Ei Electronics Ei141 Ionisation Installation Instructions Manual
| Brand: | Ei Electronics |
| Category: | Smoke Alarm |
| Model: | Ei141 Ionisation (Installation Instructions Manual) |
| File Type: | |
| File Size: | — |
| Pages: | 16 |
Text of Ei Electronics Ei141 Ionisation Installation Instructions Manual
IDEALLY INSTALL IN THE CENTRE OF CEILING
AT LEAST 300mm FROM LIGHT FITTINGS
LOCATE IONISATION ALARMS AWAY FROM
KITCHENS TO PREVENT NUISANCE ALARMS
ENSURE LIVE MAINS IS CORRECTLY
CONNECTED TO L TERMINALS ON ALL
INTERCONNECTED ALARMS - OTHERWISE
UNITS WILL BE DAMAGED
DO NOT FIT ACTUAL ALARM UNTIL ALL
BUILDING WORK IS COMPLETED TO AVOID
CONTAMINATION. AFTER CHECKING
OPERATION, COVER SMOKE ALARM WITH
DUST COVER UNTIL REQUIRED FOR USE
DISCONNECT THE ALARM BEFOR
2. ALARM REMOVAL
SLIDE ALARM OFF BASE
WITH THE SCREWDRIVER STILL INSERTED, PUSH THE LOWER
HALF OF THE ALARM AWAY FROM THE SCREWDRIVER, IN THE
DIRECTION OF THE ARROW ON THE COVER
HOLD THE LOWER HALF OF THE ALARM AND REMOVE FROM
THE BASE PLATE BY MOVING IT VERTICALLY DOWNWARDS,
TOWARDS THE FLOOR.
REMOVE ALARM
LOCATE REMOVAL SLOT
LOCATE THE ARROW ON THE FRONT FACE OF THE ALARM.
THE SLOT IS LOCATED DIRECTLY ABOVE THE ARROW.
INSERT SCREWDRIVER
INSERT A FLAT-BLA
Ei Electronics Ei141 Ionisation 2. HOW MANY ALARMS TO INSTALL
- CATEGORIES & GRADES -
The advice here follows the guidance in British Standard
BS 5839-Part 6: 2004 in general (for further information
see the BS standard itself).
The main reason for fitting Smoke & Heat Alarms in
dwellings is to ensure that when there is a fire, sufficient
early warning is given so that everybody can escape
safely.
This means that the fire alarms should ideally be located
near all potential sources of fir
Ei Electronics Ei141 Ionisation LD2: As LD3, but in addition
in all rooms or areas that
to occupants.
ed in:
be within 5.3m of potential fire
arms located in:
m (i.e. most frequently used
ated:
allways and escape routes
bedroom doors
& bathrooms )
for existing dwellings
MINIMUM PROTECTION
LD3
Minimum Protection LD3: Smoke Alarms in all
hallways, stairways and circulation areas that form
part of the escape routes from the dwelling.
Multi Storey Dwelling LD3
Living
Room
Bedroom
Bathr
Ei Electronics Ei141 Ionisation nts may be at high risk (e.g. elderly)
M PROTECTION
LD1: As LD2, but in addition
should be located in all rooms
dwelling.
athroom)
ey Dwelling LD1
ed in:
be within 5.3m of potential fire
Bathroom
Kitchen
Shower
Garage
arms located in:
m (i.e. most frequently used
ated:
allways and escape routes
edroom doors
s & areas other than listed below
& bathrooms )
Additional Protection LD2: As LD3, but in addition
Smoke or Heat Alarms in all rooms or areas tha
for dwellings where occupants may be at high risk (e.g. elderly)
OPTIMUM PROTECTION
LD1
Optimum Protection LD1: As LD2, but in addition
Smoke or Heat Alarms should be located in all rooms
and other areas of the dwelling.
(apart from toilets or bathroom)
Multi Storey Dwelling LD1
Heat Alarms located in:
(Heat Alarms must be within 5.3m of potential fire
sources)
each Kitchen
garages
Living
Room
Bedroom
Bathroom
Kitchen
Bedroom
Shower
Garage
Smoke or Heat A
2.2 Selecting Alarm Type
1 Optical Smoke Alarms are recommended due to their
excellent response to smouldering fires. If there is likely to be
problems with steam, contamination or dust build-up, or if there
is significant risk of a fast burning clean fire an Ionisation Smoke
Alarm should be fitted.
2 Some Fire Authorities recommend that both Ionisation and
Optical Smoke Alarms should be fitted for the fastest response
to all types of fires.
3 Some Fire au
The effectiveness of Category LD2 and LD3 systems can
be significantly enhanced if an additional Smoke Alarm
(interconnected) is installed in the master bedroom. This will
help ensure that a responsible person will quickly be alerted
to a fire and can arrange for an orderly evacuation of children
and other vulnerable occupants.
2.3 Grade D, E & F Systems
The mains powered Smoke and Heat Alarms with battery
back-up covered by these instr
Ei Electronics Ei141 Ionisation is less than 600mm for Smoke Alarms or 150mm for
Heat Alarms it is regarded as being flat (see Figure 2).
3.1 Locations To Avoid
DON’T place Smoke Alarms in any of the following
areas:
• Bathrooms, kitchens, shower rooms, garages or other
rooms where the smoke alarm may be triggered by
steam, condensation, normal smoke or fumes. Keep
at least 6 metres away from sources of normal smoke/
fumes.
DON’T place Heat Alarms in any of the following
areas:
•
Ei Electronics Smoke Alarm Owners Instructions:
| Device Model | Type of Document | Pages | Size | Views | Downloads | Updated |
|---|---|---|---|---|---|---|
Ei 220E |
#173ZSP: Ei 220E Smoke Alarm User instructions |
6 | 0.13 Mb | 199 | 34 | 18-07-2026 |
Ei603 |
#MD2138: Ei603 Smoke Alarm Instructions manual |
54 | 556 | 112 | 06-06-2026 | |
Ei150 |
Ei150 User instructions - D5QL6L |
1 | 0.13 Mb | 932 | 187 | 08-07-2026 |
Ei3105TYCH |
Ei3105TYCH Product manual - 1C5652 |
2 | 0.12 Mb | 470 | 109 | 06-07-2026 |
Ei 170 |
Ei Electronics Smoke Alarm Instruction leaflet (File: PDF, 18-09-2026) |
3 | 0.09 Mb | 131 | 23 | 18-09-2026 |
EiA600 Series |
Ei Electronics EiA600 Series User Manual (Instructions manual), @796JXS |
18 | 1483 | 356 | 30-07-2026 | |
Ei169 |
Ei Electronics Ei169 Manual (Product manual), @D522EK |
2 | 0.1 Mb | 64 | 13 | 04-10-2026 |
Ei2110e Series |
Ei Electronics Smoke Alarm Instruction manual (File: PDF, 07-05-2026) |
40 | 55 | 12 | 07-05-2026 | |
Ei166R |
Ei166R (Smoke Alarm ePDF Manual, #6ZU315) |
2 | 0.08 Mb | 1379 | 304 | 02-05-2026 |