Insert media to start the archiving process automatically
• Select the Channel Source
• Set the Input Filter Type: Instantanteous or Max.
and Min. Values during the sample interval.
• Select the input type, linearizer, ranges and
tag name
• Select the Alarm type, set the alarm trip points,
the tag and the hysteresis.
• Set the Count Rate, Preset & Predetermined
Count values
Channel n.n
Channels 1.1 - 1.6
Set Up
Analog I/P
Totalizer
Alarm A
Alarm B
Time
Common
Chart
Digital
Bar
Process
• Set the Mains Rejection Frequency
• Select the Relay Source and the Relay
Polarity
• Select the Analog Output Source & Ranges
• Select the Digital Output Sources & Polarity
I/O Modules
Note. Modules fitted are
detected automatically
A:Analog I/P
B:Relay
C:Hybrid
I/O Modules
.cfg
Save as Current Configuration
Save Configuration
Cancel
Exit
.cfg
Internal Storage
External Storage
Archive
• Set the Archive File Enables
– i.e. the files to be archived
• Set the Filename Tag
• Set the New File Interval
(hourly, monthly or none)
Connection
Details
SM1000 – QUICK START GUIDE
Configuration
Operator 1
Operator 2
Operator 3
Operator 4
User 1
Use the up and down keys to select your password.
Confirm with Enter key
0000
User 1
Edit Current Configuration
Open Configuration
New Configuration
Cancel
Disable Recording in Configuration
Main
Configuration
Menu
QuickStart
Template
Summary
Channels 1.1 to 1.6
QSMilliAmp
4 to 20mA inputs,
0 to 100.0 units
QSTHC_C
or QSTHC_F
Thermocouple type K
0 to 1000°C or 0 to 1000°F
QSRTD_C
or QSRTD_F
Pt100 inputs
0 to 1000°C or 0 to 1000°F
QSFlow
4 to 20mA, 0 to 180 l/hr,
Totalizer enabled
QSDairy
Delayed High/Low Process Alarm
Engineering Range –10 to 90°C
Configuration File
Common
Group 1
Channels 1.1 - 1.6
Group 2
Channels 2.1 - 2.6
Functions
I/O Modules
Exit
Chart speed
Sample Rate
On board storage
10 mm/h
60s
12 months
20 mm/h
30s
6 months
6
60 mm/h
10s
2 months
Channels
120 mm/h
5s
30 days
Enabled
240 mm/h
2s
14 days
720 mm/h
1s
6 days
Group 1
Recording
4
Set the Sample Rate
5
Select the Views Required
and the Operator Menu Choices
6
Set Up the Archive Files
7
Change the Channel Configurations
1
Make Connections
& Power-up the
Instrument
2
Select the Configuration Level
and a Quick Start Template
3
Set the Time and Date
8
Set Up I/O
9
Exit Configuration and Save Changes
10
Start Recording!
Note. For
detailed
information
on
setting
all
configuration parameters, refer to the SM1000 User
Guide, part number IM/SM1000.
Group 1 Channels and Group 2 Channels
I/O Modules
Functions
Set Up
• Source ID
• Input Filter Type
• Recording Enable
Analog I/P
• Input Type
• Tags, Units & Values
• Linearizer
• Fault Detection
Digital I/P
• ON Tag
• OFF Tag
Alarm A
• Type, Source, Tag,
• Trip Level
Alarm B
• Hysterisis
• Alarm Groups
Totalizer
• Source
• Count Rate, Cut-off, Direction
• Tag Name
• Totalizer Units
• Count, Preset, Intermediate &
Predermined Values
A:-Analog I/P
• Mains Rejection Frequency
• Input Scale/Offset Adjust
C:-Relay
• Source & Polarity
C:-Hybrid
• Digital Output Source & Polarity
• Analog Output Source, Electrical Range,
Engineering Range
C:-RS485
• Protocol
• 2-/4-Wire
• Baud Rate
• Parity
C:-Ethernet
• IP Address
• Sub-net Mask
email 1
• Default Gateway
• FTP Username/Password
email 2
• Channels Report
• Totalizers Report
• External Media Report
Linearizer
• Breakpoints
RTA1
• On Time
• Duration
RTA2
• Weekly Enables
RTA3
RTA4
Process Groups 1 and 2
Common Configuration
Set Up
• Configuration Type
• No. of Process Groups
• Language
• Global Alarm Acknowledge Source
Time
• Current Date/Time
• Daylight Saving
Security
• Usernames
• Passwords
• Config. Access Method
Logs
• Alarm, Totalizer & Audit Log Sizes
Operator Messages
• Tag Name
• Activating Source
• Add to Event Log Enable
Recording
• Group Tag
• Sample Rates
• Recording Enable
Chart
• Annotations
• Chart Divisions
• Screen Interval
• Operator Menu Options
Bar
• Display On/Off &
• Operator Menu Options
Process
Digital
Archive
• Channel Data, Log Archive Options
• Filenames
• Archive Rates
(Advanced Config. Only)
Process Group 1
Process Group 2
Logs
Chart View
Bar View
Indicator View
Process View
Alarm Event Log
Totalizer Log
Audit Log
Configuration
Set up
Historical review
View select
Operator messages
Chart annotation
Screen interval
Scales
Trace select
Channel select
Max/Min reset
Totalizer stop/Go
Totalizer reset
Filter
Alarm acknowledge
Setup
Operator messages
Alarm acknowledge
1 - 6
7 - 12
13 - 18
19 - 24
Start of batch
End of batch
Standby mode active
Cleaning in progress
No message
No message
OPERATOR FUNCTIONS
CONFIGURATION OVERVIEW
The Company's policy is one of continuous product
improvement and the right is reserved to modify the
information contained herein without notice.
© ABB 2004
Printed in UK (01.04)
ABB Limited
Howard Road, St. Neots
Cambridgeshire, PE19 8EU
UK
Tel: +44 (0)1480 475 321
Fax: +44 (0)1480 217 948
IM/SM1000–Q
Issue 3