Danfoss ECL Comfort 110 Datasheet
Text of the manual
ECL Comfort 110
230 V a.c. and 24 V a.c.
DH-SMT/DK
VD.KT.C3.02 © Danfoss 09/2008
1
Description and application
The controller is designed for easy installation:
one cable, one connector.
The ECL Comfort 110 controller has a custom-
designed display with backlight. For a quick
overview, the display readouts are based on
graphic symbols as well as text.
The controller has triac outputs for motorized
control valve and relay outputs for pump
control.
It is possible to connect up to 4 temperature
sensors (Pt 1000 types) and it has 1 input for
override. Room panel or remote control (ECA 60
/ 61) can be connected.
The ECL Comfort 110 controller can be used as
master or slave in controller systems.
It is prepared for mounting on a DIN rail, a wall
or in a panel.
The ECL Comfort 110 is a universal 1-circuit
controller for use in district heating substations
and district heating systems as well as boiler-
based systems.
The product is an electronic controller for
• weather compensated flow temperature
control (heating)
• constant temperature control (domestic hot
water e.g.)
and prepared for new applications by means of
chip card and communication interface.
Ordering
Controllers
Type
Designation
Code no.
ECL Comfort 110
Universal hardware - 230 V a.c.
087B1261
ECL Comfort 110
Universal hardware - 24 V a.c.
087B1251
ECL Comfort 110 with timer
program
Universal hardware - 230 V a.c.
087B1262
ECL Comfort 110 with timer
program
Universal hardware - 24 V a.c.
087B1252
Panel mounting kit
For ECL Comfort 110
087B1249
Instructions, appl. 116
User guide and quick guide (English)
087B8151
Instructions, appl. 130
User guide and quick guide (English)
087B8152
Pt 1000 temperature sensors
Type
Designation
Code No.
ESMT
Outdoor temperature sensor
084N1012
ESM-10
Room temperature sensor
087B1164
ESM-11
Surface sensor
087B1165
ESMB-12
Universal sensor
087B1184
ESMC
Surface sensor incl. 2 m cable
087N0011
ESMU-100
Immersion sensor, 100 mm, copper
087B1180
ESMU-250
Immersion sensor, 250 mm, copper
087B1181
ESMU-100
Immersion sensor, 100 mm, stainless steel
087B1182
ESMU-250
Immersion sensor, 250 mm, stainless steel
087B1183
VD.KT.C3.02 © Danfoss 09/2008
2
Ordering, continued
Accessories
Type
Designation
Code no.
ECA 60
Room panel with sensor
087B1140
ECA 61
Remote control with 1 zone clock and sensor
087B1141
ECA 110*
Timer program for ECL Comfort 110 (chip card)
087B1248
*
The ECA 110 is a supplement to the ECL Comfort 110 versions without a timer program, e.g., the code nos. 087B1261 and
087B1251 (see page 1). With the ECA 110 it will be possible to set personal schedules in terms of start and stop times of
the system and thereby optimize the energy supply.
Domestic hot water (DHW)
(Application 116)
Application 116 example
Constant DHW temperature control with heat exchanger
Basic principles
Constant DHW temperature control with heat
exchanger or storage tank
Typically, the flow temperature is adjusted
according to the desired flow temperature.
• Adjustment of DHW temperature
If the measured DHW temperature is lower
than the desired temperature, the motorized
control valve is opened gradually and vice
versa.
• Return temperature limitation
The return temperature to the district heating
supply should not be too high. If so, the
desired flow temperature can be adjusted
(typically to a lower value) thus resulting in a
gradual closing of the motorized control valve.
In boiler-based heating supply the return
temperature should not be too low (same
adjustment procedure as above).
• Circulation pump control
The circulation pump is ON when the desired
DHW temperature is higher than a user-
defined value (factory setting: 20 °C).
ECL Comfort 110
VD.KT.C3.02 © Danfoss 09/2008
3
ECL Comfort 110
Key functions
Flow temperature control
• Return temperature limitation
The controller automatically changes the
desired flow temperature to obtain an
acceptable return temperature when the
return temperature falls below or gets higher
than the set value. The return temperature
influence can be limited by the min. / max.
flow limitation.
Optimization
• Auto tuning
A function for automatically setting the
proportional band (Xp) and integration time
constant (Tn).
Safety functions
• Frost protection
The controller automatically switches
the circulation pump ON when the flow
temperature is lower than a user-defined
value (factory setting: 10 °C).
• Motor protection
The controller prevents unstable temperature
control thus resulting in a longer life of the
actuator.
• Pump exercise
Exercise of the pump to avoid blocking in
periods without heat demand.
Heating
(Application 130)
Application 130 examples
District heating circuit with heat exchanger
Boiler-based heating circuit
ECL Comfort 110
Data sheet
DH-SMT/DK
VD.KT.C3.02 © Danfoss 09/2008
4
Basic principles
Control of district heating circuits with or
without heat exchanger and for boiler-based
heating circuits
Typically, the flow temperature is adjusted
according to the desired flow temperature.
• Adjustment of flow temperature
The desired flow temperature is calculated
in the ECL Comfort controller, based on the
outdoor temperature. The lower the outdoor
temperature, the higher the desired flow
temperature.
The motorized control valve is opened
gradually when the flow temperature is lower
than the desired flow temperature and vice
versa.
• Return temperature limitation
The return temperature to the district heating
supply should not be too high. If so, the
desired flow temperature can be adjusted
(typically to a lower value) thus resulting in a
gradual closing of the motorized control valve.
In boiler-based heating supply the return
temperature should not be too low (same
adjustment procedure as above).
• Room temperature limitation
If the measured room temperature does not
equal the desired room temperature, the
desired flow temperature can be adjusted.
• Circulation pump control
The circulation pump is ON when the desired
flow temperature is higher than a user-defined
value (factory setting: 20 °C ) or the outdoor
temperature is lower than a user-defined
value (factory setting: 2 °C).
VD.KT.C3.02 © Danfoss 09/2008
5
ECL Comfort 110
General data
Ambient temperature
0 - 55 °C
Storage temperature
-40 - + 70 °C
Enclosure
DIN rail, wall or panel
Sensor type
Pt 1000 (1000 Ω @ 0 °C)
Grade of enclosure
IP 41 DIN 40050
- marking
in accordance with the standards
EMC-Directive: 2004/108/EC
Immunity: 61000-6-1
Emission: 61000-6-3
LVD-Directive: 2006/95/EC
Wiring - 230 V a.c.
* Connections for safety thermostat
Supply voltage
230 V a.c. - 50 Hz
Voltage range
207 to 244 V a.c. (IEC 60038)
Power consumption
3 VA
Load on relay 1 outputs
4 (2) A - 230 V a.c.
Load on triac outputs
15 VA @ 230 V a.c.
Wiring - 24 V a.c.
* Connections for safety thermostat
Supply voltage
24 V a.c. - 50 Hz
Voltage range
21.6 to 26.4 V a.c. (IEC 60038)
Power consumption
3 VA
Load on relay 2 outputs
4 (2) A - 230 V a.c.
Load on triac outputs
15 VA @ 24 V a.c.