INSTRUCTION GUIDE: AUXILIARY HEATER INSTALLATION
General
The EA series electric auxiliary heater mounts internally in vertical top and bottom discharge units to provide supplemental and/
or emergency heating capability. On horizontal and rear discharge vertical units, the EA series electric auxiliary heater control box
mounts internally wh
INSTRUCTION GUIDE: AUXILIARY HEATER INSTALLATION
Installation Steps cont.
9)
All EA*H and EAS4 Heater Kits:
•� Install auxiliary heat control box as seen in Figures 2, 4, and 5.
NOTE: Breakers, fuse, or terminal block is always located on the
side opposite from the air coil as shown in Figure 7.
NOTE: Horizontal end discharge, left
INSTRUCTION GUIDE: AUXILIARY HEATER INSTALLATION
Installation Steps cont.
•� Plug�the�5-pin�connector�(blue,�violet�and�green�wires)�hanging�from�the�auxiliary�
heat control panel into the variable speed ECM motor receptacle P11. Connect the
green ground wire to the blower housing using the previously removed
INSTRUCTION GUIDE: AUXILIARY HEATER INSTALLATION
Installation Steps cont.
•� If�unit�has�the�Aurora�Advanced�Control�option,�proceed�to�the�Energy�Monitoring�Connections�table,�for�instructions�on�
connecting the auxiliary heat kit to the auxiliary heat current transducer.
•� Proceed�to�step
INSTRUCTION GUIDE: AUXILIARY HEATER INSTALLATION
Figure 8B
Figure 8C
EALH15, EALH20
EAS4, EASH4, EAMH5, EAMH8, EAMH10
Figure 8A
Figure 7
Auxiliary Heat
Control Box
Main Control Box
Auxiliary Heater
Control Board
Terminal or
Fuse Block
Auxiliary Heat
Power Supply
Auxiliary heat control box installation in vertical rear discharge cabinets as
INSTRUCTION GUIDE: AUXILIARY HEATER INSTALLATION
Figure 8B
Figure 8C
Figure 8D
EALH15, EALH20
EAS4, EASH4, EAMH5, EAMH8, EAMH10
Figure 8A
Main Control Box
Auxiliary Heater
Control Board
Terminal or
Fuse Block
Top Discharge
Rear Discharge
Main Control Box
Auxiliary Heater
Control Board
Terminal or
Fuse Block
EAL15, EAL20
NOTE: Controls are
INSTRUCTION GUIDE: AUXILIARY HEATER INSTALLATION
Auxiliary Heat Ratings
Table 8
Table 10
MODEL
KW
STAGES
BTU/HR
MIN
CFM
208V 240V
208V
240V
EAS(H)4
2.9
3.8
1
9,700
12,900
250
EAM(H)5
3.6
4.8
1
12,300 16,300
450
EAM(H)8
5.7
7.6
2
19,400 25,900
550
EAM(H)10
7.2
9.6
2
24,600 32,700
650
EAL(H)10
7.2
9.6
2
24,600 32,700 1100
EAL(H)15
10.8
14.4
INSTRUCTION GUIDE: AUXILIARY HEATER INSTALLATION
Energy Monitoring Connections for Units with Aurora Advanced Control Option
EAS(H)4
EAM(H)5
Remove the GRAY wire from the quick connect terminal on the L2 side of the auxiliary heat supply power block. Route wire through the inside of the
current transducer and connect it back to it’s ori