Biasi RIVA plus Installation & Operation Instructions
Read Online
Read the Biasi RIVA plus Installation & Operation Instructions online using the built-in PDF viewer.
Text of the manual
BOILER INSTALLATION, OPERATION
INSTRUCTIONS
WALL HUNG GAS BOILER FOR
CENTRAL HEATING SUPPLY
Please Read Instructions Carefully
Save for Future Reference
Do not store or use gasoline or other fl ammable vapors and liquids
—
in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
—
Do not try to light any appliance.
•
Do not touch any electric switch; do not use any phone in your
•
building.
Immediately call your gas supplier from a neighbor’s phone. Fol-
•
low the gas supplier’s instructions.
If you can not reach your gas supplier call the fi re department.
•
Installation and service must be performed by a qualifi ed installer,
—
service agency or the gas supplier.
WARNING: If the information in this manual is not followed
exactly, a fi re or explosion may result causing property dam-
age, personal injury or loss of life.
Riva PLUS
Riva PLUS
RIVA PLUS MANUAL
Dear Customer:
Thank you for buying a Biasi Riva Plus Boiler System.
The Riva Plus is a high ef ciency condensing, wall mounted gas boiler which provides central
heat supply water.
We realize that it is not possible to answer all questions about the Riva boiler system in this
manual. Reading this installation manual does not make the reader an expert in all aspects
of installation and operation, and does not replace the need for a quali ed, licensed heating
contractor. We urge you to contact your installing contractor or distributor if you are in question
about any aspect of your boiler’s performance. Our main concern is that you are satis ed with
your boiler and its performance. We require that your contractor complete ef ciency tests using
instruments.
The external controls and accessories listed in this manual (excluding those supplied inside
the boiler) are intended to serve as guidelines rather than speci c recommendations. We re-
alize that other makes and models of such devices are available and can be used as suc-
cessfully as those we specify. The installing contractor is the best judge of a system’s speci c
requirements, as well as the local availability of certain makes and models of controls and
accessories. The preceding does not apply, however, to the equipment that comes with every
boiler, such as the overheat control and pressure relief valves. The installation of the spe-
cifi c devices supplied with every boiler is absolutely necessary to the safe operation of
the boiler and protection of the heating system.
All BIASI wall hung boilers are built in accordance with the ASME boiler and pressure vessel
code, and bear the “H” stamp. The Entire range of applications for the Riva boiler has been
tested to standard CSA 4.9 and is CSA compliant.
This Riva Plus boiler has a 2 year warranty, a copy of which is provided with the boiler. Please
be sure to return the warranty registration card as the warranty will be void without your boiler’s
serial numbers (located on the ratings label af xed to the boiler), date of installation and the
name of your installer being on record in our les.
Thank you for purchasing our Riva Plus boiler. If you have questions or comments, please
don’t hesitate to contact us immediately. Our goal is 100% customer satisfaction.
QHT inc.
RIVA PLUS MANUAL
3
Table of Contents
Section Title
Section Number
Page Number
Warnings
-
5-6
Important Information
-
7
General Information
1
8
Technical Information (M135.30CR)
2
8-9
Parts List
3
10
Internal Piping and Parts List
4
11
Electric Diagrams
5
12-13
Sequence of Operation
5.1
13
Installation Location
6
14
Exhaust Pipe Location
7
15
Mounting Bracket
8
16
Venting
9
17-19
Restrictor Sizing
9.1
18
Fitting the Flue System
9.2
18
Choice of Flue
9.3
19-24
Pipe Connections
10
25
Gas Pipe Connections
11
26
Electrical Connections/Wiring
12
27-29
Power Connection
12.1
27
Connection to the Electricity Supply
12.2
27
Room Thermostat Connection
12.3
28
Relay Panel Control Connection
12.4
28
Zone Valve Microswitch Connection
12.5
29
Finishing
12.6
29
Circulator Sizing
13
30
Circ. Cap. as a Function of Flow Rate
13.1
30
Expansion Vessel
13.2
30
Piping
14
31-34
Primary-Secondary Piping
14.1
32
Primary-Secondary with Zone Valves
14.2
33
Manifold Piping with Zone Valves or Circ.
14.3
34
RIVA PLUS MANUAL
Table of Contents
Section Title
Section Number
Page Number
Commissioning
15
35-40
Initial Filling of the System
15.1
35
Lightning the Boiler
15.2
35
Checking the Gas Pres. at the Burner
15.3
36
Adjustment of the Gas Pressure
15.4
37
Checking the Ignition Device
15.5
37
Checking the Burner Ignition
15.6
38
Adjustment of the Useful c.h. Output
15.7
38
Labels Placement
15.8
39
Checking the Flue System and Comb
15.9
40
Instructing the User
15.10
40
Gas Conversion
16
41
Annual Maintenance
17
42-44
Warnings
17.1
42
Dismantelling the External Panels
17.2
42
Emptying the C.h. System
17.3
42
Cleaning the Primary Heat Exch.
17.4
43
Checking the Pressuris. in C.h. Vess.
17.5
43
Cleanig the Burner
17.6
43
Checking the Combustion Fan
17.7
43
Checking the Flue
17.8
43
Visual Inspection of Appliance
17.9
44
Gas Pressures and Soundness
17.10
44
Condensate trap
17.11
44
Venting Spare Parts
18
45-47
Separate Vent
18.1
45
Coaxial Vent
18.2
46
Roof Vent
18.3
47
Installer Notes
19
48
RIVA PLUS MANUAL
5
WARNING
DANGER
Boiler is certi ed as an indoor appliance. Do not install boiler outdoors or locate where it will
be exposed to freezing temperatures.
Caution: Do not store or use fl ammable materials, chemicals or fl ammable liquids,
especially gasoline, in the vicinity of this heating appliance.
Caution: Should overheating occur or the gas supply fail to shut off, do not turn
off or disconnect the electrical supply to the pump. Instead, shut off the gas
supply at a location external to the appliance.
Caution: Do not use this boiler if any part has been under water. Immediately
call a qualifi ed service technician to inspect the boiler and to replace any part of
the control system and any gas control which has been under water.
Do not store or use gasoline or other fl ammable vapors and liquids in the
—
vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
—
Do not try to light any appliance.
•
Do not touch any electric switch; do not use any phone in your build-
•
ing.
Immediately call your gas supplier from a neighbor’s phone. Follow the
•
gas supplier’s instructions.
If you can not reach your gas supplier call the fi re department.
•
Installation and service must be performed by a qualifi ed installer, ser-
—
vice agency or the gas supplier.
WARNING: If the information in this manual is not followed
exactly, a fi re or explosion may result causing property dam-
age, personal injury or loss of life.
RIVA PLUS MANUAL
WARNING
Any appliance that burns natural gas, propane gas, fuel oil, wood or coal is capable of pro-
ducing carbon monoxide (CO). Carbon Monoxide (CO) is a gas which is odorless, colorless
and tasteless but is very toxic. CO is lighter than air and thus may travel throughout the
building.
BRIEF EXPOSURE TO HIGH CONCENTRATIONS OF CO, OR
PROLONGED EXPOSURE TO LESSER AMOUNTS OF CO MAY
RESULT IN CARBON MONOXIDE POISONING. EXPOSURE CAN BE
FATAL AND EXPOSURE TO HIGH CONCENTRATIONS MAY RESULT
IN THE SUDDEN ONSET OF SYMPTOMS INCLUDING
UNCONSCIOUSNESS.
Symptoms of CO poisoning include the following:
dizziness
vision problems
shortness of breath
headache
loss of muscle control
unclear thinking
nausea
weakness
unconsciousness
The symptoms of CO poisoning are often confused with those of in uenza, and the highest
incidence of poisoning occurs at the onset of cold weather or during u season.
A victim may not experience any symptoms, only one symptom, or a few symptoms.
Suspect the presence of carbon monoxide if symptoms tend to disappear when you
leave your home.
The following signs may indicate the presence of carbon monoxide:
Hot gasses from appliance, venting system pipes or chimney, escaping into the living
•
space.
Flames coming out around the appliance.
•
Yellow colored ames in the appliance.
•
Stale or smelly air.
•
The presence of soot or carbon in or around the appliance.
•
Very high unexplained humidity inside the building.
•
If any of the symptoms of CO occur, or if any of the signs of carbon monoxide are present,
VACATE THE PREMISES IMMEDIATELY AND CONTACT A QUALIFIED HEATING SER-
VICE COMPANY OR THE GAS COMPANY OR THE FIRE DEPARTMENT.
ONLY QUALIFIED, LICENSED SERVICE CONTRACTORS SHOULD PERFORM WORK
ON YOUR BIASI RIVA PLUS BOILER.
RIVA PLUS MANUAL
7
IMPORTANT INFORMATION
Please read this page carefully.
ALL BOILERS MUST BE INSTALLED IN ACCORDANCE WITH NATIONAL,
•
STATE AND LOCAL PLUMBING, HEATING AND ELECTRICAL CODES
AND ORDINANCES, AS WELL AS THE REGULATIONS OF THE SERVING
ELECTRICAL, WATER AND GAS UTILITIES.
All systems should be designed by competent contractors, and only persons
•
knowledgeable in the layout and installation of heating systems should attempt
the installation of any boiler. It is the responsibility of the installing contractor
to see that all controls are correctly installed and operating properly when the
installation is completed.
This boiler is intended for use, only with propane or natural gas. All fl ammable
•
liquids (especially gasoline), chemicals, rags, paper, wood scraps, debris, etc.,
should be kept away from the boiler at all times. Keep the boiler area clean and
free of all fi re hazards.
Please read the literature and warranties supplied by the manufacturers of the
•
various accessory equipment. This equipment is warranted by the respective
manufacturers, not by Quincy Hydronic Technologies, Inc. Each piece of
equipment must be installed and used according to the recommendations of
the manufacturer.
Codes and Regulations:
Installation of the boiler and related equipment must conform to national, state and
local regulating agencies and codes applicable to the installation of the equipment. In
the absence of local requirements, the following codes apply:
A. ANSI/NFPA - #70 National Electric Code
B. ANSI/NFPA - #211 Chimneys and Vents
C. ANSI/NFPA - #Z223.1 National Fuel Gas Code
C. ANSI/NFPA - Domestic Gas Conversion Burner
D. CAN/CGA
- B149 Installation Codes
E. ANSI/ASME - CSD-1
The above codes are available from:
National Fire Protection Association (NFPA)
CSA International
Battery March Park
8501 E. Pleasant Valley Road
Quincy, Massachusetts, 02269
Cleveland, OH 44134-5575
http://www.nfpa.org
http://www.csa-international.org
RIVA PLUS MANUAL
General Information
1.
Technical Information (M135.30CR)
2.
The Riva Plus is a high ef ciency condensing, wall mounted gas boiler which provides central
heat. The boiler features a gas valve which modulates the energy input from
49476 BTU/h to 116008 BTU/h. The boiler is shipped fully assembled with the components list-
ed on page 11. All units are pressure and combustion tested at the factory prior to shipping.
Key Features:
Wall mountable - saving valuable oor
•
space.
Several ue options available
•
Electronic spark ignition
•
Safety ow switch - positioned on the
•
main circuit, which monitors the ow and
protects the main heat exchanger from
thermal shock should there be a lack of
water in the system.
Frost protection - contains an integral frost
•
protection system to prevent frost dam-
age which can occur in areas susceptible
to very cold weather conditions.
Boiler operation recognition system -
•
should the boiler not be used for longer
than 24 hours, it then performs a control-
led system test to ensuring the motorized
components within the boiler do not be-
come inoperable due to lack of use.
Gas valve modulation - the gas input
•
modulates based off central heating tem-
perature to within ± 2 ºF
Diagnostic information system equipped
•
with three LED diagnostic lights for quick
error assessment.
GENERAL
Height
in
31.6
Width
in
15.8
Depth
in
13.8
Weight
lb
98.1
CENTRAL HEATING
Maximum working temp.
°F
185
Temp. Regulation range*
°F
100-176
Maximum pressure
psi
30.0
Minimum pressure
psi
4.35
Max head loss (at 4.4 GPM)
ft
8.3
*At the minimum useful output
RIVA PLUS MANUAL
9
2. Technical Information Cont.
ENERGY CAPACITY
Nominal heat input
(0/2000ft)
MBH
116.0
Nominal heat input
(2000/4500ft)
MBH
110.2
Minimum heat input
MBH
49.5
Maximum useful output
(0/2000ft)
MBH
102.0
Maximum useful output
(2000/4500ft)
MBH
97.2
Minimum useful output
MBH
41.6
GAS SUPPLY PRESSURE
Gas
Normal
Min
Max
Natural
inwc
7.0
3.5
10.5
Propane
inwc
11.0
8.0
13.0
GAS PRESSURE AT BURNER
Gas
Min
Max
Ignition
Natural
inwc
1.0
4.8
2.4
Propane
inwc
2.0
10.3
5.1
FLUE DESIGN
Minimum Venturi pressure
inwc
0.64
Flue pipe diameter
Coaxial
in
2.25/4
3.25/5
Twin split pipes
in
3.25/3.25
Nominal heat ow rate
(0/2000ft)
MBH
116.0
Nominal heat ow rate
(2000/4500ft)
MBH
110.2
Min Exhaust temperature
°F
158
Max Exhaust temperature
°F
158
INJECTORS No. Size
Natural
14
130
Propane
14
85
GAS FLOW RATE
Gas
Min
Max
Natural
ft³/h
48.7
115.1
Propane
lb/h
2.23
5.25
ELECTRICAL
Voltage
V
120
Frequency
Hz
60
Current
A
1.6
Power consumption
W
180
FLUE GAS FIGURES
Gas
Min
Max
CO2
2.5%
6.3%
O2
16.5%
9.7%
CLEARANCE TO COMBUSTIBLES
Front
in
18
Back
in
0
Top
in
8
Sides
in
2
Bottom
in
8
Flue pipe enclosed
in
2
Flue pipe free air
in
0
10 RIVA PLUS MANUAL
Parts List
3.
Primary Components:
1
Pump
2
Pump vent plug
3
Automatic air purger valve
4
Modulation gas valve
5
Flame-detecting electrode
6
Ignition electrodes
7
Burner
8
Combustion chamber
9
Primary heat exchanger
10 Fan
11 Air pressure switch
12 Air switch pres. Test points
13 Safety thermostat
14 Modulation operator
15 Gas valve outlet pres. Test point
16 Gas valve inlet pres. Test point
17 Central heating expansion vessel
18 Central heating temp. Probe NTC
19 Central heating pressure relief valve
20 Primary circuit ow switch
21 Main circuit drain cock
22 By-pass valve
23 Venturi device
24 Flue outlet pipe
25 Air Intake Pipe
26 Control panel
27 Safety thermostat probe
28 Pressure reducing automatic ll valve
29 Back ow preventer
30 Gas supply line cock
31 Water supply inlet cock
32 Condensate trap
33 Condensing heat exchanger
34 Flue termostat
RIVA PLUS MANUAL
11
Internal Piping & Parts List
4.
14
4
15
16
7
9
11
27
3
1
18
20
22
21
19
17
24
15
25
33
10
5
c
32
Note: Pressure Relief Valve (#19) should be piped to a drain or to the oor as lose as pos-
sible to a drain.
12 RIVA PLUS MANUAL
Electric Diagrams
5.
ye bk wh gy bu rd
bk
gy
gy
gy
M
~
t
C.h. temperature
probe NTC
Pump
Gas
Valve
COM
NO
M
~
COM
NO
NC
1 2 3
bk
bu
bn
rd
rd
gnye
gy
wh
bu
rd
bk
bu
wh
gy
bu
gnye
bkbk
u
b
e
y
n
g
y
g
bk
bk
bu
bu
bu
bu
rd
bk
y
g
y
g
L
N
rd bu bn
gnye
gnye
gnye bu
bn
bu
rd
gnye
Primary Circuit
Flow Switch
External
controls
terminal
block
Electric supply
terminal
block
Fan
Safety
Thermostat
Air Pressure
Switch
Ignition
Electrodes
Flame Detection
Electrode
bn - brown
bu - blue
bk - black
wh - white
rd - red
gy - grey
ye - yellow
gnye - green/yellow
wh
gy
rd
rd
bk
bu
bn
gy
ye
wh
burd
bk
rd
Thermostat
Flue
Caution: Label all wires prior to disconnection when
servicing controls. Wiring errors can cause im-
proper and dangerous operation.
Verify proper operation after servicing
14 RIVA PLUS MANUAL
Installation Location
6.
The installation location chosen must:
Comply with all clearances listed below.
•
Provide suitable location for the exhaust and intake venting.
•
Not be installed in an unheated space.
•
Comply with all local codes and standards.
•
Note: Dimensions shown are minimums. Greater clearances will simplify installation
and service.
Figure 6.1
WARNING: Do not install the boiler on carpeting
If the boiler is to be installed in an enclosed room with no fresh air intake, the room must have
proper vent louvers installed. There should be two louvers, place each within 12” of the ceiling
and oor respectively. Each vent will have a free area of 54 square inches.
8.0 in
31.6 in
15.2 in
3.0 in
18.0 in
2.0 in
15.8 in
10.0 in
2.0 in
CLOSET INSTALLATION
MINIMUM PERMANANT
CLEARANCE
FRONTV
I
S
W
E
I
DE VIEW CLOSET
INSTALLATION
CLOSET INSTALLATION
SERVICECLEARANCE
Figure 6.2
Outside
Air Opening
Air Opening
Each opening free area =
1 sq. inch per 2,000 BTU/h
0 to 12"
0 to 12"
When choosing an installation location insure the exhaust and intake pipes comply with NFPA
54. The drawing on the next page illustrates the restrictions on exhaust locations.
Note: For boilers in an enclosed space
it is recommended to install a CO
detector in the boiler room.
RIVA PLUS MANUAL
15
Exhaust Pipe Location
7.
CAUTION
EXTERNAL VENT SURFACES ARE HOT.
IT IS RESPONSABILITY OF THE HOMEOWNER TO KEEP THE VENT
TERMINAL CLEAR OF SNOW AND ICE
NOTE: USE ONLY LISTED COMPONENTS SUPPLIED WITH THE BOILER. SURFACE
DISCOLORATION OF THE BUILDING MAY OCCUR DUE TO IMPROPER INSTALLATION. QHT
WILL NOT ACCEPT RESPONSIBILITY OR LIABILITY FOR SUCH DISCOLORATION.
The Exhaust Hood must be installed on the leeward side of house and conform to the
following guidelines:
The Vent hood shall not be less than 3 feet above any forced air inlet to the house.
1.
The Vent hood shall not be less than 1 feet below, 1 foot horizontally, or 1 foot above any door,
2.
window or gravity inlet into any building.
The Vent hood shall not be less than 2 feet from an adjacent building.
3.
The Vent hood shall be not less than 7 feet above grade when located adjacent to public
4.
walkway.
The Vent hood shall be located so that ue gasses are not directed to jeopardize people, overheat
5.
combustible structures, materials or enter buildings.
Minimum of 4 feet horizontal clearance from electric meters, gas meters, regulators and relief
6.
equipment.
All joints in system are to be sealed to prevent leakage of products of combustion in the
7.
building.
Avoid installing exhaust hood on the North, West, or the side of the house receiving the prevailing
8.
winds.
The vent should not be situated so that the ue gases are directed towards brickwork, siding,
9.
or other construction, in such a manner that may cause damage from heat or condensate from
the ue gases
16 RIVA PLUS MANUAL
Mounting Bracket
8.
After a suitable installation location is chosen, verify that the mounting wall is properly
braced and strong enough to support the 110 pound weight of the unit when fi lled with
water.
NOTE: The boiler shall be installed such that the gas ignition system components are
protected from water and liquids in general (dripping,spraying, rain, etc) during
the appliance operation and service.
Use the paper template provided with the boiler to determine the location of the mounting
bracket. Securely mount the bracket to the wall using appropriate hardware for the particular
wall construction.
Mounting Steps:
Tape the paper template to the wall in the chosen location. Be sure to level the template.
1.
Pre-drill two holes in the center of the “oval” slots on the mounting bracket, sized for the
2.
hardware being used.
Mount the bracket to the wall. Be sure to level the bracket by adjusting the screw in the
3.
vertical slot.
Pre-drill the remaining hole in the mounting bracket and secure the nal screw.
4.
Mark and drill the exhaust/intake pipe holes through the house. If you are using a coaxial
5.
pipe system, drill the hole marked A (ø 4”) in the drawing below and on the paper template.
If you are using a separate pipe system drill holes marked B and C (ø 3.25”) shown below
as well as on the paper template.
Remove paper template and hang boiler on bracket.
6.
Figure 8.1
A, B, C
8.9
6.9 gas
6.5
7.9
15.2
B
Ø 3.1
Ø 3.1
27.6
9.6
15.8
7.7
Ø 4.0
C
2.9
7.9
.9
1
2
1.4
4.5
5.6
0.6
1.2
1.4
4.6
2.5 2.6
10.1
3.9
2.4
2.4
Condense
A
31.6
RIVA PLUS MANUAL
17
Venting
9.
The Riva is a mechanical draft, side wall vented boiler. There are two side wall ue options
available – separate and coaxial. The coaxial option has one con guration shown on the next
page. The separate option has two possible con gurations shown on the following pages.
There is also a vertical roof venting option. Regardless of what vent kit is installed, they should
all conform to the Provisions for combustion and ventilation air in accordance with sec-
tion 5.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, ANSI Z223.1,
or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149, Installation Codes, or applicable provi-
sions of the local building codes.
If the Biasi Riva replaces a boiler that was attached to a common vent system, the common
venting system is likely to be too large for proper venting of the appliances remaining con-
nected to it. To ensure the remaining appliances will function properly, the test procedure below
should be followed:
At the time of removal of an existing boiler, the following steps shall be followed with each
appliance remaining connected to the common venting system placed in operation, while the
other appliances remaining connected to the common venting system are not in operation.
(a) Seal any unused openings in the common venting system.
(b) Visually inspect the venting system for proper size and horizontal pitch and determine
there is no blockage or restriction, leakage, corrosion and other de ciencies which could
cause an unsafe condition.
(c) Insofar as is practical, close all building doors and windows and all doors between the
space in which the appliances remaining connected to the common venting system are
located and other spaces of the building. Turn on clothes dryers and any appliance not
connected to the common venting system. Turn on any exhaust fans, such as range
hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate
a summer exhaust fan. Close replace dampers.
(d) Place in operation the appliance being inspected. Follow the lighting instructions. Adjust
thermostat so appliance will operate continuously.
(e) Test for spillage at the draft hood relief opening after 5 minutes of main burner opera-
tion. Use the ame of a match or candle, or smoke from a cigarette, cigar or pipe.
(f) After it has been determined that each appliance remaining connected to the common
venting system properly vents when tested as outlined above, return doors, windows,
exhaust fans, replace dampers and any other gas-burning appliance to their previous
condition of use.”
(g) Any improper operation of the common venting system should be corrected so the
installation conforms with the National Fuel Gas Code, ANSI Z223.1 and/or CAN/CGA
B149, Installation Codes. When resizing any portion of the common venting system,
the common venting system should be resized to approach the minimum size as de-
termined using the appropriate tables in Part 11 of the National Fuel Gas Code, ANSI
Z223.1 and/or CAN/CGA B149, Installation Codes.
18 RIVA PLUS MANUAL
Restrictor sizing
9.1
fi tting the fl ue system
9.2
Figure 9.1
Figure 9.2
Table 9.1
9. Venting Cont.
RIVA PLUS MANUAL
19
Choice of fl ue:
9.3
The following ue kits are available for connecting to the boiler:
A
Standard coaxial horizontal fl ue kit (Exhaust & intake outside)
(Coaxial 2.4/4.0 inches – nominal lenght 3.3 ft)
Figure 9.3
It can be tted to allow discharge to the rear or either side of the boiler via the anged
boiler adapter elbow. Minimum lenght required is 2.9 ft. Maximum equivalent lenght of
8.8 ft can be achieved utilising extensions. This ue system can only be used to dis-
charge horizontally; it is not designed to enable termination in the vertical plane.
Installation:
Drill hole A (on the wall template) through the outside wall that is less than 18” thick.
•
Cut the pipe as necessary so that a no more than 6” protrudes from the house.
•
Slide the intake and exhaust pipes through the hole.
•
Slide one rubber wall trim piece on the pipe from inside and one from outside.
•
Connect exhaust (inner) pipe to concentric elbow.
•
Connect intake (outer) pipe to concentric elbow.
•
Secure elbow to boiler using gasket and four screws provided.
•
Secure end cap on the intake pipe outside the house.
•
9. Venting Cont.
20 RIVA PLUS MANUAL
9. Venting Cont.
B
Standard separate horizontal fl ue kit (Exhaust & intake outside)
(Twin pipe
Figure 9.4
φ 3.25 in)
Various twin (split) pipes kits and optional accessories (elbows) are available to assist in
the termination of the ue where the boiler is installed in a location remote to an outside
wall. These kits allow for separation of the air supply pipe from the pipe that discharges
the exhaust gasses. Consequently it is possible to extend the ue system to a greater
distance than that provided by the standard coaxial horizontal ue.
If either an additional 45° or 90° accessory elbow is used then the maximum permis-
sible lenght of either pipe must be reduced by 3.0 ft or 5.4 ft respectively. The sum of the
lenghts of the two horizontal part must be less than 49.2 ft.
Installation:
Drill holes B & C (on the wall template) through the outside wall that is less than 18” thick
•
Cut the pipes as necessary so that no more than 6” of intake pipe protrudes from the
•
house and the exhaust pipe is a minimum of 4 inches longer than the intake pipe.
Slide the Intake and exhaust pipes through the respective holes.
•
Slide one rubber wall trim piece on each pipe from inside and one from outside.
•
Attach each collar to the boiler with the gasket and screws provided.
•
Insert each elbow into its corresponding collar.
•
Connect each pipe to its corresponding elbow (as shown in the diagram).
•
Secure end cap on the intake and exhaust pipe outside the house.
•
RIVA PLUS MANUAL
21
9. Venting Cont.
C
Alternative separate confi guration (Exhaust outside & intake inside)
(Twin pipe
Figure 9.5
φ 3.25 in)
This con guration of the twin pipe kit allows to discharge the exhaust gasses outside.
The air supply is obtained with an air intake pipe. This allows to take air from the room
where the boiler is installed.
If either an additional 45° or 90° accessory elbow is used then the maximum permissible
lenght of either pipe must be reduced by 3.0 ft or 5.4 ft respectively.
Note: When utilizing this option, see page 14 for room ventilation details.
Installation:
Drill hole C (on the wall template) through the outside wall that is less than 18” thick.
•
Cut the pipe as necessary so that no more than 6” protrudes from the house.
•
Slide the exhaust pipe through the hole.
•
Slide one rubber wall trim piece on the pipe from inside and one from outside.
•
Attach each collar to the boiler with the gasket and screws provided.
•
Insert each elbow into its corresponding collar.
•
Connect each pipe to its corresponding elbow.
•
Test Ports
Exhaust Collar
Exhaust Elbow
Exhaust Pipe
Rubber Wall Trim (2X)
Exhaust Pipe End Cap
Air Intake Elbow
Air Intake Pipe
Air Intake Collar
22 RIVA PLUS MANUAL
9. Venting Cont.
D
Alternative separate kit (Exhaust outside & intake inside)
(Twin Pipe
Figure 9.6
φ 3.25 in)
This con guration of the twin pipe kit allows to discharge the exhaust gasses outside.
The air supply is obtained with an air intake pipe. This allows to take air from the room
where the boiler is installed.
If either an additional 45° or 90° accessory elbow is used then the maximum permissible
lenght of either pipe must be reduced by 3.0 ft or 5.4 ft respectively.
Note: When utilizing this option, see page 14 for room ventilation details.
Installation:
Drill hole C (on the wall template) through the outside wall that is less than 18” thick.
•
Cut the pipe as necessary so that no more than 6” protrudes from the house.
•
Slide the exhaust pipe through the hole.
•
Slide one rubber wall trim piece on the pipe from inside and one from outside.
•
Attach each collar to the boiler with the gasket and screws provided.
•
Insert each elbow into its corresponding collar.
•
Connect each pipe to its corresponding elbow.
•
RIVA PLUS MANUAL
23
9. Venting Cont.
E
Alternative separate kit (Exhaust & intake outside)
(Twin Pipe
Figure 9.7
φ 3.25 in)
These kits allow for separation of the air supply pipe from the pipe that discharges the
exhaust gasses. Consequently it is possible to extend the ue system to a greater dis-
tance than that provided by the standard coaxial horizontal ue.
If either an additional 45° or 90° accessory elbow is used then the maximum permis-
sible lenght of either pipe must be reduced by 3.0 ft or 5.4 ft respectively. The sum of the
lenghts of the two horizontal part must be less than 49. ft.
Installation:
Drill holes B & C (on the wall template) through the outside wall that is less than 18” thick.
•
Cut the pipes as necessary so that no more than 6” of intake pipe protrudes from the
•
house and the exhaust pipe is a minimum of 4 inches longer than the intake pipe.
Slide the Intake and exhaust pipes through the respective holes.
•
Slide one rubber wall trim piece on each pipe from inside and one from outside.
•
Attach each collar to the boiler with the gasket and screws provided.
•
Insert each elbow into its corresponding collar.
•
Connect each pipe to its corresponding elbow (as shown in the diagram).
•
Secure end cap on the intake and exhaust pipe outside the house.
•
24 RIVA PLUS MANUAL
9. Venting Cont.
F
Standard Vertical-roof kit (Exhaust & intake outside)
(vertical pipe
Figure 9.8
φ 3.1 / φ 4.9 in)
This kit allows vertical termination of the ue pipe through the roof. The kit is 1.2 min
length. Extension pieces (Co--axial) are also available which allows the ue system to
be extended to a total overall maximum permissible length.
Optional 45° and 90° elbows can be used to offset the ue route.
Each additional elbow reduces the overall acceptable length of the ue system as fol-
lows:
45° reduce length by 1.6 ft.
90° reduce length by 3.2 ft.
Installation:
Drill hole through the outside roof.
•
Cut the pipe as necessary.
•
Slide the intake and exhaust pipes through the hole.
•
Slide one rubber wall trim piece on the pipe from inside and one from outside.
•
Connect exhaust (inner) pipe to concentric elbow.
•
Connect intake (outer) pipe to concentric elbow.
•
Secure elbow to boiler using gasket and four screws provided.
•
Secure end cap on the intake pipe outside the house.
•
RIVA PLUS MANUAL
25
Pipe Connections
10.
The Riva boiler is supplied with a 3/4” stainless steel gas pipe (A in gure 10.1), 2 - 3/4” copper
pipe (C,D in gure 10.1), located in a plastic bag in the boiler package.
Figure 10.1
Stainless steel gas pipe
A)
Main circuit drain cock
B)
C.h. supply copper pipe
C)
C.h. return copper pipe
D)
C.h. PRV discharge copper pipe
E)
Condensate trap
F)
Installation:
Remove the protective caps off boiler connections (Figure 10.1).
•
Thoroughly clean the connections.
•
Attach the supplied components to the boiler connections (see Figures 10.1). Be sure to
•
use the proper gaskets for the pipe connections.
Attach the condensate trap to an appropriate drain pipe.
•
Before connecting the boiler to the heating system piping, review the suggested piping dia-
•
grams in Section 4 (page 11).
If the c.h. system is above the boiler level, it is advisable to install c.h. cocks close to the
•
boiler for servicing operation
Condensate trap:
The condensate trap allows the discharge of the condensate via the condensate drain pipe
avoiding in the mean timethe escape of combustion products. A plastic ball closes the trap
outlet in case that the trap is empty. The condenste trap is provided with two electrodes: if the
drain pipe is plugged or in any case in which the condensate isn’t correctly evacuated, the
condensate level in the trap rises putting in contact the electrodes thus causing the boiler lock-
out.
26 RIVA PLUS MANUAL
Gas Pipe Connections
11.
Gas supply piping is to be sized and installed properly in order to provide a supply of gas suf -
cient to meet the maximum demand without undue loss of pressure between the meter and the
boiler. Consult with the National Fuel Gas Code ANSI Z223.1 for proper sizing of gas piping
for various lengths and diameters.
Figure 11.1
Direction of flow
B
A
F
E
D
C
Manual T-handle Shutoff Valve
A)
Pressure Gauge Port
B)
Flexible Gas Line to Burner
C)
Male Union ¾” NPT
D)
Pipe Cap
E)
1” X 1” X ¾” TEE
F)
Note: Height of valve above ground level to
conform to local codes, if any. Massa-
chusetts statecode requires gas shut
off to be a tee handled gas cock.
Locate a drop pipe adjacent to, but not in front of the boiler. Locate a tee (F) in the drop pipe at
the same elevation as the gas inlet connection to the boiler. Extend the drop line with a nipple
towards the oor and cap to form a sediment trap (E). Install a shut off valve (A) before the tee
with sediment trap and a union after the tee before the combination gas valve (D).
When installing the boiler, make sure a pipe compound resistant to the action of lique ed petro-
leum is used. Check piping for leaks. Always check leaks with a water and soap solution.
The boiler and its gas connection must be leak tested before placing the boiler in operation.
The boiler and its individual shutoff valve must be disconnected from the gas supply piping sys-
tem during any pressure testing of that system at test pressures in excess of 1/2 psi (3.5 kPa).
WARNINGS
DO NOT USE A FLAME FOR CHECKING GAS LEAKS
RIVA PLUS MANUAL
27
Electrical Connections/Wiring
12.
Figure 12.1
Removing Front Panel:
Remove the front panel by removing screws A
•
and sliding the front panel up and away from
the boiler
Removing Side Panel:
Remove screws B
•
Figure 12.2
A
A
B
B
C
C
B
B
Removing Control Panel:
Remove screws C.
•
Figure 12.3
Move the lower part of the side panels ( gure
•
12.3).
Pull the control panel. When completely pulled
•
out, the panel can rotate 45° downward.
Figure 12.4
Loosen screws D and remove the service
•
panel (Fig. 12.4).
D
D
D
Power Connection:
12.1
For the electrical connection to the boiler use electric wires which conform to local regulations.
The boiler, when installed ,must be electricallybonded to ground in accordance with the require-
ments of the authority having jurisdiction or, in the absence of such requirements,with the Na-
tional Electrical Code,ANSI/NFPA 70 and/or Canadian
Electrical Code Part I CSA C22.1, Electrical Code.
Connection to the electricity supply:
12.2
Connect the electrical supply cable coming from the fused spur isolation switch to the power supply
•
terminal block of the boiler (as shown in gure 12.5) keeping the same connections for the live wire
and the neutral wire
Figure 12.5
Connect the earth wire(yellow/green). Boiler must be wired directly to earth ground on breaker panel.
•
1
2
L
N
3
To fused spur
isolation switch
Power supply
terminal block
External controls
terminal block
120 VAC
15 AMP BREAKER
Service Man's Switch
Fire - O - Matic
WARNING
Note: Do not connect live wires to
thermostat terminals 1-3.
28 RIVA PLUS MANUAL
12. Electrical Connections/Wiring Cont.
Room Thermostat Connection:
12.3
The room thermostat must be connected
•
to the terminal block situated next to the
control panel.
Figure 12.6
Any external controls and connection lines
•
must be rated at 120 VAC but under no
circumstances should external live volt-
age be connected to the room thermostat
link on the boiler.
1
2
L
N
3
To fused spur
isolation switch
Power supply
terminal block
External controls
terminal block
J
120 VAC Control
Terminal Block
Relay Panel Connection:
12.4
When connecting any type of external
•
control, the jumper J in Fig. 12.6 must be
removed.
The room thermostat must be connected
•
to the “Control Terminal Block” (Fig 12.7).
Figure 12.7
Connect the room thermostat between
•
terminals 1 and 3 as shown in Fig. 12.7.
Power supply
terminal block
External controls
terminal block
T
Room thermostat
1
2
L
N
3
(120V rating)
The relay control must be connected to
•
the terminal block situated next to the
control panel.
Figure 12.8
When connecting any type of relay con-
•
trol, the jumper J in Fig. 12.8 must be re-
moved.
1
2
L
N
3
To fused spur
isolation switch
Power supply
terminal block
External controls
terminal block
J
120 VAC Control
Terminal Block
Connect the dry contact switch of the re-
•
lay panel to the 120 VAC control terminal
block (Fig 12.9).
Figure 12.9
Connect the dry contact switch to termi-
•
nals 1 and 3 shown in Fig. 12.9.
Power supply
terminal block
External controls
terminal block
Generic Relay Control
1
2
L
N
3
(120V rating)
T
RIVA PLUS MANUAL
29
12. Electrical Connections/Wiring Cont.
Zone Valve Micro Switch Connection:
12.5
The zone valve micro switch must be con-
•
nected to the terminal block situated next
to the control panel.
Figure 12.10
When connecting the zone valve switch,
•
the jumper J in Fig. 12.10 must be re-
moved.
1
2
L
N
3
To fused spur
isolation switch
Power supply
terminal block
External controls
terminal block
J
120 VAC Control
Terminal Block
Figure 12.11
Connect the micro switch of the zone
•
valve to terminals 1 and 3 as shown in g-
ure 12.11
Connect the zone valve switch to the room
•
thermostat as shown in gure 12.11
120 VAC
Control Terminal
Block
1
L
N
3
V
T
Zone
Valve
Room
Thermostat
Finishing
12.6
Route the electrical supply cord and the external control cord as illustrated in Fig. 12.12.
•
Figure 12.12
Lock the cords in place with the exible cord clamps.
•
Replace the control panel reversing the steps on page 27.
•
To the fused spur
To the external
control device
isolation switch
30 RIVA PLUS MANUAL
Circulator Sizing
13.
Circulator capacity as a function of fl ow rate:
13.1
Figure 13.1
The hydraulic specifi cation in Fig 13.1 represent the pressure (available head for the
central heating system) as a function of the fl ow rate. The pressure loss due to the in-
ternal piping in the boiler has already been substracted.
When determining proper piping of the heating system, verify that the internal boiler circulator
will overcome the head loss of the system at the designed ow rate using the graph above.
If the internal circulator is adequate, direct system piping can be utilized. See section 4 page
11 for suggested direct supply/return piping.
If the internal circulator is inadequate, a secondary circulator must be utilized. See sections 14
for suggested primary/secondary piping.
Expansion vessel:
13.2
The height difference between the C.h. PRV (19 on page 10) and the highest point in the sys-
tem may be 23 ft at most. For greater differences, increase the pre-load pressure in the C.h.
expansion vessel (17 on page 10) and the system when cold, by 0.1 bar for additional 3.3 ft. For
systems with volumes greater than 154l, an additional expansion vessel must be provided.
RIVA PLUS MANUAL
31
Piping
14.
All external piping components are to be supplied by the installer. It is very important to use a
Primary Secondary piping scheme when an external circulator will be used. Also, when the
boiler is piped in a primary secondary manner, it is necessary to us the central heating ow
restrictor supplied with the boiler. The ow restrictor ensures that there will be enough back
pressure to make the central heating ow switch in a low head loss piping system like primary
secondary.
Installation of ow restrictor: The ow restrictor is installed inside the pipe tail that
attaches to the boiler. Place the ow restrictor into the
gasket for the central heating supply pipe tail. Place the
gasket on the pipe tail so the ow restrictor seats into
the pipe tail. Then install the pipe tail onto the boiler.
There are two methods for accomplishing a Primary Secondary piping system. The rst is
to use two closely spaced tees for the boiler supply and return. An example is shown below
in Figure 14.1. The run legs should be sized so that there is no excessive head loss on the
external circulator that is installed. In most circumstances 1 ¼” piping will be the best choice.
When the boiler is piped in this way, the external circulator will not have any hydraulic effect on
the Riva boiler. This is essential to ensure that the ow switch will operate properly.
The second method is a hydraulic separator. Hydraulic separators are available commercially;
however you can also construct your own. An example of a hydraulic separator is given in
Figure 14.2. It is important that the separator be at least 2” in size to ensure proper perfor-
mance.
Must be less than 8"
Boiler
Return
Boiler
Supply
System
Return
System
Supply
1 ¼”
¾”
2"
No more than 8"
At least 16"
1 ¼”
¾”
System
supply
System
return
Boiler supply
Boiler Return
32 RIVA PLUS MANUAL
Primary – Secondary Piping:
14.1
All external piping components are to be supplied by the installer.
It is very important to use a hydraulic separator before secondary circulators.
14. Piping Cont.
RIVA PLUS MANUAL
33
14. Piping Cont.
Primary – Secondary Piping with Zone Valves:
14.2
All external piping components are to be supplied by the installer.
It is very important to use an hydraulic separator before secondary circulators.
34 RIVA PLUS MANUAL
14. Piping Cont.
Manifold Piping with Zone Valves (shown conn. to radiators):
14.3
All external piping components are to be supplied by the installer.
RIVA PLUS MANUAL
35
Commissioning
15.
Initial fi lling of the system:
15.1
Remove the front panel of the case.
•
Unscrew the cap on the automatic air
•
purger valve 3 (Fig 15.1) one full turn and
leave open permanently.
Figure 15.1
Open the installer supplied automatic ll
•
valve between the cold water inlet and
Central Heating System (See 28 on pip-
ing diagrams in previous section).
Open each radiator air vent starting at the
•
lower point and close it only when clear
water, free of bubbles, ows out.
Purge the air from the pump by unscrew-
•
ing the pump plug 2 (Fig. 15.2); release
the pump by turning the rotor in the direc-
tion indicated by the arrow on the informa-
tion plate.
Figure 15.2
Close the pump plug.
•
Continue lling the system. The actual
•
reading should ideally be 1.3 bar (19 psi)
and not less than 0.3 bar (4.3 psi).
Close all air release valves on the c.h.
•
system.
Inspect the boiler and the system for wa-
•
ter soundness and remedy any leaks dis-
covered.
Cold ush the system to remove any loose
•
particles and any system debris before
starting the boiler for the rst time.
Reassemble the front panel of the case.
•
Return ll valve to automatic position.
•
Lighting the boiler:
15.2
Note: If external controls are tted (e.g. room thermostat) ensure they “call for heat”.
WARNING: the boiler and its gas connection must be leak tested before the boiler is placed in operation.
Turn on the electricity supply to the boiler,
•
switching on the circuit breaker switch. The
appliance operation light A will ash every 4
seconds.
Turn the function selector B as in Fig. 15.3
•
The appliance operation light A will ash ev-
ery 2 seconds.
Figure 15.3
B
A
C
D
The boiler will now go through an ignition sequence and the burner will light.
If during the ignition attempt period the boiler fails to light, the full sequence control p.c.b. will go to lock-
out and the lock-out signal lamp D will appear.
To reset the boiler turn the knob B ( gure 15.3) on the 0 position and then press and release the boiler
reset button C (Fig. 15.3).
36 RIVA PLUS MANUAL
15. Commissioning Cont.
Checking the gas pressure at the burner:
15.3
This boiler has been tested to the highest quality control standards.
The maximum and minimum gas pressures are already set during this quality control
process however the checking procedure must be followed to ensure maximum operat-
ing effi ciency from the boiler.
Remove the front panel of the case.
•
Take off the lid of the sealed chamber.
•
Loosen the internal screw 15 (Figure 15.4)
•
on the Outlet Pressure Test Point of the Gas
Valve and connect a pressure gauge using
a suitable hose.
Figure 15.4
Set the c.h. temperature control knob to its
•
maximum position. If external controls are
tted (e.g. room thermostat) ensure they
“call for heat”.
Switch on the boiler.
•
Check the maximum gas pressure and com-
•
pare the value on the gauge with the value
indicated in the Section 2 on page 9 (gas
pressures at the burner).
Check the maximum gas ow at the gas
•
meter and compare the value indicated in
the section 2 on page 9 (gas ow rate).
Switch off the boiler.
•
Disconnect the gas modulator coil by remov-
•
ing the electrical connector E (Figure 15.4).
Switch on the boiler.
•
Check the minimum gas pressure and com-
•
pare the value on the gauge with the value
indicated in the Section 2 on page 9 (gas
pressures at the burner).
Switch off the boiler and re-connect the
•
electrical connector E to the modulator coil.
Switch on the boiler.
•
Check that the boiler lights up uniformly.
•
Switch off the boiler, turn off the hot water
•
taps and disconnect the pressure gauge.
Close the lid of the sealed chamber.
•
Important: after the checks all of the test
points must be sealed.
RIVA PLUS MANUAL
37
15. Commissioning Cont.
Adjustment of the gas pressure:
15.4
Remove the front panel of the case.
•
Take off the lid of the sealed chamber.
•
Open the gas valve inlet pressure test point
•
(16 in Fig. 15.5) at the valve input, connect
a suitable pressure gauge and check the gas
pressure of the supply network.
Remove the gauge and close the pressure
•
test point 16.
Open the gas valve outlet pressure test point
•
(15 in Fig. 15.5) and connect the gauge.
Figure 15.5
Remove the protection cap I (Fig. 15.6) from
•
the mechanical pressure adjustment compo-
nents levering with a at screwdriver in the
slots H.
Start the boiler at its maximum power.
•
Figure 15.6
Ensure that the boiler is not range rated.
•
Rotate the maximum gas pressure adjustment
•
(F in Fig. 15.5) until you obtain the required
pressure (by rotating clockwise the pressure
increases).
Turn the boiler off and disconnect one of the
•
two connectors (E in Fig. 15.5).
Start the boiler and rotate the minimum gas
•
pressure adjustment (G in Fig. 15.5) until
you obtain the required pressure (by rotating
clockwise the pressure increases).
Turn the boiler off and re-connect the wire to
•
the modulating operator.
Start the boiler and check again the maximum
•
gas pressure setting.
Turn the boiler off and disconnect the gauge.
•
Close the lid of the sealed chamber.
•
Important: after the checks all of the test
points must be sealed.
Checking the ignition device:
15.5
With the burner on high ame close the gas cock. After three ignition attempts (within about three min-
utes), the lock-out signal lamp must appear (D on Figure 15.3). To reset the boiler turn the knob B ( gure
15.3) on the 0 position and then press and release the boiler reset button (C on Figure 15.3).
38 RIVA PLUS MANUAL
15. Commissioning Cont.
Checking the burner ignition:
15.6
Turn the boiler OFF.
•
Open the gas valve outlet pressure test point
•
15 ( gure 15.5) and connect the gauge.
Turn the boiler ON positioning the function se-
•
lector B in the position shown in gure 15.7
and ensure that the room thermostat is set to
“heat demand”.
Figure 15.7
Loosen screws D and remove the service
•
panel ( gure 15.9).
Figure 15.8
Watch the gauge and check to see if the ig-
•
nition pressure registerd corresponds to the
values given in the Technical Data. Turn off
the boiler and reignite it by turning the function
selector B to the 0 position and then back to
that indicated in gure 15.7.
D
D
D
Repeat this process two to three times leav-
•
ing 30 second intervals between each igni-
tion. Check the ignition pressures and visually
check that the burner lights uniformly and in a
controlled manner.
To carry out the adjustment move the function
•
selector 3 to the OFF position (Fig. 15.9) and
use the device (ACC).
Figure 15.9
Adjust the gas pressure at the injectors to the
•
value indicated in the tables of section 2. By
rotating the device clockwise the pressure in-
creases.
After the adjustment operations bring the se-
•
lector 3 of gure 15.9 back to the normal posi-
tion (ON).
Reassemble the service panel.
•
Close the gas valve outlet pressure test point
•
15 ( gure 15.5).
Reassemble the front pannel of the case.
•
Important: after the checks all of the test
points must be sealed.
2
3
4
OFF
ON
1
ACC
RISC
+
+
Adjustment of the useful c.h. output:
15.7
Turn the boiler OFF.
•
Open the gas valve outlet pressure test point 15 ( gure 15.5) and connect the gauge.
•
Turn the boiler ON positioning the function selector B in the position shown in gure 15.7 and ensure
•
that the room thermostat is set to “heat demand”.
Loosen screws D and remove the service panel ( gure 15.8).
•
To carry out the adjustment use the adjustment device (RISC) with the help of a screwdriver.
•
By rotating the device clockwise the pressure increases.
•
Adjust the gas pressure at the burner to the value according to the useful c.h. output wanted (Tab. 15.1).
•
Reassemble the service panel.
•
Close the gas valve outlet pressure test point 15 ( gure 15.5).
•
Reassemble the front pannel of the case.
•
RIVA PLUS MANUAL
39
15. Commissioning Cont.
Labels placement:
15.8
Figure 15.10
Warning: The installation is not complete unless labels supplied are placed on the boil-
er as shown in Figure 15.10.
All the labels supplied with the boiler are numbered for reference.
According to Figure 15.10 place all the labels on the boiler. Use label numbered as 1 (already installed
in the front panel) to begin the placement in the correct way.
1
4
2
3
5
40 RIVA PLUS MANUAL
15. Commissioning Cont.
Checking the fl ue system and combustion:
15.9
The ue system should be visually checked for soundness. Check all clamps, gaskets and
•
xings are secure and tight.
Ensure that the ue terminal is sited correctly in accordance with the ue tting instruc-
•
tions.
To check the exhaust gas:
Remove the plugs indicated (Fig. 15.11).
•
Insert the analyzer probe in the exhaust
•
gas sampling point or in the air intake
sampling point.
Reference tables are given in the Sec-
•
tions 2 on page 9 of this manual for proper
CO2 levels.
Figure 15.11
Air-Flue exhaust
sampling points
Instructing the user:
15.10
Hand over the User manual, this Installation,Operation and Service manual to the end user
•
and explain how to use the unit in Central Heating mode.
Take the User step by step through the lighting instructions.
•
Show the User how to switch off the appliance quickly and indicate the position of the elec-
•
tric service switch and the boiler on/off switch.
Explain the proper use and adjustment of all system controls; this will ensure the greatest
•
possible safety and fuel economy.
Explain the function and use of the function switch.
•
Explain how to turn off the appliance for both short and long periods and advise on the pre-
•
cautions necessary to prevent damage should the appliance be inoperative when freezing
conditions may occur.
Fill in the details required on the Boiler Guarantee Certi cate and hand to the User advis-
•
ing them to return the correct section for boiler Guarantee registration. Finally, advise the
User that, for continued safe and ef cient operation, the appliance must be serviced by a
competent person at least once a year.
Useful output
KW
16.7
18.9
21.1
23.2
25.4
27.5
29.6
31.8
BTU/h
56983
64490
71996
79161
86668
93833
101000
108506
Natural
Pa
inwc.
290
1.16
370
1.48
460
1.84
560
2.24
660
2.65
780
3.13
900
3.61
1040
4.17
m³/h
1.76
2.00
2.23
2.46
2.69
2.91
3.14
3.36
ft³/h
5.77
6.56
7.31
8.07
8.82
9.54
10.30
11.02
Propane
Pa
inwc.
680
1.45
860
1.69
1060
2.25
1270
3.21
1500
4.34
1740
5.62
2000
7.06
2270
8.95
Kg/h
1.3
1.5
1.7
1.9
2.0
2.2
2.3
2.5
lb/h
3.0
3.3
3.7
4.1
4.4
4.8
5.1
5.5
Table 15.1
RIVA PLUS MANUAL
41
Gas Conversion
16.
WARNINGS: Procedures to adapt the boiler to the type of gas available must be car-
ried out by a competent and responsible person. Components used to
adapt it to the type of gas available must be genuine parts only.
Procedures:
Check that the gas cock (30 on Section
•
4) tted on the gas supply pipe is turned
off and the appliance is switched off at the
circuit breaker.
Remove the front and side panels of the
•
case (see the section 17.2 Annual Main-
tenance – Dismantelling the External
Panels).
Take off the lid of the sealed chamber.
•
Remove the front panel of the combustion
•
chamber.
Figure 16.1
Loosen the screws A and remove the
•
burner 7 (Figure 16.1).
Carry out the conversion for the type of
•
gas, replacing the burner injectors cor-
rectly.
Re-assemble the burner, the front panel
•
of the combustion chamber and the lid of
the sealed chamber.
Extract the control panel as explained in
•
the section 12.1 of this manual.
Loosen the screws D and remove the ser-
•
vice panel ( gure 16.2)
A
A
7
Figure 16.2
Set correctly the dip-switch “2” to the cor-
•
rect position (Fig. 16.3) in accordance
with the following table.
Gas supply
Position of the
switch 2
Natural gas
On
L.P.G.
Off
Figure 16.3
Close the service panel.
•
Turn on the boiler.
•
Calibrate the gas valve according to the
•
instructions given in section 15.4 of this
manual.
Set the correct gas pressure for central
•
heating output required.
Stick on the inside of the left hand side
•
panel adjacent to the data badge the self-
adhesive label (included with the conver-
sion kit) indicating the type of gas, and the
gas pressures to which the appliance has
been set.
Reassemble the front and side panels of
•
the case.
D
D
D
ON
OFF
1
2
3
4
ON
OFF
1
2
3
4
Natural gas
L.P.G.
42 RIVA PLUS MANUAL
Annual Maintenance
17.
Warnings:
17.1
The procedures detailed in this chapter must be carried out only by a professionally quali ed
person. Thus you are advised to contact an Authorised Service Agent. For ef cient and con-
tinuous operation of the boiler you are advised to have, at least once a year, maintenance and
cleaning done by an Approved Service Person. Isolate the appliance from the electricity sup-
ply by turning off the fused spur isolation switch adjacent to the appliance and turn off the gas
cock, before carrying out any procedures, whatsoever, for cleaning, maintenance, opening or
dismantling boiler panels.
Dismanteling the external panels:
17.2
Front Panel:
Loosen the three screws A (Fig. 17.1)
•
Lift and remove the panel.
•
Side Panels:
Loosen the screws B (Figure 17.2). Bring the bottom of the panels away from the boiler and
•
lift them, freeing them from the top hooks.
Figure 17.1
A
A
Figure 17.2
B
B
C
C
B
B
Emptying the Central Heating System:
17.3
Close the pressure reducing automatic ll
•
valve (28 on Section 4)
Open the central heating drain cock (F in
•
Fig. 17.3).
Empty the c.h. system.
•
Close the central heating drain cock (F in
•
Fig. 17.3).
Open the pressure reducing automatic ll
•
valve (28 on Section 4)
Figure 17.3
RIVA PLUS MANUAL
43
17. Annual Maintenance Cont.
Cleaning the primary heat exchanger:
17.4
Take off the front panel of the case, then the sealed chamber lid and the front panel of the
•
combustion chamber.
If you notice dirt on the ns of the primary heat exchanger (9 on page 10), cover the sloping
surfaces of the burner (7 on page 10) entirely in a protective layer (sheets of newspaper or
similar). Brush out the primary heat exchanger (9 on page 10) with a bristle paintbrush.
Checking the pressurization in the expansion vessel:
17.5
Empty the central heating system as described in section 17.3 of this chapter and check that
the pressure in the expansion vessel is not less than 1 bar (14.5 psi). See also section 13.2
page 30 of this manual. If the pressure should be lower, take steps to correct the pressure
level.
Cleaning the burner:
17.6
Follow the instructions for removing the ex-
ternal panels from 17.2. Remove the nine
screws labelled C in gure 17.4. Now you
will have complete access to the combustion
chamber. The sloping and multi-gas type
burner (7 on page 10) does not need special
maintenance, but it is suf cient to dust it with
a bristle paintbrush.
Figure 17.4
Checking the combustion fan:
17.7
The combustion fan does not require any special maintenance. Lubrication is not necessary
due to the fact that the ball bearings are sealed. Check that the fan operates and that the vis-
ible impeller ns are free of any dirt or obstructions.
Checking the fl ue:
17.8
Have the integrity of the ue outlet pipe (24 on page 10) air intake pipe (25 on page 10),
checked periodically, the venturi device (23 on page 10) cleaned and the ef ciency of the ue
safety circuit checked at least once a year. For all the above maintenance operations it is ad-
visable to call an approved Service Engineer.
Remove the four Phillips head screws
•
from the vent connector on the boiler.
Remove the vent connector from the boil-
•
er by pulling vertically on it.
Remove the rst elbow from the horizon-
•
tal run of the exhaust to the outside.
Using a ashlight inspect each length of
•
vent pipe for obstructions and dirt buildup.
Clean any that is found with an appropri-
ate sized brush.
Inspect the venture device inside the out-
•
let of the combustion fan. Make sure that
it is free of any dirt build up or blockage.
44 RIVA PLUS MANUAL
Make sure the seals are properly seated
•
in the female ends of the vent pipe with
the ns facing the male end of the pipe.
Reinstall the elbow onto the horizontal
•
run of the pipe rst by simply pushing the
To check the pressure at the venturi device, use the test points (12 on page 10).
parts together.
Push the vent adapter down onto the top
•
of the boiler and reinstall the four Phillips
head screws.
Remove the caps of the pressure test
•
points and connect a differential pressure
gauge.
Switch on the boiler
•
Compare the value on the gauge with the
•
minimum values of venturi pressure indi-
cated in the Section 2 on page 9.
Figure 17.5
Venturi test
points
Visual inspection of appliance:
17.9
Visually inspect all water joints, seals and connections for any evidence of leakage and re-
tighten, grease or replace them as necessary.
Gas pressures and soundness:
17.10
Check appliance for gas soundness. Recheck operational pressures and adjust as necessary
as described in Section 15.4 page 37 of this manual.
Condensate trap:
17.11
To clean the condensate trap:
Remove the front and right case panels.
•
Disconnect the trap from the drain pipe.
•
Using pliers, remove the spring D moving
•
it upwards.
Disconnect the wirings from the trap.
•
Reassemble carrying out the removal op-
•
erations in reverse order.
The trap should be serviced once a year dur-
ing the annual service.
Figure 17.6
17. Annual Maintenance Cont.
RIVA PLUS MANUAL
45
Vent Part Spares
18.
Separate venting:
18.1
Description
Order Number
Twin pipe kit
10999.0393.0
46 RIVA PLUS MANUAL
Coaxial venting:
18.2
Description
Order Number
Coaxial ue kit
10999.0387.0
18. Vent Part Spares Cont.
RIVA PLUS MANUAL
47
Roof venting
18.3
Part
Description
Order Number
A
Roof ue kit
10999.0392.0
For any spare parts, please contact QHT Inc. at 800-501-7697.
18. Vent Part Spares Cont.
48 RIVA PLUS MANUAL
Installer Notes
19.
System Checkout:
Boiler Model No. ___________________
Original Purchaser:
___________________________
___________________________
___________________________
Serial No.______________________
Installer:
________________________
________________________
________________________
_______________________________________________________________________
Performance Tests:
GROSS STACK TEMPERATURE __________________
ROOM TEMPERATURE (AMBIENT) ________________
NET STACK TEMPERATURE _____________________
CO2 __________________
O2 ___________________
SMOKE READING ___________________
COMBUSTION EFFICIENCY _________________
COMMENTS ___________________________________________________________
_______________________________________________________________________
_______________________________________________________________________