Emerson Rosemount 8732E Quick Installation Manual

Text of the manual

Quick Installation Guide

00825-0100-4662, Rev CC December 2012 Rosemount 8732 Start Step 1: Pre-Installation Step 2: Handling Step 3: Mounting Step 4: Installation (Flanged Sensors) (Wafer Sensors) (Sanitary Sensors) Step 5: Grounding Step 6: Wiring Step 7: Basic Configuration Product Certifications End Rosemount 8732E

Quick Installation Guide

00825-0100-4662, Rev CC December 2012 Rosemount 8732 2 © 2013 Rosemount Inc. All rights reserved. All marks property of owner. IMPORTANT NOTICE This document provides basic installation guidelines for the Rosemount® 8732. It does not provide instructions for detailed configuration, diagnostics, maintenance, service, troubleshootin

Quick Installation Guide

00825-0100-4662, Rev CC December 2012 Rosemount 8732 3 STEP 1: PRE-INSTALLATION Before installing the Rosemount 8732 Magnetic Flowmeter Transmitter, there are several pre-installation steps that should be completed to make the installation process easier: • Identify the options and configurations that apply to your application •

Quick Installation Guide

00825-0100-4662, Rev CC December 2012 Rosemount 8732 4 Environmental Considerations To ensure maximum transmitter life, avoid excessive heat and vibration. Typical problem areas: • high-vibration lines with integrally mounted transmitters • warm-climate installations in direct sunlight • outdoor installations in cold climates.

Quick Installation Guide

00825-0100-4662, Rev CC December 2012 Rosemount 8732 5 Changing Hardware Switch Settings In most cases, it is not necessary to change the setting of the hardware switches. If you need to change the switch settings, complete the steps outlined in the manual. Electrical Considerations Before making any electrical connections to the Ros

Quick Installation Guide

00825-0100-4662, Rev CC December 2012 Rosemount 8732 6 STEP 2: HANDLING Handle all parts carefully to prevent damage. Whenever possible, transport the system to the installation site in the original shipping containers. PTFE-lined sensors are shipped with end covers that protect it from both mechanical damage and normal unrestrained

Quick Installation Guide

00825-0100-4662, Rev CC December 2012 Rosemount 8732 7 STEP 3: MOUNTING Upstream/Downstream Piping To ensure specification accuracy over widely varying process conditions, install the sensor a minimum of five straight pipe diameters upstream and two pipe diameters downstream from the electrode plane (see Figure 3). Installations with

Quick Installation Guide

00825-0100-4662, Rev CC December 2012 Rosemount 8732 8 Sensor Location The sensor should be installed in a location that ensures the sensor remains full during operation. Vertical installation allows upward process fluid flow and keeps the cross-sectional area full, regardless of flow rate. Horizontal installation should be restricte