Venmar 41502 Installation Manual
Text of the manual
These products earned the ENERGY STAR® by
meeting strict energy efficiency guidelines set by
Natural Resources Canada and the US EPA. They
meet ENERGY STAR requirements only when used
in Canada.
06010A rev. 17
INSTALLATION GUIDE FOR
VENMAR AVS UNITS
CONSTRUCTO 1.0 HRV AND CONSTRUCTO 1.0 ERV
Model no.: 41502
(HRV with top ports)
Model no.: 4150
Because of the large amount of models covered by this publication, the illustrations are typical ones. Some details of your unit may be
slightly different than the ones shown.
Please take note that this manual uses the following symbols to emphasize particular information:
NOTE: Indicates supplementary information needed to fully complete an instruction.
W
TABLE OF CONTENTS
1. TYPICAL INSTALLATIONS ......................................................................................................................... 4-5
1.1
FULLY DUCTED SYSTEM ..........................................................................................................................................4
1.2
CENTRAL DRAW POINT
Installations may vary according to the type of unit and the ports configuration (top or sides). Use the following illustrations as guidelines
to help you decide on how the unit will be installed.
All the units should be hung from the joists.
In every case, bathroom fans and a range hood should be used to exhaust stale air. Also, f
TYPICAL INSTALLATIONS (CONT’D)
1.4
ATTIC INSTALLATION FOR ERV UNITS ONLY
All 3 types of installations can be used in the attic (Fully ducted system, Central Draw Point or Simplified). The example shown below is a
Simplified installation (connection to a forced air system).
NOTE: To get the most of your ERV unit, the ambient temperature around the unit
UNIT PREPARATION (CONT’D)
The door latches location can be changed from sides to front of the unit, according to the installation needs.
To do so, turn the unit upside down. Open the latches an unscrew them from the unit. Install the latches on their new locations.
VD0176
Latches on sides of the unit
Latches in front of the
PLANNING OF THE DUCTWORK
• Keep it simple. Plan for a minimum of bends and joints.
• Keep the length of insulated ducts to a minimum.
• Do not ventilate crawl spaces or cold rooms. Do not attempt to recover the exhaust air from a dryer or a range hood. This would
cause clogging of the filters and recovery module.
• If
INSTALLING THE DUCTWORK AND REGISTERS (CONT’D)
2.6.3 SIMPLIFIED INSTALLATION (AS ILLUSTRATED IN SECTION 1.3)
There are 2 methods for connecting the unit to the furnace/air handler:
Method 1: Supply-return connection
Method 2: Return-return
Stale air intake:
• Cut an opening into the furnace/air handler return duct not les