INSTALLATION INSTRUCTIONS Bard Manufacturing Company, Inc. Bryan, Ohio 43506 www.bardhvac.com Manual No.: 2100-603B Supersedes: 2100-603A Date: 8-3-16 Q-TECTM SERIES PACKAGED HEAT PUMP Models: Q24H2DA Q24H2DB Q24H2DC Q30H2DA Q30H2DB Q30H2DC Q36H2DA Q36H2DB Q36H2DC Q42H2DA Q42H2DB Q42H2DC Q48H2DA Q48H2DB Q48H2DC Q60H2DA Q60H2DB Q60H2DC ...
CONTENTS Figures Figure 1 Unit Dimensions ....................................... 6 Figure 2 Air Seal Under Unit ................................... 7 Figure 3 Removal of Unit From Skid ........................ 7 Figure 4 Unit on Appliance Cart for Moving .............. 8 Figure 5 Installation With Duct Free Plenum ............. 9 Figure 6 Ducted Application .................................... 9 Figure 7 Supply Duct Co ...
GETTING OTHER INFORMATION AND PUBLICATIONS These publications can help you install the air conditioner or heat pump. You can usually find these at your local library or purchase them directly from the publisher. Be sure to consult current edition of each standard. National Electrical Code ..................... ANSI/NFPA 70 Standard for the Installation ............. ANSI/NFPA 90A of Air Conditioning and Ventilating Systems S ...
TABLE 1 FACTORY BUILT-IN ELECTRIC HEAT TABLE (See Table 2 for Available Electric Heat by Unit Model) Nominal KW At 240V At 208V At 480V At 460V KW 1-Ph Amps 3-Ph Amps BTUH KW 1-Ph Amps 3-Ph Amps BTUH KW 3-Ph Amps BTUH KW 3-Ph Amps BTUH 5.0 5.0 20.8 17,065 3.75 18.0 12,799 6.0 6.0 14.4 20,478 4.50 12.5 15,359 6.0 7.2 20,478 5.52 6.9 18,840 9.0 9.0 21.7 30,717 6.75 18.7 23,038 9.0 10.8 30,717 8.28 10.4 28,260 ...
MODEL Rated Volts & Phase No. Field Power Circuits Single Circuit Dual Circuit Minimum Circuit Ampacity Maximum External Fuse or Ckt. Brkr. Field Power Wire Size Ground Wire Minimum Circuit Ampacity Maximum External Fuse or Ckt. Breaker Field Power Wire Size Ground Wire Size Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Ckt. A Ckt. B Q24H2DA0Z A05 A10 230/208- 1 1 1 1 or 2 22 47 72 30 50 80 10 8 4 ...
SHIPPING DAMAGE Upon receipt of equipment, the carton should be checked for external signs of shipping damage. The skid must remain attached to the unit until the unit is ready for installation. If damage is found, the receiving party must contact the last carrier immediately, preferably in writing, requesting inspection by the carrier’s agent. UNIT REMOVAL FROM SKID FIGURE 3 REMOVAL OF UNIT FROM SKID It is recommended tha ...
HANDLING UNIT AFTER REMOVAL FROM SKID The unit will have to be turned sideways and removed from the skid to fit through a 36" doorway. If the door height allows, the unit can be slid sideways through the door. If the unit can not be slid through the door, then the unit will have to be put on a cart and tipped down to roll through the door. It is recommended that an appliance cart by used with a strap to hold the unit on the ...
FIGURE 6 DUCTED APPLICATION FIGURE 5 INSTALLATION WITH DUCT FREE PLENUM ...
DUCT WORK Any heat pump is more critical of proper operating charge and an adequate duct system than a straight air conditioning unit. All duct work must be properly sized for the design airflow requirement of the equipment. Air Conditioning Contractors of America (ACCA) is an excellent guide to proper sizing. All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conse ...
FRESH AIR INTAKE This unit is equipped with a fresh air damper assembly. The damper blade is locked in the closed position when the unit is shipped from the factory. To allow the damper to operate remove the two plastic locking pins, one on each end of the blade. This will allow for maximum fresh airflow. The damper blade will now open when the indoor blower is operating. If less than maximum fresh airflow is required, re ...
WATER TRAP FIGURE 11 REAR DRAIN (TOP VIEW) WALL (MAXIMUM 10" FOR REAR DRAIN) COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE. SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGURE 9 OPTIONAL SIDE DRAIN (SIDE VIEW) Q-TEC UNIT ...
MIS-2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A ...
SUPPLIED WITH DRAIN BOX KIT 3/4" PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR) (TIGHTEN THREADS SO TEE IS THREADS) (APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q/Tec PRODUCT 1/2" SLIP X 1/2" SLIP X 3/4" NPT TEE SUPPLIED WITH DRAIN BOX KIT PLUG INSTALLED IN SIDE Q/Tec DRAIN MIS-2470 FIGURE 12B IMPORTANT! ...
REMOVE KNOCK-OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS-2471 FIGURE 12C (If Used) ...
MIS-2472 DRAIN HOSE FROM INDOOR DRAIN PAN. MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING, SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED. ( WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN BUT AT A SLIGHT COOLING PERFORMANCE REDUCTION OF 2-3% ) FIGURE 12D ...
Washer Sleeve Stud MIS-2689 Nut Lower Control Panel Condenser Door (Removed) Return Grille FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM (2 PCS.) SIDE TRIM (2 PCS.) CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTACHMENT MOUNTING BRACKET #8 SCREW PROVIDED (LIGHT COLOR) WALL SLEEVE #10 HEX HEAD SCREW PROVIDED FIGURE 13B UNIT MOUNTING ...
INSTALLATION MOUNTING THE UNIT When installing a Q-TEC unit near an interior wall on the left side, a minimum of 8 inches is required; 12 inches is preferred. When installing a Q-TEC unit near an interior wall on the right side, a minimum of 18 inches is required as additional space is required to connect the side drain. If the rear condensate drain kit QCDS48 is used the minimum can be reduced to 8 inches. This clearance is ...
OPTIONAL CLIMATE CONTROLS SEQUENCE OF OPERATION The standard Climate Control Option X is a remote thermostat connection terminal block. See Figure 17 or Figure 18 for wiring diagram. Compatible thermostats are listed in Table 4. The Climate Control Option E is an electronic, programmable thermostat with humidistat. The subbase of the thermostat is factory wired to the front panel of the unit. See Figure 19 for wiring diag ...
If the unit is running in heat pump mode and the humidistat calls for dehumidification, the dehumidification mode takes precedence over the heat pump heating mode. The unit will not return to the heating mode until 2nd stage heating is called for. The Climate Control Option I is an electronic, programmable thermostat with humidistat and a CO2 controller. The subbase of the thermostat and CO2 controller are factory wired to ...