus to work. RS485 is so called half duplex communication: Communication
can only go in one direction at a time; i. e. the master will first send an enquiry and will
thereafter listen for the reply. A and B are used for both transmission and reception.
Chapter 16 Modbus signal types
Regio Midi manual
RS422 is a full duplex communication which means you need 4 wires, 2 for transmit
(Tx+ and Tx-) and 2 for receive (Rx+ and Rx-). Tx is used to transmit and Rx to receive, which
means that Tx in one unit must be connected to Rx in the other and vice versa. As for signal
levels, etc., RS422 and RS485 are identical.
To interconnect RS485 and RS422: On the RS422 unit connect Tx+ with Rx+ and Tx- with
Rx-. We have now changed a 4-wire system to a 2-wire system and can connect them to A and
B on the RS485 unit. Which goes where is something you most often need to find out by trial
and error. Incorrect polarity will just give nonfunction but cannot harm either unit.
Tx+ -----|---------------------------------------- A (or B)
|
Rx+ -----|
Tx- -----|---------------------------------------- B (or A)
|
Rx- -----|
Bitrate, two stop bits, parity is the next layer
These settings must correspond to the settings in the master unit. Find out how the master is
set and then give the Controller the same settings.
Parity can be set to odd, even (FS) or none. If none is chosen, two stop bits will automatically
be used. It is also possible to configure no parity using one stop bit. In this case, automatic
switching between EXOline and Modbus will not function. If odd or even is chosen, only one
stop-bit is used, or there will be too many bits altogether: 1 start-bit, 8 data-bits, 1 parity-bit
and 1 stop-bit give a total of 11 bits which is the maximum amount.
Regio Midi manual
Chapter 17 Modbus signals
69
Chapter 17 Modbus signals
Discrete inputs
Signal name
Type
Modbus
address
Description
RC_Actual_L.RegioDigIn(0)
L,2
1
Not used
RC_Actual_L.RegioDigIn1
L,2
2
Value of digital input 1
RC_Actual_L.RegioDigIn2
L,2
3
Value of digital input 2
RC_Actual_L.RegioUDigIn1
L,2
4
Value of universal digital input 1
RC_Actual_L.RegioDigOut(0)
L,2
5
Not used
RC_Actual_L.RegioDigOut1
L,2
6
Value of digital output 1
RC_Actual_L.RegioDigOut2
L,2
7
Value of digital output 2
RC_Actual_L.RegioDigOut3
L,2
8
Value of digital output 3
RC_Actual_L.RegioDigOut4
L,2
9
Value of digital output 4
RC_Actual_L.RegioDigOut5
L,2
10
Value of digital output 5
RC_Actual_L.RegioUDigOut1
L,2
11
Value of universal digital output 1
RC_Actual_L.RegioUDigOut2
L,2
12
Value of universal digital output 2
RC_Actual_L.RegioDIOpenWindow
L,2
13
Indicate open window
RC_Actual_L.RegioDICondenseAlarm
L,2
14
Indicate condense alarm from digital input
RC_Actual_L.RegioDIPresences
L,2
15
Indicate presence from digital input
RC_Actual_L.RegioDIChangeOver
L,2
16
Indicate change over from digital input
RC_Actual_L.RegioFanSpeed1
L,2
17
Indicate fan speed 1
RC_Actual_L.RegioFanSpeed2
L,2
18
Indicate fan speed 2
RC_Actual_L.RegioFanSpeed3
L,2
19
Indicate fan speed 3
RC_Actual_L.RegioForcedventilation
L,2
20
Indicate forced ventilation
RC_Actual_L.RegioCVHeatPulsProp
L,2
21
Indicate pulse prop heating
RC_Actual_L.RegioCVCoolPulsProp
L,2
22
Indicate pulse prop cooling
RC_Actual_L.RegioCVHeatInc
L,2
23
Indicate increase heating
RC_Actual_L.RegioCVHeatDec
L,2
24
Indicate decrease heating
RC_Actual_L.RegioCVCoolInc
L,2
25
Indicate increase cooling
RC_Actual_L.RegioCVCoolDec
L,2
26
Indicate decrease cooling
RC_Actual_L.RegioAIChangeOverState
L,2
27
Indicate change-over state from analogue
input
RC_Actual_L.RegioChangeOverState
L,2
28
Indicate change-over state from both digital
and analogue input
Not used in this model
L,2
29
RC_Actual_L.RegioDigOut3
L,2
30
Value of universal digital output 3
RC_Actual_L.RegioPresence
L,2
31
Indicate presence
RC_Actual_L.RegioRoomTempHighTempAlarm L,2
32
Indicate high room temperature alarm
RC_Actual_L.RegioRoomTempLowTempAlarm
L,2
33
Indicate low room temperature alarm
RC_Actual_L.RegioDICO2
L,2
34
Indicate high CO2 level
Chapter 17 Modbus signals
Regio Midi manual
Signal name
Type
Modbus
address
Description
RC_Actual_L.RegioLighting
L,2
38
Lighting control, indication
RC_Actual_L.RegioDIindacation
L,2
39
Run indication, when DI2 is configured as
such
RC_Actual_L.RegioPresenceByCo2
L,2
40
Indicates presence from CO2 sensor
Coil status register
Signal name
Type
Modbus
address
Default
value
Description
RC_Setp_L.RegioBypass
L,1
1
0
Force the unit in Bypass mode. Is
automatically returned after Bypass
time.
0=No bypass
1=Bypass
RC_Setp_L.RegioShutDown
L,1
2
0
Force the unit in Shutdown state.
0=No Shutdown
1=Shutdown
RC_Setp_L.RegioNotUsed
L,1
3
Not used
RC_Setp_L.RegioDiNC(0)
L,1
4
Not used
RC_Setp_L.RegioDi1NC
L,1
5
0
State NO/NC digital input 1:
0=NO (Normally open)
1=NC (Normally closed)
RC_Setp_L.RegioDi2NC
L,1
6
1
State NO/NC digital input 2:
0=NO (Normally open)
1=NC (Normally closed)
RC_Setp_L.RegioUDi1NC
L,1
7
0
State NO/NC universal input 1:
0=NO (Normally open)
1=NC (Normally closed)
RC_Setp_L.RegioCVHeatPulsPropNC L,1
8
0
Selection of heating output function
(NO/NC):
0=NO (Normally open)
1=NC (Normally closed)
Not used in this model
L,1
9-13
0
RC_Setp_L.RegioMinFanSpeed
L,1
14
0
The fan will never stop:
0=Off
1=On
RC_Setp_L.RegioCVCoolPulsPropNC L,1
15
0
Selection of cooling output functions
(NO/NC):
0=NO (Normally open)
1=NC (Normally closed)
RC_Setp_L.RegioComFactoryDefault
L,1
16
0
Resets communication to default
values:
1=Reset (returns to 0)
RC_Setp_L.RegioBlockConfig
L,1
21
0
Prevents parameter menu access via
display
Regio Midi manual
Chapter 17 Modbus signals
71
Signal name
Type
Modbus
address
Default
value
Description
RC_Setp_L.RegioPreventManualFanS
peed
L,1
22
0
Function to prevent user from setting
manual fan speed if fan should not
run due to cooling/heating output
according to parameter 50.
0 = Not active
1 = Active
RC_Setp_L.Regio3PEndlimProtect
L,1
23
0
Shuts down the three-position
actuator output after 1 minute at 0 %
or 100 % output
RC_Setp_L.RegioSteppableBPTimer
L,1
24
0
Activate manual bypass timer
setting. When the function is active,
the user may step through bypass
time in 1 hour increments.
0 = Not active
1 = Active
RC_Setp_L.RegioChangeOverAdvanc
ed
L,1
25
1
Select simple or advanced analog
change-over
RC_Setp_L.RegioDisableAutoSave
L,1
26
0
Disables automatic saving to
EEPROM
RC_Setp_L.RegioSaveNow
L,1
27
0
Save current settings to EEPROM
now
Input register
Signal name
Type
Modbus
address
Scale
factor
Description
RC_Actual_X.RegioSoftware
X, 4
1
-
Model
RC_Actual_X.RegioVerMajor
X, 4
2
-
Version Major
RC_Actual_X.RegioVerMinor
X, 4
3
-
Version Minor
RC_Actual_X.RegioVerBranch
X, 4
4
-
Version Branch
RC_Actual_X.RegioRevision
X, 4
5
-
Revision
RC_Actual_X.RegioFanSwitch
X, 4
6
-
Indicates the position of the fan switch:
0=Fan switched off
1=Fan speed 1
2=Fan speed 2
3=Fan speed 3
4=Auto
RC_Actual_X.RegioUnitState
X, 4
7
-
Indicate current unit state:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
4=Bypass
RC_Actual_X.RegioControllerState
X, 4
8
-
Indicate current controller state:
0=Off
1=Heating
2=Cooling
Chapter 17 Modbus signals
Regio Midi manual
Signal name
Type
Modbus
address
Scale
factor
Description
RC_Actual_X.RegioFanSpeed
X, 4
9
-
Indicate current fan speed:
0=Off
1=Fan speed 1 is on
2=Fan speed 2 is on
3=Fan speed 3 is on
RC_Actual_R.RegioNotUsedX
X, 4
10
-
Not used
RC_Actual_R.RegioRoomTemp
R, 4
11
10
Room temperature
RC_Actual_R.RegioRoomTempExt
R, 4
12
10
Room temperature from external sensor
RC_Actual_R.RegioRoomTempInt
R, 4
13
10
Room temperature from internal sensor
RC_Actual_R.RegioAIChangeOver
R, 4
14
10
Change-over temperature
RC_Actual_R.RegioAnaIn1
R, 4
15
10
Value of analogue input 1
RC_Actual_R.RegioUAnaIn1
R, 4
16
1
Value of universal analogue input 1
RC_Actual_R.RegioUAnaOut1
R, 4
17
-
Value of universal analogue output 1
RC_Actual_R.RegioUAnaOut2
R, 4
18
-
Value of universal analogue output 2
RC_Actual_R.RegioSetPAdjustment R, 4
19
10
Setpoint adjustment from internal
device
RC_Actual_R.RegioPIDSetP
R, 4
20
10
The controller setpoint
RC_Actual_R.RegioPIDOutput
R, 4
21
-
The controller output (0…100 %)
RC_Actual_R.RegioHeatOutput
R, 4
22
-
Heat output (0…100 %)
RC_Actual_R.RegioCoolOutput
R, 4
23
-
Cool output (0…100 %)
RC_Actual_R.RegioAI1Raw
R, 4
24
10
The raw value on analogue input 1
RC_Actual_R.RegioUI1Raw
R, 4
25
1
The raw value on universal input 1
RC_Actual_R.RegioUO3Output
R, 4
26
10
Value of universal output 3
RC_Actual_R.RegioUAnaOut3
R, 4
27
10
Value of universal analogue output 3
RC_Actual_R.RegioRoomCO2
R, 4
32
-
CO2 input value (ppm)
Not used in this model
R, 4
44
-
RC_Actual_R.RegioVoltInput
R, 4
45
10
Value of 0…10 V DC input at AI2
RC_Actual_R.RegioRoomFlow
R, 4
46
10
Value of Room Air Flow at AI2
RC_Actual_R.RegioSupplyAirTemp R, 4
47
10
Supply air temperature from sensor
connected to A1
RC_Actual_R.RegioSupplyAirPIDo
ut
R, 4
48
-
Supply air controller output
RC_Actual_R.RegioPID2Setp
R, 4
49
10
Room controller output (scaled) and
supply air controller setpoint
Holding register
Signal name
Type
Modbus
address
Default
value
Scale
factor
Description
RC_Setp_X.AlaModStat
X, 3
1
-
-
Not used
RC_SetP_X.RegioFreeCoolAvailable
X, 3
2
0
-
Sequence order for Y2 and
Y3:
0=Y2 activates before Y3
1=Y3 activates before Y2
Regio Midi manual
Chapter 17 Modbus signals
73
Signal name
Type
Modbus
address
Default
value
Scale
factor
Description
RC_Setp_X.RegioHeatOutputSelect
X, 3
3
2
-
Manual/Auto Heating output:
0=Off
1=Manual
2=Auto
RC_Setp_X.RegioCoolOutputSelect
X, 3
4
2
-
Manual/Auto Cooling output:
0=Off
1=Manual
2=Auto
RC_Setp_X.RegioFanSelect
X, 3
5
4
-
Select fan mode:
0 = Off
1 = Manual speed 1
2 = Manual speed 2
3 = Manual speed 3
4 = Auto
RC_Setp_X. RegioFanControlMode
X, 3
6
3
-
Configuration of fan control:
0=No control
1=Fan is controlled by
heating demand
2=Fan is controlled by
cooling demand
3=Fan is controlled by both
heating and cooling demand
RC_Setp_X.RegioFanSpeed1Start
X, 3
7
5 %
-
Start signal in % for fan
speed 1 on heating or cooling
control
RC_Setp_X.RegioFanSpeed2Start
X, 3
8
60 %
-
Start signal in % for fan
speed 2
RC_Setp_X.RegioFanSpeed3Start
X, 3
9
100 %
-
Start signal in % for fan
speed 3
RC_Setp_X.RegioFanSpeedHyst
X, 3
10
5 %
-
Hysteresis for start/stop of
fans
RC_Setp_X.RegioFanSpeedMax
X, 3
11
3
-
State number of speeds for
the fan
RC_Setp_X.RegioForcedVentSelec
X, 3
12
2
-
Manual/Auto Y3 forced
ventilation output:
0=Off
1=Manual
2=Auto
RC_Setp_X.RegioChangeOverSelect
X, 3
13
2
-
Manual/Auto control of
change-over mode:
0=Heat control
1=Cool control
2=Automatic change over
depending on analogue
sensor input or digital input
RC_Setp_X.RegioRemoteState
X, 3
14
5
-
Select operating mode for
central control:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied
5=No central control
Chapter 17 Modbus signals
Regio Midi manual
Signal name
Type
Modbus
address
Default
value
Scale
factor
Description
RC_Setp_X.RegioUnitReturnState
X, 3
15
3
-
Pre-set operating mode:
0=Off
1=Unoccupied
2=Stand-by
3=Occupied. Forced
ventilation is not set in
Occupied mode.
RC_Setp_X.RegioUnitShutDownState
X, 3
16
1
-
State operating mode by
pressing the occupancy
button for 5 s:
0=Off
1=Unoccupied.
RC_Setp_X.RegioBtnOnOffTime
X, 3
17
5 s (0 s
for F-
models)
-
Time to keep the occupancy
button depressed before
switching to Shutdown state.
RC_Setp_X.RegioControllerMode
X, 3
18
3
-
Control mode:
0=Heating
1= Heating / Heating
2= Heating or Cooling via
change over
3= Heating /Cooling
4= Heating /Cooling with
VAV-control and forced
supply air function
5= Heating /Cooling with
VAV-control
6= Cooling
7= Cooling/Cooling
8= Heating /Cooling/VAV
(C3-models, except RC-
C3DFOC)
9=Heating/Heating or
Cooling via change-over
(only available in models
with fan control)
10= Change-over with VAV-
function
RC_Setp_X.RegioCVHeatType
X, 3
19
0
-
State output signal range for
Heating-actuators:
0=0…10 V
1=2…10 V
2=10…2 V
3=10…0 V
RC_Setp_X.RegioCVCoolType
X, 3
20
0
-
State output signal range for
Cooling actuators:
0=0…10 V
1=2…10 V
2=10…2 V
3=10…0 V
RC_Setp_X.RegioCVHeatExerciseInter
val
X, 3
21
23h
-
Time in hours between
exercise of heating actuators
RC_Setp_X.RegioCVCoolExerciseInter
val
X, 3
22
23h
-
Time in hours between
exercise of cooling actuators
Not used in this model
X, 3
23
-
-
Regio Midi manual
Chapter 17 Modbus signals
75
Signal name
Type
Modbus
address
Default
value
Scale
factor
Description
RC_Setp_X.RegioAi1
X, 3
24
0
-
State connected sensor on
AI1:
0=Internal sensor
1=External room sensor
2=Change over sensor
(RC-C3DOC,
RCC-C3DOCS,
RC-C3DFOC)
3-10= No function
11= Supply air temperature
limitation sensor
RC_Setp_X.RegioAi2
X, 3
25
5
-
State the connected sensor at
AI2: (Only RC-C3DOC,
RCC-C3DOCS,
RC-C3DFOC)
0=None
1– 4=No function
5=CO2-sensor
6=No function
7=0…100 % (OEM-function)
8=Flow calculation
9=0…10 V
Not used in this model
X, 3
26
-
-
RC_Setp_X.RegioDi1
X, 3
27
3
-
State connected sensor on
DI1:
0=Not active
1=Window contact
2= No function
3=Presence detector
4=Change over sensor
(RC-C3DOC,
RCC-C3DOCS,
RC-C3DFOC)
RC_Setp_X.RegioDi2
X, 3
28
2
-
State connected sensor on
DI2:
1=Window contact
2=Condensation sensor
3=No function
4=Change over sensor
(RC-C3DOC,
RCC-C3DOCS,
RC-C3DFOC)
3-10= No function
11= Supply air temperature
limitation sensor
Not used in this model
X, 3
29
0
-
RC_Setp_X.RegioUi1
X, 3
30
2
-
State connected sensor on
UI1: (All models except
RC-C3DOC, RCC-C3DOCS,
RC-C3DFOC)
0=None
1=Change-over digital
2=Change-over analogue
Not used in this model
X, 3
31-34
-
-
Chapter 17 Modbus signals
Regio Midi manual
Signal name
Type
Modbus
address
Default
value
Scale
factor
Description
RC_Setp_X.RegioDo1
X, 3
35
1 (-F-
models),
4 (other
models)
-
0=Not active
1=Fan speed 1
2=Fan speed 2
3=Fan speed 3
4=Forced ventilation
5=Thermal actuator heating
6=Thermal actuator cooling
7=Increase/Decrease valve,
heating increase
8=Increase/Decrease valve,
heating decrease
9=Increase/Decrease valve,
cooling increase
10= Increase/Decrease valve,
cooling decrease
11=Lighting control
RC_Setp_X.RegioDo2
(only used for -F- and -T- models)
X, 3
36
2 (-F-
models),
7 (-T-
models)
-
2=Fan speed 2
7= Heat valve increase
RC_Setp_X.RegioDo3
(only used for -F- and -T- models)
X, 3
37
3 (-F-
models),
8 (-T-
models)
-
3=Fan speed 3
8=Heat valve decrease
RC_Setp_X.RegioDo4
(only used for -F- and -T- models)
X, 3
38
4 (-F-
models),
9 (-T-
models)
-
4=Forced ventilation
9= Cool valve increase
RC_Setp_X.RegioDo5
(only used for -T- models)
X, 3
39
10 (-T-
models)
-
10=Cool valve decrease
Not used in this model
X, 3
40-41
-
-
RC_Setp_X.RegioUo1 (Not –T-
models)
X, 3
42
3
-
State connected function on
UO1:
0=None
1=Thermal actuator heat
2=None
3=Heating actuator 0...10 V
4=None
5=On/off actuator heat
6=None
RC_Setp_X.RegioUo2 (Not –T-
models)
X, 3
43
4
-
State connected function on
UO2:
0=None
1=None
2=Thermal actuator Cool
3=None
4=Cooling actuator 0…10 V
5=None
6=On/off actuator cool
RC_Setp_X.RegioModbusSlaveAddr
X, 3
44
Factory
set
-
Controller Modbus address
Regio Midi manual
Chapter 17 Modbus signals
77
Signal name
Type
Modbus
address
Default
value
Scale
factor
Description
RC_Setp_X.RegioModbusParity
X, 3
45
2
-
Parity of Modbus
communication:
0=No parity
1=Odd parity
2=Even parity
3=No parity, 1 stop bit
RC_Setp_X.RegioModbusCharTimeout X, 3
46
3 ms
-
Modbus timeout for character
(t1.5), in ms. Should be 1.5
times a character, i.e. at least
2 ms.
RC_Setp_X.RegioModbusAnswerDelay X, 3
47
5 ms
-
Answer delay in Modbus
(t3.5), in ms. Should be 3.5
times a character, i.e. at least
5 ms.
RC_Setp_X.RegioDispBacklightLO
X, 3
48
10
-
10=Backlight low
RC_Setp_X.RegioDispBacklightHi
X, 3
49
30
-
30=Backlight high
RC_Setp_X.RegioDispContrast
X, 3
50
15
-
15=Display contrast
RC_Setp_X.RegioDisplayViewMode
X, 3
51
0
-
Select if setpoint or actual
value is to be shown in the
display.
0=Actual value
1=Heat setpoint
2=Cool setpoint
3=Average value of heating
and cooling setpoint
4=Only setpoint offset
5=CO2-concentration in the
room in ppm (RC-C3DOC,
RCC-C3DOCS,
RC-C3DFOC)
6=Heating setpoint +setpoint
offset
7=Cooling setpoint+setpoint
offset
8=Average of heating and
cooling setpoint+setpoint
offset
9=The calculated flow in the
duct in l/s (RC-C3DOC,
RCC-C3DOCS,
RC-C3DFOC )
Chapter 17 Modbus signals
Regio Midi manual
Signal name
Type
Modbus
address
Default
value
Scale
factor
Description
RC_Setp_X.RegioDispSetpMode
X, 3
52
0
-
Setpoint display at setpoint
adjustment:
0=The offset is shown in the
display
1=The active setpoint + offset
is shown in the display. Heat
or Cool is shown depending
on whether heat or cool is
active when entering the
menu
2=Heat setpoint + offset is
shown in the display
3=Cooling setpoint + offset is
shown in the display
4=Heating occupied setpoint
+ offset is shown in the
display
5=Cooling occupied setpoint
+ offset is shown in the
display
6=Average of heating and
cooling setpoints + offset is
shown in the display
RC_Setp_X.RegioUo3
X, 3
53
6 (RC-
C3DFO
C)
or
1 (other
C3…
models)
-
State connected function on
UO3:
0=None
1=Forced ventilation, digital
2=Analogue output (OEM)
3=Lighting control, digital
4=Ordinary analogue output
5=None
6=Control of a EC fan (RC-
C3 and RCC-… models)
RC_Setp_X.RegioForcedVentControlM
ode
X, 3
54
0
-
Forced ventilation, control
function:
0=Not active
1=Forced ventilation at 100
% output of heat or cool
2=Forced ventilation at 100
% cool output
RC_Setp_X.RegioUnitDIPresenceState
I, 3
55
4
-
Operating mode at presence
detection:
3=Occupied
4=Bypass
RC_Setp_I.RegioBypassTime
I, 3
56
120 min -
Time in Bypass mode
RC_Setp_I.RegioPresenceOffTime
I, 3
57
10 min
-
Disconnect timer with
Occupancy/Unoccupancy
RC_Setp_I.RegioPresenceOnTime
I, 3
58
0 min
-
Switch-on delay for
Occupancy
RC_Setp_I.RegioCVHeatPeriodTime
I, 3
59
60s
-
Period time for heating
actuators with thermal
actuator
RC_Setp_I.RegioCVCoolPeriodTime
I, 3
60
60s
-
Period time for cooling
actuators with thermal
actuator
Regio Midi manual
Chapter 17 Modbus signals
79
Signal name
Type
Modbus
address
Default
value
Scale
factor
Description
RC_Setp_I.RegioCVHeatRunTime
I, 3
61
120 s
-
Run time for heating
actuators with
increase/decrease actuators
RC_Setp_I.RegioCVCoolRunTim
I, 3
62
120 s
-
Run time for cooling
actuators with
increase/decrease actuators
Not used in this model
X, 3
63-67
-
-
RC_Setp_R.RegioOccSetPHeat
R, 3
68
22°C
10
Basic Heating setpoint
RC_Setp_R.RegioOccSetPCool
R, 3
69
24°C
10
Basic Cooling setpoint
RC_Setp_R.RegioStandbySetPDeadBan
d
R, 3
70
3°C
10
Neutral zone at Stand-by,
Heating sp=basic sp .heating-
3 by default,
Coolsp=Basic sp.cool+3 by
default
RC_Setp_R.RegioUnOccSetPHeat
R, 3
71
15°C
10
Heating setpoint at
Unoccupied
RC_Setp_R.RegioUnOccSetPCool
R, 3
72
30°C
10
Cooling setpoint at
Unoccupied
RC_Setp_R.RegioFrostSetP
R, 3
73
8°C
10
Frost protection setpoint
RC_Setp_R.RegioSetpointOffsetPos
R, 3
74
3°C
10
Highest permitted setpoint
adjustment uppwards
RC_Setp_R.RegioSetpointOffsetNeg
R, 3
75
3°C
10
Highest permitted setpoint
adjustment downwards
RC_Setp_R.RegioSetPOffset
R, 3
76
0 °C
10
The setpoint adjustment
RC_Setp_R.RegioPIDPGain
R, 3
77
10°C
10
P-band for room controller
RC_Setp_R.RegioPIDITime
R, 3
78
300 s
I-time (s) for room controller
RC_Setp_R.RegioCVDeadband
R, 3
79
2%
Deadband for
increase/decrease actuators
(%)
RC_Setp_R.RegioAIChangeOverDiffHe
at
R, 3
80
3K
10
The difference between the
temperature in the room and
the media temperature for
change over to cooling
RC_Setp_R.RegioAIChangeOverDiffCo
ol
R, 3
81
4K
10
The difference between the
temperature in the room and
the media temperature for
change over to heating
RC_Setp_R.RegioAi1Comp
R, 3
82
0°C
10
Temperature compensation
on AI1
RC_Setp_R. RegioUi1Comp
R, 3
83
0°C
10
Temperature compensation
on UI1
RC_Setp_R.RegioInternalTempComp
R, 3
84
0°C
10
Temperature compensation
on internal room sensor
RC_Setp_R.RegioTempFilterFactor
R, 3
85
0,2
10
Filter factor for analogue
temperature inputs
Chapter 17 Modbus signals
Regio Midi manual
Signal name
Type
Modbus
address
Default
value
Scale
factor
Description
RC_Setp_R.RegioMinFlow
R, 3
86
20
-
Min flow at cool output when
control mode
Heating/Cooling with VAV-
control is selected
Min flow at Y3 output when
control mode
Heating/Cooling/VAV is
selected
RC_Setp_R.RegioMaxFlowHeat
R, 3
87
0%
-
Max flow on cool output
when control mode
Heating/Cooling with VAV-
control is selected and
heating is applied.
RC_SetP_R.RegioRoomTempHighLimi
t
R, 3
88
40°C
10
Alarm limit for high room
temperature
RC_SetP_R.RegioRoomTempLowLimit R, 3
89
15°C
10
Alarm limit for low room
temperature
RC_Setp_R.RegioVAVMaxHeatCool
R, 3
90
100 %
-
VAV-damper max limitation.
Applies to control modes 4, 5
and 8.
Not used in this model
R, 3
90-92
-
-
RC_Setp_R.RegioUo3OutputManual
R, 3
93
0%
-
Y3 Output in manual mode
RC_Setp_R.RegioHeatOutputManual
R, 3
94
0%
-
Heating output in manual
mode
RC_Setp_R.RegioCoolOutputManual
R, 3
95
0%
-
Cooling output in manual
mode
RC_Setp_R.RegioRoomTempRemote
R, 3
96
-255
10
Room temp set by remote
control if external room
sensor is configured (-255 =
disabled)
RC_Setp_R.RegioCO2_0V
R, 3
120
0ppm
-
CO2-level at 0 V
(RC-C3DOC,
RCC-C3DOCS,
RC-C3DFOC)
RC_Setp_R.RegioCO2_10V
R, 3
121
2000pp
m
-
CO2-level at 10 V
(RC-C3DOC,
RCC-C3DOCS,
RC-C3DFOC)
RC_Setp_R.RegioCO2FilterFactor
R, 3
125
0,2
10
Filter factor for CO2-input
(RC-C3DOC,
RCC-C3DOCS,
RC-C3DFOC)
RC_Setp_R.RegioCO2PresenceLimit
R, 3
133
800ppm -
Activate presence if CO2
level is higher (RC-C3DOC,
RCC-C3DOCS,
RC-C3DFOC)
RC_Setp_R.RegioCO2PresenceHyst
R, 3
134
160ppm -
Deactivate presence if the
CO2 level is lower than the
limit minus this hysteresis
(RC-C3DOC,
RCC-C3DOCS,
RC-C3DFOC)
Regio Midi manual
Chapter 17 Modbus signals
81
Signal name
Type
Modbus
address
Default
value
Scale
factor
Description
RC_Setp_R.RegioCO2LimitLow
R, 3
147
600ppm -
Min limit for VAV-damper at
CO2-control
(RC-C3DOC,
RCC-C3DOCS,
RC-C3DFOC)
RC_Setp_R.RegioCO2LimitHigh
R, 3
148
800ppm -
Max limit for VAV-damper
at CO2-control
(RC-C3DOC,
RCC-C3DOCS,
RC-C3DFOC)
RC_SetpExt_R.RegioFlowFilterFactor
R, 3
149
0
10
Flow filter factor
RC_Setp_R.RegioFanBoostTime
R, 3
276
0
-
Fan boost function.
Activation time:
0= Not active
1-10 = The function is active
for 10 s.
10-600 = Total activation
time
RC_SetpExt_R.RegioFlow_0V
R, 3
277
0 l/s
-
Flow at 0 V input in AI2 (l/s)
RC_SetpExt_R.RegioFlow_10V
R, 3
278
100 l/s
-
Flow at 10 V input in AI2
(l/s)
RC_SetpExt_R.RegioThermostatHystH
eat
R, 3
279
2K
10
Hysteresis for On/Off
actuators and heating
RC_SetpExt_R.RegioThermostatHystC
ool
R, 3
280
2K
10
Hysteresis for on/off
actuators and cooling
RC_SetpExt_R.RegioMinHeat
R, 3
281
0 %
-
Min. limit for the heat output
RC_SetpExt_R.RegioMinECFanSpeed
R, 3
282
10 %
-
Min. limit for EC fan (%)
RC_SetpExt_R.RegioMaxECFanSpeed
R, 3
283
100 %
-
Max. limit for EC fan (%)
RCPSettings.RegioMinFlowStandby
R, 3
285
10 %
-
Basic flow at “Standby”
when control state
“Heating/Cooling with VAV-
control” or
“Heating/Cooling/VAV” is
configured
RCPSettings.RegioMinFlowUnoccupied R, 3
286
10 %
-
Basic flow at “Unoccupied”
when control state
“Heating/Cooling with VAV-
control” or
“Heating/Cooling/VAV” is
configured
RCPSettings.RegioMinFlowOff
R, 3
287
0 %
-
Basic flow at “Off” when
control state
“Heating/Cooling with VAV-
control” or
“Heating/Cooling/VAV” is
configured
RC_Setp_R.SupplyAirTLim_HeatHi
R, 3
289
35°C
10
Supply air max limitation for
cascade control and heating
control
Chapter 17 Modbus signals
Regio Midi manual
Signal name
Type
Modbus
address
Default
value
Scale
factor
Description
RC_Setp_R.SupplyAirTLim_HeatLo
R, 3
290
24°C
10
Supply air min limitation for
cascade control and heating
control
RC_Setp_R.SupplyAirTLim_CoolHi
R, 3
291
24°C
10
Supply air max limitation for
cascade control and cooling
control
RC_Setp_R.SupplyAirTLim_CoolLo
R, 3
292
12°C
10
Supply air min limitation for
cascade control and cooling
control
RC_Setp_R.SupplyAirTLim_CascadeFa
ct
R, 3
293
3°C
10
Cascade factor between room
controller and supply air
controller
RC_Setp_R.SupplyAirTLim_FrostProte
ct
R, 3
294
8°C
10
Frost protection temperature
for supply air when supply air
temperature limitation is
active
RC_Setp_X.RegioExerciseSelect
X, 3
296
1
-
Use valve exercise
0 = Never
1 = Regularly
2 = Regularly and at power-
up
3 = Regularly, at power-up
and when changing state to
Occupied
Regio Midi manual
Chapter 18 BACnet signal types
83
Chapter 18 BACnet signal types
BACnet
Bacnet communication is only available in models with display. In order to communicate via
BACnet, the protocol has to be changed either via Regio tool© or via the parameter list in the
display. Once the protocol has been set to BACnet it can only be switched back to EXOline
and Modbus via the display.
MS/TP mode
Both MS/TP master and slave are supported. The mode is controlled by setting the MAC
address. If < 127, master mode is selected. A MAC address of > 127 enables slave.
Object Type
The BACnet types of the signals (types in the list below):
•
Analogue inputs
•
Analogue values
•
Binary inputs
•
Binary values
•
Loop
•
Multistate inputs
•
Multistate values
•
Device
Out_of_service
The property out_of_service is not writable for all Object Types.
Commandable
The value objects are not commandable (i.e. does not use a priority array).
Chapter 19 BACnet signals
Regio Midi manual
Chapter 19 BACnet signals
Analogue inputs
Object name
Object-ID
Description
Unit
Writable
RC_Actual_R.RegioRoomTemp
Analog input, 0 Room temperature
°C
No
RC_Actual_R.RegioAIChangeOver
Analog input, 1 Change over temperature
°C
No
RC_Actual_R.RegioAnaIn1
Analog input, 2 Value of analogue input 1
°C
No
RC_Actual_R.RegioUAnaIn1
Analog input, 3 Value of universal analogue input 1
V
No
RC_Actual_R.RegioRoomCO2
Analog input, 4 CO2 input value
ppm
No
RC_Actual_R.RegioSupplyAirTemp
Analog input, 5 Supply air temperature
°C
No
RC_Actual_R.RoomFlow
Analog input, 6 Air flow
l/s
No
RC_Actual_R.VoltInput
Analog input, 7 Value on analogue input 2
V
No
Analogue values
Object name
Object-ID
Description
Unit Writable
RC_Actual_R.RegioUAnaOut1
Analog value, 0
Value of universal analogue
output 1
V
No
RC_Actual_R.RegioUAnaOut2
Analog value, 1
Value of universal analogue
output 2
V
No
RC_Actual_R.RegioSetPAdjustment
Analog value, 2
Setpoint adjustment from
internal device
°C
No
RC_Actual_R.RegioPIDSetP
Analog value, 3
Controller setpoint
°C
No
RC_Actual_R.RegioPIDOutput
Analog value, 4
Controller output
%
No
RC_Actual_R.RegioHeatOutput
Analog value, 5
Heat output
%
No
RC_Actual_R.RegioCoolOutput
Analog value, 6
Cool output
%
No
RC_Setp_R.RegioOccSetPHeat
Analog value, 7
Room base setpoint heating
°C
Yes
RC_Setp_R.RegioOccSetPCool
Analog value, 8
Room base setpoint cooling
°C
Yes
RC_Setp_R.RegioUnOccSetPHeat
Analog value, 9
Room heat setpoint in
unoccupied mode
°C
Yes
RC_Setp_R.RegioUnOccSetPCool
Analog value, 10
Room cool setpoint in
unoccupied mode
°C
Yes
RC_Setp_R.RegioFrostSetP
Analog value, 11
Frost protection setpoint
°C
Yes
Regio Midi manual
Chapter 19 BACnet signals
85
Object name
Object-ID
Description
Unit Writable
RC_Setp_R.RegioSetPOffset
Analog value, 12
Setpoint adjustment
°C
Yes
RC_Setp_R.RegioHeatOutputManual
Analog value, 13
Manual value heating output
%
Yes
RC_Setp_R.RegioCoolOutputManual
Analog value, 14
Manual value cooling output
%
Yes
RC_Setp_R.RegioRoomTempRemote
Analog value, 15
Remote control of room
temperature
°C
Yes
RC_Setp_R.RegioStandbySetPDeadBand
Analog value, 16
Deadband in Standby mode
°C
Yes
RC_Setp_R.RegioCVDeadband
Analog value, 17
Deadband control valve
%
Yes
RC_Setp_R.RegioAIChangeOverDiffHeat
Analog value, 18
Difference between media
temperature and room
temperature to switch to
heating control
K
Yes
RC_Setp_R.RegioAIChangeOverDiffCool
Analog value, 19
Difference between media
temperature and room
temperature to switch to
cooling control
K
Yes
RC_Setp_R.RegioRoomTempHighLimit
Analog value, 20
Alarm limit for high room
temperature
°C
Yes
RC_Setp_R.RegioRoomTempLowLimit
Analog value, 21
Alarm limit for low room
temperature
°C
Yes
RC_Setp_R.RegioFlow_0V
Analog value, 22
Flow at 0 V input signal at AI2 l/s
Yes
RC_Setp_R.RegioFlow_10V
Analog value, 23
Flow at 0 V input signal at AI2 l/s
Yes
RC_Setp_R.RegioThermostatHystHeat
Analog value, 24
Hysteresis when On/Off
control and Heat control
K
Yes
RC_Setp_R.RegioThermostatHystCool
Analog value, 25
Hysteresis when On/Off
control and Cool control
K
Yes
RC_Setp_R.RegioMinHeat
Analog value, 26
Minimum heat output at Heat
control
%
Yes
RC_Setp_R.RegioMinECFanSpeed
Analog value, 27
Minimum speed for the EC fan %
Yes
RC_Setp_R.RegioMaxECFanSpeed
Analog value, 28
Maximum speed for the EC fan %
Yes
RC_Setp_R.RegioAnaOut3
Analog value, 29
Value on universal analogue
output 3
V
No
RC_Setp_R.RegioUO3Output
Analog value, 30
UO3 Output (0…100 %)
%
No
RC_Actual_R.RegioPID2Setp
Analog value, 31
Calculated supply air setpoint
°C
No
No function
Analog value, 32-34
RC_SetpExt_R.RegioCO2LimitLow
Analog value, 35
CO2 value when damper starts
to open
ppm
Yes
RC_SetpExt_R.RegioCO2LimitHigh
Analog value, 36
CO2 value when damper is
fully open
ppm
Yes
Chapter 19 BACnet signals
Regio Midi manual
Binary inputs
Object name
Object-ID
Description
Values
Writable
RC_Actual_L.RegioDIOpenWindow
Binary input, 0
Indicate open window
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioDICondenseAlarm
Binary input, 1
Indicate condense alarm
from digital input
YES/
NO
No
RC_Actual_L.RegioDIPresences
Binary input, 2
Indicate presence from
digital input
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioDIChangeOver
Binary input, 3
Indicate change over
from digital input
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioRoomTempHighTempAlarm Binary input, 4
Room high temperature
alarm
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioRoomTempLowTempAlarm Binary input, 5
Room low temperature
alarm
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioDICO2
Binary input, 6
Indicates high CO2 level ACTIVE/
INACTIVE
No
RC_Actual_L.RegioDIindacation
Binary input, 7
Run indication, when
DI2 is configured as
such
ACTIVE/
INACTIVE No
All binary inputs have normal polarity.
Binary values
Object name
Object-ID
Description
Values
Writable
RC_Actual_L.RegioForcedVentilation
Binary
value, 0
Indicate forced ventilation
ON/OFF
No
RC_Actual_L.RegioCVHeatPulsProp
Binary
value, 1
Indicate pulse prop heating
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioCVCoolPulsProp
Binary
value, 2
Indicate pulse prop cooling
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioCVHeatInc
Binary
value, 3
Indicate increase heating
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioCVHeatDec
Binary
value, 4
Indicate decrease heating
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioCVCoolInc
Binary
value, 5
Indicate increase cooling
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioCVCoolDec
Binary
value, 6
Indicate decrease cooling
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioChangeOverState
Binary
value, 7
Indicate change over state from
both digital and analogue input
ACTIVE/
INACTIVE
No
RC_Actual_L.RegioRoomTempSensorAlarm Binary
value, 8
Indicate sensor alarm on room
sensor
ACTIVE/
INACTIVE
No
RC_Setp_L.RegioBypass
Binary
value, 9
Force the unit in Bypass mode.
Is automatically returned after
Bypass time (default=120 min)
ACTIVE/
INACTIVE
Yes
RC_Setp _L.RegioShutDown
Binary
value, 10
Force the unit in ShutDown
state
ACTIVE/
INACTIVE
Yes
Regio Midi manual
Chapter 19 BACnet signals
87
Object name
Object-ID
Description
Values
Writable
RC_Setp_L.RegioComDefaults
Binary
value, 11
Resets communication settings
to default values
ACTIVE/
INACTIVE Yes
RC_Setp_L.RegioBlockConfig
Binary
value, 12
Prevents unauthorised access to
the configuration menu via
controller buttons
ACTIVE/
INACTIVE Yes
All binary values have normal polarity.
Loop
Object name
Object-ID
Description
Regulator
Loop, 0
The Regio Regulator
Multistate inputs
Object name
Object-ID
Description
Values
Writable
RC_Actual_X.RegioFanSwitch
Multistate
input, 0
Fan switch state
1=OFF
2=LOW
3=MEDIUM
4=HIGH
5=AUTO
No
RC_Actual_X.RegioUnitState
Multistate
input, 1
Current unit state
1=Off
2=Unoccupied
3=Stand-by
4=Occupied
5=Bypass
No
RC_Actual_X.RegioControllerState
Multistate
input, 2
Current controller state
1=Off
2=Heating
3=Cooling
No
RC_Actual_X.RegioFanSpeed
Multistate
input, 3
Current fan speed
1=Off
2=Fan speed 1
3=Fan speed 2
4=Fan speed 3
No
Multistate values
Object name
Object-ID
Description
Values
Writable
RC_Setp_X.RegioHeatOutputSelect
Multistate
value, 0
Manual/Auto heat output
1=Off
2=Manual output
3=Automatic output
Yes
RC_Setp_X.RegioCoolOutputSelect Multistate
value, 1
Manual/Auto cool output
1=Off
2=Manual output
3=Automatic output
Yes
Chapter 19 BACnet signals
Regio Midi manual
Object name
Object-ID
Description
Values
Writable
RC_Setp_X.RegioFanSelect
Multistate
value, 2
Fan mode select
1=Off
2=Manual speed 1
3=Manual speed 2
4=Manual speed 3
5=Auto
6=Auto 2
7=Auto 1
Yes
RC_Setp_X.RegioForcedVentSelect Multistate
value, 3
Manual/Auto forced
ventilation
1=Off
2=Manual On
3=Auto
Yes
RC_Setp_X.RegioChangeOverSelect Multistate
value, 4
Manual/Auto change-over 1=Heating
2=Cooling
3=Auto
Yes
RC_Setp_X.RegioRemoteState
Multistate
value, 5
Remote control unit state
1=Off
2=Unoccupied
3=Stand-by
4=Occupied
6=No remote control
Yes
RC_Non_Modbus.RegioButtonActiv
eConf
Multistate
value, 6
Active buttons
1=No buttons
2=Occupancy button
only
3=INCREASE/DECR
EASE only
4=Occupancy button
and
INCREASE/DECREA
SE
5=Fan button only
6=Occupancy button
and fan button
7=INCREASE/DECR
EASE and fan button
8=All buttons
Yes
Device
The device object contains two writable properties; Description and Location. Description can
be 17 characters long, and Location can be 33 characters long, if using single byte character
encoding.
About the manual 5
More information 5
Terms 5
Activation of the different operating modes 44
Actuators 49
Analogue actuators 49
Exercise 50
On/Off actuators 49
Thermal actuators 49
Three-point actuators 49
Analogue actuators 49
Analogue values 83
Applications 6
Auto control 51
B
BACnet signal types 82
BACnet signals 83
Basic setpoint 47
Binary values 85
Bypass 43
C
Calculation of the active setpoint 47
Central command 46
Central control 46
CO2 sensor and VAV control 38
Communication 7
Configuration 13
Control modes 32
Cooling 34
Cooling/Cooling 35
Heating 32
Heating or cooling via change-over 33
Heating/Cooling 33
Heating/Cooling with VAV-control 34
Heating/Cooling with VAV-control and forced supply
air function 33
Heating/Heating 32
Cooling 34
Cooling/Cooling 35
D
Device 87
Different operating modes 42
DIP switches 14
Display handling 58
Display indications 58
Display indications 58
E
Exercise 50
F
Fan control 51
Auto control 51
Fan stopped 51
Manual control 51
H
Heating 32
Heating or cooling via change-over 33
Heating/Cooling 33
Heating/Cooling with VAV-control and forced supply
air function 33
Heating/Cooling/VAV 35
Heating/Heating 32
Holding register 81
I
INCREASE/DECREASE buttons 58
Indications 57
Communication 57
Occupancy button 57
Inputs
Analogue 83
Binary 85
Multistate 86
Installation 15
preparations 12
L
Labels 12
Loop 86
M
Manual control 51
Measurement and testing 17
Memory function on power failure 66
Modbus signal types 67
Modbus signals 69
Models 8
More information 5
Mounting 6
Multistate values 86
O
Occupancy button 46, 57
Occupancy detector 45, 46
Occupied 43
Occupied/Bypass 47
Off 42, 47
On/Off actuators 49
Operating modes 42
Activation of the different operating modes 44
Different operating modes 42
P
Parameter menu 59
Preset operating mode 44
R
Register
Holding 81
S
Setpoint
display of setpoint at setpoint displacement 48
Setpoint calculation 47
Basic setpoint 47
Calculation of the active setpoint 47
Setpoint displacement 47
Setpoint displacement 47
Special functions 55
Special input CI 55
Split output signal 35
Stand-by 42, 47
SW1-7 14
T
Technical data 10
Terms 5
Thermal actuators 49
Three-point actuators 49
U
Unoccupied 42, 47
W
Wiring 15
Wiring for basic models with 3 analogue outputs 18
Wiring for model for CO2 control 21
Wiring for models for CO2 control and fan control 25
Wiring for models for fan control 27
Wiring for models for three-point control 30