DSE DSE892 SNMP Manual 

Text of the manual

DSE892 SNMP Gateway Manual ISSUE 1

DEEP SEA ELECTRONICS PLC DSE892 SNMP Gateway Manual Document Number : 057-179 Author : Anthony Manton

DSE892 SNMP Gateway Manual

2 Deep Sea Electronics Plc Highfield House Hunmanby North Yorkshire YO14 0PH ENGLAND Sales Tel: +44 (0) 1723 892099 Sales Fax: +44 (0) 1723 893303 E-mail : [email protected] Website : www.deepseaplc.com DSE892 SNMP Gateway Hardware Manual © Deep Sea Electronics Plc All rights reserved. No part of this publication may be reprod

DSE892 SNMP Gateway Manual

3 Table of Contents 1 BIBLIOGRAPHY .................................................................................................. 5 2 INTRODUCTION .................................................................................................. 5 2.1 SNMP ........................................................................

DSE892 SNMP Gateway Manual

4 6.3.1 MODULE PAGE ......................................................................................................... 33 6.3.1.1 MONITORING EVENTS ...................................................................................... 33 6.3.1.2 MONITORING INSTRUMENTATION .....................................................

This document refers to and is referred to by the following DSE publications which can be obtained

from the DSE website www.deepseaplc.com DSE Part Description 053-148 DSE892 installation instructions 057-178 DSE43xx Configuration Suite PC Software Manual 057-093 DSE44xx Configuration Suite PC Software Manual 057-172 DSE45xx Con

Simple Network Management Protocol (SNMP) is an internet standard protocol for managing devices

on IP networks. It is used to monitor network-attached devices for conditions that warrant administrative attention. An administrative computer (SNMP manager) monitors a group of DSE controllers using a variety of connection methods (detail

3.1 PART NUMBERING

0892 - 001 - 01 3.2 POWER SUPPLY Minimum supply voltage 8V continuous, 4V for up to 5 minutes. Cranking dropouts Able to survive 0V for 100mS providing the supply was at least 8V before the dropout and recovers to 8 volts afterwards. Maximum supply voltage 32V continuous (transient protection to 64V) Power

3.6 RS232 CONNECTOR

This socket provides support for connection to one DSE controller. PIN No NOTES 1 Received Line Signal Detector (Data Carrier Detect) 2 Received Data 3 Transmit Data 4 Data Terminal Ready 5 Signal Ground 6 Data Set Ready 7 Request To Send 8 Clear To Send 9 Ring Indicator View looking into the male connector on the module

3.7 RS485 CONNECTOR

This socket provides support for connection to a maximum of 16 (sixteen) DSE controllers in a daisy chain RS485 network. Ensure termination resistors (120Ω) are fitted as shown to the ends of the link as per RS485 standard. PIN No NOTES A (-) Two core screened twisted pair cable. 120Ω impedance suitable for RS485 use.