Installation instructions manual [PDF] (8 pages)
- Updated: 10.08.2026
Document Preview & Text Transcription
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Catalog No. 04-53300200-01
Printed in U.S.A.
Form 30XV-9SI
Pg 1
9-17
Replaces: New
Installation Instructions
Part No.: 30XV70000701
CONTENTS
Page
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 1
GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
Package Contents. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Configuration (All Sizes) . . . . . . . . . . . . . . . . . . . . . . . . . 5
Temperature Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
•
4 TO 20 mA
•
SPACE TEMPERATURE
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
•
4 TO 20 mA
•
SWITCH CONTROLLED
Additional EMM Functions . . . . . . . . . . . . . . . . . . . . . . . 6
•
INPUTS
•
OUTPUTS
SAFETY CONSIDERATIONS
Installation of this accessory can be hazardous due to sys-
tem pressures, electrical components, and equipment location
(such as a roof or elevated structure).
Only trained, qualified installers and service technicians
should install, start up, and service this equipment.
When installing this accessory, observe precautions in the
literature, labels attached to the equipment, and any other
safety precautions that apply.
•
Follow all safety codes.
•
Wear safety glasses and work gloves.
•
Use care in handling and installing this accessory.
GENERAL
The standard Touch Pilot™ controls software provided on
all 30XV chillers is programmed to accept various options to
modify the unit operation. The Energy Management Module
(EMM) board is required for 4 to 20 mA, 2 or 3-step demand
limit control, chilled water temperature reset by space tempera-
ture or 4 to 20 mA, and Ice Mode. Chilled water temperature
reset by return water or cooler delta T does not require the addi-
tion of this accessory. See Table 1 for EMM functions. The fol-
lowing functions are available with the EMM board:
•
Chilled Water Temperature Reset — Resets the chilled
water set point under less than full load capacity condi-
tions by the following methods:
— 4 to 20 mA Input: A field-supplied signal generator
and 1/2-watt, 250-ohm resistor are required.
— Space Temperature: A field-supplied space tempera-
ture sensor is required.
•
Demand Limit — Limits the capacity of the machine from
unit capacity by the following methods:
— 4 to 20 mA Input: A field-supplied signal generator
and 1/2-watt, 250-ohm resistor are required.
— 2 or 3-Step Switch Control: A field-supplied dry con-
tact switch is required (One-Step Demand Limit does
not require the EMM board).
•
Occupancy Override — Extends the occupied period for
machine operation. A field-supplied dry contact switch is
required.
•
Remote Chiller Lockout — Disables the chiller when
closed. A field-supplied dry contact switch is required.
•
Ice Done Control Switch — Signals the machine to exit
the Ice Build mode and enter an unoccupied time period.
A field-supplied dry contact switch is required.
The following status functions are available with the EMM
board:
•
Capacity Output Signal — A 0 to10 vdc analog output
signal indicating chiller capacity is available.
•
Shutdown Status Relay — A 24 vac output signal indi-
cating that the machine is shutting down.
•
Alert Relay — A 24 vac output signal indicating the unit
has an active alert.
•
Compressor Run Status — A 24 vac output signal (one
for compressor A, one for compressor B), indicating the
compressor is on.
The EMM board can be configured with the Touch Pilot
module.
Table 1 — EMM Functions by Unit
Package Contents — Examine the package contents
for correct part numbers. Refer to Table 2 for package con-
tents and usage. If any of the components are damaged, file
a claim with the shipping company and notify your Carrier
representative.
WARNING
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation. There
may be more than one disconnect switch. Tag all discon-
nect locations to alert others not to restore power until work
is completed.
INPUT/OUTPUT
INPUTS
Demand Limit, 2 or 3-Step
Demand Limit, 4-20 mA
Ice Done
Occupancy Override
Space Temperature Thermistor
Remote Chiller Lockout
Temperature Reset, 4-20 mA Signal
Temperature Set Point, 4-20 mA Signal
OUTPUTS
Alert Relay
Compressor A Run Status
Compressor B Run Status
Shutdown Status Relay
Total Capacity Output, 0-10 vdc
30XV140-500
Energy Management Module Accessory
2
Table 2 — 30XV Accessory Package Contents and Usage
*Terminal Block (TB6) is included in wiring harness assembly for P/Ns 30XV50074001 and 30XV50074101.
INSTALLATION
1.
Disconnect unit power. Follow proper lockout-tagout
procedures.
2.
Locate the control panel enclosure. See Fig. 1 and 2 for
control panel layout and location for installation of EMM
board and TB6. See Table 3 for main base board location.
3.
Install EMM board in the location shown in Fig. 1
(30XV140-325) or Fig. 2 (30XV350-500) using the
screws included in the accessory package.
4.
See Table 4 for TB6 mounting tools and location. Install
TB6 in the location shown in Fig. 1 (30XV140-325) or
Fig. 2 (30XV350-500) using the screws included in the
accessory package. TB6 should have harness already at-
tached as shown in Table 5. Correct connections should
be verified.
5.
Install circuit breaker CB5 in the hole on the display
mounting bracket. See Fig. 1 and 2 for location. Locate the
accessory-supplied
wiring
harness
30XV50074001
(30XV140-325) or 30XV50074101 (30XV350-500) and
install 2-pin power plug labeled EMM-J1 on the EMM
board terminal J1. Connect the 2 red wires labeled CB5 to
the installed CB5 circuit breaker. Run red wires labeled
TB11-X1 and brown wires labeled TB11-X2 to the termi-
nal blocks with matching labels.
6.
Also, the red (+), black (-) and white (G) wires labeled
TBC should be connected to the appropriate terminals
with matching labels. See Fig. 3. Locate the plug labeled
EMM-J9B in the accessory-supplied wiring harness and
connect it to the EMM board.
7.
Each of the remaining accessory-supplied EMM board
wiring harness connectors labeled J2A, J3, J4, J5, J6, J7A
and J7B should be connected to their respective connec-
tors on the EMM board.
Table 3 — 30XV Main Base Board Location
Table 4 — 30XV TB6 Installation
DESCRIPTION
PART NO.
QTY
USED ON
140-325
350-500
ENERGY MANAGEMENT BOARD
00PSN500038300A
1
X
X
TERMINAL BLOCK (TB6)
30XV50074301*
1
X
X
WIRING HARNESSES
30XV50074001
1
X
30XV50074101
1
X
TERMINAL BLOCK MOUNTING SCREWS, NO. 8
A6X10004352
3
X
X
EMM BOARD MOUNTING SCREWS
8-32 X 0.38 IN. LONG
AC41AB100
6
X
X
CIRCUIT BREAKER CB5
HH83ZB010
1
X
X
UNIT SIZE
VOLTAGE
MAIN BASE BOARD LOCATION
140-325
ALL
Behind left door of powerbox on end of
the chiller, mounting location on lower
right of the low voltage backpanel
350-500
ALL
Behind the center door of the powerbox
on end of the chiller, mounting location
on the fixed bracket in the low voltage
section
VOLTAGE
MOUNTING TOOLS AND LOCATION
SEE
FIG.
NO.
ALL
Locate terminal block TB5 in the low voltage
section of the powerbox (upper left door for
30XV140-325 units and top middle door for
30XV350-500 units). Using the accessory-
supplied mounting screws, mount terminal
block TB6 to the open spot on the bracket
below TB5.
1, 2
3
Table 5 — EMM Board Wiring
UNIT
WIRING HARNESS
EMM BOARD CONNECTION LOCATION
WIRE
COLOR
MBB CONNECTION LOCATION
30XV140-325
(All Voltages)
30XV50074001
EMM-J4-1
BLUE
TB6-12
EMM-J4-2
BLUE
TB6-13
EMM-J4-3
RED
TB6-14
EMM-J4-4
RED
TB6-15
EMM-J4-5
VIOLET
TB6-5
EMM-J4-6
VIOLET
TB6-6
EMM-J4-7
GRAY
TB6-9
EMM-J4-8
GRAY
TB6-10
EMM-J8-2
GREEN
TB6-17
EMM-J8-1
BLACK
TB6-16
EMM-J3-4
BLACK
TB6-18
EMM-J3-3
RED
TB6-19
EMM-J3-2
BLACK
TB6-20
EMM-J3-1
RED
TB6-21
EMM-J2A-5
BLACK
TB6-22
EMM-J2A-6
RED
TB6-23
EMM-J2A-7
BLACK
TB6-24
EMM-J2A-8
RED
TB6-25
EMM-J5-9
RED
EMM-J5-10
EMM-J6-6
ORANGE
TB6-8
EMM-J6-5
ORANGE
TB6-7
EMM-J7B-2
ORANGE
TB6-1
EMM-J7B-3
BLACK
TB6-2
EMM-J7A-2
ORANGE
TB6-3
EMM-J7A-3
BLACK
TB6-4
30XV350-500
(All Voltages)
30XV50074101
EMM-J4-1
BLUE
TB6-12
EMM-J4-2
BLUE
TB6-13
EMM-J4-3
RED
TB6-14
EMM-J4-4
RED
TB6-15
EMM-J4-5
VIOLET
TB6-5
EMM-J4-6
VIOLET
TB6-6
EMM-J4-7
GRAY
TB6-9
EMM-J4-8
GRAY
TB6-10
EMM-J8-2
GREEN
TB6-17
EMM-J8-1
BLACK
TB6-16
EMM-J3-4
BLACK
TB6-18
EMM-J3-3
RED
TB6-19
EMM-J3-2
BLACK
TB6-20
EMM-J3-1
RED
TB6-21
EMM-J2A-5
BLACK
TB6-22
EMM-J2A-6
RED
TB6-23
EMM-J2A-7
BLACK
TB6-24
EMM-J2A-8
RED
TB6-25
EMM-J5-9
RED
EMM-J5-10
EMM-J6-6
ORANGE
TB6-8
EMM-J6-5
ORANGE
TB6-7
EMM-J7B-2
ORANGE
TB6-1
EMM-J7B-3
BLACK
TB6-2
EMM-J7A-2
ORANGE
TB6-3
EMM-J7A-3
BLACK
TB6-4
4
CB5
TB6
EMM
TBC
TB11
Fig. 1 — Component Layout — 30XV 140-325 Units
CB5 LOCATION
TB6
EMM
TBC
TB11
Fig. 2 — Component Layout — 30XV 350-500 Units