Pure Sine Wave Inverter

User Manual 200 Butterfield Drive, Ashland, MA 01721, Tel: (508)881-7330, Fax: (508)231-0861 Website: http://www.schaeferpower.com Email: [email protected]

Table of Contents

1. Features 1-1 Applications 2 1-2 Electrical performance 3 1-3 Mechanical drawings 4 2. Introduction 2-1 Front panel operations 5-6 2-2 Rear panel operations 6-7 2-3 Installation 7-8 2-4 Quick hook up and testing 8-9 2-5 AC safety grounding 9 2-6 Making DC wiring connections 9-11 2-7 Inverter operation 11-14 2-8 Output power 14 2-9 Cooling fan operation 15 3. Maintenance ……………………………………………………………….………………. 15 4. Troubleshooting Guide ..………………………………………………………………… 15-16 5. Warranty …………………………………………………………………………..……….. 16 6. Important Safety Instructions 6-1 General safety precautions 17 6-2 Precautions when working with batteries 17 7. Appendix A 7-1 Dip switch (110V) 18 7-2 Dip switch (220V) 18

� Pure sine wave output (THD < 3%)

� Output frequency: 50 / 60Hz switch selectable � RS – 232C interface / remote controls port / wire connection to PC � Wired remote control (optional) � Thermostatically controlled cooling fan � Advanced microprocessor design � Protection : � Input low voltage � Overload � Short circuit � Low battery alarm � Input over voltage � Over temperature 1-1 Applications 1-1-1 Power tools – circular saws, drills, grinders, sanders, buffers, landscaping tools, air compressors. 1-1-2 Office equipment – computers, printers, monitors, facsimile machines, scanner. 1-1-3 Household items – vacuum cleaners, fans, fluorescent and incandescent lights, shavers, sewing machines, 1-1-4 Kitchen appliances – microwave ovens, refrigerators and freezers, coffee makers, blenders, ice markers, toasters. 1-1-5 Industrial equipment – test equipment, communications equipment, factory automation equipment, field portable instrumentation, remote facility power, security systems, metal halide lamp, high pressure sodium lamp. 1-1-6 Home entertainment/electronics - television, VCRs, video games, stereos, musical instruments, satellite equipment.

1-2 Electrical Performance

Model Specification AEP-700-121 AEP-700-241 AEP-700-481 AEP-700-122 AEP-700-242 AEP-700-482 Continuous Output Power 700W Maximum Output Power (3Min.) 780W Surge Rating (1 ms) 1400W Input Voltage 12VDC 24VDC 48VDC 12VDC 24VDC 48VDC Input Voltage Range 10.5-16 VDC 21.5-32 VDC 42-62 VDC 10.5-16 VDC 21.5-32 VDC 42-62 VDC Output Voltage Regulation 100/110/115/120V RMS ±3% 200/220/230/240V RMS ±3% Frequency 50/60Hz ±0.05% (Switch Selectable) Efficiency (full load) 88% 90% 91% 92% 94% 94% No Load Current Draw 0.87A 0.43A 0.23A 0.83A 0.43A 0.22A Output Waveform Pure Sine Wave < THD 3% Protection Overload, Short Circuit, Reverse Polarity (Fuse), Over/Under Input Voltage, Over Temperature. Digital Display OVP / UVP / OTP / OLP / VAC/ AMP / WATTS / VDC / TEMP / Hz Interface Control Port RS-232C With Baud Rate 2400,4800,9600,19200 (Switch Selectable) Operating Temperature Range 0ºC to +50ºC (+32ºF to +122ºF) Storage Temperature Range -30ºC to +70ºC (-22ºF to +158ºF) Cooling Load controlled fan Dimensions 11.77”(L) x 7.00”(W) x 3.15”(H) 299mm x 178mm x 80mm Weight 6.17 lbs. (2.8kgs)

The AEP-700 Series is part of Schaefer’s line of advanced technology, pure sine wave DC/AC

power inverters. For optimum performance, the instruction manual should be read to ensure proper installation and use of the AEP-700. 2-1 Front Panel Operation: 2-1-1 Front view: 2-1-2 ON / OFF Switch: Please keep the Power ON/OFF switch in the OFF position during installation. 2-1-3 Function Key When sequentially pushing the “Function Key”, the screen will display various status items such as VAC, Amps, Watts, etc. When a malfunction has occurred, the corresponding error will be displayed on the screen.

2-1-4 AC Outlet (sockets available; the Universal socket is standard with the AEP-700):

2-2 Rear Panel Operation: 2-2-1 Ventilation openings: Do not obstruct; allow at least 3 inches for airflow. 2-2-2 Battery terminals: Connect to a 12VDC/24VDC/48VDC battery or other 12VDC/24VDC/48VDC power source. Red [+] is positive; black [-] is negative. Reverse polarity connection will blow the internal fuse and may damage inverter permanently.

Connect to remote control unit (optional accessory) or connect to computer for

remote control working status. 2-2-4 Connect chassis ground terminal to earth or to vehicle chassis using # 8 AWG wire. 2-3 Installation: Where to install: The power inverter should be installed in a location that meets the following requirements: 2-3-1 Dry: Do not allow water to drip or splash on the inverter. 2-3-2 Cool: Ambient air temperature should be between 0C and 40C. 2-3-3 Safe: Do not install in a battery compartment or other areas where flammable fumes may exist, such as fuel storage areas or engine compartments. 2-3-4 Ventilated: Allow at least three inches of clearance around the inverter for air flow, ensuring that the ventilation openings on the rear and bottom of the unit are not obstructed. WARNING! Do not connect the 12VDC model to a 24VDC battery. The unit will be destroyed immediately! WARNING! Operation of the inverter without a proper ground connection may result in an electrical safety hazard WARNING! Shock Hazard! Before proceeding, carefully check the AEP-700 inverter is NOT connected to any batteries and is disconnected from any electrical source. Do not connect the output terminals of the AEP-700 to an incoming source at this time.

2-3-5 Dust Free: Do not install the AEP-700 Inverter in a dusty environment where dust,

wood particles or other filings/shavings are present that may be pulled into the unit when the cooling fan is operating. 2-3-6 Close to Batteries: Avoid excessive cable lengths but do not install the AEP-700 Inverter in the same compartment as batteries. Use the recommended wire lengths and sizes (see section 2-6). Avoid mounting the AEP-700 Inverter where it may be exposed to the gases produced by the battery. Prolonged exposure to these corrosive gases will damage the AEP-700 Inverter. 2-4 Quick Hook Up and Testing: 2-4-1 Unpack and inspect the power inverter, verifying that the power switch in the OFF position. 2-4-2 Connect the cables to the power input terminals on the rear panel of the power inverter. The red terminal is positive (+) and black terminal is negative (-). Insert the cables into the terminals and tighten the nut to securely clamp the wires . 2-4-3 Before proceeding, confirm that your cable is connected from the negative terminal of inverter to the negative output of your power source. 2-4-4 Connect the cable from the positive terminal of the inverter to the positive terminal of the power source. Make a secure connection. CAUTION! Reverse polarity connection will blow a fuse in the inverter and may cause damage. Damage caused by reverse polarity connection is not covered by our warranty WARNING! You may observe a spark when you make this connection as current may flow to charge the capacitors in the inverter. Do not make this connection in the presence of flammable fumes. Explosion or fire may result!

2-4-5 Set the power switch to the ON position; you will hear a beeping sound, while the

display shows the word “ASIAN” for twice. After that, you will hear a continuous tone from internal alarm. Finally, the AC voltage shows on the display, signaling that the inverter has done the start up. 2-4-6 Set the power switch to the OFF position; the device shut down completely. 2-4-7 Please use a power meter to accurately measure the true output R.M.S. voltage of inverter. 2-5 AC Safety Grounding: During the AC wiring installation, AC input and output ground wires are connected to the inverter. The AC input ground wire must connect to the incoming ground from your AC utility source. The AC output ground wire should go to the grounding point for your loads (for example, a distribution panel of bus chassis). 2-6. Making DC Wiring Connections: Follow this procedure to connect the battery cables to the DC input terminals on the AEP-700 Inverter. Your cables should be as short as possible (ideally, less than 10 feet / 3 meters) and large enough to handle the required current in accordance with the electrical codes or regulations applicable to your installation. Cables that are not an adequate gauge (too narrow) or are too long will cause decreased inverter performance such as poor surge capability and frequent low input voltage warnings and shutdowns. WARNING! Do not operate the power inverter without connecting it to ground. Electrical shock hazard may result. WARNING! Make sure that all DC connections are tight (torque to 9-10 foot pounds). Loose connections will overheat and could result in a potential hazard

These low input voltage warnings are due to DC voltage drop across the cables from the

inverter to the batteries. The longer and narrower these cables, the greater the voltage drop. Increasing your DC cable size will help improve the situation. We recommend the following cables for optimum inverter performance. Use only high quality copper wiring and keep cable length short (from 3-6 feet). Model No Wire AWG Inline Fuse AEP-700-121 #4 100A AEP-700-122 #4 100A AEP-700-241 #6 50A AEP-700-242 #6 50A AEP-700-481 #8 30A AEP-700-482 #8 30A WARNING! The installation of a fuse must be on positive cable. Failure to place a fuse on “+ “cables running between the inverter and battery may cause damage to the inverter and will void warranty.

2-7 Inverter Operation:

To operate the power inverter, turn it on using the ON/OFF switch on the front panel. The power inverter is now ready to deliver AC power to your loads. If you are operating several loads from the power inverter, turn them on separately after the inverter has been turned on. This will ensure that the power inverter does not have to deliver the starting currents for all the loads at once. 2-7-1 Controls and indicators: The ON / OFF switch turns the control circuit in the power inverter on and off. The AEP-700 Inverter operates from an input voltage ranging from: 10.5 to 15.0 VDC for 12VDC models 21.0 to 30.0 VDC for 24VDC models 42.0 to 60.0 VDC for 48VDC models

The AEP-700 Inverter will indicate high and low DC voltage conditions as follows:

Model Dc Input over voltage shut-down Dc Input over voltage alarm Dc Input under voltage alarm Dc Input under voltage shut-down AEP-700-121 AEP-700-122 16.0VDC 15.5VDC 10.5VDC 10.0VDC AEP-700-241 AEP-700-242 32.0VDC 31VDC 21.0VDC 20.0VDC AEP-700-481 AEP-700-482 62.0VDC 61VDC 43.0VDC 42.0VDC 2-7-2 Output Voltage Indicator: VAC LED illuminated. Display indicates output voltage value. 2-7-3 Output Current Indicator: AMP LED illuminated. Display indicates output current value. 2-7-4 Output Watts Indicator: Watts LED illuminated. Display indicates Watts value. 2-7-5 Input DC Voltage Indicator: VDC LED illuminated. Display indicates input DC voltage value 2-7-6 Temperature Indicator: TEMP LED illuminated. Display indicates internal operating temperature value. 2-7-7 Output Frequency DC Indicator: Hz LED illuminated. Display indicates output frequency value

The accuracy of the six display functions is below:

Functions VAC AMP WATT VDC TEMP Frequency Ranges 100-120 VAC 200-240 VAC 0-10A 0-1KW 10-16 VDC 20-32 VDC 42-62 VDC 0-120� 50Hz 60Hz Accuracy ± 1% ± 1% ± 1% ± 3% ± 2% ± 2% ± 2% ± 1% ±0.01 ±0.01 2-7-8 Over Voltage Protection Indicator: (OVP) The over voltage indicator indicates that the power inverter has shut itself down because its input voltage exceeded the limits of the inverter (see Page 12). 2-7-9 Under Voltage Protection Indicator: (UVP) The under voltage indicator indicates that the power inverter has shut itself down because its input voltage fell below the limits of the inverter (see Page12). 2-7-10 Over Temperature Protection Indicator: (OTP) The over temperature indicator indicates that the power inverter has shut itself down because the inverter has overheated. The power inverter may overheat because it has been operated at power levels above its rating or because it has been installed in a location which does not allow it to dissipate heat properly. The power inverter will automatically restart, once the temperature has decreased.

2-7-11 Over Load Protection Indicator: (OLP)

The overload indicator indicates that the power inverter has shut itself down due to the output being overloaded. The inverter must be manually restarted. Turn off the AEP-700 inverter, correct the fault condition, then, turn the AEP-700 inverter back on. 2-8 Output Power: The AEP-700 inverter will operate most AC powered devices within its power rating. When deeming whether a microwave oven can be operated by the AEP-700 inverter, remember that the power commonly advertised for microwave ovens is the cooking power, not the power actually consumed by the microwave oven. The microwave oven will consume 40% to 100% more than its advertised cooking power. Check the rating sticker on the back of the oven to determine its actual power requirements. The AEP-700 inverter will operate small microwave oven (0.2 to 0.3 cubic foot capacity) that draws about 780 watts. It will provide 3 minutes of cooking time. Some induction motors used in refrigerators, freezers, pumps and other motor operated equipment require very high surge currents to start. The AEP-700 may not be able to start some of these motors even though their rated current requirement is within the power inverter. If the motor will not start, observe the battery voltage indicator while trying to start the motor. If the battery voltage indicator drops below 11 volts while inverter is attempting to start the motor, this may be the cause. Ensure that the battery connections are good and the battery is fully charged. If the connections are good and the battery is fully charged, but the voltage still drops below 11 volts, you may need to use a larger battery.

2-9 Cooling Fan Operation:

The AEP-700’s cooling fan operates by detecting output power and over temperature conditions of the inverter. Upon starting the inverter, with the output power is under 1/2 capacity (300W), the cooling fan remains off, complying with energy savings specifications. After the output power exceeds 1/2 capacity (300W), the cooling fan will turn on to decrease the internal temperature. If the ventilation opening is obstructed, the inverter will enter over temperature protection mode (OTP). The cooling fan will continue working to drop the inner temperature. When the internal temperature decreases sufficiently, the inverter will turn on automatically. 3. Maintenance: Very little maintenance is required to keep your inverter operating properly. You should clean the exterior of the unit periodically with a dry cloth to prevent accumulation of dust and dirt. At the same time, tighten the Screws on the DC input terminals. 4. Troubleshooting Guide: A common problem with inverter operation is television interference. Operation of the power inverter can interfere with television reception on some channels. In this situation, the following steps may help to alleviate the problem: � Make sure that the chassis ground lug on the back of the power inverter is solidly connected to the ground system of your vehicle, boat or home. � Do not operate high power loads with the power inverter while watching television. � Make sure that the antenna feeding your television provides an adequate (“snow free”) signal and that you are using good quality cable between the antenna and the television. � Move the television as far away from the power inverter as possible. � Keep the cables between the battery and the power inverter as short as possible and twist them together about 2 to 3 twists per foot. This minimizes radiated interference from the cables.

We warranty this product against defects in materials and workmanship for a period of 24 months

from the date of purchase and will repair or replace any defective power inverter when directly returned (shipping prepaid) to us. This warranty will be considered void if the unit has suffered any obvious damage by natural and man-made factors or has been internally or externally altered. The warranty does not cover damage arising from improper use such as plugging the unit into an unsuitable power source, attempts to operate products with excessive power consumption requirements or use in unsuitable environments. This is the only warranty that the company makes. No other warranties are expressed or implied including warranties of merchantability and fitness for a particular purpose. Repair or replacement are the sole remedies and the company shall not be liable for damages, whether direct, incidental, special or consequential, caused by negligence or other fault. Problem and Symptoms Possible Cause Solution Low output voltage (110V: 95-105VAC 220V: 190-210VAC) Using average reading voltmeter Use true RMS reading meter and cable( see page 9, Point 2-4-7 of manual) Load Display OLP flash. Over load Reduce load. No output voltage Fault input voltage. Low/High input voltage Recharge battery, check connections and cable. (see page 11) No output voltage Over Temp indicator Load less than 500W Thermal shutdown Improve ventilation , Make sure ventilation openings in inverter are not obstructed , Reduce ambient temperature. No output voltage, Over load indicator Short circuit or wiring error Very high power load Check AC wiring for short circuit or improper polarity (hot and neutral reversed ) Remove load. WARNING Do not open or disassemble the AEP-700 Inverter, Attempting to service the unit yourself may result in a risk of electrical shock or fire.

6. Important Safety Instructions

6-1 General Safety Precautions 6-1-1 Do not expose the AEP-700 Inverter to rain, snow, spray, bilge or dust. To reduce risk of hazard, do not cover or obstruct the ventilation openings. Do not install the AEP-700 Inverter in a zero-clearance compartment. Overheating may result. 6-1-2 To avoid the risk of fire and electronic shock, make sure that existing wiring is in good electrical condition and that wire size is not undersized. Do not operate the AEP-700 Inverter with damaged or substandard wiring. 6-2 Precautions When Working with Batteries 6-2-1 If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters eye, immediately flush with running cold water for at least 20minutes and seek medical attention immediately. 6-2-2 NEVER smoke or allow a spark or flame in the vicinity of battery or engine compartment. 6-2-3 Do not drop a metal tool on the battery. The resulting spark or short-circuit on the battery or other electrical part may cause an explosion. 6-2-4 Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a lead-acid battery. A lead-acid battery produces a short-circuit current high enough to weld a ring other metal to the skin, causing a severe burn. WARNING! Before installing and using your AEP-700 inverter, be sure to read and save these safety instructions.

7. Appendix A

7.1 110VAC Dip Switch Settings (left side of inverter) S1 ( FREQ. Hz ) – 50Hz/60Hz S2/S3 (BAUD RATE ) – 2400 / 4800 / 9600 / 19200 S4/S5 (VOLTAGE OUTPUT ) – 100VAC/110VAC/115VAC/120VAC S1 FREQ. (Hz) S2 S3 BAUD RATE S4 S5 OUTPUT VOLTAGE (VAC) ON 60 OFF OFF 2400 OFF OFF 100 OFF 50 OFF ON 4800 OFF ON 110 ---- ---- ON OFF 9600 ON OFF 115 ---- ---- ON ON 19200 ON ON 120 7-2 220VAC Dip Switch Settings (left side of inverter) S1 ( FREQ. Hz ) – 50Hz/60Hz S2/S3 (BAUD RATE ) – 2400 / 4800 / 9600 / 19200 S4/S5 (VOLTAGE OUTPUT ) – 200VAC/220VAC/230VAC/240VAC S1 FREQ. (Hz) S2 S3 BAUD RATE S4 S5 OUTPUT VOLTAGE (VAC) ON 60 OFF OFF 2400 OFF OFF 200 OFF 50 OFF ON 4800 OFF ON 220 ---- ---- ON OFF 9600 ON OFF 230 ---- ---- ON ON 19200 ON ON 240