Philips EasyAir SNS200 Quick Installation Manual

Text of the manual

office sensor advanced

grouping SNS200 January 2018 Quick Installation Guide XITANIUM SR LED DRIVER EASYAIR LED+ LED+ LED- LED- LEDset GNDset NFC ANTENNA SR- Connectors SR+ SR SR LINE NEUTRAL GROUND NC NC Connectors (non-polarized) Use 0.75 mm2 solid copper wire, rated >= 600 V / 90 °C. Strip wire to 8 mm. EasyAir office sensor advanced grouping SNS200 Ordering data Commercial product name Color Description EOC 12NC Carton Quantity EasyAir SNS200/w White Office Sensor Advanced Grouping 8718696 698945 00 929000 766 803 50 pcs EasyAir SNS200/g Grey Office Sensor Advanced Grouping 8718696 712412 00 929001 560 703 50 pcs Compatible LED Drivers Logistic code 12NC Description 929001516306 Xitanium 36W 0.3-1A 54V SR 230V 929001505006 Xitanium 75W 0.7-2.0A 54V SR 230V 929001540406 Xitanium 35W 0.08-0.35A 150 V SR 230V 929001540506 Xitanium 60W 0.08-0.35A 220 V SR 230V 929001540606 Xitanium 60W 0.08-0.35A 300 V SR 230V 929001540706 Xitanium 100W 0.25-0.7A 220 V SR 230V 929001540806 Xitanium 100W 0.15-0.5A 300 V SR 230V iXt 929001540906 Xitanium 100W 0.2-0.7A 300 V SR 230V iXt 1. View limited warranty at: http://images.philips.com/is/content/PhilipsConsumer/PDFDownloads/Global/ ODLI20150105_001-UPD-en_GB-152795-PHI-component_warranty-HR.PDF

2 - 5

Quick Installation Guide - EasyAir office sensor advanced grouping SNS200 January 2018 Mounting Dimensions (mm) Mounting in U-shaped slot in sheet metal (max thickness 1 mm) EasyAir office sensor Sensor Dimensions (mm) 43.8 MAX 16.8 MAX 7.5 MAX 24.3 MAX 50.0 MAX 2.3 43.5 43.5 16.0 16.0 Mounting in cut-out in sheet metal (thickness 0.7 mm to 1.2 mm) 44.0 17.0 2.3 Mounting hole dimension (+/- 0.2mm)

3 - 5

Quick Installation Guide - EasyAir office sensor advanced grouping SNS200 January 2018 EasyAir office sensor Luminaire with EasyAir installed Mounting in a slot Mounting in SMB-50 bracket All dimensions in mm. Installing EasyAir office sensor with ceiling mount bracket (SNS200CMP) The ceiling mount bracket SNS200CMP is premounted with EasyAir SNS200 sensor and the cable. See the cut-out in ceiling and mounting dimensions below, all in mm. 74 Radius min 5 mm 74 86 Ø 63 Ø 74 Radius min 5 mm 74 46 86 Ø 63 Ø 74 Radius min 5 mm

4 - 5

Quick Installation Guide - EasyAir office sensor advanced grouping SNS200 January 2018 Product Data Operation and Configuration via Mobile App EasyAir operates immediately upon installation and energization without further commissioning. If changes from default settings are desired, EasyAir can be configured via an app through NFC or IR embedded within the sensor. Compliance to Radio Equipment Directive (RED) The Directive ensures a single market for Radio and Telecom mu nica- tion Terminal Equipment by setting harmonized standards for safety and health, electromagnetic compatibility and the efficient use of the radio spectrum. This applies to all products using the radio frequency spectrum. This device is compliant to the underlying harmonized standards which is verified by an independent Notified Body. Any changes or modifications not expressly approved by Philips could void the user’s authority to operate this equipment. This product is intended for commercial use only. Electrical Information Input Voltage Powered by SR driver low-voltage interface Current Consumption 13 mA Nominal Power Consumption 200 mW Standby Power < 1 W on luminaire level, including driver standby power Occupancy Sensing Type Passive infrared (PIR) Occupancy based control Default enabled Occupancy Mode Auto-on/off, Manual-on/off, Manual-on/auto-off; Red LED indicates “on” Group Occupancy Sharing Enabled/disabled Group Light Behaviour Background Light Level, Field Task Level Hold Time 0.5 - 60 minutes Viewing Angle X = 72°, Y = 86° ( See detection pattern) Background Light Level 0-100% Prolong Time 0 minutes - infinity Grace Fading 0-25 sec Response Time/Fading to Switch On/Off 0.7 sec Daylight Sensing Daylight based control Default enabled Auto-calibration Upon power-up Daylight dependent switching Default disabled Daylight dependent override Default disabled Viewing Angle 40° (half value sensitivity); 2% cut-off point at 75° Task Tuning Full Light Setting 0-100% Environment & Approbation Operating Ambient Temperature Range 0 °C to 55 °C Operating Humidity 0 – 95% non condensing Storage Temperature -25 °C to 85 °C Storage Humidity 0-95% non condensing Max Case Temperature (Tcase) 55 °C Agency Approbations CE, ENEC, RTTE, EMC Warranty 5 years warranty for released Philips system combination (sensor and compatible driver). 3 years warranty for sensor only. Digital Interface Xitanium SR Other Status Indicators Red, Yellow. Yellow LED on: Vacancy & Sensor is functional; Red LED on: Motion is detected Energy reporting Calculated from last “power on”: % On, Energy Consumed (Whr), System on time (hrs), Avg power consumed (w-hr), Lamp on time (hrs) No. Drivers per Sensor 4 max Max Distance Switch-to-First-Luminaire 10 m line-of-sight Max Distance Luminaire-to-Luminaire 12 m line-of-sight No. Switches per Group 10 max Field Configuration via NFC or IR, parameters set via Philips field apps

© Philips Lighting Holding B.V. 2018. All rights reserved. Philips reserves the right to make

changes in specifications and/or to discontinue any product at any time without notice or obligation and will not be liable for any consequences resulting from the use of this publication. 01/2018 Data subject to change www.lighting.philips.co.uk/oem-emea/ products/connected-lighting