Danfoss PTU 025 Installation Instructions Manual
Read Online
Read the Danfoss PTU 025 Installation Instructions Manual online using the built-in PDF viewer.
Text of the manual
See Illustration 1.1 for the list of supplied items.
1
M25 nut
5
Pressure Transmitter Unit PTU 025
2
M25 ground washer connection
6
Tube relief plate
3
M25 star washer
7
Interface cable for the C-option port
4
M25 gasket
8
Cable binders
Table 1.1
Illustration 1.1 Pressure Transmitter Unit PTU 025 and Items Supplied
Installation Instructions
Pressure Transmitter Unit PTU 025
VLT® HVAC Drive FC 102
Danfoss A/S © 12/2017 All rights reserved.
MI08A102
To order the unit, use the following ordering number:
Model
Ordering number
PTU 025, 4 inputs
134B5925
Table 1.2 Ordering Numbers
NOTICE
The PTU 025 unit can be installed in IP55 and IP66
enclosures, and can be connected with the frequency
converter using the C-option interface. This instruction is
applicable for a frequency converter in a standard configu-
ration without any modifications.
Safety Instructions
For important information about safety precautions for installation, refer to the product-specific operating guide.
WARNING
DISCHARGE TIME
The frequency converter contains DC-link capacitors, which can remain charged even when the frequency converter is not
powered. High voltage can be present even when the warning LED indicator lights are off. Failure to wait the specified time
after power has been removed before performing service or repair work can result in death or serious injury.
•
Stop the motor.
•
Disconnect AC mains and remote DC-link power supplies, including battery back-ups, UPS, and DC-link connections to
other frequency converters.
•
Disconnect or lock PM motor.
•
Wait for the capacitors to discharge fully. The minimum duration of waiting time is specified in Table 1.3.
•
Before performing any service or repair work, use an appropriate voltage measuring device to make sure that the
capacitors are fully discharged.
Voltage [V]
Minimum waiting time (minutes)
4
7
15
20
30
40
200–240
1.1–3.7 kW
(1.50–5 hp)
–
5.5–45 kW
(7.5–60 hp)
–
–
–
380–480
1.1–7.5 kW
(1.50–10 hp)
–
11–90 kW
(15–121 hp)
–
–
315–1000 kW
(450–1350 hp)
400
–
–
–
90–315 kW
(121–450 hp)
–
–
500
–
–
–
110–355 kW
(150–500 hp)
–
–
525
–
–
–
75–315 kW
(100–450 hp)
–
–
525–600
1.1–7.5 kW
(1.50–10 hp)
–
11–90 kW
(15–121 hp)
–
–
–
690
–
–
–
90–315 kW
(100– 350 hp)
–
–
525–690
–
1.1–7.5 kW
(1.50–10 hp)
11–90 kW
(15–121 hp)
–
400–1400 kW
(500–1550 hp)
450–1400 kW
(600–1550 hp)
–
Table 1.3 Discharge Time, VLT® HVAC Drive FC 102
Installation Instructions
Pressure Transmitter Unit PTU 025
VLT® HVAC Drive FC 102
2
Danfoss A/S © 12/2017 All rights reserved.
MI08A102
Prepare the hole for the installation
The options to mount the PTU 025 unit on an IP55/66
enclosure include the following:
•
Factory-installed M25 tread.
•
Using the knock-out plate.
•
Making a new hole in the connection plate. Hole
diameter: 25 mm (0.98 in).
Illustration 1.2 PTU 025 Installation Hole
For grounding purpose, ensure that there is a good electrical
connection between the PTU 025 mounting star washer and
the enclosure.
Installing the Unit
To install PTU 025:
1.
Place the gasket between the PTU 025 unit and the
enclosure. This is necessary for the IP55/66 rating.
2.
Inside the enclosure, place the star washer, the
ground connection, and the nut. See Illustration 1.3.
3.
Put the ground wire inside the enclosure through the
star washer, the ground connection, and the nut.
4.
Rotate the unit to the required position. The unit can
be rotated 360°.
5.
Fasten the nut with the momentum 5 Nm. The unit
cannot be rotated after fastening the nut. See
Illustration 1.4.
Illustration 1.3 The Nut, The Ground Connection, The Washer, The
Gasket
Illustration 1.4 Positioning the Unit
Installation Instructions
Pressure Transmitter Unit PTU 025
VLT® HVAC Drive FC 102
MI08A102
Danfoss A/S © 12/2017 All rights reserved.
3
Connect the PTU 025 unit to the C-option port.
Ensure that the connectors are secure in sockets on
both ends and secure the cable inside the enclosure
with cable binders. See Illustration 1.5.
2.
Wire the outputs for the related signals and statuses.
3.
Mount the front cover of the frequency converter.
4.
Power up the frequency converter. Ensure that the
frequency converter identifies the PTU 025 unit.
Illustration 1.5 PTU 025 Electrical Connection to the C-option Port
Installation Instructions
Pressure Transmitter Unit PTU 025
VLT® HVAC Drive FC 102
4
Danfoss A/S © 12/2017 All rights reserved.
MI08A102
Pressure Signals on Outputs
The frequency converter can be configured to transmit the pressure values on analog output or active status on digital and relay
outputs. Perform the configuration in parameter group 5-** Main Menu - Digital In/Out and parameter group 6-** Main Menu - Analog
In/Out. See the wiring diagram in Illustration 1.6.
Illustration 1.6 Wiring Diagram
Installation Instructions
Pressure Transmitter Unit PTU 025
VLT® HVAC Drive FC 102
MI08A102
Danfoss A/S © 12/2017 All rights reserved.
5
Mounting the Pressure Tubes
PTU 025 has 5 mm (0.2 in) tube connection taps. Attach high-pressure input tubes to the taps labeled H +, and the low-pressure
tubes on the L - taps. To prevent clogging of sensors, attach tubes to all connection taps. See Illustration 1.7.
Illustration 1.7 Mounting Pressure Tubes
NOTICE
Put a tube connection on all pressure transmitter taps to minimize the amount of dirt entering the unit. The minimum tube
length is 80 mm (3.1 in). If a sensor uses the surrounding pressure level, cut the tube at a place farther than the tube relief
plate.
Installation Instructions
Pressure Transmitter Unit PTU 025
VLT® HVAC Drive FC 102
6
Danfoss A/S © 12/2017 All rights reserved.
MI08A102
After PTU 025 is installed, power up the frequency converter.
The LCP shows alarm A80, Drive initialized, which indicates that
the frequency converter detected the new device. Press [Reset]
to reset the alarm.
Illustration 1.8 Alarm A80, Drive Initialized
Use the LCP or MCT 10 Set-up Software to configure PTU 025.
The PTU 025 option can be configured for the following
purposes:
•
Monitoring of the pressure transmitter signals.
•
Showing the readouts on the LCP or transmitting
them via the fieldbus.
•
Integration of the pressure monitoring into a system
solution.
•
PID closed-loop control based on airflow or pressure
levels.
Signals from all PTU 025 sensors are active all the time and
the frequency converter can show the values on the LCP
continuously. Use parameters in parameter group 31-2*
Readouts to monitor filters, airflow, and pressure levels on the
LCP or configure warnings or alarms. Values in parameter
group 31-2* Readouts are also available via the fieldbus.
MCT 10 Set-up Software and the frequency converter check
whether the entered pressure values are within the operating
ranges of sensors. The LCP shows a warning if the entered
pressure value is outside the operating range.
Use parameter 31-30 Press Sens Cmp State in the smart logic
control to achieve application-specific functionality. Use
parameters in parameter group 13-9* User-defined Alerts and
Readouts to configure application-specific messages, warnings,
and alarms. For more information, see the programming guide.
31-** Pressure Sensor Option
Parameters related to the PTU 025 option.
31-2* Configuration
Each pressure-related status has its own below-level and
above-level trigger thresholds. The thresholds can be activated
individually. When the actual pressure level exceeds the
threshold level, the frequency converter waits for the value in
parameter 31-23 On Delay Time, and then performs a status
change of a status. When the actual pressure goes below the
threshold level, the value in parameter 31-24 Reset Delay Time
defines when the status is reset. The value in
parameter 31-25 Pressure filter time constant adjusts the
dynamic of the reaction to the actual pressure input, to ensure
reliable and stable status generation.
31-20 Pressure/Speed Curve
Select the type of the pressure/speed curve.
Each pressure sensor can have a different setting.
For options [1] Linear and [2] Square root, the pressure threshold
at 0 speed equals 10% of the value entered in
parameter 31-21 Below level threshold or parameter 31-22 Above
level threshold.See Illustration 1.9.
Illustration 1.9 Pressure/Speed Dependency
Option:
Function:
[0] *
None
The pressure threshold is
constant and does not
depend on speed.
[1]
Linear
The pressure threshold is
proportional to the speed.
[2]
Square root
The pressure threshold
depends on the speed.
The dependency is
quadratic.
31-21 Below level threshold
Range:
Function:
#*
[ -2500 - 2500 Pa]
Enter the below-level threshold.
Installation Instructions
Pressure Transmitter Unit PTU 025
VLT® HVAC Drive FC 102
MI08A102
Danfoss A/S © 12/2017 All rights reserved.
7
31-22 Above level threshold
Range:
Function:
#*
[ -2500 - 2500 Pa]
Enter the above-level threshold.
31-23 On Delay Time
Range:
Function:
60 s*
[0 - 3600 s]
Enter the on delay time.
31-24 Reset Delay Time
Range:
Function:
9999 s*
[0 - 9999 s]
Enter the reset delay time.
31-25 Pressure filter time constant
Range:
Function:
1 s* [0.01 - 60 s] Enter the pressure filter time constant. A
longer value make the pressure signal more
stable but less dynamic. A shorter value
allows to eliminate signal spikes and keep
control more dynamic.
31-2* Readouts
Parameters in this group contain the actual pressure levels and
the status information. The LCP can be configured to show the
values of these parameters in different display lines. The
toggle function allows to show multiple pressure signals in the
same LCP line. The number is followed by the hash sign (#).
See Illustration 1.9.
Use parameter 0-20 Display Line 1.1 Small to
parameter 0-24 Display Line 3 Large to configure the LCP to
show different pressure values.
Illustration 1.9 Pressure Sensor Data on the LCP
31-26 Pressure Sensor 1
Range:
Function:
0 Pa*
[-500 - 500 Pa]
Shows the readout of pressure sensor 1.
31-27 Pressure Sensor 2
Range:
Function:
0 Pa*
[-500 - 500 Pa]
Shows the readout of pressure sensor 2.
31-28 Pressure Sensor 3
Range:
Function:
0 Pa* [-1000 - 1000 Pa] Shows the readout of pressure sensor
3.
31-29 Pressure Sensor 4
Range:
Function:
0 Pa* [-2500 - 2500 Pa] Shows the readout of pressure sensor
4.
31-30 Press Sens Cmp State
Range:
Function:
0* [0 -
255]
Shows the pressure sensor state. The state is an 8-
digit binary value, where 1 indicates an active status
and 0 indicates an inactive status. Reading from
right to left, the first 4 digits indicate the alarms for
the below-level threshold, and the last 4 digits the
alarms for the above-level threshold. For instance,
counting from right to left, sensor 1 for the below-
level threshold is at position 1, and sensor 1 for the
above-level threshold is at position 5. See
Illustration 1.9.
NOTICE
When using this parameter in the smart logic
controller, the output status signal for the
below-level threshold and for the above-level
threshold is the same for a specific sensor.
For example, in the following cases the
output status signal is the same:
•
The below-level threshold for sensor
1 is active.
•
The above-level threshold for sensor
1 is active.
31-31 Press Sens toggle
Range:
Function:
[0 - 4] Shows the pressure values on all sensors. The
readout switches between sensors in a loop, going
from sensor 1 to sensor 4. The sensor number is
followed by a hash sign, see Illustration 1.9.
Installation Instructions
Pressure Transmitter Unit PTU 025
VLT® HVAC Drive FC 102
8
Danfoss A/S © 12/2017 All rights reserved.
MI08A102
PTU 025 is designed for central air handling units with 1 or more filters in the inlet/outlet part and with fan control based on the
airflow or pressure level in the ventilation system. Separate frequency converters with separate pressure transmitter units control
the inlet and outlet. PTU 025 has 4 pressure inputs. See the pressure ranges in Table 1.4. Sensors 3 and 4 can be configured for
either filter monitoring or PID control of the airflow or the pressure level.
Illustration 1.10 Application Integration Example
#
Range
Typical function
1
0–500 Pa
Filter monitoring
2
0–500 Pa
Filter monitoring
3
0–1000 Pa
Filter monitoring or PID control of the airflow or the pressure level
4
0–2500 Pa
Filter monitoring or PID control of the airflow or the pressure level
Table 1.4 PTU 025 Sensors and their Functions
Integrating pressure signals into a system solution
The pressure values can be read as analog values on the
analog output or as pulses on digital outputs. Use
parameter 5-30 Terminal 27 Digital Output,
parameter 5-31 Terminal 29 Digital Output, and
parameter 5-40 Function Relay to send the sensor status to the
relay or digital outputs. For more information about using the
pressure values in applications and in the smart logic control,
see the programming guide.
PID closed-loop control based on the airflow or pressure
level
Use parameters in parameter group 20-0* Feedback to use the
pressure values for the frequency converter’s closed-loop PID
controller.
Use parameters in parameter group 22-** Application Functions
to configure the monitoring of HVAC applications based on
airflow. For more information, see the operating guide and the
programming guide.
Installation Instructions
Pressure Transmitter Unit PTU 025
VLT® HVAC Drive FC 102
MI08A102
Danfoss A/S © 12/2017 All rights reserved.
9
Illustration 1.11 Dimensional Drawings
Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without notice. This also applies to products already on
order provided that such alterations can be made without subsequential changes being necessary in specifications already agreed. All trademarks in this material are property of the respective companies. Danfoss
and the Danfoss logotype are trademarks of Danfoss A/S. All rights reserved.
Danfoss A/S
Ulsnaes 1
DK-6300 Graasten
vlt-drives.danfoss.com
*MI08A102*
MI08A102
130R0803
12/2017