Siemens REV24RF User Instruction
Read Online
Read the Siemens REV24RF User Instruction online using the built-in PDF viewer.
Text of the manual
Radio set with 7-day
room temperature
controller
REV24RF../SET
Comprising a room temperature controller (with integrated radio transmitter)
and receiver with relay outputs
•
Mains-independent, battery-operated room temperature controller featuring
user-friendly operation, easy-to-read display and large numbers.
•
Self-learning two-position controller with PID response (patented).
•
Operating mode selection:
- 7-day automatic mode with max. 3 heating or cooling phases.
- Continuous comfort mode.
- Continuous energy saving mode.
- Protection against frost or overheating.
- Exception day (24 hour operation) with max. 3 heating or cooling phases.
•
A separate temperature setpoint can be entered in automatic mode and for
the exception day for each heating or cooling phase.
•
Heating zone control.
•
Possibility to control cooling equipment.
•
Advantage for retrofitting, renovating, and reconstruction purposes
(completely wireless room unit).
Use
Room temperature control in:
• Single-family and vacation homes.
• Apartments and offices.
• Individual rooms and professional office facilities.
• Commercially used spaces.
Control for the following equipment:
• Magnetic valves of an instantaneous water heater.
2 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
• Magnetic valves of an atmospheric gas burner.
• Forced draught gas and oil burners.
• Electrothermal actuators.
• Circulating pumps in heating systems.
• Electric direct heating.
• Fans of electric storage heaters.
• Zone valves (normally open and normally closed).
• Air conditioning and cooling equipment.
Function
• Bidirectional radio transmission.
• PID control with self-learning or selectable switching cycle time.
• 2-point control.
• 7-day time switch.
• Preselected 24-hour operating modes.
• Override function.
• Holiday mode.
• Party mode.
• Protection function (protection against frost or overheating).
• Information level to check settings.
• Reset function.
• Sensor calibration.
• Heating or cooling.
• Minimum limitation of setpoint.
• Periodic pump run.
Protection against valve seizure.
• Optimum start control in the morning (P.1).
• Synchronization to radio time signal from Frankfurt, Germany (REV24RFDC).
• Manual override of the receiving relay.
Type summary
Radio set comprising:
- Room temperature controller REV24RF with 7-day time switch,
Base and receiver RCR10/868
REV24RF/SET
Radio set comprising
- Room temperature controller REV24RFDC with 7-day time switch,
Receiver for time signal from Frankfurt, Germany (DCF77),
Base and receiver RCR10/868
REV24RFDC/SET
Ordering
Please indicate the type number as per the "Type summary" when ordering.
Delivery
The controller/transmitter REV24RF.. is delivered with batteries.
Mechanical design
Plastic casing with an easy-to-read display and large numbers, easily accessible
operating elements, and removable base. The casing accommodates the electronics
with the DIP switches. The easily accessible battery compartment allows for easy
exchange of two 1.5 V alkaline batteries, type AA.
The base helps attach the room controller to the wall. The supplied table stand allows
you to stand the controller anywhere in the room. You can manually attach the table
stand without tools.
Room controller and
base
Base and
table stand
3 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
Plastic housing with large operating elements, removable cover and easily accessible
terminal block with lots of space to attach the wires. You can mount and wire the unit on
most commercially available recessed conduit boxes or directly on the wall. The
potential-free changeover contact and the antenna for reception are integrated in the
unit.
1
Display
Change battery
Time of day
Alarm
Room temperature (measured)
Heating mode
Clear text display line
(max. 18 spaces)
Cooling mode
Weekday (max. 3 spaces)
0 4 8 12 16 20 24
24 hour timeframe with
switching pattern with flashing
time cursor
Info
Info
Setpoint for comfort mode
Weekday block
Weekend block
Weekday
Setpoint for absence
h
Time unit
Room temperature
Absence/holiday mode set
Setpoint for frost protection
mode
Absence/holiday mode active
Without language selection
Energy saving mode setpoint
Party mode active
Time signal from Frankfurt
°C / °F
Temperature unit °C or °F
Date (day - month - year)
Heating/cooling/pump on
Receiver
Display and operating
elements
4 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
2
Operating mode selector
Automatic weekly mode with max. three heating or cooling phases per
day.
Exception day with max. three heating or cooling phases.
Continuous comfort mode (= continuous comfort temperature).
Continuous energy saving mode (= continuous energy saving
temperature).
Protection mode (protection against frost or overheating).
3
INFO
Pressing the Info button once illuminates the display. Illumination
automatically turns off after a short period of time.
Pressing the Info button again activates the information display:
is lit.
The unit first displays queued error messages followed by important
information (e.g. time switch programs, etc.).
4
Plus button
Increase values, set time, or make a selection.
5
Override button / party mode
In the time switch program, this button allows you to quickly change from the
active temperature level to the next and back.
Thus, you can quickly change to energy saving temperature when you leave
the apartment for a short period of time, thus saving energy.
The display indicates the change. It is valid only until the next switching time.
rty mode: Press the button for 3 seconds.
Party mode is available only in operating modes
and
. In party mode,
the controller controls to a freely selectable temperature for a freely
selectable period of time.
In party mode, symbol is displayed along with the end of party mode.
6
Minus button
Decrease values, set time, or make a selection.
5 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
7
Program selection slider
Time
Day – Month – Year (2 spaces for day, month, and year).
Weekday, weekend, or individual day blocks.
1, 2, or 3 comfort phases.
Start
Comfort phase 1
Start
Comfort phase 2
Start
Comfort phase 3
Setpoint
Comfort phase 1
Setpoint
Comfort phase 2
Setpoint
Comfort phase 3
End
Comfort phase 1
End
Comfort phase 2
End
Comfort phase 3
Energy saving temperature in the automatic mode and exception day time
switch programs.
Start of absence.
Temperature setpoint during absence.
End of absence.
RUN
Slider position RUN allows for closing the cover.
Operating modes
The controller offers the two time switch programs
and
.
Enter a start time and end time for each comfort phase. Also comfort temperature
setpoint can be freely entered for each comfort phase. Between the comfort phases
the controller always switches to the same, freely selectable energy saving
temperature setpoint.
2205Z04
16
°C
18
20
22
06
08
18
22
h
Heating
phase 1
12
14
21
Heating
phase 2
Heating phase 3
The controller also offers the three 3 continuous modes
comfort mode,
energy saving mode and
frost protection mode.
Operation with
time switch program
Example with
3 heating phases
Continuous operating
modes
6 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
You can freely adjust the setpoints for the weekly and 24-hour operating modes.
Setting range for all setpoints without setpoint limitation 3…35 °C.
Setting range for all setpoints with setpoint limitation 16…35 °C.
Factory setting for heating
Factory setting for cooling
,
,
,
20 °C
24 °C
,
16 °C
28 °C
8 °C
35 °C
12 °C
30 °C
Factory settings: Switching times
Comfort phases
P1
P2
P3
P4
P5
P6
1.
07:00
23:00
PASS
PASS
PASS
PASS
2.
06:00
08:00
17:00
22:00
PASS
PASS
3.
06:00
08:00
11:00
13:00
17:00
22:00
Three different switching patterns are available to simplify entry of switching times. These
can be assigned as blocks to the corresponding weekdays 1…5 and weekend days
6…7. As a result, you need to adapt the switching times and room temperatures only
once for each block.
Switching pattern
Blocks
You can also enter individual days
…
.
You can enter the beginning, temperature and end of your holidays. At the beginning of
the holidays, the controller switches to the desired holiday temperature and returns to the
previously set operating mode at the end of the holidays.
In holiday mode, symbol
is displayed along with the end of holiday mode.
Proceed as follows to enter your settings:
Set slider to position 15 (start of absence): Press
or
to set the start date
for your holidays.
Set slider to position 16 (temperature during absence): Press
or
to set
the desired temperature while on holidays.
Set slider to position 17 (end of absence): Press
or
to set the end date
for your holidays.
RUN
Return the slider to position RUN. Symbol
is displayed to the left of the
symbol.
Press
,
,
,
or move the slider to end holiday mode prematurely.
Setpoints
Factory setting
7-day time switch
Enter holidays or
absences
7 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
Technical features
DIP switches
DIP switch
ON /
OFF
1
2
3
4
5
6
7
8
9
10
Sensor calibration On
Periodic pump run and
anti-lime function On
A
Sensor calibration Off
Periodic pump run and
anti-lime function Off
E
Setpoint limitation 16…35 °C
Start optimization: 1 h/°C
B
Setpoint limitation 3…35 °C
Start optimization: ¼ h/°C
Temperature display °F
Start optimization: ½ h/°C
C
Temperature display °C
Start optimization: Off
F
PID self-learning
(Op. mode: Cooling)
PID 6
(Op. mode: Heating)
G
PID12
Quartz
D
2-point
Radio clock
H
J
DIP switch reset
ON
1
3
4
2
2211Z32
5
6
7
8
9
After you change one or several DIP switch positions, you must press the DIP switch reset button to reset the DIP
switch. Otherwise, the previous setting remains active!
J
Factory setting: All DIP switches to
OFF
If the displayed room temperature does not match the measured room temperature, the
temperature sensor can be recalibrated.
Set DIP switch to ON and press the DIP switch reset button:
CAL symbol is displayed. The currently measured temperature flashes.
Press
or
to recalibrate by max. ± 5 °C.
Set DIP switch to OFF and press the DIP switch reset button to save the settings.
The minimum setpoint limitation of 16 °C prevents undesired heat transfer to neighboring
spaces in buildings featuring several heating zones.
DIP switch ON: Setpoint limitation 16…35 °C.
DIP switch OFF: Setpoint limitation 3…35 °C (factory setting).
Press the DIP switch reset button to save the settings.
DIP switch ON: Temperature display in °F.
DIP switch OFF: Temperature display in °C (factory setting).
Press the DIP switch reset button to save the settings.
The REV24… is a two-position controller with PID control. The room temperature is
controlled through cyclic switching of an actuating unit.
DIP switches 4 ON and 5 ON:
PID self-learning
Adaptive control for all applications.
DIP switches 4 ON and 5 OFF: PID 6
Fast controlled system for applications in locations with
large temperature deviations.
DIP switches 4 OFF and 5 ON: PID 12
Normal controlled system for applications in locations with
normal temperature deviations.
DIP switches 4 OFF and 5 OFF: 2-point
A Sensor calibration:
DIP switch 1
B Setpoint limitation:
DIP switch 2
C Temperature display in
°C or °F:
DIP switch 3
D Control behavior:
DIP switches 4 and 5
8 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
For complex controlled systems, simple two-position controller with
0.5 °C switching difference (factory setting).
Press the DIP switch reset button to save the settings.
Only applicable with controlled circulating pump or valve!
This function protects the pump or valve during extended OFF periods against possible
seizure caused by liming. Periodic pump run is activated every 24 hours at 12 p.m. for
three minutes (symbol ▲ is displayed during active pump run).
DIP switch ON: Pump run On.
DIP switch OFF: Pump run On (factory setting).
Press the DIP switch reset button to save the settings.
Optimization advances the switch-on point P.1 to ensure that the selected setpoint is
reached at the desired time. The setting depends on the controlled system, i.e., on heat
transmission (piping system, radiators), building dynamics (building mass, insulation),
and heat output (boiler capacity, flow temperature).
DIP switches 7 ON and 8 ON:
1 h/°C For slow controlled systems.
DIP switches 7 ON and 8 OFF:
¼ h/°C For fast controlled systems.
DIP switches 7 OFF and 8 ON:
½ h/°C For medium controlled systems.
DIP switches 7 OFF and 8 OFF: OFF
Off, no effect (factory setting).
Press the DIP switch reset button to save the settings.
t
T
17
18
19
- 4
- 2
2254D01
16
- 3
1/4h/°C
1/2h/°C
1h/°C
P.1
- 2
- 1
- ½
- 1½
- 1
- ½
- ¼
- ¾
Pon
20
°C
T1
- 1 h
h
h
TRx
h
h
h
h
h
h
h
h
h
Key for diagram:
T
Temperature (°C)
t
Forward shift of switch-on point (h)
TRx
Room temperature actual value
Pon
Starting point for optimized heat-up time.
The controller can be switched over for cooling applications on DIP switch 9.
DIP switch 9 ON:
Cooling
DIP switch 9 OFF:
Heating (factory setting).
Press the DIP switch reset button to save the settings.
Only applicable to REV..DC (with integrated DCF77 receiver to receive time signal from
Frankfurt, Germany)!
DIP switch ON: Clock run by controller-internal quartz.
DIP switch OFF:
Time signal DCF77 from Frankfurt, Germany.
Press the DIP switch reset button to save the settings.
During startup, REV..DC synchronizes automatically to the time signal (DCF77) from
Frankfurt, Germany. Synchronization takes max. 10 minutes. Synchronization restarts
each time you press the button or move the program selection slider from the RUN
position during these 10 minutes. Siemens recommends to set the desired settings upon
startup, install the REV..DC in the desired location, and not carry out any actions on the
REV..DC for the next 10 minutes.
In normal operation, the REV..DC synchronizes to the radio clock every day at 3:10 a.m.
E Periodic pump run
and anti-lime function:
DIP switch 6
F Start optimization:
DIP switches 7 and 8
G Operating mode heating
or cooling:
DIP switch 9
H Radio clock:
DIP switch 10
Note
on synchronization
9 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
The time signal from Frankfurt is modulated to a radio signal. The reception of this radio
signal depends on the distance to Frankfurt, atmospheric conditions as well as the
location where the REV..DC is installed. Siemens cannot guarantee that the REV..DC
can receive the time signal from Frankfurt at any time and any place.
The radio clock symbol is deactivated and an error message is displayed if the clock was not
able to synchronize the time for 7 consecutive days. The controller then runs on the internal
quartz.
After you change one or several DIP switch positions, you must press the DIP switch
reset button to reset the DIP switch.
Otherwise, the previous setting remains active!
Access to the expert level
Set the program selection slider to RUN. Press
and
simultaneously for 3 seconds, release the buttons, and
within 3 seconds press and hold down
and
simultaneously for 3 seconds, release
, and press
for another 3
seconds. This releases the engineering settings.
is displayed.
The display first shows language selection with Code 00. Press the buttons
or
to navigate the settings.
Confirm settings by pressing
.
Press the operating mode selector
to exit the engineering settings.
Code list
This entry has no effect if the radio clock either is inactive or not available.
The time signal received from Frankfurt is shifted by the value set in Code 30 (time zone)
if the radio clock is active.
The time is always changed over at 2 a.m. on the Sunday preceding the set date if there
is no radio clock or if it is inactive. The time change is shifted by the value set in Code 30
(time zone) when the radio clock is active.
The time is always changed over at 3 a.m. on the Sunday preceding the set date if there
is no radio clock or if it is inactive.
Functional check
a) Check the display. If there is no display, check insertion and function of the batteries.
b) Operating mode “Continuous comfort mode“
, read displayed temperature.
c) REV.. in heating mode: Set the temperature setpoint higher than the displayed room
temperature (see operating instructions).
REV.. in cooling mode: Set the temperature setpoint lower than the displayed room
temperature (see operating instructions).
Note
on reception
No reception
J DIP switch reset
ON
1
3
4
2
2211Z32
5
6
7
8
9
Function block
Code
Name
Factory setting
Your setting
00
Language
English
01
Sensor calibration
off
Basic settings
02
Switching differential 2-point
0.5 °C
10
Illumination time
10 seconds
11
Background brightness
0
LCD
optimization
12
Contrast
0
30
Time zone
Deviation from time signal in Frankfurt
(Central European Time CET) (see Note 1)
0 hours
31
Start of daylight saving time (see Note 2)
March 31 (03-31)
Clock settings
32
End of daylight saving time (see Note 3)
October 31 (10-31)
Note 1:
Note 2:
Note 3:
10 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
d) The relay and, as a result, the actuating device must switch at the latest after one minute.
Symbol ▲ is displayed. If not displayed:
• Check actuating device and wiring.
• It is possible that in heating mode the room temperature is higher than the set
temperature setpoint (and lower for cooling mode).
e) Set the temperature setpoint for operating mode “Continuous comfort mode“
to the
desired value.
f) Select the desired operating mode.
Reset
User-defined settings:
,
and
simultaneously for 3 seconds:
This resets all temperature and time settings of the program selection slider to default
values (see also "Factory settings" in the operating instructions). The expert settings
remain unchanged.
The clock starts at 12 p.m., the date on 01-01-08 (01 January 2008).
During the reset, all display fields are lit and can be checked accordingly.
All user-defined settings plus expert settings:
Press the DIP switch reset button
ON
1
3
4
2
2211Z32
5
6
7
8
9
,
and
simultaneously for 5
seconds:
After the reset, all factor settings are reloaded. This applies to the program selection
slider as well as to the expert settings.
Simultaneously press the "Test and "Learn" buttons on the rear of the REV24RF.. for
1 second. This deletes all data saved from the receivers listed as faulty in Info mode.
After this reset, the REV24RF.. indicates that all faulty receivers were deleted.
Simultaneously press the "Test and "Learn" buttons on the rear of the REV24RF.. for
5 seconds. This deletes the data saved from all receivers.
After this reset, the REV24RF.. indicates that no more receivers are connected to the room
controller.
Open the RCR10/886 cover. Simultaneously press the "Learn" and override buttons on the
front of the RCR10/868 for 4 seconds. This deletes the data saved from the room controller.
LED_1 flashes red. This indicates that no room controller is connected to the receiver.
Engineering
• Place the room unit in the main living room by considering the following aspects (wall
mounting or free placement using stand).
• The distance to the receiver may not exceed 20 meters or 2 floors.
• Choose the place of installation so that the sensor can capture the air temperature in
the room as accurately as possible without being adversely affected by direct solar
radiation or other heat or cooling sources (about 1.5 meters above the floor for wall
mounting).
Room controller
REV24RF..:
Temperature controller
data
Room controller
REV24RF..:
Data from faulty
receivers
Room controller
REV24RF..:
Data from all receivers
Receiver RCR10/868:
Data from the room
controller
Room controller
REV24RF..:
11 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
• Choose the location to ensure largely interference-free transmission. Observe the
following:
− Do not mount on metallic surfaces.
− Do not mount near electrical cables and equipment like PCs, TVs, microwaves, etc.
− Do not mount near larger metallic structures or constructional elements with fine
metal meshes such as special glass or special concrete.
• Use the DIP switches to adapt the control behavior.
• Recalibrate the temperature sensor (see "Sensor calibration") if the displayed room
temperature does not match the room temperature measured.
• Mount the unit base for the REV24RF.. in the desired location.
• See also "Mounting and commissioning notes".
• Attach the base first and then slide the unit in the base from top to bottom. You can
mount the base on most commercially available recessed conduit boxes or directly on
the wall.
• When mounting on a wall, make sure there is sufficient clearance above the unit to
allow for removing and refitting the unit.
min.
10 cm
2261Z03
• See the installation instructions printed on the stand.
• Place the REV24RF.. in the desired location.
.
• Install the receiver close to the controlled unit if possible.
• Choose the location to ensure largely interference-free reception. Observe the
following for mounting the room unit:
− Do not mount in a control panel.
− Do not mount on metallic surfaces.
− Do not mount near electrical cables and equipment like PCs, TVs, microwaves, etc.
− Do not mount near larger metallic structures or constructional elements with fine
metal meshes such as special glass or special concrete.
• Make sure the location is dry and protected against splash water.
• You can mount the unit on most commercially available recessed conduit boxes or
directly on the wall.
Make sure the receiver is not connected to power during wiring!
Reconnect the unit to power only after the unit is fully mounted.
• During installation, attach first and wire the unit rear without cover (L/N = mains 230
VAC, LX/L1 = consumer). Slide in the cover from above, swing downward and secure
with a screw in the upper portion of the housing.
• For more detailed information, see the installation instructions supplied with the unit.
• Comply with all local regulations on electrical installations.
Mounting the room
controller REV24RF..
on the wall
Stand for REV24RF..
Receiver RCR10/868:
Mounting and
installation of
receiver
RCR10/868
12 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
Commissioning
•
The room unit and receiver are interconnected at the factory in the RF/SET. As a result,
you do not need to manually connect the two units.
However, you can still manually connect the room unit and the receiver as needed.
See Point "7. Manually connect REV24RF.. and RCR10/868“.
•
Remove the black transit tabs; the unit starts to operate as soon as you remove the
transit tabs on the battery contact. : Select desired language by
or
.
Confirm by
.
•
If possible, mount the receiver temporarily (e.g. using dual-sided adhesive tape) to try
to identify the best possible location for RF reception. To do this, fully wire the
RCR10/868 and close the front cover.
•
See Point "4 Test radio link / identify best RF reception location“.
a) Switch on RCR10/868
b) Press the Test button on the rear or the REV24RF.. and place the unit in the best RF
reception location. Test the radio link between the room controller and all connected
receivers. On the RCR10/868, LED_2 flashes quickly.
The test turns off automatically after 10 minutes or you can manually end it by
pressing one of the following buttons:
,
or
.
c) The REV24RF.. shows the quality of the radio link to the connected RCR10/868. If
more than one receiver is connected to the same REV24RF.., the display changes
every 10 seconds from RCR 01 to RCR 02, etc..
Select the receiver with
or
. The selected receiver is tested continuously for
1 minute.
d) REV24RF..: The greater the visible bar under numbers 0…9, the better the radio link.
If the bar is below the number 0, radio link is not guaranteed. In this case, move the
room controller to a different location and shorten the distance between the
REV24RF.. and RCR10/868.
Repeat the test until quality is sufficient.
Insufficient
Sufficient
Good
Very good
e) RCR10/868: LED_1 also indicates the radio link quality:
Red
= Insufficient or no radio link
Orange = Good
Green
= Very good
f)
If radio link quality is insufficient, shorten the distance between the REV24RF.. and
RCR10/868.
Repeat the test until quality is sufficient.
a) Switch off power.
b) Mark the place where the RCR10/868 is located.
c) Loosen the wiring as needed.
d) Mount the receiver at the marked location, wire completely and close the housing.
e) Switch on power.
f)
The receiver does not require operation after commissioning.
1. REV24RF../SET
2. Switch on the
REV24RF..
3. Temporarily mount
the RCR10/868
4. Test radio link /
Identify best RF
reception location
LED_1 LED_2
5.
Finish mounting the
RCR10/868
13 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
Press the override button
on the receiver to manually override the relay. LED_1
flashes. Override is active for at least 15 minutes. Press again
to remove manual
override.
If the room controller sends a control telegram within these 15 minutes, the telegram is
suppressed and executed only after these 15 minutes. This function allows for testing the
unit connected to the receiver.
After expiration of manual override, the RCR10/868 immediately executes every control
telegram received.
In the even of errors (e.g. empty batteries), the room controller no longer sends control
telegrams. Press the override button
on the receiver to permanently turn on the
connected unit. This function allows you to e.g. run the heating system even if the room
controller is off.
When the room controller resumes operation (e.g. after inserting new batteries), its
control telegrams overwrite manual override. Synchronization takes max. 130 minutes.
The receiver delivered with REV24RF../SET is connected to the controller at the factory.
Manually connect RCR10/868 and REV24RF.. :
a) On the RCR10/868 press the “Learn“ button for about 4 seconds: The blue LED_2
flashes slowly, learning mode is active.
b) Also press the "Learn" button within 20 minutes on the REV24RF.. : The REV24RF..
now either shows confirmation that receiver (RCR 01, RCR02, etc.) is connected or
that connection failed.
Display on the RCR10/868: When connection is successful, the blue LED_2 briefly
flashes quickly, and LED_1 goes from red to green. If connection failed, learning
mode remains active: The blue LED_2 flashes slowly.
c) You can connect max. 15 receivers to 1 room controller. For unique identification of
each receiver, the REV24RF.. assigns a number to each RCR10/868 connected. The
REV then displays this number after a successful learning process.
•
The error indication
on the REV24RF.. can point out a radio issue to one of the
connected receivers. Check the error message with
.
Check the receiver as needed.
•
LED_1 is red when the RCR10/868 receives a weak, garbled or no control telegram
for about. 65 minutes. Check the display on the REV24RF.. for an error message.
•
As long as the RCR10/868 correctly receives the control telegrams, the receiver
operates normal. If a control telegram is not received correctly, the relay remains in
the position last switched.
As soon as the RCR10/868 again receives a correct control telegram from the
REV24RF.., the receiver resumes normal operation.
•
The relay switches off, if the RCR10/868 receives no or an incorrect control telegram
from the REV24RF… This switches off the controlled unit. LED_1 is red.
As soon as the RCR10/868 again receives a correct control telegram from the
REV24RF.., the receiver resumes normal operation.
•
In the case of power interruption at the RCR10/868, the relay goes to OFF.
This is a software class A controller designed for use at a normal degree of pollution.
6.
RCR10/868
Manually override
the relay
7.
Manually connect
REV24RF.. and
RCR10/868
LED_1 LED_2
LEARN
Notes
14 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
Technical data for room controller REV24RF..
Power
Batteries (alkaline AA)
Life
Backup of clock when changing battery
(all other data remain in EEPROM)
DC 3 V
2 x 1,5 V
Ca. 2 years
Max. 1 min
Protection class
II as per EN 60 730-1
Sensing element
Measuring range
Time constant
NTC 10 kΩ ±1 % at 25 °C
0…50 °C
Max. 10 min
Setpoint setting ranges
All temperature settings
3…35 °C
Resolution for settings and displays
Setpoints
Switching times
Actual value measurement
Actual value display
Time display
0.2 °C
10 min
0.1 °C
0.2 °C
1 min
CE conformity
Electromagnetic compatibility
Low voltage directive
R&TTE directives
2004/108/EEC
2006/95/EC
EN 301 489-3
Approval
Valid for the following countries
0359
All EU member states
Norway, Iceland, Switzerland
Radio equipment
Automatic electrical controls for household
and similar use
EN 301 489-3
EN 60 730-1
Electromagnetic compatibility
Immunity
Emissions
Radio equipment
EN 61000-6-2
EN 61000-6-3
EN 300 220-3
Degree of protection
IP20
Operation
Climatic conditions
Temperature
Humidity
3K3 as per IEC 60 721-3
5...40 °C
< 85 % r.h.
Storage and transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
2K3 as per IEC 60 721-3
-25...+70 °C
< 93 % r.h.
2M2 as per IEC 60 721-3
Without packaging
REV24RF..
REV24RF../SET
0.29 kg
0.45 kg
Housing
RAL9003 signal white
Base
RAL7038 gray
Housing with base
94 x 134.5 x 30 mm
General unit data
Standards
Product safety
Environmental conditions
Weight
Color
Size
15 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
Technical data for receiver RCR10/868
Operating voltage
Power
AC 230 V +10/−15 %
< 10 VA
Frequency
45 – 65 Hz
Switching capacity of relay
Voltage
Current
AC 24…250 V
0.2…16 (2) A
Protection class
II as per EN 60 730-1
- Conformity
EMC guidelines
Low voltage directive
R&TTE directives
2004/108/EC
2006/95/EC
EN 301 489-3
Approval
Valid for the following countries
0359
All EU member states
Norway, Iceland, Switzerland
Radio equipment
Automatic electrical controls for household
and similar use
Special requirements for energy
controllers
EN 301 489-3
EN 60 730-1
EN 60 730-2-11
Electromagnetic compatibility
Immunity
Emissions
Radio equipment
EN 61 000-6-2
EN 61 000-6-3
EN 300 220-3
Degree of protection
IP20
Operation
Climatic conditions
Temperature
Humidity
Class 3K3 as per IEC 60 721-3
0...+45 °C
<85 % r.h.
Storage and transport
Climatic conditions
Temperature
Humidity
Mechanical conditions
Class 2K3 as per IEC 60 721-3
−25...+70 °C
<93 % r.h.
Class 2M2 as per IEC 60 721-3
Without packaging
RCR10/868
REV24RF../SET
0.16 kg
0.45 kg
Housing front
Housing bottom
RAL 9003 signal white
RAL 7038 gray
Housing with base
88 x 114 x 31.5 mm
General unit data
Standards
Product safety
Environmental conditions
Weight
Color
Size
16 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
Connection diagram fro receiver RCR10/868:
L
Phase, AC 230 V
N
Neutral conductor AC 230 V
Lx
Phase, AC 24...250 V
L1
N.O. contact,
AC 24 ….250 V / 16 (2) A
L2
N.C. contact,
AC 24 … .250 V / 16 (2) A
M1
Circulating pump
N2
Receiver RCR10/868
Lx
L1
Y1
M1
N2
Nx
L
N
L2
2255A01
AC 230 V
AC 24...250 V
Lx
Nx
N
L
Y1
Actuating device
Application examples
T
T
F1
F2
N2
M1
Y2
2255S01
N1
T
F1
F2
N2
M1
Y2
2255S02
T
T
T
N1
Instantaneous water heater
Atmospheric gas burner
N1
Y4
2255S03
Y3
N2
T
N4
T
N3
T
N1
2255S05
E1
N2
Zone valve
Cooling unit
17 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
Y1
2252S04
M1
N2
T
N1
Circulating pump with precontrol by manual mixing valve
E1
Cooling unit
F1
Thermal reset limit thermostat
F2
Manual reset safety limit thermostat
M1
Circulating pump
N1
Room temperature controller (transmitter) REV24RF..
N2
Receiver RCR10/868
N3
Room temperature controller (transmitter) REV24RF..
N4
Receiver RCR10/868
Y1
3-port valve with manual adjustment
Y2
Magnetic valve
Y3
Three-port valve with actuator
Y4
Two-port valve with actuator
18 / 18
Siemens
Room temperature controller radio set REV24RF../SET
CE1N2206en
Building Technologies
24.04.2008
Dimensions
Room temperature controller (transmitter) REV24RF..
130
94
134,5
82
56
16,2
83,5
13
56
Ø 60
30
2206M03
Receiver RCR10/868
Ø 60
56
15,2
56
11,7
114
88
31,5
2206M04
©2008 Siemens Switzerland Ltd
Subject to change