Turn on the power to the HPC or HPC Plus. Make sure that power to the heat
pump unit and its control circuitry is on. If the executive module is operating properly, the HPC or HPC Plus begins to control the heat pump in about 3 minutes (after performing a self-diagnostic check -
An auxiliary potentiometer can be connected to the HPC or HPC Plus at the
terminals labeled “Aux Pot.” Step Procedure 1 Connect the wiper wire to Terminal 1. 2 Connect the clockwise wire to Terminal 2. 3 Connect the counterclockwise wire to Terminal 4 at the “Temp Senso -
Take the following precautions during installation:
� Observe national and local electrical codes. � Observe voltage and current limits marked on the module. � Do not connect 115 volts to any terminal of the HPC or HPC Plus. They are Class 2 (low voltage) control devices. � Do no -
Setting the Module