2.2.1 Instrument Cable Twisted pair low capacitance shielded instrument cable 7 x 0.3mm (0.5mm²) should

be used for electrical connection between the flowmeter and remote instrumentation, use Belden® number 9363 or similar. The cable drain or screen should be terminated on a DC COMMON or a specifically assigned shield termination at the ...

2.1 Meter & totaliser orientation

Flomec D-40 The flowmeter MUST be mounted so that the rotor shafts are in a horizontal plane. This is achieved by mounting the meter so that the digital display is facing the user in a horizontal direction, it should never point towards the sky or towards the ground. If installed incorrectly the weight of the rotors will ...

Index / contents 1

Flomec D-40 1.0 General Page 1.1 Overview 2 1.2 Operating principal 2 1.3 Specifications 3 2.0 Installation 2.0 Mechanical installation 4 2.0.1 Meter & totaliser orientation 4 2.1 Flow conditioning & locations 5 2.2 Electrical Installation 5 2.2.1 Instrument Cable 6 2.2.2 Hazardous Area Wiring 6 2.3 Pulse output ...

I N S T R U C T I O N M A N U A L

Flomec D-40 Model: 1/2” (D-40) Medium Capacity positive displacement Pulse flowmeters OVAL GEAR ...

IM-D-40 - Pulse 3216

Flomec D-40 Each meter has been calibrated on mineral oil and will contain a small amount of oil residue. The oil used is Castrol Diesel Calibration Fluid 4113 (product code 055830). © 2017 Great Plains Industries, Inc., All Rights Reserved. Great Plains Industries, Inc. / 888-996-3837 / FLOMEC.net ...

The Oval Gear meter is a precise positive displacement flowmeter incorporating a pair of oval geared rotors.

Flomec D-40 These meters are capable of measuring the flow of a range of clean liquids such as fuels, fuel oils & lubricating liquids. The flowmeter is available with a pulse output only for safe or hazardous areas. The meter also ...

5.0 Fault Finding Pulse meters have two distinct sections: the mechanical wetted section housing the rotors

Flomec D-40 and the electrical section housing the pulse output board. Meters fitted with integral instruments have these two sections plus the instrument. The aim of fault finding is to trace the source of the fault to one of these sections ...

Mechanical Installation Prior to installing the meter check that :

• The fluid is compatible with the meter materials of construction using appropriate information such as fluid compatibility charts and site experience. • The application and process conditions are compatible with the meter specifications. Minimum and maximum flow ...

3.0 Commissioning Once the meter has been mechanically installed the meter is ready for commissioning.

The meter must NOT be run until the pipework is flushed of foreign matter, more often than not foreign matter is present after pipework fabrication or modification; weld slag, grinding dust, sealing tape & compound &/or sur ...

12 Trouble shooting

Flomec D-40 5.1 TROUBLE SHOOTING Symptom Solution 1. 1. Ground shield of signal cable 2. Re-route cable from high electrical energy sources 2. 1. Remove source of air or gas entrapment 2. Install an upstream air eliminator 3. 1. Increase back pressure on pump 2. Install a fast response one w ay check valve 3. Install a surge arrestor betw ...

Flomec D-40 user guide recommended for: QSE Series, OM025, Oval Gear, TM Series, EGM Series.