1.1 General Description
This instruction manual describes the communication command of the HR-700 Recorder. Please refer to the
instruction manual for the transmission of the measurement data, setup of communication and wiring.
Modbus RTU protocol as well as Original protocol can be used from version 4.00.
1.2 Difference between RS-485 and RS-232C
There is no difference between RS-232C and RS-485 with respect to the communication command in this
recorder. However, wiring and signal levels may differ.
1.3 Basic item about the Original protocol command
The communication command consists of a command distinction code, a parameter, delimiter (comma), and
terminator. The format of the command is as follows.
(Example) SR02 VOLT, 200mV, 0, 20000 (terminator)
Command distinction code:
This code is defined by two capital letters. (e.g. SR)
If the command needs a channel number, the channel number is described after the distinction
code.
Parameter:
Each parameter is divided by a comma.
All the setting values are shown with an integer. (The plus sign can be omitted.)
The space character in the input parameter is ignored. However, the space character in the
unit code, the comment printout code and the tag printout code are not ignored. Parameters
can be omitted unless the parameters are varied. However, the comma (,) cannot be omitted.
Commas which come before the terminator can be omitted.
(Example) SR02, VOLT,,, (CR)(LF)
The date parameter, the time parameter and the channel number parameter have fixed length.
Different length of these parameters may cause errors.
(1) Date YY/MM/DD (8 characters)
(2) Time HH:MM:SS (8 characters)
(3) Channel Number: CHXX (2 characters)
Can be omitted.
Contents
Wiring and
communication
procedure
Request
measurement
value
Setting of the
recorder
Control of the
recorder
HR-700 Hybrid Recorder
instruction manual
O
O
HR-700 Hybrid Recorder
Communication Command
manual
O
O
O: Please refer to the corresponding manual.
Basic item about the Modbus RTU protocol
Modbus protocol is a communication protocol which was developed for PLC by Modicon Inc. (AEG
Schneider Automation International SAS), and is listed in the protocol specification (PI-MBUS-300 Rev.J).
Regarding the Modbus protocol specification, refer to the protocol specification (PI-MBUS-300 Rev.J).
In this manual, we describe the function codes and data contents of Modbus protocol which can be used
for the recorder.
2. ORIGINAL PROTOCOL – DATA RECEPTION
2.1
Setup command
2.1.1 Setup command list
Table 2.1.1 Setup command list
Command
Setting item
Number of
parameters
Contents of parameter
SR
Setting the range
MAX 7
Channel, Mode,
Range (Reference Channel)
Span lower limit value
Span upper limit value
Scaling lower limit value
Scaling upper limit value
SA
Setting the Alarm
7
Channel
Alarm level
Alarm ON/OFF
Alarm type, Alarm set point
Relay ON/OFF, Relay No.
SN
Setting the Unit
2
Channel, Unit
SC
Setting the Chart Speed
1
1st Chart speed
SD
Setting the Date/Time
2
Date, time
SF
Setting the Digital Print
2
Channel
Digital print ON/OFF
ST
Setting the Tag
2
Channel, Tag characters
SG
Setting the Comment
2
Comment number
Comment characters
SZ
Setting the Zone
recording
3
Channel
Left end position
Right end position
SP
Setting the Partial
Compression/Expansion
recording
4
Channel, Partial ON/OFF
Compression
Expansion
SE
Setting the Chart Speed
1
2nd chart speed
SY
Copying the Setting
data
2
Channel to copy from
Channel to copy to
SS
Setting the recording
cycle
1
Recording Cycle
(Multipoint type only)
2.1.2 Setting of INPUT RANGE/RECORD SPAN
Sets the input range and record span for each channel as follows.
SR(CH), (Mode), (Pr1), (Pr2), (Pr3), (Pr4), (Pr5), (Pr6), (Pr7), (CR)(LF)
CH: Specify a channel number to set.
Mode: Mode setting
PrN: The number of PrN varies depending on the contents of the Mode.
(1) Record skip setting
The record of the specified channel (CH) stops.
[For the pen type recorder, No. 1 pen (red) is fixed on the left side (approx. 15%) and
No. 2 pen (green) on the right side (approx. 85%), respectively.]
CH: Setting Channel 01 to 06 (01 and 02 for the pen type)
Mode: SKIP
Example) SR05,SKIP(CR)(LF)
The 5th channel doesn't record.
(2) Input range setting of the Voltage, Current, Thermocouple and RTD
CH: Setting Channel 01 to 06 (01 and 02 for the pen type)
Mode: VOLT, TC or RTD
Pr1: Range
Pr2: Left end (Zero Input Value)
Refer to Table 2.1.2.
Pr3: Right end (Span Input Value)
Example)SR02,TC,K,0,3000(CR)(LF)
The input of the 2nd channel is Thermocouple K, 0.0-300.0
(3) Difference/Sum/Mean operation setting.
CH: Setting Channel 01 to 06 (01 and 02 for the pen type)
Mode: DELT,SIGM or MEAN
Pr1: Reference Channel
Choose a smaller channel than CH.
The reference channel must be VOLT, TC, RTD or SCL mode.
Pr2: Left end (Zero Input Value)
Pr3: Right end (Span Input Value)
Example) SR05,02,DELT,0,3000(CR)(LF)
The output of the 5th channel shows a difference between the input of the 5th channel and
the 2nd channel (CH5-CH2). In this case, the input range of the 5th channel is the same as
that of the 2nd channel.
Refer to Table 2.1.2.
(4) Scaling setting
CH: Setting Channel 01 to 06 (01 and 02 for the pen type)
Mode: SCL
Pr1: VOLT, TC, RTD
Pr2: Scaling Mode
Pr3: Left End (Zero Input Value)
Pr4: Right End (Span Input Value)
Pr5: Scaling Left End
Pr6: Scaling Right End
Pr7: Decimal point position (0 to 4)
Example) SR04,SCL,RTD,PT,0,3000,0,30000,2(CR)(LF)
(5) Square Root setting
CH: Setting Channel 01 to 06 (01 and 02 for the pen type)
Mode: SQRT
Pr1: Range (Only VOLT Input)
Pr2: Left End (Zero Input Value)
Pr3: Right End (Span Input Value)
Pr4: Scaling Left End
Pr5: Scaling Right End
Pr6: Decimal point position (0 to 4)
Example) SR03,SQRT,mA,400,2000,0,10000,2(CR)(LF)
(6) Decade setting
CH: Setting Channel 01 to 06 (01 and 02 for the pen type)
Mode: DECAD
Pr1: Range (Only VOLT Input)
Pr2: Left End (Zero Input Value)
Pr3: Right End (Span Input Value)
Pr4: Scaling Left End
Pr5: Scaling Right End
Example) SR01,DECAD,10mV,0,1000,10E+01,10E+06(CR)(LF)
[CAUTION]
Pr5 through Pr7 can be omitted. When omitting parameters, three parameters must be
omitted simultaneously.
[CAUTION]
Pr5 through Pr7 can be omitted. When omitting parameters, three parameters must be
omitted simultaneously.
Refer to Table 2.1.2.
Refer to Table 2.1.2.
Refer to Table 2.1.2.
Table 2.1.2 Setting range
Input
Range
Range or
Scaling
Mode
Zero Input
Value
(Left End)
Span Input
Value
(Right End)
Decimal
Point
(Fixed)
Note
VOLT
10mV
-1000
1000
2
10mV
20mV
0
2000
2
0 to 20mV
50mV
0
5000
2
0 to 50mV
200mV
-2000
2000
1
200mV
1V
-1000
1000
3
1V
5V
0
5000
3
0 to 5V
10V
-10000
10000
2
10V
mA
400
2000
2
4 to 20mA
TC
B
0
18200
1
0 to 1820
320
33080
1
32 to 3308
R
0
17600
1
0 to 1760
320
32000
1
32 to 3200
S
0
17600
1
0 to 1760
320
32000
1
32 to 3200
K
-2000
13700
1
-200 to 1370
-3280
24980
1
-328 to 2498
E
-2000
8000
1
-200 to 800
-3280
14720
1
-328 to 1472
J
-2000
11000
1
-200 to 1100
-3280
20120
1
-328 to 2012
T
-2000
4000
1
-200 to 400
-3280
7520
1
-328 to 752
C
0
23200
1
0 to 2320
320
42080
1
32 to 4208
Au-Fe
10
3000
1
1 to 300K
N
0
13000
1
0 to 1300
320
23720
1
32 to 2372
PR40-20
0
18800
1
0 to 1880
320
34160
1
32 to 3416
PL-
0
13900
1
0 to 1390
320
25340
1
32 to 2534
U
-2000
4000
1
-200 to 400
-3280
7520
1
-328 to 752
L
-2000
9000
1
-200 to 900
-3280
16520
1
-328 to 1652
RTD
Pt100
-2000
6500
1
-200 to 650
-3280
12020
1
-328 to 1202
JPt100
-2000
6300
1
-200 to 630
-3280
11660
1
-328 to 1166
Example) When decimal point position is "1", the input value "1000" is recognized as "100.0".
2.1.3 Setting of the Alarm
Sets Alarm for each channel as follows.
SA(CH), (LEVEL), (ON/OFF), (TYPE), (VALUE), (RLY ON/OFF), (RLY No.) (CR)(LF)
The underlined part can be omitted.
2.1.4 Setting of the Unit
Sets the Unit for each channel as follows.
SN(CH),(UNIT)(CR)(LF)
CH: Setting Channel 01 to 06 (01 and 02 for the pen type)
UNIT: The Unit can be set with cods as shown in Table 2.1.13 (Within 6 characters).
When you use the code beyond 7FHEX, 8-bit data length must be used.
Please refer to Section 7.2.7 of the instruction manual (HR-700) for the data
length setting.
2.1.5 Setting of the 1st chart speed
Sets the 1st chart speed as follows.
SC (CHART SPEED) (CR) (LF)
A chart speed is chosen from the following table.
CHART SPEED (Dot printing type)
CHART SPEED (Pen type)
Item
Contents
Setting Range
Note
CH
Channel number
01 to 06 (multi)
01 to 02 (pen)
LEVEL
Alarm level
1 to 4
ON/OFF
Alarm ON/OFF
ON or OFF
Can be omitted.
TYPE
Alarm Type
H:Upper-limit
L:Lower-limit
Can be omitted.
VALUE
Set Value
Can be omitted.
RLY ON/OFF
Relay ON/OFF
ON or OFF
Can be omitted.
RLY No.
Relay No.
I01 to I06 (multi)
I01 to I03 (pen)
Can be omitted.
0
1
2
3
4
5
10
15
20
25
30
40
50
60
75
80
90
100
120
150
160
180
200
240
300
360
375
450
600
720
750
900
1200
1500
5
10
15
20
25
30
40
50
60
75
80
90
100
120
150
160
180
200
240
300
360
375
450
600
720
750
900
1200
1500
1800
2400
3000
3600
4500
4800
5400
6000
7200
9000
10800
12000
2.1.6 Setting of the date/time
Sets date/time of the internal clock of the recorder as follows.
SD(DATE),(TIME)(CR)(LF)
DATE: YY/MM/DD
(YY) Year 00 to 99
(MM) Month 01 to 12
(DD) Day 01 to 31
TIME: HH:MM:SS
(HH) Hour 00 to 23
(MM) Minute 00 to 59
(SS) Second 00 to 59
2.1.7 Copying the Setting Data of the channel
The setup data of any channel can be copied to another channel.
SY(CHS),(CHD) (CR)(LF)
CHS: Channel to copy from, 01 to 05 (Only 01 for the Pen type)
CHD: Channel to copy to (CHS < CHD)
The number of the channel to be copied must be bigger than the channel to copy from.
2.1.8 Setting of the Printing cycle (Dot printing type only)
Sets Printing cycle of the recorder as follows.
SS(PRINTING CYCLE)(CR)(LF)
PRINTING CYCLE: 10, 20, 30 and 60 (sec.)
2.1.9 Setting of the Zone Recording
Sets Zone Recording of each channel as follows.
SZ(CH),(LEFTPOSITION),(RIGHTPOSITION)(CR)(LF)
CH: Setting Channel 01 to 06 (01 and 02 for the pen type)
LEFT POSITION: 0 to 95%
RIGHT POSITION: 5 to 100%
The underlined parts can be omitted.
2.1.10 Setting of the Partial Compression/Expansion
Sets Partial Compression/Expansion recording of each channel as follows.
SP(CH),(ON/OFF),(BOUNDARY POSITION),(BOUNDARY VALUE)(CR)(LF)
CH: Setting Channel 01 to 06 (01 and 02 for the pen type)
ON/OFF: Partial Compression/Expansion function ON or OFF
BOUNDARY POSITION: 1 to 99%
BOUNDARY VALUE:
CH is VOLT, TC, RTD, DELT, SIGM or MEAN mode: In the span data
CH is SCALE, SQRT, DECAD mode: In the scale data
The underlined part can be omitted.
2.1.11 Setting of the Digital Print ON/OFF
Sets Digital Print ON/OFF of each channel as follows.
SF(CH),(ON/OFF)(CR)(LF)
CH: Setting Channel 01 to 06 (01 and 02 for the pen type)
ON/OFF: ON or OFF
2.1.12 Setting of the Tag Character
Sets Tag Character of each channel.
ST(CH),(TAG)(CR)(LF)
CH: Setting Channel 01 to 06 (01 and 02 for the pen type)
TAG: The Tag Character can be set with character codes shown in Table 2.1.13.
(Dot printing type is within 7 characters. Pen type is within 5 characters.)
When you use the character code beyond 7FHEX, 8-bit data length of communication
function must be used.
Please refer to Section 7.2.7 of the instruction manual (HR-700) for the data length setting.
2.1.13 Setting of the Comment Character
Sets Comment Character to be printed by the Digital Input.
SG(Cn),(COMMENT)(CR)(LF)
Cn: Comment Number(1 to 3)
COMMENT: A Comment Character is set up with the character code shown in Table 2.1.13.
(Dot printing type is within 16 characters. Pen type is within 12 characters.)
When you use the character code beyond 7FHEX, the data length of communication
function must be used as 8 bits.
Please refer to Section 7.2.7 of the instruction manual (HR-700) for the data length
setting.
Character Code Table
Table 2.1.13 Character Code Table
2
3
4
5
6
7
A
B
C
D
E
F
0
SP
0
@
P
p
0
0
Π
π
1
!
1
A
Q
a
q
1
1
A
P
α
ρ
2
"
2
B
R
b
r
2
2
B
Σ
β
σ
3
#
3
C
S
c
s
3
3
Γ
T
γ
τ
4
$
4
D
T
d
t
4
4
Y
δ
υ
5
%
5
E
U
e
u
5
5
E
Φ
ε
φ
6
&
6
F
V
f
v
6
6
Z
X
ζ
χ
7
'
7
G
W
g
w
7
7
H
Ψ
η
ψ
8
(
8
H
X
h
x
8
8
Θ
θ
ω
9
)
9
I
Y
i
y
9
9
I
ι
A
:
J
Z
j
z
K
κ
B
+
;
K
[
k
{
+
+
Λ
λ
C
,
<
L
l
|
M
μ
D
–
=
M
]
m
}
N
ν
E
.
>
N
^
n
 ̄
-
-
Ξ
ξ
F
/
?
O
_
o
o
o
Ο
o
Example) The character code "43HEX" represents as the character "C".
2.2 Control command
2.2.1 Control command list
Table 2.2.1 Control command list
Command
Control item
Number of
parameters
Explanation of operation
PS0
Recording Start
–
The same as the recording by the RUN
key.
PS1
Recording Stop
–
MP0
Manual Print start
–
The same as the manual print by key
operation
MP1
Manual Print stop
–
LS0
List Print start
–
The same as the List Print by key
operation
LS1
List Print stop
–
SU0
Engineering List Print start
–
The same as the Engineering List Print
by key operation.
SU1
Engineering List Print stop
–
UD0
Auto Display selection
–
When the manual display is selected,
channel number can be set. However,
the channel number can be omitted.
(e.g.)Displaying the measurement value
of the 5th channel:
UD1, 05 (CR)(LF)
UD1
Manual Display selection
1
UD2
Date Display selection
–
UD3
Time Display selection
–
UD4
Display OFF selection
–
PR0
Communication comment print
out (Sync printout)
2
Prints out characters received by the
communication function.
The parameter consists of printout colors
and printout characters.
PR1
Communication comment print
out (Async printout)
2
BO0
Byte output order
(High byte earlier)
2
This command is valid only in the binary
mode.
(Please
refer
to
Chapter
8
of
the
instruction manual for details.)
BO1
Byte output order
(Low byte earlier)
2
TS0
Measurement value output
–
The recorder sets output information in
the
memory,
and
returns
the
corresponding
data
after
“ESC
T”
command is received.
(Please
refer
to
Chapter
8
of
the
instruction manual for details.)
TS1
Setting value output.
(Refer to Chapter 3)
–
TS2
Decimal point position and the
unit character output.
(Refer to Chapter 3)
–
FM0
The ASCII mode output of the
measurement data
2
This command outputs the measurement
value. The parameter consists of the
output start channel and output end
channel.
(Please
refer
to
Chapter
8
of
the
instruction manual for details.)
FM1
The Binary mode output of the
measurement data
2
LF
The output of the setting value,
the unit character and the
decimal point position
2
This command outputs the setting value.
The parameter consists of the output
start channel and output end channel.
(Please
refer
to
Chapter
8
of
the
instruction manual for details.)
2.2.2 Recording Start/Stop
This command starts or stops recording.
PS0(CR)(LF): The recorder starts recording.
PS1(CR)(LF): The recorder stops recording.
2.2.3 Manual Print Start/Stop
This command starts or stops the Manual print.
MP0(CR)(LF): The manual print starts.
MP1(CR)(LF): The manual print stops.
2.2.4 List Print Start/Stop
This command starts or stops the List print.
LS0(CR)(LF): The list print starts.
LS1(CR)(LF): The list print stops.
2.2.5 Engineering list Print Start/Stop
This command starts or stops the Engineering list print.
SU0(CR)(LF): The Engineering list print starts.
SU1(CR)(LF): The Engineering list print stops.
2.2.6 Selection of the display contents
This command selects the display mode of the recorder.
The Auto Display, the Manual Display, the Date Display, the Time Display and Display OFF can be chosen.
When receiving this command, the display of the recorder changes automatically.
UD0(CR)(LF)
: Auto Display
UD1, (CH)(CR)(LF) : Manual Display
UD2(CR)(LF)
: Date Display
UD3(CR)(LF)
: Time Display
UD4(CR)(LF)
: Display OFF
CH: The manual display channel 01 to 06 (01 and 02 for the pen type)
The underlined part can be omitted.
2.2.7 Communication comment print out
This command prints the character strings, which have been received by the communication function.
Please refer to Table 2.1.13 for the character code. When you use the character code beyond 7FHEX,
8-bit data length of communication function must be used.
Please refer to Section 7.2.7 of the instruction manual (HR-700) for the data length setting.
PR0, (COLOR), (TEXT)(CR)(LF): Sync printout
PR1, (COLOR), (TEXT)(CR)(LF): Async printout
COLOR: Chooses a printout color. (The Pen type has only PRP.)
PRP: Purple, RED: Red, BLK: Black, GRN: Green, BRN: Brown, BLU: Blue
TEXT: Maximum character number for the Dot printing type is 47.
Maximum character number for the Pen type is 21.
3. ORIGINAL PROTOCOL - DATA TRANSMISSION
3.1 Setting Value Reading
When the recorder receives "(TS1)+ (ESC T) + (LF)", the recorder continuously sends the setting value
according to Table 3.1 below.
The output format of each command when reading is the same as that of when setting.
Table 3.1
Order of the setting value transmission
Order
Command
Description
1
PS
Recording start/ Recording stop
2
SR
Input range, recording span
3
SN
Unit
4
SA
Alarm
5
SC
1st chart speed
6
SS
Analog printing period
(only for Dot printing type)
7
SZ
Zone recording
8
SP
Partial compression/expansion recording
9
SF
Digital printing
10
ST
Tag character
11
SG
Comment character
12
SE
2nd chart speed
13
UD
Display indication mode
14
EN
End
3.2 Data Reception Example
Send the setting value in this order
Open command
Opens the link
Setting value data
output designation
command (TS1)
Prepares
setting value
data output
Data update
command (ESC T)
Prepares the
update data
Data output request
command (LF)
Sends the
update data
Close command
Closes the link
Send the command to the
recorder which starts data
transmission.
Designates setting value
data to send when the recorder
receives ESC T command
once.
The designated data remains
unchanged until the recorder
receives TS0 and TS2
commands.
Send this command to the
recorder when transmitting
data to another recorder.
4. ORIGINAL PROTOCOL - NOTES FOR COMMUNICATION
4.1 Half-Duplex Transmission
Half-duplex transmission is used for the recorder side. The recorder cannot receive data while it
is sending data. When sending the command, the host computer should send the next command
after it received data from the recorder.
4.2 Multiple access
Do not open another recorder when one recorder is open on the same line.
4.3 Continuation of Opening the Link
Do not allow an extended interval after sending the open command. A syntax error may occur when
not sending data. Be sure to send the close command "ESC C" when you do not use communication
function. If a syntax error occurs, send the status output command " ESC S" to reset the error.
(The close command cannot reset syntax errors.)
4.4 Outputting the Status
When the open-link recorder has a data error on its link, the recorder saves the error in the internal
status area as a communication error. The "ESC S" command reads this status. Issuing this
command clears the on-going error. Refer to Section 8.5 in the instruction manual (HR-700).
Be sure to reset the error when setting data to the recorder. If the error is not reset, you may not be
able to assess which command caused errors.
5. MODBUS RTU PROTOCOL – OVERVIEW
5.1 Modbus RTU protocol
Item
Specification
Interface
RS-485/RS-232C
Protocol
Modbus RTU
Communication speed
1200 /2400 /4800 /9600 /19200/ 38400 [bps]
Parity
None/Even/Odd
Data length
8bit(※)
Stop bit
1bit / 2bit
Slave address
1~247(0 invalid)
※Please use 8bit data length when using the Modbus RTU protocol.
Communication can’t be performed successfully if you use 7bit.
5.2 Adding new items and Map version
Depending on the version up of the recorder, there is that the contents of the Modbus map is hanged.
If the Modbus map is modified, Modbus map version (address 30025) will also be updated.
Newly added setting items are available in the corresponding version or later. (Table below)
Body version
Map version
Contents
Note
before Ver4.00
-
Modbus RTU is not available.
Ver4.00
01
The first release of the Modbus
RTU function.
[CAUTION]
In the old version, you can’t use features added in the new version.
In that case, there is a possibility that it does not work properly when reading / writing to
the address of the newly added function.
6. MODBUS RTU PROTOCOL - DATA TRANSMISSION
AND RECEPTION
6.1 Communication protocol
This equipment is compatible with Modbus RTU protocol.
Data format of the protocol is as below. It is composed of slave address, function code,
data, and CRC section.
Modbus RTU Data format
Slave address
(1byte)
Function code
(1byte)
Data
(variable)
CRC
(2byte)
6.2 Function codes
Function code that can be used in this equipment is as follows.
Code
Function
Maximum
data length
Modbus original function (reference)
03H
Setting data read
123 words
Data read from holding register
04H
Input data read
123 words
Data read from input register
06H
One-time setting data write
1 words
Data write to holding register
10H
Continuous setting data writes
123 words
Data write to holding register
6.3 Error response
In accordance with the communication protocol for the pertinent function code, if an error occurs during
command transmission, an error response is returned in the fixed format described in this section.
■ Example of slave response (function code = 06H, command error = 10H)
Configuration
Data length
Data
Slave address
1
-
Function code + 80H
1
86H
Error code
1
10H
Error check (Only for Modbus RTU)
2
CRC
Total number of bytes
5
-
●Error codes and their occurrence conditions.
Error
code
Description
Occurrence condition(s)
01H
Invalid function code
An unsupported function code is specified.
02H
Invalid register address
The relative address range exceeds "9999."
03H
Invalid number of registers
- The length of the accessed data is "0" or the sum of the relative
address and data length exceeds the limit.
- It is assumed that two or more function codes, each executable for
one area, are involved.
- Data longer than 2 words is specified for a one-time write command.
- The data length exceeds 123 words.
04H
Device error
The received data is shorter than the predefined data length.
10H
Command error
An attempt at a write over an area exceeding the writable range.
6.4 Reading of input register area
The input register area is a read-only area.
The current measured value and the current time are mapped. Specify the start
address (relative) and data count (assuming that one word is two bytes) of the data to be read.
6.4.1 Reading of input register area
Function code :04H
■ Example of master transmission (with a start address of 0032H and a data count of 2 words)
Component
Data
length
Data
Slave address
1
-
Function code
1
04H
Data
Relative start address (high-order)
1
00H
Relative start address (low-order)
1
32H
Read data count (high-order)
1
00H
Read data count (low-order)
1
02H
Error check
2
CRC (16 bits)
Total number of bytes
8
■ Example of slave response (with a start address of 0032H and a data count of 2 words)
Component
Data
length
Data
Slave address
1
-
Function code
1
04H
Data
Number of data bytes
1
04H
Data 1 (high-order)
1
00H
Data 1 (low-order)
1
09H
Data 2 (high-order)
1
00H
Data 2 (low-order)
1
0AH
Error check
2
CRC (16 bits)
Total number of bytes
9
6.4.2 Input Register Area Map
【Input Register Area Map】Function code: 04H
Address
Relative
address
(HEX)
Name
Array
Content
Remarks
30001
0
Model type(1/8)
1
ASCII
Multipoint type
:"MULTI"
30002
1
Model type(2/8)
2
Pen type
:"PEN"
30003
2
Model type(3/8)
3
After the blank
30004
3
Model type(4/8)
4
30005
4
Model type(5/8)
5
30006
5
Model type(6/8)
6
30007
6
Model type(7/8)
7
30008
7
Model type(8/8)
8
30009
8
Software version(1/16)
1
ASCII
Version information on a system.
30010
9
Software version(2/16)
2
30011
A
Software version(3/16)
3
30012
B
Software version(4/16)
4
30013
C
Software version(5/16)
5
30014
D
Software version(6/16)
6
30015
E
Software version(7/16)
7
30016
F
Software version(8/16)
8
30017
10
Software version(9/16)
9
30018
11
Software version(10/16)
10
30019
12
Software version(11/16)
11
30020
13
Software version(12/16)
12
30021
14
Software version(13/16)
13
30022
15
Software version(14/16)
14
30023
16
Software version(15/16)
15
30024
17
Software version(16/16)
16
30025
18
Modbus map version
1
Binary
30026
19
Reserve
30027
1A
Reserve
30028
1B
Reserve
30029
1C
Reserve
30030
1D
Reserve
30031
1E
Reserve
30032
1F
Reserve
30033
20
Reserve
30034
21
Reserve
30035
22
Reserve
30036
23
Reserve
30037
24
Reserve
30038
25
Reserve
30039
26
Reserve
30040
27
Reserve
30041
28
Reserve
30042
29
Reserve
30043
2A
Reserve
30044
2B
Reserve
30045
2C
Reserve
30046
2D
Reserve
30047
2E
Reserve
30048
2F
Reserve
30049
30
Reserve
Every second update
30052
33
Month
1~12
30053
34
Day
1~31
30054
35
Hour
0~24
30055
36
Minute
0~59
30056
37
Second
0~59
30057
38
Recording status
0~1
0:Recording not in progress
1:Recording in progress
30058
39
Chart sensor status
0~1
0:With chart
1:Without chart
30059
3A
Manual print status
0~1
0:Print stops
1:During printing
30060
3B
List print status
0~1
0:Print stops
1:During printing
30061
3C
Engineering
list print status
0~1
0:Print stops
1:During printing
30062
3D
Reserve
30100
63
Reserve
30101
64
Channel status
CH01
00bit:
Alarm 1 1= ON 0= OFF
01bit:
Alarm 2 1= ON 0= OFF
02bit:
Alarm 3 1= ON 0= OFF
03bit:
Alarm 4 1= ON 0= OFF
30102
65
CH02
30103
66
CH03
30104
67
CH04
30105
68
CH05
30106
69
CH06
30107
6A
Measurement data(BIN)
CH01
-32000~32000
Data of more than±32000,
the minus side will be 8181H,
the plus side will be 7E7EH.
30108
6B
CH02
30109
6C
CH03
30110
6D
CH04
30111
6E
CH05
30112
6F
CH06
30113
70
Decimal point position
CH01
0~4
30114
71
CH02
30115
72
CH03
30116
73
CH04
30117
74
CH05
30118
75
CH06
30119
76
Measurement data(Float)
CH01 Float (high-order 2 byte)
Float (low-order 2 byte)
30120
77
30121
78
CH02
30122
79
30123
7A
CH03
30124
7B
30125
7C
CH04
30126
7D
30127
7E
CH05
30128
7F
30129
80
CH06
30130
81
Unused or later.
39999
270E
6.5 Reading and writing of the holding register area
The holding register area is a read-write area. Parameter settings and the start and stop command of the
recording state are mapped. For read, specify the start address (relative) and data count (assuming that one
word is two bytes) of the data to be read. For write, specify the start address and the data to be written.
6.5.1 Reading of the holding register area
It is used when calling the parameters that are currently set.
Also, it cannot be read in the case of the operation command system. It becomes writing only.
Function code (Reading): 03H
■ Example of transmitting master (starting address=00C8H, data length=2words)
Component
Data
length
Data
Slave address
1
-
Function code
1
03H
Data
Relative start address (high-order)
1
00H
Relative start address (low-order)
1
C8H
Read data count (high-order)
1
00H
Read data count (low-order)
1
02H
Error check
2
CRC (16 bits)
Total number of bytes
8
■ Example of slave's responding (starting address=0032H, data length =2words)
Component
Data
length
Data
Slave address
1
-
Function code
1
03H
Data
Number of data bytes
1
04H
Data 1 (high-order)
1
00H
Data 1 (low-order)
1
05H
Data 2 (high-order)
1
00H
Data 2 (low-order)
1
00H
Error check
2
CRC (16 bits)
Total number of bytes
9
6.5.2 Writing of the holding register area (Single)
It is used when carrying out a set of command operations or parameters.
In the case of operation command, it will take effect immediately when you send.
In the case of parameter settings, it is reflected by sending a separate "settings save"
command (address 40104 (relative address 0067H)).
Function code(Writing): 06H
■ Example of transmitting master(starting address=00C8H, data =5)
Component
Data
length
Data
Slave address
1
-
Function code
1
06H
Data
Relative start address (high-order)
1
00H
Relative start address (low-order)
1
C8H
Write data (high-order)
1
00H
Write data (low-order)
1
05H
Error check
2
CRC (16 bits)
Total number of bytes
8
■ Example of slave's responding (starting address=00C8H, data =5)
Component
Data
length
Data
Slave address
1
-
Function code
1
06H
Data
Relative start address (high-order)
1
00H
Relative start address (low-order)
1
C8H
Write data (high-order)
1
00H
Write data (low-order)
1
05H
Error check
2
CRC (16 bits)
Total number of bytes
8
6.5.3 Writing of the holding register area (Continuation)
Time setting command and the like, and then used when the data needs to send in succession.
In the case of operation command, it will take effect immediately when you send.
In the case of parameter settings, it is reflected by sending a separate "settings save" command
(address 40104 (relative address 0067H)).
Corresponding to that memory map is part. Please refer to Section 6.5.4 for the area which is
corresponding.
Function code(Writing): 10H
■ Master transmission example (Start address =006EH, Number of data =7words
Data =AA01H,000FH,0001H,0002H,0017H,001EH,0000H)
( Clock set command January 2, 2015 23:30:00 )
Component
Data length
Data
Slave address
1
-
Function code
1
10H
Data
Relative start address (high-order)
1
00H
Relative start address (low-order)
1
6EH
Number
of
write
register
(high-order)
1
00H
Number of write register
(low-order)
1
07H
Cut the number of bytes
1
0EH
Write data 1 (high-order)
1
AAH
Write data 1 (low-order)
1
01H
Write data 2 (high-order)
1
00H
Write data 2 (low-order)
1
0FH
Write data 3 (high-order)
1
00H
Write data 3 (low-order)
1
01H
Write data 4 (high-order)
1
00H
Write data 4 (low-order)
1
02H
Write data 5 (high-order)
1
00H
Write data 5 (low-order)
1
17H
Write data 6 (high-order)
1
00H
Write data 6 (low-order)
1
1EH
Write data 7 (high-order)
1
00H
Write data 7 (low-order)
1
00H
Error check
2
CRC(16bit)
Total number of bytes
23
-
■ Slave response example(Response of Start address =006EH, Number of data =7words)
Component
Data length
Data
Slave address
1
-
Function code
1
10H
Data
Relative start address (high-order)
1
00H
Relative start address (low-order)
1
6EH
Number
of
write
register
(high-order)
1
00H
Number of write register
(low-order)
1
07H
Error check
2
CRC(16bit)
Total number of bytes
8
-
6.5.4 Holding register area map
【Holding register area map】Function Code:03H(Reading),06H(Writing),10H(Continuous writing)
Address
Relative
address
(HEX)
Name
Array
Content
Remarks
40001
0
Reserve
Unused
…
40100
63
Reserve
Operation command
40101
64
Recording start / stop
AA01:Start
AA00:Stop
Invalid except left.
The disabled in selecting DI.
40102
65
Reserve
40103
66
Reserve
40104
67
Save the settings
AA01:Save
Invalid except left.
40105
68
Manual print
AA01:Start
AA00:Stop
40106
69
LIST print
40107
6A
ELIST print
40108
6B
Comments 1 print
AA01:Sync
AA02:Async
40109
6C
Comments 2 print
40110
6D
Comments 3 print
40111
6E
Clock set
AA01:Run
AA01 ignored except
7 words continuous writing only
valid
Clock sets in the received values.
When isn’t time has come ignored
(month = 0, etc.).
40112
6F
Year(00~99)' 2 digits
40113
70
Month(01~12)
40114
71
Day(01~31)
40115
72
Time(00~23)
40116
73
Minute(00~59)
40117
74
Second(00~59)
40118
75
Reserve
40119
76
Reserve
40120
77
Reserve
40121
78
Communication
printing
set
AA01:Sync
AA02:Async
AA01 and AA02 ignored except
Multipoint type:3~26 words
Pen type:3~13 words
Continuous writing only valid
40122
79
Printing color
0~5
Pen type recorder is invalid.
40123
7A
Printing character (01/24)
ASCII
Multipoint type:0~47 character
40124
7B
Printing character (02/)
Pen type:0~21 character
40125
7C
Printing character (03/)
40126
7D
Printing character (04/)
40127
7E
Printing character (05/)
40128
7F
Printing character (06/)
40129
80
Printing character (07/)
40130
81
Printing character (08/)
40131
82
Printing character (09/)
40132
83
Printing character (10/)
40133
84
Printing character (11/)
40134
85
Printing character (12/)
40135
86
Printing character (13/)
40136
87
Printing character (14/)
40137
88
Printing character (15/)
40138
89
Printing character (16/)
40139
8A
Printing character (17/)
【Holding register area map】Function Code:03H(Reading),06H(Writing),10H(Continuous writing)
Address
Relative
address
(HEX)
Name
Array
Content
Remarks
40140
8B
Printing character (18/)
40141
8C
Printing character (19/)
40142
8D
Printing character (20/)
40143
8E
Printing character (21/)
40144
8F
Printing character (22/)
40145
90
Printing character (23/)
40146
91
Printing character(24/24)
40147
92
Reserve
…
40200
C7
Reserve
Setup mode parameters(channel)
40201
C8
Mode
CH1
0~6 , 8 ( 7: Error )
※
( 1)Mode
40202
C9
Input type
0~34
※
( 2)Range code
40203
CA
Reference channel
0~4
CH1 configurable value:
None(Setting disable)
CH2 configurable value:0
CH3 configurable value:0~1
CH4 configurable value:0~2
CH5 configurable value:0~3
CH6 configurable value:0~4
40204
CB
Measurement range (L)
depends on the range
※
( 2) Measurement range
40205
CC
Measurement range (H)
depends on the range
※
( 2) Measurement range
40206
CD
Scaling range (L)
-32000~32000
※
( 3) Depends on the Scaling
40207
CE
Scaling range (H)
-32000~32000
※
( 3) Depends on the Scaling
40208
CF
Decimal point position
0~4
Only when a Scaling is “ON”, this
setting is enable.
40209
D0
Unit (1/3)
ASCII
Units at the time of
the scaling "ON" (Note.1)
40210
D1
Unit (2/3)
40211
D2
Unit (3/3)
40212
D3
Reserve
40213
D4
Tag (1/4)
ASCII
Multipoint type:7 character
Pen type:5 character
40214
D5
Tag (2/4)
40215
D6
Tag (3/4)
40216
D7
Tag (4/4)
40217
D8
Digital print ON/OFF
0~1
0:OFF
1:ON
40218
D9
Partial compression /
expansion ON/OFF
0~1
0:OFF
1:ON
40219
DA
Zone L
0~99
40220
DB
Zone H
1~100
40221
DC
Partial
compression
boundary point position.
1~99
40222
DD
Partial
compression
boundary
point
measurements.
depends on the range
Scaling "ON":Depends on the scaling
Other : measurement range.
※
( 3) Scaling dependent
(Note 1) The setting of the unit is enabled, the range setting is only case of "SCALE","SQRT","DECAD",
"DELT","SIGM","MEAN".
(However, "DELT" "SIGM" "MEAN" is valid only when the range setting of the reference channel is "SCALE".)
Otherwise the range setting, the unit is automatically determined according to the range.
【Holding register area map】Function Code:03H(Reading),06H(Writing),10H(Continuous writing)
Address
Relative
address
(HEX)
Name
Array
Content
Remarks
40223
DE
Alarm 1 action ON/OFF
CH1
0~1
0:OFF
1:ON
40224
DF
Alarm 1 type
0~1
0:H
1:L
40225
E0
Alarm 1 Set value
-32000~32000
※
( 3) Depends on the Scaling
40226
E1
Alarm
1
RLY
output
ON/OFF
0~1
0:OFF
1:ON
40227
E2
Alarm 1 DO No.
0~5
Multipoint type:0~ 5(RLY1~RLY6)
Pen type:0~ 2 (RLY1~RLY3)
40228
E3
Alarm 2 action ON/OFF
0~1
0:OFF
1:ON
40229
E4
Alarm 2 type
0~1
0:H
1:L
40230
E5
Alarm 2 Set value
-32000~32000
※
( 3) Depends on the Scaling
40231
E6
Alarm
2
RLY
output
ON/OFF
0~1
0:OFF
1:ON
40232
E7
Alarm 2 DO No.
0~5
Multipoint type:0~ 5(RLY1~RLY6)
Pen type:0~ 2 (RLY1~RLY3)
40233
E8
Alarm 3 action ON/OFF
0~1
0:OFF
1:ON
40234
E9
Alarm 3 type
0~1
0:H
1:L
40235
EA
Alarm 3 Set value
-32000~32000
※
( 3) Depends on the Scaling
40236
EB
Alarm
3
RLY
output
ON/OFF
0~1
0:OFF
1:ON
40237
EC
Alarm 3 DO No.
0~5
Multipoint type:0~ 5(RLY1~RLY6)
Pen type:0~ 2 (RLY1~RLY3)
40238
ED
Alarm 4 action ON/OFF
0~1
0:OFF
1:ON
40239
EE
Alarm 4 type
0~1
0:H
1:L
40240
EF
Alarm 4 Set value
-32000~32000
※
( 3) Depends on the Scaling
40241
F0
Alarm
4
RLY
output
ON/OFF
0~1
0:OFF
1:ON
40242
F1
Alarm 4 DO No.
0~5
Multipoint type:0~ 5(RLY1~RLY6)
Pen type:0~ 2 (RLY1~RLY3)
40243
F2
Reserve
・・・
40250
F9
Reserve
40251
FA
Scaling range (L)
(float)
2 words continuous writing only
40252
FB
※
is valid. ( 4)float Format
40253
FC
Scaling range (H)
(float)
2 words continuous writing only
40254
FD
is valid. ※
( 4)float Format
40255
FE
Alarm1 set value (float)
2 words continuous writing only
40256
FF
Alarm1 set value (float)
※
is valid. ( 4)float Format
40257
100
Alarm2 set value (float)
2 words continuous writing only
40258
101
Alarm2 set value (float)
※
is valid. ( 4)float Format
40259
102
Alarm3 set value (float)
2 words continuous writing only
40260
103
Alarm3 set value (float)
※
is valid. ( 4)float Format
40261
104
Alarm4 set value (float)
2 words continuous writing only
40262
105
Alarm4 set value (float)
※
is valid. ( 4)float Format
【Holding register area map】Function Code:03H(Reading),06H(Writing),10H(Continuous writing)
Address
Relative
address
(HEX)
Name
Array
Content
Remarks
40263
106
Reserve
CH01
…
40300
12B
Reserve
40301
12C
Mode
CH02
Input channel
…
40400
18F
Reserve
40401
190
Mode
CH03
Input channel
…
40500
1F3
Reserve
40501
1F4
Mode
CH04
Input channel
…
40600
257
Reserve
40601
258
Mode
CH05
Input channel
…
40700
2BB
Reserve
40701
2BC
Mode
CH06
Input channel
…
40800
31F
Reserve
Setup mode parameters(Other)
40801
320
Recording
paper
feed
speed (1st)
Multipoint:0~33
※
( 5)
Recording
paper
feed
speed
40802
321
Recording
paper
feed
speed (2nd)
Pen type:0~40
40803
322
Recording period
0~3
(Multipoint Type only)
0:10sec
1:20sec
2:30sec
3:60sec
40804
323
Reserve
40805
324
Comment (1/8)
Cmt1
ASCII
Multipoint type:0~8 Words
Pen type:0~6 Words
40806
325
Comment (2/8)
40807
326
Comment (3/8)
40808
327
Comment (4/8)
40809
328
Comment (5/8)
40810
329
Comment (6/8)
40811
32A
Comment (7/8)
40812
32B
Comment (8/8)
40813
32C
Reserve
40814
32D
Reserve
40815
32E
Comment (1/8)
Cmt2
ASCII
Multipoint type:0~8 Words
Pen type:0~6 Words
40816
32F
Comment (2/8)
40817
330
Comment (3/8)
40818
331
Comment (4/8)
40819
332
Comment (5/8)
40820
333
Comment (6/8)
40821
334
Comment (7/8)
40822
335
Comment (8/8)
40823
336
Reserve
40824
337
Reserve
【Holding register area map】Function Code:03H(Reading),06H(Writing),10H(Continuous writing)
Address
Relative
address
(HEX)
Name
Array
Content
Remarks
40825
338
Comment (1/8)
Cmt3
ASCII
Multipoint type:0~8 Words
Pen type:0~6 Words
40826
339
Comment (2/8)
40827
33A
Comment (3/8)
40828
33B
Comment (4/8)
40829
33C
Comment (5/8)
40830
33D
Comment (6/8)
40831
33E
Comment (7/8)
40832
33F
Comment (8/8)
…
40900
383
Reserve
Engineering parameters
40901
384
Burnout
CH1
0~1
0:OFF 1:ON
40902
385
Offset
±32000
40903
386
Offset DP
0~4
40904
387
RJC setting
0~2
0:INT
1:EXT
2:CH
40905
388
RJC EXT fixed value
-32000~32000
Uv
40906
389
RJC CH destination
Multipoint type
:0~5
Pen type:0~1
40907
38A
Printing color
0~5
(Multipoint type only)
※
( 6)Printing color
40908
38B
Digital filter
0~10000
(Pen type only)
Decimal point:4-digit fixed
40909
38C
Reserve
40910
38D
Reserve
40911
38E
Burnout
CH2
Same as CH1
…
40920
397
Reserve
40921
398
Burnout
CH3
Same as CH1
…
40930
3A1
Reserve
40931
3A2
Burnout
CH4
Same as CH1
…
40940
3AB
Reserve
40941
3AC
Burnout
CH5
Same as CH1
…
40950
3B5
Reserve
40951
3B6
Burnout
CH6
Same as CH1
…
40960
3BF
Reserve
40961
3C0
Hysteresis setting
0~1
0:OFF
1:ON
40962
3C1
Alarm printing function
0~2
0:OFF
1:Alarm printing 1
2:Alarm printing 2
40963
3C2
RUN trigger setting
0~1
0:INT
1:EXT
40964
3C3
CH
/
TAG
printing
switching
0~1
0:CH
1:TAG
【Holding register area map】Function Code:03H(Reading),06H(Writing),10H(Continuous writing)
Address
Relative
address
(HEX)
Name
Array
Content
Remarks
40965
3C4
Logging print ON/OFF
0~1
0:OFF
1:ON
40966
3C5
Logging print interval
0~11
※
( 7) Logging print interval
40967
3C6
Logging print reference
time
0~23
Unit:Hour
40968
3C7
Logging
print
criteria
minute
0~59
Unit:Minute
40969
3C8
Logging
print
Sync/Async
0~1
0:Sync
1:Async
40970
3C9
Record
start/end
print
presence or absence
0~2
0:OFF
1:Sync
2:Async
40971
3CA
Host address
1~32
40972
3CB
Communication speed
(Note.1)
0~5
0:1200 bps
1:2400 bps
2:4800 bps
3:9600 bps
4:19200 bps
5:38400 bps
40973
3CC
Data length
(Note.2)
0~1
0:7bit
1:8bit
40974
3CD
Parity
(Note.2)
0~2
0:Even
1:Odd
2:OFF
40975
3CE
Stop bit
(Note.2)
0~1
0:1bit
1:2bit
40976
3CF
Communication protocol
0~1
0:Original
1:Modbus RTU
40977
3D0
Logging
print
scale
presence or absence
0~1
(Multipoint type only)
0:OFF
1:ON
40978
3D1
Printing gap setting
0~1
(Pen type only)
0:OFF
1:ON
40979
3D2
DI1 function
0~12
※
( 8)DI function
Can’t select the same function in
DI1,2,3.
40980
3D3
DI2 function
0~12
※
( 8)DI function
40981
3D4
DI3 function
0~12
※
( 8)DI function
40982
3D5
Reserve
Unused later
…
49999
270E
Reserve
6.5.5 Holding register area setting range detail
Setting range of register on the map written in the ※are listed below.
※1 Mode
Value
Content
Remarks
0
Scaling OFF
1
Scaling ON
2
Square root
calculation (SQRT)
It can be set only when the range code is 0 to 7 (voltage current range).
3
exponent display
(DECAD)
It can be set only when the range code is 0 to 7 (voltage current range).
4
Difference
calculation (DELT)
Change of input width after calculation, please change by entering a
value in the "measurement range".
5
Sum calculation
(SIGM)
Change of input width after calculation, please change by entering a
value in the "measurement range".
6
Average
calculation (MEAN)
Change of input width after calculation, please change by entering a
value in the "measurement range".
7
Disable
If you select this, it will result in an error.
8
Skip
※2 Range code, Measurement range.
Code
Input type
※
Measurement range
0
DC voltage
±10mV
(-10.00 to 10.00)
1
0-20mv
(0.00 to 20.00)
2
0-50mV
(0.00 to 50.00)
3
±200.0mV
(-200.0 to 200.0)
4
±1V
(-1.000 to 1.000)
5
0-5V
(-0.000 to 5.000)
6
±10V
(-10.00 to 10.00)
7
DC current
4-20mA
(4.00 to 20.00)
8
TC
(Unit: ℃)
(Au-Fe is K)
B
(0.0 to 1820.0)
9
R1
(0.0 to 1760.0)
10
R2
(0.0 to 1200.0)
11
S
(0.0 to 1760.0)
12
K1
(-200.0 to 1370.0)
13
K2
(-200.0 to 600.0)
14
K3
(-200.0 to 300.0)
15
E1
(-200.0 to 800.0)
16
E2
(-200.0 to 300.0)
17
E3
(-200.0 to 150.0)
18
J1
(-200.0 to 1100.0)
19
J2
(-200.0 to 400.0)
20
J3
(-200.0 to 200.0)
21
T1
(-200.0 to 400.0)
22
T2
(-200.0 to 400.0)
23
C
(0.0 to 2320.0)
24
Au-Fe
(1.0 to 300.0)
25
N
(0.0 to 1300.0)
26
PR40-20
(0.0 to 1880.0)
27
PL2
(0.0 to 1390.0)
28
U
(-200.0 to 400.0)
29
L
(-200.0 to 900.0)
30
RTD
(Unit: ℃)
Pt100-1
(-200.0 to 650.0)
31
Pt100-2
(-200.0 to 200.0)
32
JPt100-1
(-200.0 to 630.0)
33
JPt100-2
(-200.0 to 200.0)
※3 Depends on the Scaling
Scaling range, the alarm set value, partial compression boundary point measurement is depends on
the holding register address 40201 "mode" and 40208 "decimal point position".
The set value is reflected in the form that is dependent on the "decimal point position" if the mode is
scaling ON ( “SCALE” and “SQRT” ). In the case of OFF will reflect decimal point position of
the range.
Example 1: "Scaling range (L)" set to 123.45 at Scaling "ON".
Holding register address "40208 (decimal point position)" : Set the value to 2.
Holding register address "40206(scaling range (L))" : Set the value to 12345.
Example 2: "Alarm 1 Set value" set to 12.3 at Scaling "OFF" (In the case of range code 4 selection).
(Range code 4 ±1V(Measurement range:-1.000~1.000))
Holding register address "40224(Alarm 1 Set value)" : Set the value to 12300.
※4
float(Floating point)
Floating-point notation in IEEE-compliant.
※5
Chart speed
There is a difference in the contents of the numbers in Multipoint type and Pen type.
[Multipoint type]
Value
Speed
(mm/h)
Value
Speed
(mm/h)
Value
Speed
(mm/h)
Value
Speed
(mm/h)
0
0
10
30
20
160
30
750
1
1
11
40
21
180
31
900
2
2
12
50
22
200
32
1,200
3
3
13
60
23
240
33
1,500
4
4
14
75
24
300
5
5
15
80
25
360
6
10
16
90
26
375
7
15
17
100
27
450
8
20
18
120
28
600
9
25
19
150
29
720
[Pen type]
Value
Speed
(mm/h)
Value
Speed
(mm/h)
Value
Speed
(mm/h)
Value
Speed
(mm/h)
Value
Speed
(mm/h)
0
5
10
80
20
360
30
2,400
40
12,000
1
10
11
90
21
375
31
3,000
2
15
12
100
22
450
32
3,600
3
20
13
120
23
600
33
4,500
4
25
14
150
24
720
34
4,800
5
30
15
160
25
750
35
5,400
6
40
16
180
26
900
36
6,000
7
50
17
200
27
1200
37
7,200
8
60
18
240
28
1500
38
9,000
9
75
19
300
29
1800
39
10,800
※6 Printing color
Value
Content
Remarks
0
Purple
1
Red
2
Green
3
Blue
4
Brown
5
Black
※7 Logging print interval
Value
Content
Remarks
0
10min
1
15min
2
20min
3
30min
4
1H
5
2H
6
3H
7
4H
8
6H
9
8H
10
12H
11
24H
※8 DI function
Value
Content
Remarks
0
OFF(No function)
1
RCD(Recording Start/Stop)
ON:RUN OFF:STOP
2
SPEED(Chart speed change)
ON:Spd-1 OFF:Spd-2
3
CMNT1(Comment print (Sync))
ON Rising:Start
4
CMNT2(Comment print (Sync))
5
CMNT3(Comment print (Sync))
6
MAN-P(Manual print (Sync))
7
TIM-P(Time print(Sync))
8
A.CMT1(Comment print (Async))
9
A.CMT2(Comment print (Async))
10
A.CMT3(Comment print (Async))
11
AMAN.P(Manual print (Async))
12
ATIM.P(Time print (Async))