ABB EXCOUNT-II Operation & User’s Manual

Text of the manual

2501en EXCOUNT-II Users Manual

Legal disclaimer Any responsibility or liability for loss or damage in connection with the use of this product and the accompanying documentation is disclaimed. The information in this document is furnished for informational use only, is subject to change without notice, may contain errors or inaccuracies, and represents no commitment whatsoever. Federal Communications Commission Statement This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interfe- rence that may cause undesired operation. WARNING! Any changes or modifications to this product not expressly approved by the manufacturer could void any assurances of safety or performance and could result in violation of Part 15 of the FCC Rules. Trademark acknowledgements Windows 95, 98, ME, NT4 and 2000 are registred trademarks of Microsoft Corporation. Safety instructions Do not connect the Transceiver to other voltage sources than a standard 9 volt battery type 6LR61/PP3 Ensure that the battery is connected correctly. The Transceiver contains a radio transmitter and receiver which must not be used where the use of radio transmitters or other electronic devices is prohibited. WARNING! All work related to the EXCOUNT-II´s sensors and the surge arresters shall be made with disconnected and earthed conductors. Follow all regulations and rules stated by international or national safety regula- tions. Normally, the EXCOUNT-II´s sensors and the surge arresters operate at a high voltage. Therefore they must be installed in such a way that only qualified personnel has access to them.

2501en EXCOUNT-II Users Manual

EXCOUNT-II is an advanced surge arrester monitor for effectively, reliably and safety monitoring and recording surges on high voltage electrical networks. EXCOUNT-II incorporates a sensor, which is mounted on the surge arrester, a transceiver, for remote reading and a PC-program (Windows 95/98/2000/ME and NT). This users manual desribes the functions of EXCOUNT-II to give you total control over surge monitoring. Table of contents 1. Using the transceiver Description of the buttons 4 Normal maintenance 4 2. Getting started First time usage 5 Installation/uninstallation of software 5 Administration of sensors 6 3. Flowchart, make measurements 7 4. Transceiver symbols 8 5. Transceiver menu system 9 6. Transceiver error codes 14 8. Sensor installation 16 9. More information 19 Introduction

2501en EXCOUNT-II Users Manual

Enter Increase value Display screen Decrease value Move down Move up Go back NOTE! To turn on the transceiver press To turn off the transceiver press Normal maintenance To achieve the best possible lifetime out of your EXCOUNT-II Transceiver, avoid exposure to strong sunlight for extended periods, hot temperatures (over +50 º C), cold temperatures (under -10 º C ) and water (the design is showerproof but not watertight). To clean the transceiver use only a damp soft cloth with a mild detergent. Using the transceiver

2501en EXCOUNT-II Users Manual

Getting started First time usage Open the package and verify that the following items are present together with this manual: Transceiver Data cable (RS232) CD with software Familiarize yourself with the above safety instructions. Fit a new 9 volt battery type 6LR61/PP3. Press the button on the front panel and verify that the transceiver powers up and that the stand-by menu appears. Press the button and verify that the transceiver powers down. Using this manual together with the transceiver and familiarize yourself with the different menus and how they are used. Particulary ensure that the date and clock on the Transceiver are set correctly. Load the EXCOUNT-II software onto your PC and famliarize yourself with its use by reading the individual HELP files within each respective section. Installation/unistallation of software Installation of software Insert the CD into your computer. Press the START button in lower left corner Select SETTINGS then CONTROL PANEL Double-click on the icon ADD/REMOVE PROGRAMS Select ADD NEW PROGRAMS Follow the instructions on the screen Uninstalling of software Press the START button in lower left corner Select SETTINGS then CONTROL PANEL Double-click on the icon ADD/REMOVE PROGRAMS Browse to the EXCOUNT-II software and click REMOVE

2501en EXCOUNT-II Users Manual

Administration of Sensors Fit the sensor to the arrester as described in the installation instructions supplied with it. Record the following details as specified in the EXCOUNT-II HELP system for administration: station data arrester data EXCOUNT-II data Input this data into the software as described in the HELP system. IMPORTANT! After installation of a new sensor and input of the adminis- tration details, an initial reading must always be made to establish a link between the administration details in the PC software and the sensor on site. Connect the transceiver to the PC via the data cable Download the sensor’s ID from the EXCOUNT-II software into the Transcei- ver. IMPORTANT! Check that the date and time on the Transceiver are correct, otherwise set them as described in this manual. Note! If this is not done the date stamp from the sensor will be incorrect. Before going to site, check the Transceiver’s battery status. If necessary, install a new battery. Once at site, individually check that it is possible to make contact with each sensor. This is most easily done by taking a leakage current mea- surement as described in this manual. If the sensor is not connected properly, an error code will be displayed on the Transceiver. If desired, a full set of measurements can be made for reference and then transferred to the PC software as described in the HELP system for Transfer data. Getting started

2501en EXCOUNT-II Users Manual

Flowchart, make measurements The main menu is accessed by pressing enter Press to turn on the transceiver 1. Prepare the transceiver for measurements See 1.1.1 Set the transceiver to "Prepare the transceiver for measurements" mode. Connect the transceiver to the PC via the data cable. Select which Sensors are to be read by station, position and phase. Select Sensor ID from the menu in the transceiver and press enter. Different types of measurements can be performed by following the instructions in 1.3. Click "Send list to transceiver" when ready. This erases all stored data in the transceiver. 2. Make measurements See 1.3 3. Transmit data to the EXCOUNT-II software See 1.1.2 Set the transceiver to "Data transfer from Transceiver to PC" mode. Connect the transceiver to the PC via the data cable Open the EXCOUNT-II PC software and select "Transfer data" followed by "Receive measured data from transceiver". Click "Request data" when ready. Click "save" to store the details in the database. Before going to the site check the battery status. See 1.2. Then turn off the transceiver to save the batteries. Ensure the sensor to be read is within the range for transmission (normally up to 60 m). Set the transceiver to "Make measurements" mode. Select type of measurement by following the instructions in 1.3. Open the EXCOUNT-II PC- software and select "Transfer data" followed by "Prepare transceiver for measurement".

2501en EXCOUNT-II Users Manual

Transceiver menu system ABB 2.0.0 E Stand-by Turn the transceiver on by pressing Turn the transceiver off by pressing Got to the main menu by pressing The transceiver turns itself off automatically after 5 minutes. The program version is shown in the lower left corner. The E stands for extended version which includes resistive leakage current measurement. 1. Main menu Select alternative with the key. Then press the Transfer data (see 1.1) Battery check (see 1.2) Make measurements (see 1.3) Set clock and date (see 1.4) Back to stand-by 1.1 Transfer data Select alternative with the key. Then press the Data transfer from PC to Transceiver (see 1.1.1) Data transfer from Transceiver to PC (see 1.1.2) Back to main menu

2501en EXCOUNT-II Users Manual

� 1.1.1 Data transfer from PC to Transceiver In this mode, Sensor ID’s can be transfered from the PC to the transceiver. Connect the data cable to the PC serial port. PC Serial port Com 1 is selected as default by the software. See also the software help instructions. Back to transfer data menu Transceiver menu system � 1.1.2 Data transfer from Transceiver to PC In this mode data collected from the Sensors can be transmitted to the PC. Connect the data cable to the PC serial port. PC Serial port Com 1 is selected as default. See also the software help instructions. Back to transfer data menu 0 %� � � 100% 1.2 Battery check Displays the condition of the battery. Always check the condition of the battery before transfering data to/from the transceiver. Change battery if necessary. If the battery expires during a measurement session,data can be corrupted or lost. In such case download the sensor ID’s again and take new readings. NOTE! Whenever the battery is replaced the transcei- ver clock and date must be reset. (see 1.4) Back to main menu

2501en EXCOUNT-II Users Manual

Σ A A 1.3 Make measurements Select alternative with the key. Then press the Leakage current measurement (see 1.3.1) Read surge counter data (see 1.3.2) Resistive leakage current measurement (see 1.3.3) Full measurement (all of the above) Back to main meny Transceiver menu system � 1.3.1 Leakage current measurement Select sensor ID to read data from with the Start the reading by pressing A successful transmission is marked with A failed transmission is marked with If the transmission was unsuccessful, an error code will be displayed. Back to read data menu Progress bar Error code 1.3.2 Read surge counter data Select sensor ID to read data from with the key. Start the reading by pressing A successful transmission is marked with A failed transmission is marked with If the transmission was unsuccessful, an error code will be displayed. Back to read data menu � Progress bar Error code

2501en EXCOUNT-II Users Manual

Transceiver menu system � 1.3.3 Resistive leakage current measurement *) Select sensor ID to read data from with the key. Start the reading by pressing Before the transmission begins the operating voltage must be given. (see 1.3.3.1) A successful transmission is marked with A failed transmission is marked with If the transmission was unsuccessful, an error code will be displayed. Back to read data menu *) Not available in all versions. Progress bar Error code 1.3.3.1 Operating voltage *) The actual operating voltage must be given when measuring the resistive leakage current. The system voltage is displayed as a default value. Adjust the value to the actual value with and keys. Enter the correct value by pressing NOTE! If the system is 3-phase, the value should be the actual phase-phase voltage. Otherwise, for 1-phase systems, the value should be the phase- ground voltage. The progress bar will indicate that the transmission has begun. *) Not available in all versions.

2501en EXCOUNT-II Users Manual

Transceiver menu system 1.3.4 Total reading *) Select sensor ID to read data from with the key. Start the reading by pressing Before the transmission begins, the operating voltage must be given. (see 1.3.3.1) Each reading is made in turn automatically. A successful transmission is marked with A failed transmission is marked with If the transmission was unsuccessful, an error code will be displayed If any reading is unsuccessfull press key again to repeat the reading. Back to total reading menu *) Not available in all versions. � � 1.4 Set clock and date The cursor highlights which digit to adjust. The cursor is moved to the next digit by pressing the key. Each digit is changed by using the and keys. After changing any digit the status symbol is changed to X . When the correct date and clock is set move the cursor to the X and enter the value by pressing This changes the status symbol to

2501en EXCOUNT-II Users Manual

Transceiver error codes Error code 01 11 21 31 32 41 42 51 52 Description System error Prohibited action Checksum error EEPROM data read error EEPROM data write error Low temperature High temperature Too low field probe current Too high field probe current Suggested cause and action Turn off the transceiver and re-start. If the error persists, a serious internal fault has occurred with the Transceiver. Contact your EXCOUNT-II service representative. The user has attempted to do something which is prohibited. An error occurred in the data transmission and the data has been lost or corrupted. Interference from a nearby cellular/mobile phone can be a likely cause. Try to re-transmit the data. The transceiver could not read from the internal EEPROM memory. Turn off the transceiver and re-start. If the error persists, contact your EXCOUNT-II service representative. The transceiver could not write to the internal EEPROM memory. Turn off the transceiver and re-start. If the error persists, contact your EXCOUNT-II service representative. The ambient temperature is lower than defined in the data- base for resistive current measurements. (Lowest defined temperature is -10 º C). Take new measurements at another time. The ambient temperature is higher than defined in the data- base for resistive current measurements. (Highest defined temperature is +60 º C). Take new measurements at another time. The system voltage is too low to generate sufficient current in the field probe in the sensor. Check that the line is correctly energised. The system voltage is too high. Check that the line is cor- rectly energised.

2501en EXCOUNT-II Users Manual

Transceiver error codes Suggested cause and action The measured leakage current is too low. Check that the line is correctly energised. The measured leakage current is too high. Check that the line is correctly energised. If so, try taking another measurement. If the error persits, the arrester may be suspect. A stable value for the leakage current cannot be measured. A likley cause may be an unstable line voltage. Take new measurements at another time. The sensor ID was not recognised by any locally present sensor. Try retransmitting again. If contact still cannot be established, check: a) the chosen sensor ID is present at this station b) the distance to the sensor is not too far (max 60 m, but can depend on interference from buildings and structures) c) interference from a cellular/mobile phone d) battery status to ensure the voltage in the transceiver battery is not too low Turn off the transceiver and re-start. If the error persists, a serious internal fault has occurred with the Transceiver. Contact your EXCOUNT-II service representative. The sensor recognised it’s ID but the connection was lost during the transmission. Try re-transmiting again. If the error persists, check: a) the distance to the sensor is not too far (max 60m, but can depend on interference from buildings and structures). b) interference from a cellular/mobile phone. c) battery status to ensure the voltage in the transceiver battery is not too low. Description Low leakage current High leakage current Unstable leakage current Sensor not found Transmission buffer error Connection lost Error code 61 62 70 80 81 82

2501en EXCOUNT-II Users Manual

Sensor installation 1 Screws, nuts, sockets, washers and conductors are not supplied by ABB unless specified. Mount EXCOUNT-II (3) on surge arrester´s bottom flange (4) above insula- ting base (5) according to figure 1 and 2. Do not place close to venting duct (if any). Bolt joint (1 and 2) is supplied with ABB insulating base (5). Fittiing and tightening torque according to instructions supplied with insulating base.

2501en EXCOUNT-II Users Manual

Sensor installation 2 EXCOUNT-II is used as earth connection. Connect earth cable with tinplated socket (7) according to figure 2. Recommended screw: M12 (6) Tightening torque for M12: 84 Nm, use washers Top view Side view

2501en EXCOUNT-II Users Manual

Sensor installation Mounting for special applications NOTE! Resistive current measurement is not supported with this special application. Mount EXCOUNT-II against planar surface. Use 2 X M6 bolts. Connect upper terminal to flange, bottom terminal to earth via conductor. Recommended screw: M12. Do not mount on earthed plate. Back view Side view Front view Antenna area, min distance to groundplane: 60 mm Planar surface Connect to earth terminal on surge arrester flange Connect to earth Min 60 mm to ground plane

2501en EXCOUNT-II Users Manual

More information For more information about EXCOUNT-II and for downloading updates of the EXCOUNT-II software, please visit: http://www.abb.com/arrestersonline Select HIGH VOLTAGE SURGE ARRESTERS (HV) Select EXCOUNT-II

2501en EXCOUNT-II Users Manual

PTHVP/A 2501 en, Edition 1 02-02 ABB Power Technology Products AB High Voltage Products Surge Arresters SE-771 80 LUDVIKA, Sweden Tel. +46 (0)240 78 20 00 Fax. +46 (0)240 179 83 E-mail: [email protected] Internet: http://www.abb.com/arrestersonline