AMX NXA-PDU-1508-08 Operation/reference Manual

Specifications

Brand: AMX
Category: Power distribution unit
Model: NXA-PDU-1508-08 (Operation/reference Manual)
File Type: PDF
File Size: —
Pages: 20

Read Online

Read the AMX NXA-PDU-1508-08 Operation/reference Manual online using the built-in PDF viewer.

Text of the manual

Control System Accessories

NXA-PDU-1508-08 Power Distribution Unit (240V / 10A) Last Revised: 6/03/2011 NXA-PDU-1508-08 Power Distribution Unit (240V/10A) Operation/Reference Guide

AMX Limited Warranty and Disclaimer

This Limited Warranty and Disclaimer extends only to products purchased directly from AMX or an AMX Authorized Partner which include AMX Dealers, Distributors, VIP’s or other AMX authorized entity. AMX warrants its products to be free of defects in material and workmanship under normal use for three (3) years from the date of purchase, with the following exceptions: • Electroluminescent and LCD Control Panels are warranted for three (3) years, except for the display and touch overlay compo- nents are warranted for a period of one (1) year. • Disk drive mechanisms, pan/tilt heads, power supplies, and MX Series products are warranted for a period of one (1) year. • AMX lighting products are guaranteed to switch on and off any load that is properly connected to our lighting products, as long as the AMX lighting products are under warranty. AMX also guarantees the control of dimmable loads that are properly con- nected to our lighting products. The dimming performance or quality there of is not guaranteed, impart due to the random combi- nations of dimmers, lamps and ballasts or transformers. • AMX software is warranted for a period of ninety (90) days. • Batteries and incandescent lamps are not covered under the warranty. • AMX AutoPatch Epica, Modula, Modula Series4, Modula CatPro Series and 8Y-3000 product models will be free of defects in materials and manufacture at the time of sale and will remain in good working order for a period of three (3) years following the date of the original sales invoice from AMX. The three-year warranty period will be extended to the life of the product (Limited Lifetime Warranty) if the warranty card is filled out by the dealer and/or end user and returned to AMX so that AMX receives it within thirty (30) days of the installation of equipment but no later than six (6) months from original AMX sales invoice date. The life of the product extends until five (5) years after AMX ceases manufacturing the product model. The Limited Lifetime Warranty applies to products in their original installation only. If a product is moved to a different installation, the Limited Lifetime Warranty will no longer apply, and the product warranty will instead be the three (3) year Limited Warranty. All products returned to AMX require a Return Material Authorization (RMA) number. The RMA number is obtained from the AMX RMA Department. The RMA number must be clearly marked on the outside of each box. The RMA is valid for a 30-day period. After the 30-day period the RMA will be cancelled. Any shipments received not consistent with the RMA, or after the RMA is cancelled, will be refused. AMX is not responsible for products returned without a valid RMA number. AMX is not liable for any damages caused by its products or for the failure of its products to perform. This includes any lost profits, lost savings, incidental damages, or consequential damages. AMX is not liable for any claim made by a third party or by an AMX Autho- rized Partner for a third party. This Limited Warranty does not apply to (a) any AMX product that has been modified, altered or repaired by an unauthorized agent or improperly transported, stored, installed, used, or maintained; (b) damage caused by acts of nature, including flood, erosion, or earth- quake; (c) damage caused by a sustained low or high voltage situation or by a low or high voltage disturbance, including brownouts, sags, spikes, or power outages; or (d) damage caused by war, vandalism, theft, depletion, or obsolescence. This limitation of liability applies whether damages are sought, or a claim is made, under this warranty or as a tort claim (including negligence and strict product liability), a contract claim, or any other claim. This limitation of liability cannot be waived or amended by any person. This limitation of liability will be effective even if AMX or an authorized representative of AMX has been advised of the possibility of any such damages. This limitation of liability, however, will not apply to claims for personal injury. Some states do not allow a limitation of how long an implied warranty last. Some states do not allow the limitation or exclusion of inci- dental or consequential damages for consumer products. In such states, the limitation or exclusion of the Limited Warranty may not apply. This Limited Warranty gives the owner specific legal rights. The owner may also have other rights that vary from state to state. The owner is advised to consult applicable state laws for full determination of rights. EXCEPT AS EXPRESSLY SET FORTH IN THIS WARRANTY, AMX MAKES NO OTHER WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING ANY IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. AMX EXPRESSLY DISCLAIMS ALL WARRANTIES NOT STATED IN THIS LIMITED WARRANTY. ANY IMPLIED WARRANTIES THAT MAY BE IMPOSED BY LAW ARE LIMITED TO THE TERMS OF THIS LIMITED WARRANTY. EXCEPT AS OTHERWISE LIMITED BY APPLICABLE LAW, AMX RESERVES THE RIGHT TO MODIFY OR DISCONTINUE DESIGNS, SPECIFICATIONS, WARRAN- TIES, PRICES, AND POLICIES WITHOUT NOTICE.

Table of Contents

i NXA-PDU-1508-8 Power Distribution Unit (240V / 10A) Table of Contents NXA-PDU-1508-8 ...............................................................................................1 Overview .................................................................................................................. 1 Features.................................................................................................................... 1 Product Specifications ............................................................................................. 1 SAFETY INSTRUCTIONS ........................................................................................... 2 Rack-Mounting.......................................................................................................... 3 Installation ..........................................................................................................5 Front Panel Components .......................................................................................... 5 RESET Pushbutton........................................................................................................... 5 Rear Panel Components............................................................................................ 5 AXLINK POWER Connectors 1-8 ..................................................................................... 6 MASTER Connector......................................................................................................... 6 TEMP Connector ............................................................................................................. 6 Preparing Captive Wires ................................................................................................. 7 AxLink Data and Power Connections .............................................................................. 7 AxLink Wiring Guidelines ................................................................................................ 7 CONFIG DIP Switch......................................................................................................... 8 Setting the Device Address of the PDU .......................................................................... 8 Power Outlets 1-8 ........................................................................................................... 8 Power Inlet...................................................................................................................... 9 Powering On the NXA-PDU-1508-8.......................................................................... 9 NetLinx Programming ......................................................................................11 Device IDs............................................................................................................... 11 Supported SEND_COMMANDs .............................................................................. 11 PERSIST ..................................................................................................................................... 11 ?PERSIST ................................................................................................................................... 11 ?PHASEANGLE.......................................................................................................................... 11 RESET........................................................................................................................................ 11 ?SERIAL ..................................................................................................................................... 11 TRIGGER.................................................................................................................................... 12 ?TRIGGER.................................................................................................................................. 12 VER............................................................................................................................................ 12 ZAP!........................................................................................................................................... 12 Channels ................................................................................................................. 12 Levels ..................................................................................................................... 13 Resetting Level 4 (Accumulated Energy Reading)......................................................... 13 Overcurrent Reporting ........................................................................................... 13

NXA-PDU-1508-8 Power Distribution Unit (240V / 10A)

NXA-PDU-1508-8 Overview The NXA-PDU-1508-8 Power Distribution Unit - 240V / 10A (FG673-02) provides switching of mains power to each of eight AC power outlets. The two built-in AxLink bus strips provide connectivity (AxLink data / power) for up to eight AxLink connections. Features Supplies, controls, and monitors power to other electronics, to allow power staging and monitoring as well as management of standby power consumption. Measures current on each power outlet, as well as the total current draw of the entire PDU. The AxLink bus strip power line is divided into two banks of four connectors each (“Bank 1” and “Bank 2”), with power switched separately to the two banks. Product Specifications FIG. 1 NXA-PDU-1508-8 NXA-PDU-1508-8 (240V) Specifications Power Specifications: • Powered via 240VAC, 50/60Hz mains power on an IEC-320 C-14 connector. • Required voltage = 240VAC, 50/60Hz • Total Combined Current (including AxLink): 10A • Idle current draw (240VAC 50/60HZ): 0.5W max Front Panel Components: POWER LEDs (1-8): Eight green LEDs illuminate to indicate that the associated Power Outlet (#1 - #8) is in use. AXLINK LEDs: Two green LEDs illuminate to indicate when the associated AxLink Bus Strips (Bank 1 or Bank 2) on the PDU is in use. STATUS LED: Yellow LED illuminates to indicate AxLink communication activity between the PDU and the NetLinx Master: • ON - power, no master connection • OFF - no power • Blink - powered, communicating with master RESET pushbutton AxLink STATUS LED AxLink BANK 1 POWER (Output 1-8 Status) LEDs Status LED AxLink BANK 2 Status LED Power Inlet Fuse Compartment AXLINK POWER Connectors BANK 1 (1-4) MASTER AxLink Connector (to NetLinx Master Controller) TEMP (RTS) Input Connector Power Outlets 1-8 AXLINK POWER Connectors BANK 2 (5-8) CONFIG DIP Switch 8 7 6 5 4 3 2 1

NXA-PDU-1508-8 Power Distribution Unit (240V / 10A)

SAFETY INSTRUCTIONS There are NO user serviceable parts within the NXA-PDU-1508-8. DO NOT install or operate the NXA-PDU-1508-8 in an area where the ambient temperature exceeds 40ºC (104ºF) or falls below 0ºC (32ºF). DO NOT install or operate the NXA-PDU-1508-8 in an area in which the ambient relative humidity exceeds 85% or an area that is prone to condensation. DO NOT install or operate the NXA-PDU-1508-8 near water or in a location which may be prone to water seepage, dripping or splashing. DO NOT place objects containing liquids on the NXA-PDU-1508-8. DO NOT operate the NXA-PDU-1508-8 externally. NXA-PDU-1508-8 (240V) Specifications (Cont.) RESET pushbutton: The RESET pushbutton is a momentary breaker reset switch for the MASTER power connection. Trippage of the RESET pushbutton causes a 0.5 second toggle on the AxLink power line. Press the RESET button to reset the PDU. Rear Panel Components: AXLINK POWER connectors (8): A 13.5VDC, 6.5A power supply is provided for AxLink power. Eight 3.5mm (4-pin) AxLink captive-wire connectors provide power and data to up to eight AxLink devices. • AxLink power is switched in two banks of four outputs each. BANK 1 contains AxLink connectors 1-4 BANK 2 contains AxLink connectors 5-8 • The PDU provides 6.5A total across all AxLink outputs. MASTER connector 3.5mm Phoenix (4-pin) AxLink connector provides connectivity to the NetLinx Master (always on). TEMP (RTS) input: 3.5mm Phoenix (2 pin) connector provides connection to a Remote Temperature Sensor (RTS). CONFIG DIP Switch: Eight-position DIP switch sets the AxLink device address. International Power Outlets (8): Connector Type: IEC C-13, 10A Maximum allowable current on a single high-voltage output: 8A International Power Inlet (1): • Connector Type: IEC C-14, 10A (10A Input) • Equipped with a safety fuse (see Included Accessories) Dimensions (HWD): • 1 3/16" x 17" x 9 11/16" (2.97cm x 43.18cm x 24.54 cm) • 1 RU Weight: 9 lbs (4.08 kg) Enclosure: Steel, black powder coated finish. Environmental: • Operating Environment: 0°C - 40°C (32°F - 104°F) • Storage Environment: -10°C - 60°C (14°C - 140°F) • Relative Humidity: 5% - 85%, non-condensing Certifications: • CE • CB Scheme • SGS • C-Tick Included Accessories: • ENV-VST-TSO Indoor/ Outdoor Temperature Sensor (FG2050-22) • Removable rack ears • Safety Fuse: 10A @ 240VAC Note: When replacing the fuse, use only a 10A 240V Slo-Blo fuse Other AMX Equipment: • ENV-VST-TSF Flush-Mount Indoor Temperature Sensor (FG2050-21) • NEMA to C14 Power Cable (FG10-673-02)

NXA-PDU-1508-8 Power Distribution Unit (240V / 10A)

Rack-Mounting Before rack mounting the PDU, pay particular attention to the following factors: Temperature: Since the temperature within a rack assembly may be higher than the ambient room temperature, check that the rack-environment temperature is within the specified operating temperature range. Mechanical Loading: Do not place any equipment on top of a rack-mounted unit. Circuit Overloading: Be sure that the supply circuit to the rack assembly is not overloaded. Grounding: Rack-mounted equipment should be properly grounded. Particular attention should be given to supply connections other than direct connections to the mains. The NXA-PDU-1508-8 can be mounted in a standard 19-inch equipment rack: 1. Attach the brackets to the PDU using the screws provided in the Bracket Mounting Kit (FIG. 2). 2. Mount the PDU in the rack, using 4 rack-mounting screws (not provided, see FIG. 3). For safety, the socket-outlet should be installed near the NXA-PDU-1508-8 and must be easily accessible. FIG. 2 Attaching the Brackets FIG. 3 Installing the Switch in a Rack

NXA-PDU-1508-8 Power Distribution Unit (240V / 10A)

Installation Front Panel Components The front panel components of the NXA-PDU-1508-8 are shown in FIG. 4: RESET Pushbutton The RESET pushbutton is a momentary breaker reset switch for the MASTER AxLink power connection. Press the RESET button to reset the PDU in the event that the PDU’s circuit breaker is tripped (due to overcurrent protection). Trippage of the RESET pushbutton causes a 0.5 second toggle on the AxLink power line. Rear Panel Components The rear panel components of the NXA-PDU-1508-8 are described below (FIG. 5): FIG. 4 NXA-PDU-1508-8 - Front Panel Components RESET pushbutton AxLink STATUS LED AxLink BANK 1 POWER (Output 1-8 Status) LEDs Status LED AxLink BANK 2 Status LED See the Specifications table for descriptions of the LEDs on the front panel. FIG. 5 NXA-PDU-1508-8 - Rear Panel Components Power Inlet Fuse Compartment AXLINK POWER Connectors BANK 1 (1-4) MASTER AxLink Connector (to NetLinx Master Controller) TEMP (RTS) Input Connector Power Outlets 1-8 AXLINK POWER Connectors BANK 2 (5-8) CONFIG DIP Switch 8 7 6 5 4 3 2 1

NXA-PDU-1508-8 Power Distribution Unit (240V / 10A)

AXLINK POWER Connectors 1-8 The 8 AxLink connectors (labelled “AXLINK POWER” are standard 4-pin AxLink captive-wire connectors that provide data and power to up to 8 AxLink devices. (FIG. 6): The AxLink device connectors are separated into two Banks: BANK 1 includes AxLink connectors 1-4 BANK 2 contains connectors 5-8 The PDU provides switched power to banks 1 and 2. MASTER Connector The 4-pin captive-wire AxLink connector labelled “MASTER” provides AxLink connectivity between the PDU and the NetLinx Master. TEMP Connector The PDU measures temperature with an accuracy of 1 degree C) via a remote temperature probe. Temperature data is kept in non-volatile storage to retain across reboot. The 3.5mm Phoenix (2 pin) connector labelled “TEMP” allows you to connect a Remote Temperature Sensor (RTS) as an optional accessory (FIG. 8). The PDU comes with one ENV-VST-TSF Flush Mount Indoor Temperature Sensor (FG2050-21). Connect either wire from the RTS to either pin on the TEMP connector. FIG. 6 AxLink Connectors 1-8 The AxLink bus strip does not provide switching on AxLink data lines. FIG. 7 MASTER (4-pin AxLink) and TEMP (2-pin) Connectors This connector is always ON. FIG. 8 TEMP Connector PDU RTS The NXA-PDU-1508-8 is also compatible with the ENV-VST-TSO Outdoor Temperature sensor (optional).

NXA-PDU-1508-8 Power Distribution Unit (240V / 10A)

Preparing Captive Wires 1. Strip 0.25 inch (6.35 mm) of wire insulation off all wires. 2. Insert each wire into the appropriate opening on the connector according to the wiring diagrams and connector types described in this section. 3. Turn the flat-head screws clockwise to secure the wires in the connector. AxLink Data and Power Connections Connect the AxLink device’s AxLink connector to one of the AxLink connectors (1-8) on the rear panel of the PDU for data and 12 VDC power as shown in FIG. 9. AxLink Wiring Guidelines AxLink devices require 12 VDC power to operate properly. The necessary power is supplied via the AxLink cable. The maximum AxLink wiring distance is determined by power consumption, supplied voltage, and the wire gauge used for the cable. Use the 3-step formula below to calculate the maximum wiring lengths allowable between the PDU and connected AxLink devices. 1. < Total current consumption of all connected AxLink devices > x < Resistance/Foot > x 2 = < voltage drop per foot > (see table below for Resistance/Foot values.) 2. < Power supply voltage > - 12 VDC = < surplus voltage dissipation for cable run >. 3. / < voltage drop per foot > = Maximum distance in feet. The following table lists the resistance factors used in the formula. Do not over-torque the screws; doing so can bend the seating pins and damage the connector. FIG. 9 AxLink straight-thru wiring PWR AXP AXM GND AxLink Device NXA-PDU-1508-8 PWR AXP AXM GND (see note below) If the PDU is connected to a NetLinx Master that is self-powered (powered by a stand-alone power supply other than the PDU, or the DVX-2100HD which features an internal power supply), do not use the AxLink Power connection between the PDU and the NetLinx Master. Cable Gauge/Resistance Factors Solid Copper Wiring Stranded Copper Wiring Wire gauge Resistance/Foot Resistance/Foot 18 AWG .00639 .00692 20 AWG .0101 .01090 22 AWG .0162 .01690 24 AWG .0257 .02770

NXA-PDU-1508-8 Power Distribution Unit (240V / 10A)

CONFIG DIP Switch The NXA-PDU-1508-8 uses an 8-position DIP Switch (labelled “CONFIG”) to specify a unique device address for itself in a NetLinx Control System (FIG. 10). Setting the Device Address of the PDU The NXA-PDU-1508-8 firmware implements 8 AxLink device IDs, starting from the device ID denoted by the DIP switch. The device IDs used by the NXA-PDU-1508-8 are as follows: Dev 1: (Power Outlet 1) + (AxLink-Bank 1 Power) + (Input Voltage) + (Temp) Dev 2: (Power Outlet 2) + (AxLink-Bank 2 Power) Dev 3-8: (Power Outlets 3-8) To set the Device Address: 1. If connected, disconnect the power supply. 2. Set the CONFIG DIP switch according to the values shown below: The device number is set by the total value of DIP switch positions that are in the ON position. Note that the ON position is indicated on the DIP Switch. If you later change the device number, remove and reconnect the power connector to enter the new device number into memory. Power Outlets 1-8 The eight 100-240VAC 50/60 Hz, IEC C-13, 10A AC Power Outlet Connectors provide AC power to connected devices (FIG. 11). The PDU measures current use of each individual power outlet, including the two AxLink power outputs, with an accuracy of 0.1A. The PDU also reports the total current use of the entire unit. FIG. 10 CONFIG DIP Switch Switch 1 2 3 4 5 6 7 8 Value 1 2 4 8 16 32 64 128 1 2 3 4 5 6 7 8 Use the "Dip Switch2" software application to calculate dip switch position values (available to download from www.amx.com). FIG. 11 Power Outlets 1-8 8 5 4 3 2 1 6 7 Power Inlet Fuse compartment Power Outlets 1-8

NXA-PDU-1508-8 Power Distribution Unit (240V / 10A)

Power Inlet The IEC C-14, 10A Power Inlet Connector provides 100-240VAC, 50/60Hz mains power to the PDU (FIG. 11). The PDU measures the main input voltage with an accuracy of 1VAC The Power Inlet Connector is equipped with a safety fuse (10A @ 240VAC) Powering On the NXA-PDU-1508-8 When power is applied to the PDU for the first time, the outlets are powered in sequence (1-8), with a delay of 0.5 second between outlets. The factory default state of all outlets upon initial power-up is ON. By default, Persistence for all outlets is set to ON. Persistence can be turned off via the PERSIST SEND_COMMAND (see page 11). For subsequent power-ups (from a power off state or on system reset), the PDU will restore the last recorded state of any outlet in a sequenced fashion, starting from outlet 1 in numerical order, with a delay of 0.5 second between energizing any two outlets, assuming the default Persistence setting of ON has not been changed via the PERSIST command. When replacing the fuse, use only a 10A 240V Slo-Blo fuse Since the number of write cycles to the storage of the persistent data is limited, setting an outlet to PERSIST ON should only be used when absolutely necessary, and never for very frequent toggling operations.

NXA-PDU-1508-8 Power Distribution Unit (240V / 10A)

NetLinx Programming Device IDs The NXA-PDU-1508-8 uses 8 AxLink device IDs, starting from the device ID denoted by the DIP switch: Dev 1: Output 1 + AxLink Power 1 + Input Voltage + Temperature Dev 2: Output 2 + AxLink Power 2 Dev 3-8: Outputs 3-8 Supported SEND_COMMANDs SEND_COMMANDs PERSIST Configures the designated power outlet to return to the last state on loss of power or reset of the PDU. By default, a shipping PDU shall have all power outlets PERSIST setting ON. Syntax: PERSIST-= Variables: • may be ON or OFF • 1-8 for AC outlets, 9 and 10 for AxLink 1 and 2 bus power, respectively. Note: As there are limited write cycles to the storage of the persistent data, setting an outlet to PERSIST ON should only be used when absolutely necessary, and never for very frequent toggling operations. ?PERSIST Queries the PERSIST state of all outlets. Returns a comma-delimited list in the form: PERSIST-1=,2=,3=,4=,5=, 6=,7=,8=,9=,10= will be 1 for ON or 0 for OFF, (e.g.): PERSIST-1=1,2=0,3=0,4=0,5=0,6=0,7=0,8=0,9=1,10=0 ?PHASEANGLE Syntax: ?PHASEANGLE- Responds with: PHASEANGLE-= Note: "Phase angle" is the difference in phase between Voltage and Current, useful for determining inductive vs. capacitive loading. RESET Syntax: RESET Triggers a Power-On-Reset of the PDU. A Power-On-Reset toggles all interruptible power outlets. ?SERIAL Syntax: ?SERIAL Retrieves the 16-byte serial number assigned to the PDU. Responds with: SERIAL where is the 16-byte serial number assigned to the unit.

NXA-PDU-1508-8 Power Distribution Unit (240V / 10A)

Channels The PDU uses channels as specified in the following table. Relay On/Off: relay status Temp Scale: Off = C, On = F, The PDU measures temperature with an accuracy of 1 degree C) via a remote temperature probe. Temperature kept in non-volatile storage to retain across reboot. Power Sense: Signals that power (in watts) is above or below the specified trigger level (set via the TRIGGER command). SEND_COMMANDs (Cont.) TRIGGER Syntax: TRIGGER-= Sets the Power Sense Trigger of the specified outlet to the specified value in tenths of Watts. Note: A "Trigger" is a current level which will cause a power sense channel to activate if the current exceeds the value. ?TRIGGER Syntax: ?TRIGGER- Responds with: TRIGGER-= to report the trigger value in use on the outlet. VER Syntax: VER Responds with: Version (string) - example: "Vx.xx" ZAP! Syntax: ZAP! Restores all settings on the PDU to factory default settings. Unsupported options in responses are ignored / not reported. Channel Dev 1 Dev 2 Dev 3 Dev 4 Dev 5 Dev 6 Dev 7 Dev 8 1 Relay On/Off Relay On/Off Relay On/Off Relay On/Off Relay On/Off Relay On/Off Relay On/Off Relay On/Off 2 Temp Scale (off=C/on=F) 3 Ax 1 On/Off Ax 2 On/Off 255 Power Sense Power Sense Power Sense Power Sense Power Sense Power Sense Power Sense Power Sense

NXA-PDU-1508-8 Power Distribution Unit (240V / 10A)

Levels Power (W): Resolution to 0.1W (data scale factor = 10) Current (A): Resolution to 0.1A (data scale factor = 10) Voltage (V): Resolution to 0.1V (data scale factor = 10) Power Factor: W/VA, 2 decimal places (data scale factor = 100). "Power Factor " is the ratio of real power to apparent power. Energy (W-hr): Power over time, resolution to 0.1W-hr (Data scale factor = 10, writing 0 resets counter) Temp (Degrees C or F): Resolution to 0.1C (data scale factor = 10) Resetting Level 4 (Accumulated Energy Reading) The Level 4 value (accumulated energy reading) can be reset to 0 (zero) in three ways: 1. When the PDU is reset or power cycled, Level 4 will go to 0 on all outputs (see Powering On the NXA-PDU-1508-8 on page 9). 2. If SEND_LEVEL ,4,0 is sent, Level 4 will go to 0 on that output (if not already at 0). 3. The max value of the level is 65535, if that is exceeded the level will roll over to 0. Overcurrent Reporting The PDU reports alerts of overcurrent via the following AxLink string: OVERCURRENT-= 16-bit Level Dev 1 Dev 2 Dev 3 Dev 4 Dev 5 Dev 6 Dev 7 Dev 8 1 Power Power Power Power Power Power Power Power 2 Current Current Current Current Current Current Current Current 3 Power Factor Power Factor Power Factor Power Factor Power Factor Power Factor Power Factor Power Factor 4 Energy Energy Energy Energy Energy Energy Energy Energy 5 Input Voltage Ax Voltage 6 Ax 1 Power Ax 2 Power 7 Ax 1 Current Ax 2 Current 8 Temp For power factor, AMX has added an offset of 100 to the value to cope with the possibility of negative numbers. To obtain the correct value of the power factor, first subtract 100 from the level returned by the PDU, then divide by 100. Example: fPowerFactor1 = (LEVEL.VALUE-100)/100.0 //NB fPowerFactor1 is a FLOAT variable” The level range is 0-200. If reporting overcurrent for the entire unit, the outlet # is specified as 0 (zero).

6/11 ©2011 AMX. All rights reserved. AMX and the AMX logo are registered trademarks of AMX. AMX reserves the right to alter specifications without notice at any time.

3000 RESEARCH DRIVE, RICHARDSON, TX 75082 USA • 800.222.0193 • 469.624.8000 • 469-624-7153 fax • 800.932.6993 technical support • www.amx.com Increase Your Revenue through education + knowledge In the ever-changing AV industry, continual education is key to success. AMX University is dedicated to ensuring that you have the opportunity to gather the information and experience you need to deliver strong AMX solutions. Plus, AMX courses also help you earn CEDIA, NSCA, InfoComm, and AMX continuing education units (CEUs). Visit AMX University online for 24/7/365 access to: - Schedules and registration for any AMX University course - Travel and hotel information - Your individual certification requirements and progress