Emerson Load Bus Sync Installation Manual
Read Online
Read the Emerson Load Bus Sync Installation Manual online using the built-in PDF viewer.
Text of the manual
Connecting an NX Series or APM UPS to an NX Series or APM UPS . . . .. . . . . . . . . . . . . . . . . . . . . 2
ACRONYM
NX series : NX product series comprises of NX, NXr, Nxc, Hipulse U, ITA(30/40 kVA) UPS
Non NX series : Non NX product series comprises of Ul33, NXL, 80-net, and any other brand UPS
Load Bus Sync (LBS) Extender/Adapter for Dual Bus UPS is designed to extend the LBS function,
up to 150m (492 ft.) between NX series or APM series uninterruptible power system (UPS) modules of a
dual bus system (DBS). The adapter also enables an NX Series or APM UPS to synchronize with other
UPS models.
Figure 1
LBS Adapter dimensions
Figure 2
Horizontal installation
Figure 3
Vertical installation
DY3-4ZPW
POWER?ON
SWITCH
LED1
COM2
COM1
(216.2mm)
5.25"
(133.5mm)
1.8"
(45.5mm)
DY3-4ZPW
COM1
COM2
SWITCH
LED1
POWER ON
2.1 NX Series or APM UPS to NX Series or APM UPS
1.
Connect the power cables of the adapter to the Phase A, Neutral and Ground output of each UPS.
2.
For NX Series UPS except for NXr, connect the LBS cable (with two DB9 ports) to COM1 of the LBS
Signal Adapter; for NXr UPS and APM UPS, connect the end of the LBS cable (with a DB9 port
and an RJ45 port) with DB9 port to COM1 of the LBS Signal Adapter.
3.
For NX Series UPS except for NXr, connect the other end of the LBS cable (with two DB9 ports) to X4 on
the parallel board (UHW241M3) in the UPS; for NXr UPS and APM UPS, connect the end of the
LBS cable (with a DB9 port and an RJ45 port) with RJ45 port to the J4 port of the bypass module
!
WARNING
Installation by qualified electrical personnel only- hazardous voltage may be present at the
UPS output connectors.
of the UPS.
4.
Connect the communication cable (up to 492 ft. [150m]) to the COM2 interface of each LBS Signal
Adapter.
5.
The switch of both LBS signal adapters should be in the right position (see Figure 4).
Figure 4
Connecting an NX Series or APM UPS to an NX Series or APM UPS
COM1
COM1
COM2
COM2
SWITCH
SWITCH
Power ON
LED1
Power ON
LED1
Power Cable
Connect to NX Series or APM UPS
LBS
Cable
Communication Cable
up to 492 ft. (150m)
Power Cable
Connect to NX Series or APM
UPS
LBS
Cable
2.2 NX Series or APM UPS to Non NX Series or non-APM UPS
.
!
WARNING
Installation by qualified electrical personnel only - hazardous voltage may be present at the
UPS output connectors.
1.
Connect the power cables of the adapter to the Phase A, Neutral and Ground Output of each UPS.
2.
For NX Series UPS except for NXr, connect the LBS cable (with two DB9 ports) to COM1 of the LBS
Signal Adapter connectedto the UPS; for NXr UPS and APM UPS, connect the end of the LBS cable
(with a DB9 port and an RJ45 port) with DB9 port to COM1 of the LBS Signal Adapter.
3.
For NX Series UPS except for NXr, connect the other end of the LBS cable (with two DB9 ports) to X4 on
board the parallel (UHW241M3) in the UPS; for NXr UPS and APM UPS, connect the end of the
LBS cable (with a DB9 port and an RJ45 port) with RJ45 port to the J4 port of the bypass module of
the UPS.
.
4.
Connect the communication cable (up to 492 ft. [150m]) to the COM2 interface of each LBS Signal
Adapter.
.
5.
The switches of LBS signal adapters connected to the NX Series or APM UPS should be in the right
position and the switches of LBS signal adapters connected to the Non NX Series or non-APM UPS
should be in the left position (see Figure 5).
Connecting an NX Series or APM UPS
to a Non NX Series
or non-APM UPS
Table 1
Human interface - indicators and switches
Item
Description
Power port
Connect to Phase A, Neutral and Ground of output of UPS.
LED1 (red)
Power LED. It illuminates when the power is on, turns o ffwhen the power fails.
COM1
LBS Signal interface.
Connect to NX Series or APM UPS.
COM2
RS485 interface.
Connect to other Signal Adapter.
Green LED: Communication Power is OK.
Yellow LED: Adapter is connected to Non NX Series or non-APM UPS.
SWITCH
Switch to left: Connect to Non NX Series or non-APM UPS.
Switch to right: Connect to NX Seires or APM UPS.
Table 2
Electrical rating
Description
Rating
Voltage
120V-277VAC
Frequency
45-65HZ
Current
1.5A Max.
Table 3
Part number description
Description
Part Number
150 Meter Kit
NX150MLBSKIT
50 Meter Kit
NX050MLBSKIT
COM1
COM2
SWITCH
COM1
COM2 SWITCH
Power ON
LED1
Power ON
LED1
Power Cable
Connect to NX Series or APM UPS
LBS
Cable
Power Cable
Connect to Non NX Series or non-APM UPS
Communication Cable
up to 492 ft. (150m)
Emerson Network Power, a business of Emerson
(NYSE:EMR),a global company that leads by applying a unique
combination of industry expertise, technology, and resources to
make the future of our customers' enterprises and networks
possible.
Emerson Network Power provides innovative solutions and
expertise in areas including AC and DC power and precision
cooling systems, embedded computing and power,
integrated racks and enclosures, power switching and
controls, infrastructure management and connectivity.
All solutions are supported globally by local Emerson
Network Power service technicians.
While every precaution has been taken to ensure the accuracy and completeness of this
literature, Emerson Network Power assumes no responsibility and disclaims all liability for
damages resulting from use of this information or for any errors or omissions.