1 pdf manual(s) TemperZone CWP Series for free download (Document Types: Installation & maintenance)
TemperZone CWP Series Installation & maintenance [PDF] (12 pages)
- Identifier: id-2312363
- Brand: TemperZone
- Device: TemperZone CWP Series Air Conditioner
- Type: Installation & maintenance, PDF
- Key Aspects: Product Performance Metrics, Future Product Updates, Technical Drawings and Schematics
- UPD Date: 07.07.2026
- Source File: 1975261.pdf
- Pages: 12
- Description: User instruction booklet for the TemperZone CWP Series.
Pages Preview:
Document Preview & Text Transcription (Main Page)
Click to expand and read text
GENERAL INSTALLATION DUCTED WATER COOLED PACKAGED AIR CONDITIONERS CWP models (c/w UC8) Installation & Maintenance 1. GENERAL 1.1 Introduction Follow these instructions to ensure the optimum performance, reliability and durability. Units must be installed in accordance with all national and regional and local regulations and bylaws. The appropriate permits must be acquired and adhered to. Seismic restraints must be fitted if required. The accompanying 'R32 Handling Ducted Units' pamphlet forms part of these Installation & Maintenance instructions. ! WARNING. These units use R32 refrigerant (Class A2L) which is mildly flammable. The system shall be installed, operated and stored in a adequately ventilated space where there is no continuously operating open flames (eg an operating gas appliance) or other R32 ignition source. If the refrigerant gas comes into contact with fire, a poisonous gas may occur. Be aware that R32 does not contain an odour. 2. INSTALLATION 2.1 Positioning & Mounting CWP units are designed to be fitted in a ventilated cupboard or closet and used with simple, short duct layouts. Units should be located as close to the space to be air conditioned as acoustic criteria allows. When determining the position of the air conditioner, allow adequate space around the unit to facilitate water pipe/ hose connections, condensate drainage, future servicing and maintenance. For apartment/hotel buildings, locate the units as close as possible to the shared foyer/corridor of each floor of the building to minimise the length and cost of water piping, and electrical conduit. The CWP unit has two pair of IN/OUT water connections (top or front). Choose the best pair to suit your application. For major changes of components, the whole unit would need to be removed from a tight closet space. Please consider this when installing the CWP. This should include, but not be limited to, the use of isolation valves and barrel unions on waterlines, easily accessible electrical isolations on all external (including control circuit) power supply, and easily detached flexible duct connection. Ensure there is enough working space in front of the electrical access panel. Allow adequate clearance for the filter to be removed for cleaning. Ventilation of the installation space, at the base level, permits refrigerant to disperse in the unlikely event of a leak. Fasten the unit to a solid base using at least two of the four mounting points in the feet. Some commercial rubber pads between the unit feet and the base can minimise transmission of vibration. Alternatively, use holding straps to secure the unit to the place. 2.2 Condensate Drain Mount the unit level as it comes with a sloping drain tray. The unit condensate drain is 'U' trapped inside the unit, therefore NO EXTERNAL TRAP REQUIRED. The external drain line must not be trapped or piped to a level above the drain tray. The drain line must be maintained at least 19 mm ID along its full length. A vent pipe is recommended (refer figure 1). OPEN DRAIN MINIMUM SLOPE 20 mm PER m (1 IN 50) 100 mm APPROX. AIR VENT PIPE (10 ID) 500 mm MAX. FROM UNIT NO TRAP REQUIRED Figure 1 Condensate Drain Check drain by pouring water into the drain tray (at the coil, behind the filter) and ensuring that it clears (with the unit operating). Failure to adhere to these instructions could cause flooding. If necessary, fit an external condensate lift-pump to assist in achieving adequate slope in the drain line. Do not install the drain line in front of any access panel. 2.3 Air Ducts, Filters and Grilles Rigid Ducting: a. Use flexible connections between unit and rigid ducting. b. Use appropriately sized insulated ducting with consideration for noise transmission through the ducting (refer Appendix II). c. Option: If access to the unit's air filter is restricted, then a return air grille with filter incorporated could be installed. d. Supply air grilles should be selected and installed to avoid draughts and noise but give good air distribution. 003-000-145 11/20
Similar Manuals in the Air Conditioner Category
| Device Model | Type of Document | Pages | Size | Views | Downloads | Updated | All Manuals for Device |
|---|---|---|---|---|---|---|---|
Audi A8 1994 |
Automobile #A453Z8 |
168 | 786 | 166 | 05-06-2026 | view all manuals | |
Truma Aventa eco |
#SAYM2S: Aventa eco Air Conditioner Operating instructions manual |
36 | 652 | 144 | 25-05-2026 | view all manuals | |
Ideal Air 700021 |
Air Conditioner #73A68O |
28 | 1332 | 307 | 28-04-2026 | view all manuals | |
LG ASNW07GB1U0 |
LG ASNW07GB1U0 Manual (Owner's manual), @5XR9ZF |
25 | 315 | 51 | 31-08-2026 | view all manuals | |
Haier AS072AZADA |
AS072AZADA (Air Conditioner ePDF User Guide, #AQ1HR5) |
20 | 2.86 Mb | 225 | 57 | 19-08-2026 | view all manuals |
stefani BOREA E Series |
#S92EQU: BOREA E Series Air Conditioner Instructions for assembly, use and maintenance |
23 | 785 | 118 | 28-03-2026 | view all manuals |