Bentel Security FireClass 100 Operation & User’s Manual
Text of the manual
BENTEL SECURITY srl reserves the right to modify the contents of this manual without prior notice.
via Florida - Z.I. Valtesino - 63013 GROTTAMMARE (AP) - ITALY
User guide: Analogue Fire Control Panel FireClass100
ISTRUZIONI USO INGLESE ANTINC. FC100/UK
ISTUSOFC100/UK
TABLE OF CONTENTS
OVERVIEW
5
Signalling . . . . . . . . . . . . . . . . . . . . . . . . . . 6
LEDs . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Buzzer . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Display . . . . . . . . . . . . . . . . . . .
Disable . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Delete Verify . . . . . . . . . . . . . . . . . . . . . . . 25
Delete logger . . . . . . . . . . . . . . . . . . . . . . . 25
Telecom Module . . . . . . . . . . . . . . . . . . . . . 26
READI
This manual holds all the necessary information for proper use of the Fire-
Class100 system.
The components of the FireClass100 modular system depend on the size
and complexity of the installation. Some of the components and functions
mentioned in this manual may not be present on your system.
FireClass100 system comprises:
� a FireClass100 Contro
The control panel status is signalled by:
� the LEDs on the front of the panel;
� the back-lit display of 20 characters on 4 rows;
� the built-in buzzer.
LEDs
ALARM
ON: - indicates ALARM status. In the event of False Alarm - press the SI-
LENCE button to inhibit momentarily the SILENCEABLE Outputs, or the
RESET button to deactivate all the o
As per the green MAIN POWER LED. This LED will go ON during Mains
power failure (the MAIN LED has memory).
LOW BATTERY
ON: - indicates that the control panel batteries are low, and therefore, in the
event of blackout, will not be able to guarantee proper functioning of the con-
trol panel. Wait for several hours - if the LED remains ON call the in
The control panel has an incorporated buzzer which signals the panel sta-
tus.
3 sec. sound
1 sec. pause
Signals PREALARM status.
1 sec. sound
0.5 sec. pause
Signals FIXED Delay running.
1 sec. sound
2 sec. pause
Signals - the PAS delay running.
0.2 sec. sound
0.2 sec. pause
Signals - the control panel is in ALARM status.
05 sec. sound
0.5 sec. pause
The message opposite signals STANDBY
status.
The first row shows the control panel La-
bel (programmed by the Installer).
The fourth row shows the Time, date and
day of the week.
WARNING
status
The message opposite signals WARNING
status. An Input Point has exceeded the
WARNING threshold, and there is risk of
ALARM status.
PREALARM
s