Eaton BladeUPS Operation & User’s Manual

File Specifications

Brand: Eaton
Category: UPS
Model: BladeUPS (Operation & User’s Manual), prAbSsfBFJf5s
File Info: Adobe Acrobat PDF (DjVu)
File Size:
Pages: 139 pages

Download PDF

Download Eaton BladeUPS Manual (139 pages)

Read Online:

Read the Eaton BladeUPS Operation & User’s Manual online using the built-in PDF viewer. This document explains how to operate the device, adjust settings and perform regular maintenance.

Key Pages of Document

Standard System Installation

86 Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7 6. Check each UPS front panel display for active alarms or notices (other than “Batteries Disconnected”). Resolve any active alarms before continuing. See “Troubleshooting” on page 135. 7. Switch all UPS battery circuit breakers to the ON ( ) position. 8. If optional EBMs are installed, switch all EBM battery circuit breakers to the ON ( ) position. 9. Verify that the “Batteries Disconnected” alarm on each UPS has cleared. Verify that no other alarms appear on any UPS front ...

Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide

164201649—Rev 7 125 Chapter 8 Specifications This chapter provides the following specifications: l Model list l Weights and dimensions l Electrical input and output l Environmental and safety l Battery Table 16. Model List UPS Model Number Power Levels (Rated at Nominal Inputs) BladeUPS 12 12 kVA or 12 kW at 208V See Note BladeUPS 12i 12 kVA or 12 kW at 400V See Note EBM Model Number BladeUPS EBM BladeUPS Bar Model Number BladeUPS Bar 4-High For up to 4 UPSs BladeUPS Bar 6-High For up to 6 UPSs NOTE Derated for line cord and nominal line ...

Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide

164201649—Rev 7 97 11. Press any button on the front panel display to activate the menu options. Select CONTROL and GO TO BYPASS MODE. The indicator illuminates solid and the indicator flashes, indicating the UPS is operating in Bypass mode. The load is now powered by utility power. If the indicator is flashing, do not proceed until all alarms are clear. Check the UPS status from the front panel to view the active alarms. Correct the alarms and restart if necessary. 12. Switch the load connector circuit breaker to the ON ( ) ...

Standard System Installation

84 Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7 l Gently loop and twist the parallel input cords as shown to minimize stress on the cords. The loop and twist for each cord may vary depending on configuration and strain relief to the BladeUPS Bar in the rack. 21. Continue to “Parallel System Initial Startup” on page 85. If you installed the additional UPS(s) without shutting down the parallel system, perform the steps in “Parallel System Initial Startup”on the additional Standalone UPS Initial Startup To start up a standalone UPS: ...

Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide

164201649—Rev 7 89 Chapter 5 Operation This chapter contains information for operating the BladeUPS module, including: l Control panel operation l Operating modes l UPS startup and shutdown l Transferring the UPS between modes l Setting the power strategy l Configuring the UPS for battery settings Control Panel Functions The UPS has a four-button graphical LCD with backlight. It provides UPS load status, events, measurements, current settings, and other useful information (see Figure 68). Figure 68. BladeUPS Module Control Panel The Mimic ...

Standard System Installation

Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7 83 11. If not already installed, using the supplied connectors, install a CAN Bridge Card cable between each UPS as shown in Figure 63 on page 75, connecting the CAN OUT port on one UPS to the CAN IN port on the next UPS. On startup, the parallel system will identify the UPS wired after UNIT 1 as UNIT 2, and so forth. 12. For a parallel system not previously shut down, verify that any alarms related to reconfiguring the CAN Bridge Cards have cleared. 13. Install a redundant signal cable between ...

Eaton BladeUPS 12 kVA to 60 kVA (N+1) User’s Guide 164201649—Rev 7

8. If you are shutting down all the UPSs in a parallel system, repeat Steps 1 through 7 for each UPS, then remove utility power from the system. Otherwise, continue to Step 9. 9. If it is necessary to completely remove power from the individual UPS, disconnect the UPS from the BladeUPS Bar. Parallel System Shutdown To remove power to the parallel UPS system output (see Figure 59 on page 70): 1. Switch each UPS load connector circuit breaker to the OFF (O) position. 2. Press any button on any front panel displa ...

Eaton BladeUPS user guide recommended for: 93PM-150(400), 9910-E16, 9395 550, 9393PM, Powerware 3105 UPS.