Potter PFC-4064 Keypad Programming Manual

Specifications

Brand: Potter
Category: Control Panel
Model: PFC-4064 (Keypad Programming Manual)
File Type: PDF
File Size: —
Pages: 25

Read Online

Read the Potter PFC-4064 Keypad Programming Manual online using the built-in PDF viewer.

Text of the manual

Conventional Fire Alarm Panel

Keypad Programming Guide Manual #8870080–Rev A 12/17 Potter Electric Signal Company, LLC St. Louis, MO Customer Service: (866) 240-1870 • Technical Support: (866) 956-1211 • Fax: (314) 595-6999 www.pottersignal.com

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

Potter Electric Signal Company, LLC 5757 Phantom Drive Ste 125 • St. Louis, MO 63042 • 314-595-6900 • 800-325-3936 WARRANTY INFORMATION The essential purpose of any sale or contract for sale of any of the products listed in the POTTER catalog or price list is the furnishing of that product. It is expressly understood that in furnishing said product, POTTER does not agree to insure the Purchaser against any losses the Purchaser may incur, even if resulting from the malfunction of said product. POTTER warrants that the equipment herein shall conform to said descriptions as to all affirmation of fact and shall be free from defects of manufacture, labeling and packaging for a period of one (1) or five (5) year(s), depending on the product, from the invoice date to the original purchaser, provided that representative samples are returned to POTTER for inspection. The product warranty period is stated on the exterior of the product package. Upon a determination by POTTER that a product is not as warranted, POTTER shall, at its exclusive option, replace or repair said defective product or parts thereof at its own expense except that Purchaser shall pay all shipping, insurance and similar charges incurred in connection with the replacement of the defective product or parts thereof. This Warranty is void in the case of abuse, misuse, abnormal usage, faulty installation or repair by unauthorized persons, or if for any other reason POTTER determines that said product is not operating properly as a result of causes other than defective manufacture, labeling or packaging. The Aforesaid Warranty Is Expressly Made In Lieu Of Any Other Warranties, Expressed Or Implied, It Being Understood That All Such Other Warranties, Expressed Or Implied, Including The Warranties Of Merchantability And Fitness For Particular Purpose Are Hereby Expressly Excluded. In No Event Shall Potter Be Liable To Purchaser For Any Direct, Collateral, Incidental Or Consequential Damages In Connection With Purchaser’s Use Of Any Of The Products Listed Herein, Or For Any Other Cause Whatsoever Relating To The Said Products. Neither Potter Nor Its Representatives Shall Be Liable To The Purchaser Or Anyone Else For Any Liability, Claim, Loss, Damage Or Expense Of Any Kind, Or Direct Collateral, Incidental Or Consequential Damages Relative To Or Arising From Or Caused Directly Or Indirectly By Said Products Or The Use Thereof Or Any Deficiency, Defect Or Inadequacy Of The Said Products. It Is Expressly Agreed That Purchaser’s Exclusive Remedy For Any Cause Of Action Relating To The Purchase And/or Use Of Any Of The Products Listed Herein From Potter Shall Be For Damages, And Potter's Liability For Any And All Losses Or Damages Resulting From Any Cause Whatsoever, Including Negligence, Or Other Fault, Shall In No Event Exceed The Purchase Price Of The Product In Respect To Which The Claim Is Made, Or At The Election Of Potter, The Restoration Or Replacement Or Repair Of Such Product. ii

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

iii Table of Contents Section 1: Introduction ..............................................................................................................................1 Section 2: Pre-Programming Procedures and Defaults ..........................................................................2 Section 3: Operation ..................................................................................................................................4 Section 4: Programming Options .............................................................................................................6 Section 5: Manual Programming Overview ............................................................................................9 The Programming Cycle ............................................................................................................................ 9 System Setup: Software Zone Attributes ................................................................................................... 9 System Setup: Points................................................................................................................................ 10 System Setup: Assign Zones .................................................................................................................... 12 LEARN Programming ............................................................................................................................. 14 Section 6: DACT Programming ..............................................................................................................15 Section 7: Panel Menu Trees ...................................................................................................................18

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

Section 1: Introduction The PFC-4064 Conventional Fire Panel is a compact, expandable panel designed to monitor all facets of a fire alarm system and communicate the status to a monitoring station. The PFC-4064 panel is a listed and approved microprocessor based conventional fire panel and complies with UL-864, NFPA-70, and NFPA-72. Purpose Of This Manual This manual is intended to assist in the programming of the PFC-4064 Conventional Fire Panel via its keypad. Refer to this manual to properly program the PFC-4064. It is recommended that the user follows the procedures as outlined in this manual to assist in proper programming and prevent damage to the control panel and associated equipment. System Overview The PFC-4064 system is designed for use as a fire control panel for life safety applications. System Features yy The PFC-4064 has six (6) programmable input circuits, and is expandable to 192 using thirty-one (31) IDC-6 cards, each providing six (6) additional programmable input circuits. yy Four (4) Notification Appliance Circuits (NAC) rated at 3.0A maximum y Power Limited y Built in Sync y Cadence and Temporal Patterns y Programmable to activate on a Supervisory condition yy Support for all major strobe synchronization patterns. y Gentex® y AMSECO® y Wheelock® y System Sensor® yy Auto Silence and Silence Inhibit. yy Built-in Ethernet port for programming and network connectivity. yy Built-in Email support to communicate system status and event information. yy Customizable Reminder Emails. yy 4,000 event non-volatile history buffer yy 99 Software Zones yy 4 X 20 character LCD display yy Built-in IP Reporting How To Use This Manual Refer to this manual before contacting Technical Support. The information in this manual is the key to a successful programming and will assist you in understanding proper system start up, device designation, and other guidelines specific to the PFC-4064 system. 1

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

Section 2: Pre-Programming Procedures and Defaults Before beginning PFC-4064 programming, install the panel following the directions included in the PFC-4064 Installation and Operations Manual (Potter document # 5403638). Failure to properly install and wire the physical panel and any devices/ accessories being used in conjunction with it can result in system errors and difficulty in programming, as well as potentially damaging the fire alarm system. System Defaults: Input Circuit The PFC-4064 has a total of 6 built-in input circuits available for use. These inputs are for monitoring devices such as smoke detectors, pull stations and waterflow switches. The terminals for input devices (shown below) are located at the top right corner of the control panel’s circuit board. Each circuit has a factory default setting that can be used to connect to a specific type of input device for ease of installation and programming. System Defaults: Output Circuit The PFC-4064 has a total of 4 built-in output notification appliance circuits (NACs) available for use. These outputs are for notification devices, The output NAC terminals (shown below) are located at the bottom right corner of the control panel’s circuit board. Each circuit has a factory default setting that can be used to connect to a specific type of output device for ease of installation and programming. Input Terminal Default Settings Terminal # Setting Type 1 Waterflow 2 Smoke 3 Pull Station 4 General Fire Alarm 5 General Fire Alarm 6 Non-latching Tamper Supervisory NAC Output Terminal Default Settings Terminal # Activation Setting Type 1 Waterflow Only 2 Any Alarm 3 Any Alarm 4 Any Alarm 2

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

System Defaults: Relay Circuit The PFC-4064 has a total of 4 built-in relays available for use. The relays (shown below) are located along the central bottom edge of the control panel’s circuit board. Relay Output Terminal Default Settings Terminal # Activation Setting Type 1 Alarm 2 Supervisory 3 Waterflow 4 Trouble 3

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

Section 3: Operation This section provides an overview of the control panel’s basic operations, which includes the status LEDs, function pushbuttons, and a Control Panel Menu Tree quick reference sheet. Control Panel Basic Operation The control panel is comprised of a four (4) line x 20-character LCD display panel, arrow keys, push button function keys, status LEDS, and the numeric keypad. A description of each component is included in this section; please refer to the figure shown below. Figure 1. PFC-4064 Control Panel Display Note: Authorized system operators must use a key to open the outer door of the cabinet. LCD Display The LCD panel displays the standard Start-up menu as shown below. The LCD displays up to eighty (80) characters of information displays, providing important feedback to system users, i.e., system messages, status information, trouble conditions, or input changes. The LCD also provides access to the Main Menu for daily system operations and specific programming functions. Figure 2. LCD Start-Up Screen Note: You may customize the Start-up screen to display a specific job site name or other relevant descriptive text by selecting ‘Panel Name’ in the System Setup submenu. SILENCE POWER EARTH FAULT SILENCED ALARM SUPERVISORY TROUBLE RESET ACK DRILL 1 2 3 4 5 6 7 8 9 0 ESC ENTER Status LEDs Numeric Keypad Arrow Keys LCD Display Function Pushbuttons PFC-4064 All Systems Normal 11/16 21:20:00 PFC-4064 All Systems Normal 11/16 21:20:00 System Setup 1=Panel Name 2=Idle Message 3=Display Option 4

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

Menu Navigation Keys The arrow keys allow you to scroll or move through the control panel menus. The Enter and Esc keys may also be used to navigate through menus; they are located on the numeric keypad. The table shown below provides a summary of the navigation keys. Table 1: Menu Navigation Keys Push button Description Moves/scrolls up or down through menus, select numbers and letters where appropriate. Scrolls to the left or right to display details, if any, of current menu item, select numbers and letters where appropriate. Note: When the LCD panel displays a LEFT and/or RIGHT arrow, this indicates more information may be viewed. Displays the Main Menu or selects the current menu option. Note: The blinking “” indicates the current menu option. Returns to previous menu or backs up to previous screen. Numeric Keypad The numeric keypad allows you to enter user codes when required to access restricted functions. Alternatively, the numbers may be used to quickly select menu options vs. using the arrow and Enter keys to select a function. Figure 3. Control Panel Numeric Keypad Function Pushbuttons The four (4) function pushbuttons are used when system alarm / trouble conditions occur or to perform a fire drill. Refer to the table below for a brief summary of the pushbuttons: Table 2: Control Panel Pushbuttons Pushbutton Description Press to acknowledge the currently displayed condition. Press to silence all outputs programmed as silenceable and buzzer. Press to reset panel to normal condition. Press to begin a fire drill. 5

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

Section 4: Programming Options The control panel is configured using the built in keypad. The panel stores the site specific configuration data in non-volatile memory. NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below. Topic Feature or Option Permitted in UL (Y/N) Possible Settings Setting(s) Permitted in UL864? Comment Misc Idle LCD Message Y Yes/No All Settings Allowed Misc Display Events Y Initial Event Newest Event Initial Event Auto display of first event Misc SLC Blink Y Normal/Slow/Off All Settings Allowed Misc Alarm Verification Time Y 0-60 Sec All Settings Allowed Misc Waterflow Delay Y 0-255 Sec All Settings Allowed Misc AC Report Delay Y 30 Minutes to 30 Hours 1-3 Hours For UL864 use 1-3 Hr Misc DH Low AC Dropout Delay Y No delay, 15 Sec, 1 minute, 5 minute All Settings Allowed Misc Autotest Time Y Time of Day All Settings Allowed Misc Autotest Interval Y 1-24 Hours All Settings Allowed Misc Strobes Active When Silenced Y Yes/No All Settings Allowed Misc 50 Hz AC Y Yes/No All Settings Allowed Misc CO Tone on Annunciators Y Yes/No All Settings Allowed Misc Low Temp Events Are Supervised Y Yes/No All Settings Allowed Misc Disable 24 hours PZT Resound Y Yes/No No Misc Display AM/PM Y AM/PM, 24 Hour All Settings Allowed Misc Synchronize to Network Time Y Yes/No All Settings Allowed Misc SNTP Server Y North-America.Pool.NTP. org All Settings Allowed Misc Time Zone Y 24 Time Zone Selections All Settings Allowed Misc DST Enabled Y Yes/No All Settings Allowed Misc DST Start Y Month/Day All Settings Allowed Misc DST End Y Month/Day All Settings Allowed 6

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

Topic Feature or Option Permitted in UL (Y/N) Possible Settings Setting(s) Permitted in UL864? Comment Zone Zone Style Y Alarm Supervisory PAS Auxiliary Fire Drill Waterflow System Alarm System Supervisory System Trouble CO Alarm CO Supervisory All Settings Allowed Zone Alarm Count Y 1-10 All Settings Allowed Zone Silenceable Y Yes/No All Settings Allowed Zone Silence Inhibit Y Yes/No All Settings Allowed Zone Auto Silence Y Yes/No All Settings Allowed Zone Auto Unsilence Y Yes/No All Settings Allowed Zone Restore Delay Y 0-300 Sec Full range allowed Zone Latching Y Yes/No All Settings Allowed Zone Local Y Yes/No All Settings Allowed Zone Output Pattern Y Constant ANSI Temp 3 March Code Double Time ANSI Temp 4 All Settings Allowed IDC-6 Dry Contact Input Functions Y Pull Station Water Flow Supervisory Tamper Fire Drill Trouble Monitor Aux Abort Release Follower Reset Silence Fire Alarm Disable Inputs Disable Outputs Disable Inputs and Outputs Lamp Test CO Alarm CO Supervisory HVAC Reset All Settings Allowed Exception: Disabled functions allowed when used with a keyed switch. Applies to all dry-contact input devices & circuits 7

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

Topic Feature or Option Permitted in UL (Y/N) Possible Settings Setting(s) Permitted in UL864? Comment NACs Function Y General Purpose AMSECO Sync Gentex Sync Gentex Sync with T4 System Sensor Sync Wheelock Sync Constant Output Resettable Output Door Holder Output ANSII Output City Tie Output All Settings Allowed Except: A Supervisory event cannot trigger a T4 NAC. Specifies use of NAC circuit(s) AUX PWR Function Y Constant Output Resettable Output Door Holder Output ANSII Output All Settings Allowed DACT Daily Test Call Y Any time of day All Settings Allowed Alternates between line 1 and 2 if line 2 is enabled. E-Mail Email Status Reports N Alarms, Troubles, Supervisory, Test, History & Status Reports IP-Reporting IP Based Central Station Reporting Y Alarm, Supervisory, Trouble & Test Reports All Settings Allowed On-Board Programmable Relays Function Y Alarm, Supervisory, Trouble, Low AC & Waterflow All Settings Allowed Specifies use of programmable relays 1-4 8

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

9 Section 5: Manual Programming Overview The panel can be programmed using either the keypad or Potter’s panel programming software. The Programming Cycle The following is the recommended approach to program the FACP via the panel’s keypad. Active selections are indicated in Italics in this manual, while the panel will indicate an active selection with a small flashing arrow on the screen where the “=” symbol is. The “Enter” button is used to access a menu and save any changes. System Setup: Software Zone Attributes To begin setting up zones and points on the PFC-4064 system, press “Enter” on the keypad to bring up the Main Menu. Scroll down to Programming using the arrow keys, or press “6”. NOTE: Full menu trees are shown in Section 5 You will be prompted to enter an access code. The default code is 1111, which can be changed under “8 = User Codes” in the System Setup submenu at a later date for security purposes. When the code is entered, the PFC 4064 will automatically take you to the Programming sub menu shown below. Once inside the programming options, select “System Setup”, then press “Enter” to bring up the System Setup sub menu shown below, then select “Zones”. This is where software zones are configured. In latter steps, input circuits and output circuits (NACs) are assigned to these software zones. The attributes assigned to these zones will influence how the circuits operate. Options include; Alarm or Supervisory zone styles ,silenceable or non-silenceable signaling devices, latching or non latching, etc. Once inside the Zones sub menu, you can edit each zone’s (in order) style, name, count, latching, local zone, output pattern, auto silence/unsilence, silence inhibit time, restore delay, relay activate delay. A full name of the selected field will alternate between itself and “Press ENTER to edit” at the bottom of the screen. Use the right arrow button to access all the available options. Main Menu 4=Walk Test 5=System Tools 6=Programming Programming 1=System Setup 2=Learn Menu 3=Panel Default System Setup 1=Zones 2=Points 3=Assign Zones # Name Style Count 1 Zone Alarm 1 2 Zone Alarm 2 Press ENTER to edit # Silnc Latch Local 1 No No n/a 2 No No n/a Press ENTER to edit

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

10 To edit/rename an entry, select the field you would like to change using the arrow keys. Press “Enter” to open the field, which should display (example shown below) with the first character blinking. Once the field is available, scroll through the available characters to find the letter, number, or special character desired using the Up/Down arrow keys. Move to the next character space using the left/right arrow keys. When finished, press “Enter” to save changes. Note: When selecting the order the zones are listed in, the screen will allow you to change the number through either the up/ down arrow keys or by manually typing in the order number preferred. All single digit number selections must use a zero. It is highly recommended that the assigned zone name and number is written down to avoid confusion and programming errors. System Setup: Points Once the software zones are established, the next step is to configure the input circuits and NAC circuits (Points) of the fire alarm system. Points are input or output signal devices, with the functions and description of both being set here. The on-board output NAC & Aux Power circuits will be found under Built-In Power Supply while the on-board input zones are located under Built-In IDC6 It is recommended to do this immediately after setting up the Zones. Within the Programming submenu, select System Setup, then select Points. You will then have a choice between setting up points for the Built-in Power Supply (used for NAC output devices such as horns, strobes, door holders, etc) or the Built-in IDC6 (used for input devices such as smoke detectors, pull stations, flowswitches, etc.). Use the right arrow button to access all the available options. System Setup 1=Zones 2=Points 3=Assign Zones Select: Built-in PWR Sup Built-in IDC6 Zone Name Zone 1 # Name Funct Suprv 1 Conv Smoke 1 2 Conv Smoke 2 Press ENTER to edit Select Zone: Current: 1 Set: [01] # Suprv AlVer EOL 1 No No n/a 2 No No n/a Press ENTER to edit

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

11 To edit/rename an entry, select the field you would like to change using the arrow keys as done when setting up the software zones. Press “Enter” to open the field. Once the field is available, scroll through the available characters to find the letter, number, or special character desired using the Up/Down arrow keys. Move to the next character space using the left/right arrow keys. When finished, press “Enter” to save changes before pressing “ESC”. When selecting the order the points are listed in, the screen will allow you to change the number through either the up/down arrow keys or by manually typing in the order number preferred. All single digit number selections must use a zero. It is highly recommended that the assigned point name and number is written down to avoid confusion and programming errors. When selecting a Point Function, use the up/down arrow keys to select a function for the notification or signaling circuit. The options for the output (NAC) circuits are: • City Tie • Aux Door Holder Low AC (Aux D-Hold-AC) • Aux Door Holder (Aux D-Hold) • Aux Resettable • Aux Constant • Wheelock Sync • System Sensor Sync (Sys Sensor) • Gentex Sync w/T4 • Gentex Sync • AMSECO Sync • NAC Gen Purp • Unused Zone Name NAC 1 Select Point: Current: 1 Set: [1] NAC 1 Point Function Curr: NAC Gen Purp Set: [City Tie ] The options for the input circuits are: • Smoke • HVAC Restart • Supervisory • CO Alarm • Lamp Test • Disable Inputs/Outputs • Disable Outputs • Disable Inputs • Fire Alarm • Silence • Reset • Aux Input • Trouble Monitor • Fire Drill • Tamper • Waterflow • Pull Station • Heat • Unused

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

12 System Setup: Assign Zones Once the input and output points have been set, they will need to be assigned to an appropriate zone. Zones are where input and output device correlations are established. An Input Circuit will activate an output circuit (NAC) when they are assigned to the same zone. Circuits that initiate an Alarm are assigned to Alarm Style Zones. Circuits that initiate a Supervisory signal must be assigned to a supervisory style zone. Within the Programming submenu, select System Setup, then select Assign Zones. When inside the Zone Assignment submenu, you’ll have the option to add or delete points to the software zones you established earlier. Select “Add to Zone” or “Delete From Zone” to bring up the selection screen. The options are through the Power Supply and IDC6, which contain the respective points you programmed into each earlier. Scroll through the available points previously assigned by using the up/down arrow keys. Select the point being assigned or deleted by pressing “Enter”. You will see one of the following two screens displayed as shown below depending on whether the point is being added or deleted. Use the up/down arrow keys to scroll through the available choices, then press “Enter” when the zone number desired has been reached and highlighted by the flashing arrow. You will receive a message on the screen stating “Point has been added /deleted” if done correctly. Note: If a point has already been assigned to the zone selected, you will receive a message stating so. Zone Assignment 1=Add to Zone 2=Del From Zone ESC=Exit Select: Built-in PWR Sup Built-in IDC6 Select: NAC 1 NAC 2 NAC 3 Select Zones: Zone 1 Zone 2 Zone 3 Del from Zone [001] System Setup 1=Zones 2=Points 3=Assign Zones

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

13 System Setup: Program Relays The relays are configured to activate on a specific panel condition (Alarm, Trouble, Supervisory and Waterflow). The relay default settings are detailed in Section 2. To change the defaults, go to the Programming submenu, enter the four digit access code when prompted, then go to the System Setup submenu, and select “Program Relays”. Once inside the Program Relays submenu, select the relay being changed from the four options available. The screen will show the currently selected relay’s function. To change the function, use the up/down arrow keys. Press “Enter” to select and save the new function. Main Menu 4=Walk Test 5=System Tools 6=Programming Programming 1=System Setup 2=Learn Menu 3=Panel Default System Setup 3=Assign Zones 4=Program Relays 5=P-Link Devices Select. Prog. Relay 1=Prog. Relay 1 2=Prog. Relay 2 3=Prog. Relay 3 Relay Function Curr: Alarm Set: [Waterflow ] Point is already assigned to this zone.

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

14 LEARN Programming The LEARN function is available through the control panel, and is an efficient way to add the UD-1000 DACT and other accessory cards wired to the P-Link circuit. LEARN detects all connected devices, assigns a name and selects the applicable device type To run the LEARN mode: 1. From the control panel, press the Enter button to display the Main Menu. •� Press 6 to select Programming. The “Enter Code” prompt displays. •� Enter the user code when prompted. Factory default code is 1111. •� Press 2 to select LEARN. Press 1 to select LEARN ALL. System begins searching for devices. 2. Results are grouped by device type. If no changes are detected, the prompt “No changes” displays. •� Use down arrow to scroll through results by device type: It is recommended that the assigned number of each point is written down at this time. Note: The abbreviation “Pts” refers to addressable input and output points. •� Select Esc when finished reviewing results. The system prompts to save or discard file. 3. Press 1 to Accept changes; press 2 to Cancel changes. • When user presses ‘1’ to accept changes, user will need to press the ESC button to back out to the main menu. The panel will prompt the user to press Enter to accept the changes or ESC to cancel • The PFC-4064 will either restart to save the changes or exit back to the programming submenu depending on the selection. Main Menu 4=Walk Test 5=System Tools 6=Programming Programming 1=Learn All 2=EOL Learn 3=PSN Learn Programming 1=System Setup 2=Learn Menu 3=Panel Default Programming 1=P-Link Found 2=P-Link Removed 3=Pts Found Programming 4=Pts Removed 5=Pts Changed Esc=Exit

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

15 Section 6: DACT Programming The PFC-4064 uses a Potter UD-1000 Digital Alarm Communicator Transmitter (DACT) which allows for communication with a monitoring station. The Programming Cycle The following is the recommended approach to program the UD-1000 via the panel’s keypad. Before beginning programming, ensure the card and phone cords have been properly installed following the directions listed in the UD-1000 Installation Manual (Potter document # 5406079) and the LEARN programming has been run. To change the defaults, go to the Programming submenu, enter the four digit access code when prompted, then go to the System Setup submenu, and select “PLink Devices”. Once in the PLink Devices submenu, select “Edit Device” to begin programming the UD-1000. Scroll down to and select the appropriate “Dialer #” [number (#) will be determined during the LEARN programming] from the list. Main Menu 4=Walk Test 5=System Tools 6=Programming Programming 1=System Setup 2=Learn Menu 3=Panel Default System Setup 3=Assign Zones 4=Program Relays 5=P-Link Devices Plink Devices: 1=Edit Device 2=Add New Device 3=Delete Device Select: Built-in Keypad Built-in IDC6 Dialer #

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

16 The UD-1000 Options allow you to edit the name of the dialer if desired, where it reports to and how, and connect to the monitoring station provider. To begin, select Line 1 Setup. The following options are available. The exact same options will be used when setting up Line 2. • Enable/Disable activates or deactivates the phone line connection. Options are Yes or No. • Answering Machine allows for the dialer to bypass any answering machines. Options are Yes or No. • Line Monitor enables the device to monitor the phone line voltage. Options are Yes or No. • Dialtone Detection enables the device to monitor the phone line dial tone. Options are Yes or No. • Number Of Rings determines how many times the phone line rings before the panel picks up. Factory default is 3. • Line Prefix is used when an extra number is needed for the panel to dial out of the facility or if a pause is needed in dialing. All changes are saved by pressing “Enter” and using “Esc” to return to the UD-1000 options menu • The Priority option is used if two different communication paths are being utilized by the panel. If the UD-1000 dialer is the only path being used, it will automatically default to the primary option. Potter offers five different account options in the event separate primary and secondary receivers need to be reported to. To begin, select Account Setup. The following screen will display. Select the account being updated to bring up the Options screen. Secondary Setup (not displayed) is an available option and is programmed the same way as Primary Setup. UD-1000 Options 1=Edit Name 2=Line 1 Setup 3=Line 2 Setup UD-1000 Options 4=Priority 5=Account Setup Esc=Exit Phone Line Setup 1=Enable/Disable 2=Ans Machine 3=Line Monitor Phone Line Setup 4=DialTone Det 5=No. Of Rings 6=Line Prefix Reporting Method Priority Curr Val: Primary Set Val: [Primary] Select Account 1=Account 1 2=Account 2 3=Account 3 Account Options 1=Event Types 2=Rpt by Option 3=Primary Setup

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

17 Event Types specifies what events the panel will be reporting over the DACT. By default the panel will not report any Alarms, Supervisory, or Troubles when those occur. The value change screen for the Reporting options will look similar, the options are Yes and No. You can make the change by using the Up and Down arrows. The Report By Option lets the user determine when reports to the monitoring station are sent depending on the panel, point or zone creating an active alert. The default reporting option is by Panel, which reports General Alarm, Supervisory, or Trouble. When finished with setting up event types and reporting options, select the Primary Setup option. The following options are available. • The Account ID option is for entering in the account number given to the user by the monitoring station company. Note: Some accounts from monitoring stations will include letters and numbers. The PFC-4064 panel can only enter in numbers. • Account Format allows the user to determine whether report codes sent to the monitoring station are sent via CID or SIA The PFC-4064 reporting format is set to CID by default • Phone Number allows the user to enter in a specific receiver number the panel will contact during an active alert. When programming any secondary and additional accounts, a different phone number must be used in the event the number assigned to the primary account fails Note: Not a requirement for all municipalities, check with your local AHJ for requirements before beginning programming. • Report Test allows the panel to conduct a connectivity test every 24 hours. The options are Yes and No. Select Esc to back out of programming when finished. • When user presses ‘1’ to accept changes, user will need to press the ESC button to back out to the main menu. The panel will prompt the user to press Enter to accept the changes or ESC to cancel • The PFC-4064 will either restart to save the changes or exit back to the programming submenu depending on the selection. Report Options 1=Report Alarms 2=Report Troubles 3=Report Supervisory Report Alarms Curr Val: No Set Val: [No ] Account Report by: Curr: Panel Set: [Panel] Account Options 1=Account ID 2=Format 3=Phone Number Account Options 4=Report Test Esc=Exit

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

4=Walk Test 2=Enable/Disable 1=View History 3=Set Date/Time PFC-4064 All Systems Normal 11/16 21:20:00 6=Programming 5=System Tools 1-By Point 2-By Zone ESC-Exit Allows user to enable or disable devices either by a single point or zone. Press “Enter” Allows user to view all events that have occurred during use of the panel (alarms, fire drills, walk tests, etc.) Allows user to set date and time for the control panel. 7=Data Transfer 1-Point Control 2-Ethernet Tools 3-DACT Test 4-DACT Reset 5-Erase History 6-Lamp Test 7-App Revisions ESC-Exit Menu Tree 1 See Menu Tree 2 Select Data 1-Remote Access 2-Email History 3-Email Config 4-Email Test 5-Server Status ESC-Exit Allows users to configure remote access to the panel, set up email alerts, and server connection checks. Start Walk Test? Yes No Allows users and inspectors to initiate any devices at will to verify correct installation and functionality Section 7: Panel Menu Trees 18

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

Remote User/ Pswd 1-Username 2-Password ESC-Exit Menu Tree 2 6=Programming 1-System Setup 2-LEARN Menu 3-Panel Default 4-IP Settings 5-Dflt ID/Pswd 6-Prog ID/Pswd ESC-Exit 4-IP Settings 2-LEARN Menu 1-System Setup 1-Zones 2-Points 3-Assign Zones 4-Prog. Relays 5-PLink Devices 6-Email Setup 7-IP Reporting 8-User Codes 9-More 3-Panel Default 6-Prog ID/Pswd 5-Dflt ID/Pswd More 1-AC Report Delay 2-Waterflow Delay 3-Door Hold Delay 4-Alarm Verification 5-Autotest Setup 6-Time Zone 7-DST Setup 8-Job Details 9-More More 1-Panel Name 2-Idle Message 3-Display Option 4-Clock Option 5-Strobe Silence 6-CO Tone 7-24 Hour Resound 8-Cross Zones See Menu Tree 3 1-Zones Software zone attributes are set here. Includes options like Alarm or Supervisory zone styles, silenceable or non-silenceable signaling devices, latching or non latching, etc. Points are assigned to zones in option 3 = Assign Zones 2-Points Function and description of both input and output circuits are set here. The on-board NAC & Aux Power circuits will be found under Built-In Power Supply. The on board input zones are located under Built-In IDC6 3-Assign Zones Input zones and outputs (NAC) are added or removed from one or more software zones. This is where input output correlations are established. 4-Program Relays This pertains to the 4 on-board relays. They can each be individually set for Alarm, Trouble, Supervisory, Waterflow 5-PLink Devices The panel supports several different types of devices wired to the P-link circuit including the UD-1000 DACT, LCD Annunciators, PSN-1000 Power Supply, CA4064 Class A Module, etc. These devices can be added or removed from the panel configuration here. 6-Email Setup The PFC-4064 is capable of sending panel status reports, scheduled history reports and responding to email requests for up to 20 different email users / accounts. 7-IP Reporting Allows the panel the report to a monitoring station reciever by IP. By default IP reporting is turned off. The submenu in IP Reporting allows you to configure the IP Dialer. 8-User Codes The Users option allows you to create up to ten (10) user code profiles, as needed. Each profile may have different access rights, which controls the panel functions a user may access as well as the option to connect to the Facility Management Tool (FMT). 1-AC Report Delay Sets the AC Report Delay Default = 1 hr (0 - 30 hr) 2-Waterflow Delay Sets the Waterflow Delay (If enabled) Default = 0 sec (0 - 255 sec) 3-Door Holder Delay Sets the Door holder Delay Default = 15 sec (0 - 5 min) 4-Alarm Verification Sets the Alarm Verification time (If enabled) Default = 60 sec (30 - 60 sec) 5-Autotest Setup Sets the test timer for both dialers on the panel and reporting frequency Default Reporting Time= 2:00 AM Default Reporting Intveral = 24 hr 6-Time Zone Sets the panel’s time zone. Automatically adjusts to current time & date when plugged into network 7-DST Setup Sets Daylight Standard Time if enabled and when the DST starts and ends. 8-Job Details Submenu in section allows you to enter site specific information 1-Panel Name Enter a descriptive panel name. 2-Idle Message Changes the panel description on the panel’s LCD (When enabled) 3-Display Option Choose how the panel displays history events 4-Clock Option Submenus in this selection allows you to configure the panel’s automatic time setup. 5-Strobe Silence Allows strobes to remain active when panel is silenced (When enabled) 6-CO Tone Allows CO tone to be annuciated over remote annunciators 7-24 Hour Resound Panel’s buzzer will resound after a 24 hour period if off normal condition is present on the panel. 8-Cross Zones Allows panel’s inputs to be cross zoned together to turn on outputs See Menu Tree 3 See Menu Tree 3 Resets the FACP Remote Password See Menu Tree 4 See Menu Tree 5 19

PFC-4064 KEYPAD PROGRAMMING • 8870080 • REV A • 12/17

6=Programming 1-System Setup 2-LEARN Menu 3-Panel Default 4-IP Settings 5-Dflt ID/Pswd 6-Prog ID/Pswd ESC-Exit 4-IP Settings 2-LEARN Menu 1-System Setup 3-Panel Default 6-Prog ID/Pswd 5-Dflt ID/Pswd Programming 1-Learn all 2-EOL Learn 3-PSN Learn ESC-Exit Press 1-Accept 2-Cancel Resets panel to factory default See Menu Tree 2 Ethernet Options 1-DCHP Settings 2-Static IP 3-Subnet Mask 4-Default Gtway 5-Alternate IP 6-Alt. Subnet 7-Alt. Gateway ESC-Exit 1=System Setup 6-Email Setup 7-IP Reporting Email Set Up 1-Email Reports 2-Email Reminder 3-Outgoing Addr Email Reports Send Options 1-Time of Day 2-Days of Week 3-Day of Month 4-Select Account Select Account Email Options 1-Email Address 2-Report Options Email Reminders 1-Schedule 2-Attachments 3-Recipients 4-Subject 5-Message Body Recipients 1-Edit Recipients 2-Add Recipient 3-Del Recipient IP Report Options 1-Reporting Path 2-Priority 3-Account Setup 4-Add Account 5-Del IP Dialer Menu Tree 3 6=Programming Menu Tree 4 1=System Setup 6=Programming Menu Tree 5 See Menu Tree 2 See Menu Tree 2 20

Other Control Panel Manuals