DSE DSE892 SNMP Manual
Text of the manual
DSE892 SNMP Gateway Manual ISSUE 1
DEEP SEA ELECTRONICS PLC
DSE892 SNMP Gateway Manual
Document Number : 057-179
Author : Anthony Manton
DSE892 SNMP Gateway Manual
2
Deep Sea Electronics Plc
Highfield House
Hunmanby
North Yorkshire
YO14 0PH
ENGLAND
Sales Tel: +44 (0) 1723 892099
Sales Fax: +44 (0) 1723 893303
E-mail : [email protected]
Website : www.deepseaplc.com
DSE892 SNMP Gateway Hardware Manual
© Deep Sea Electronics Plc
All rights reserved. No part of this publication may be reprod
DSE892 SNMP Gateway Manual
3
Table of Contents
1
BIBLIOGRAPHY .................................................................................................. 5
2
INTRODUCTION .................................................................................................. 5
2.1
SNMP ........................................................................
DSE892 SNMP Gateway Manual
4
6.3.1
MODULE PAGE ......................................................................................................... 33
6.3.1.1
MONITORING EVENTS ...................................................................................... 33
6.3.1.2
MONITORING INSTRUMENTATION .....................................................
This document refers to and is referred to by the following DSE publications which can be obtained
from the DSE website www.deepseaplc.com
DSE Part
Description
053-148
DSE892 installation instructions
057-178
DSE43xx Configuration Suite PC Software Manual
057-093
DSE44xx Configuration Suite PC Software Manual
057-172
DSE45xx Con
Simple Network Management Protocol (SNMP) is an internet standard protocol for managing devices
on IP networks. It is used to monitor network-attached devices for conditions that warrant
administrative attention.
An administrative computer (SNMP manager) monitors a group of DSE controllers using a variety of
connection methods (detail
3.1 PART NUMBERING
0892
-
001
-
01
3.2 POWER SUPPLY
Minimum supply voltage
8V continuous, 4V for up to 5 minutes.
Cranking dropouts
Able to survive 0V for 100mS providing the supply was at least 8V
before the dropout and recovers to 8 volts afterwards.
Maximum supply voltage
32V continuous (transient protection to 64V)
Power
3.6 RS232 CONNECTOR
This socket provides support for connection to one DSE controller.
PIN No NOTES
1
Received Line Signal Detector (Data Carrier Detect)
2
Received Data
3
Transmit Data
4
Data Terminal Ready
5
Signal Ground
6
Data Set Ready
7
Request To Send
8
Clear To Send
9
Ring Indicator
View looking into the male connector on the module
3.7 RS485 CONNECTOR
This socket provides support for connection to a maximum of 16 (sixteen) DSE controllers in a daisy
chain RS485 network.
Ensure termination resistors (120Ω) are fitted as shown to the ends of the link as per RS485 standard.
PIN No
NOTES
A (-)
Two core screened twisted pair cable.
120Ω impedance suitable for RS485 use.