Crank ON Time Maximum crank time 5 Sec 1-999 Sec Crank Gap Time The delay between two successive cranks 5 Sec 1-999 Sec Crank Attempts The maximum number of cranks that shall be issued to start the Engine 3 1-10 Solenoid ON time The time for which stop solenoid will be kept active while stopping the engine 22 Sec 1-999Sec Disp Auto Scroll Setting ON will enable Auto Scroll of display. OFF: No scroll and next parameter can be viewed by pressing next switch ON ON/OFF Battery UV Warning Min. permissible battery voltage, below this the voltage is treated unhealt ...

2.0 Salient features, Protection & Supervision

3.0 Display/ Front Panel 4.0 Switches Description 5.0 LED Annunciations Description 6.0 Lamp Test 7.0 Digital Input 8.0 Analog Input 9.0 Digital Output 10.0 Modes of Operation 10.1 AMF Mode (ECON-A & ECON -A-4C) 10.1.1 Auto Mode 10.1.2 Semi Auto Mode 10.1.3 Manual Mode 10.2 Auto Stop Mode ( ECON-A & ECON - A-4C or ECON-S) 10.3 Manual Controller ( All models) 11.0 Setting Procedure 12.0 Parameter Mode 12.1 System Parameter 12.2 Generator Parameter 12.3 ...

Led lights up when ECON is in Semi Auto

Mains Voltage This symbol lights up continuously if Main is healthy else starts blinking. MCB LED turns on in case the mains breaker is switched on or else turned off GCB LED turns on in case the DG breaker is switched on or else turned off DG Voltage This indication glows continuously when the generator is running. Warning This LED blinks in case of a warning. Fault This LED blinks in case of a fault • 6.0 Lamp Test: If the ECON is switched on while the reset switch is pressed, all the ...

These are three programmable

output which can be configured for any one function from the list None None Unit Healthy Load Warning Fuel Pump Heater / Choke Pull Solenoid Over Load KW The Power(KW) above which the over load fault monitoring will start. The timer for it is as described in 13. This fault is only enabled while the generator is running. On expiry of the timer the generator is stopped 40 1-9999 Over Current The current above which the over current fault monitoring will start. The timer for it is as described in 13. This fault is only enabled while the g ...

This can be configured for one out

the listed below Parameters. HET Oil Level Oil Temperature Canopy Temperature HWT HWT Oil Level Oil Temperature, Canopy Temperature Digital Input 5# This can be configured for one out the listed below Parameters. Canopy door open Oil Level Oil Temperature Canopy Temperature Oil Temp. Oil Level Oil Temp., Canopy Temp. Digital Input 6# This can be configured for one out the listed below Parameters. Fire Oil Level Oil Temperature Canopy Temperature Oil Level Oil Level Oil Temperature Canopy Temperature Digital Input 7# This can be configured ...

Page - 27

31 Programmable Output 2 32 Programmable Output 1 33 Hooter 34 Solenoid 35 Crank 36 GCB 37 MCB 38 Chg. Alt. Contact 39 Battery(+ve)(8-35 V DC) 40 Battery(-ve) 41 Sensor(-ve) 42 D Input 5 43 D Input 6 44 D Input 7 45 D(+): RS485 46 D(-):RS485 ...

Fuel Sensor Select the installed sensor for Fuel

Type A Type A, Sam-0, Sam-1, Electronics, Linear, 0-5V(0-100%), Disabled* HWT Sensor Select the installed sensor for HWT Type A Type A, Type B,M&M, MNEPL,VE, TMTL AIR 1C, TMTL AIR 3C, TMTL WATER HUAFANG, TATA, GC(VDO), GC(MURPHY), Disabled * Oil Temp. Sensor Select the installed sensor for Oil Temp. Type A Type A, Type B,M&M, MNEPL,VE, TMTL AIR 1C, TMTL AIR 3C, TMTL WATER HUAFANG, TATA, GC(VDO), GC(MURPHY), Disabled * Sensor Open User can select the action to be taken in case of sensor open, it can be configured as a fault, or as warning or ...

Page - 19

Phase Sequence Delay This setting determines if the engine shall be started and load switch to generator in case of reverse phase sequence of mains. Disable Disable 1-999 Sec Mains Restoration Time The time for which Mains should be continuously healthy before stopping the Generator and load transferred to Mains. 10 Sec 1-999 Sec Warm Up Time The load is transferred to generator after expiry of this time 0Sec 0-999 Sec Gen Start Delay The starting of generator is delayed by this time after the mains unhealthy timers have expired and the mains contact has been r ...

Procom ECON-A-4C user guide recommended for: DGC-6D, Maschine, Vista SD, 68738, SER-1P.

⚠️ Download Safety

The Controller Operating instructions manual (32 pages) is completely safe to download (last scan date: 29/06/2026).

Related PDF Instructions for Procom ECON-A-4C:

Controller Equipment: Frequently Requested

Have some Questions about Procom ECON-A-4C Device?

Get valuable and actionable advices from other Procom ECON-A-4C device users. Describe your problem or question, regarding the using of ECON-A-4C, in as much detail as possible, and other users will be able to answer you.