FIRECLASS Fire detection system
Panel Accessories
Fixing instructions Doc. version 1.0
1/12
Installing the FireClass FC700 Series
POS800/PCS800 Ethernet Switch
Introduction
This leaflet covers the installation of an Ethernet
Switch (an optional accessory) on the following
FireClass panels:
FC708D
FC718D
FC702D
FC702S (PCS800 only)
Table 1 outlines the three Ethernet switch types
available.
The FireClass POS800-S and POS800-M
Ethernet switches are used to connect devices
(for example a panel and an AC repeater) with a
single, redundant optical or metallic layer.
The POS800-S/POS800-M Ethernet switch has
four 10/100Base-T(X) RJ45 ports that connect it
to the FC-FI board, the primary graphical user
interface (GUI) and additional AC/ DC repeaters.
The switch also has two optical ports that can
connect an AC repeater using a redundant (or a
single) optical path if you require redundant wir-
ing or long distance wiring. After you connect the
Ethernet switch, configure it. Refer to the “Con-
figuring the POS800-S and POS800-M Ethernet
switches” section.The total maximum number
of devices on the network is 254 and this is split
between all devices (repeaters, the FC-FI board
and Ethernet switches). For the maximum num-
ber of LNET GUI repeaters, refer to the latest
FireClass Express documentation.
The FireClass PCS800 Ethernet switch provides
five 10/100Base-T(X) RJ45 ports that connect it
to the FC-FI board, the primary GUI and addi-
tional AC/DC repeaters. The PCS800 does not
require additional configuration.
Refer to Table 2 for limiting distances for each
type of cable.
Ethernet Switches allow the use of a dual power
supply to provide backup power in the event of,
for example, a component failure or a blown
fuse. Note that there is one power rail in the
panel.
Switch
Type
Optical Ports
Copper
Ports
POS800-S
2x 100Base-FX
(Single Mode)
4x 10/
100Base-T(X)
RJ45 Ports
POS800-M
2x 100Base-FX
(Multi-Mode)
4x 10/
100Base-T(X)
RJ45 Ports
PCS800
-
5x 10/
100Base-T(X)
RJ45 Ports
Table 1: Ethernet switch types
Switch
Type
Limiting Dis-
tance (Opti-
cal)
Limiting Dis-
tance (Cop-
per)[1]
POS800-S
30km
100m
POS800-M
2km
100m
PCS800
-
100m
Table 2: Limiting distances
[1] Limiting distances without a repeater. The distance
can increase if a switch or a repeater is used.
CAUTION
Before you install an Ethernet switch,
ensure that the panel is isolated from
the mains supply and it is not running on
batteries.
2/12
Fixing instructions Doc. version 1.0
Panel Accessories
FIRECLASS Fire detection system
Installing the Ethernet
Switch (POS800/PCS800) on
a FireClass Panel
1 Slide the Ethernet switch (refer to item 1 in
Fig. 1) into the slot cage holder (item 2).
2 Align the back of the Ethernet switch with the
back of the slot cage holder and secure it with
the screws supplied (item 3).
3 Prepare the power supply cables and feed
them through the top of the slot cage holes
(refer to item 4 in Fig. 2). Connect the wires
into the terminal block on the Ethernet
switch. Observe the correct polarity. If you
require redundant power supply wiring, fol-
low the same procedure.
4 Fit the other end of the cable to the FC-FI
board (XT6 or XT7 connectors) using the con-
nector supplied with the FC-FI. Refer to Table
3. Use both XT6 and XT7 connectors on the
FC-FI board for a redundant power supply.
5 The POS800 Ethernet switch also provides a
volt-free relay contact to which you can con-
nect the FC-FI isolated inputs (ISOLIN 1, ISO-
LIN 2) for fault monitoring. If required, con-
nect a bypass wire from V1+ (pin 5) on the
Ethernet switch connector to pin 4 on the
same connector. Additionally, connect the
wire from pin 3 on the Ethernet switch to
ISOL IN+ on the FC-FI board and from V1- on
the Ethernet switch to ISOL IN– on the FC-FI.
Refer to Fig. 3. Use a minimum 16/0.2 wire
(not supplied).
Note: Using a volt-free relay contact on the
Ethernet switch allows the panel to see faults
which would otherwise go undetected (for
example, a power port failure or an Ethernet
port downlink). You can select situations in
which the relay will actuate in configuration
on an individual basis (see the section, “Con-
figuring the POS800-S and POS800-M Ether-
net switches”). Each Ethernet switch reports
only faults related to its own ports.
6 Plug the power supply connector into the
Ethernet switch.
7 Fit the fibre-optic modules into the Ethernet
switch and connect the optical cables
(POS800 only).
8 Slide the slot cage holder (refer to item 2 in
Fig. 2) into the slot cage in the panel.
9 If the switch is a POS800, attach the fibre-
optic holder (item 5) into the slot cage and
secure it with screws (item 3).
10 Connect the metallic cables from the GUI and
the FC-FI board to the Ethernet port on the
switch.
A redundant cable is not provided. If
required, use a minimum 16/0.2 wire.
XT6, XT7
Ethernet Switch
+24V
V1+
-
V1-
Table 3: FC-FI connections
Fig. 1: Mounting the Ethernet switch to the slot cage
holder
1 – Ethernet switch
2 – Slot cage holder
3 – Screws
1
2
1
1
2
3
FIRECLASS Fire detection system
Panel Accessories
Fixing instructions Doc. version 1.0
3/12
Fig. 2: Mounting the Ethernet switch and slot cage
holder into the slot cage.
1 – Ethernet switch
2 – Slot cage holder
3 – Screws
4 – Slot cage holes
5 – Fibre-optic holder
4
1
2
3
1
2
3
4
5
+24V
(&Ͳ&/-XT7)
-
-
ISOL IN +
ISOL IN -
+24V
(&Ͳ&/-XT6)
Pin 1
Pin 6
Reset
buƩon[1]
Fig. 3: POS800 connectors overview
The dashed line indicates optional switch fault
monitoring.
[1] Press the reset button for 10 seconds to restore the
switch to the factory default configuration.
1
Fig. 4: Installing the Ethernet switch on a FC8AS AC repeater
1 – Earth cable screw (optional)
4/12
Fixing instructions Doc. version 1.0
Panel Accessories
FIRECLASS Fire detection system
Installing the Ethernet Switch on a FC8AS AC
Repeater
To mount the Ethernet switch on an FC8AS
repeater, complete these steps:
1 Ensure that the panel is isolated from the
mains and it is not running on batteries.
2 Mount the fixing elements (refer to item 2 in
Fig. 4) with screws (supplied) on the Ethernet
switch housing.
3 Connect the DC power supply to the Ethernet
switch connector (refer to item 4 in Fig. 4),
observing the correct polarity. If you require a
redundant power supply, connect a minimum
16/0.2 wire (not supplied).
4 Connect the other end of the DC supply cable
to the PMM800 board. Refer to Table 4.
5 If you require a redundant supply, use the
other pins on the same terminals on the
PMM800 board and connect to V2+ and V2-
on the Ethernet switch.
6 Fit the fibre-optic modules on to the Ethernet
switch and connect the optical cables.
7 Connect the metallic cable from the GUI to
the Ethernet port on the switch.
PMM800
Ethernet switch
24V (TB6)
V1+
0V (TB4)
V1-
Table 4: Power supply wiring connection