Philips EasyAir SNS200 Quick Installation Manual
Text of the manual
office sensor advanced
grouping SNS200
January 2018
Quick Installation Guide
XITANIUM SR
LED DRIVER
EASYAIR
LED+
LED+
LED-
LED-
LEDset
GNDset
NFC ANTENNA
SR-
Connectors
SR+
SR
SR
LINE
NEUTRAL
GROUND
NC
NC
Connectors
(non-polarized)
Use 0.75 mm2 solid copper wire,
rated >= 600 V / 90 °C.
Strip wire to 8 mm.
EasyAir office sensor
advanced grouping SNS200
Ordering data
Commercial product name
Color
Description
EOC
12NC
Carton Quantity
EasyAir SNS200/w
White
Office Sensor Advanced Grouping
8718696 698945 00
929000 766 803
50 pcs
EasyAir SNS200/g
Grey
Office Sensor Advanced Grouping
8718696 712412 00
929001 560 703
50 pcs
Compatible LED Drivers
Logistic code 12NC
Description
929001516306
Xitanium 36W 0.3-1A 54V SR 230V
929001505006
Xitanium 75W 0.7-2.0A 54V SR 230V
929001540406
Xitanium 35W 0.08-0.35A 150 V SR 230V
929001540506
Xitanium 60W 0.08-0.35A 220 V SR 230V
929001540606
Xitanium 60W 0.08-0.35A 300 V SR 230V
929001540706
Xitanium 100W 0.25-0.7A 220 V SR 230V
929001540806
Xitanium 100W 0.15-0.5A 300 V SR 230V iXt
929001540906
Xitanium 100W 0.2-0.7A 300 V SR 230V iXt
1. View limited warranty at: http://images.philips.com/is/content/PhilipsConsumer/PDFDownloads/Global/
ODLI20150105_001-UPD-en_GB-152795-PHI-component_warranty-HR.PDF
2 - 5
Quick Installation Guide - EasyAir office sensor advanced grouping SNS200
January 2018
Mounting Dimensions (mm)
Mounting in U-shaped slot in sheet metal (max thickness 1 mm)
EasyAir office sensor
Sensor Dimensions (mm)
43.8 MAX
16.8 MAX
7.5 MAX
24.3 MAX
50.0 MAX
2.3
43.5
43.5
16.0
16.0
Mounting in cut-out in sheet metal (thickness 0.7 mm to 1.2 mm)
44.0
17.0
2.3
Mounting hole dimension (+/- 0.2mm)
3 - 5
Quick Installation Guide - EasyAir office sensor advanced grouping SNS200
January 2018
EasyAir office sensor
Luminaire with EasyAir installed
Mounting in a slot
Mounting in SMB-50 bracket
All dimensions in mm.
Installing EasyAir office sensor with ceiling mount bracket (SNS200CMP)
The ceiling mount bracket SNS200CMP is premounted with EasyAir SNS200 sensor and the cable. See the cut-out in ceiling
and mounting dimensions below, all in mm.
74
Radius min 5 mm
74
86
Ø 63
Ø 74
Radius min 5 mm
74
46
86
Ø 63
Ø 74
Radius min 5 mm
4 - 5
Quick Installation Guide - EasyAir office sensor advanced grouping SNS200
January 2018
Product Data
Operation and Configuration via Mobile App
EasyAir operates immediately upon installation and
energization without further commissioning. If changes from
default settings are desired, EasyAir can be configured via an
app through NFC or IR embedded within the sensor.
Compliance to Radio Equipment Directive (RED)
The Directive ensures a single market for Radio and Telecom mu nica-
tion Terminal Equipment by setting harmonized standards for safety
and health, electromagnetic compatibility and the efficient use of
the radio spectrum. This applies to all products using the radio
frequency spectrum. This device is compliant to the underlying
harmonized standards which is verified by an independent Notified
Body. Any changes or modifications not expressly approved by
Philips could void the user’s authority to operate this equipment.
This product is intended for commercial use only.
Electrical Information
Input Voltage
Powered by SR driver low-voltage interface
Current Consumption
13 mA
Nominal Power Consumption
200 mW
Standby Power
< 1 W on luminaire level, including driver standby power
Occupancy Sensing
Type
Passive infrared (PIR)
Occupancy based control
Default enabled
Occupancy Mode
Auto-on/off, Manual-on/off, Manual-on/auto-off; Red LED indicates “on”
Group Occupancy Sharing
Enabled/disabled
Group Light Behaviour
Background Light Level, Field Task Level
Hold Time
0.5 - 60 minutes
Viewing Angle
X = 72°, Y = 86° ( See detection pattern)
Background Light Level
0-100%
Prolong Time
0 minutes - infinity
Grace Fading
0-25 sec
Response Time/Fading to Switch On/Off
0.7 sec
Daylight Sensing
Daylight based control
Default enabled
Auto-calibration
Upon power-up
Daylight dependent switching
Default disabled
Daylight dependent override
Default disabled
Viewing Angle
40° (half value sensitivity); 2% cut-off point at 75°
Task Tuning
Full Light Setting
0-100%
Environment & Approbation
Operating Ambient Temperature Range
0 °C to 55 °C
Operating Humidity
0 – 95% non condensing
Storage Temperature
-25 °C to 85 °C
Storage Humidity
0-95% non condensing
Max Case Temperature (Tcase)
55 °C
Agency Approbations
CE, ENEC, RTTE, EMC
Warranty
5 years warranty for released Philips system combination (sensor and compatible driver).
3 years warranty for sensor only.
Digital Interface
Xitanium SR
Other
Status Indicators
Red, Yellow. Yellow LED on: Vacancy & Sensor is functional; Red LED on: Motion is detected
Energy reporting
Calculated from last “power on”: % On, Energy Consumed (Whr), System on time (hrs), Avg power consumed
(w-hr), Lamp on time (hrs)
No. Drivers per Sensor
4 max
Max Distance Switch-to-First-Luminaire
10 m line-of-sight
Max Distance Luminaire-to-Luminaire
12 m line-of-sight
No. Switches per Group
10 max
Field Configuration
via NFC or IR, parameters set via Philips field apps
© Philips Lighting Holding B.V. 2018. All rights reserved. Philips reserves the right to make
changes in specifications and/or to discontinue any product at any time without notice or
obligation and will not be liable for any consequences resulting from the use of this publication.
01/2018
Data subject to change
www.lighting.philips.co.uk/oem-emea/
products/connected-lighting