Endress+Hauser Proservo NMS5 Operating Instruction
Text of the manual
Intelligent Tank Gauge
Table of contents
1
Safety instructions. . . . . . . . . . . . . . . . . . . . . . . . 3
1.1
Designated use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2
Installation, commissioning, and operation . . . . . . . . . 3
1.3
Product requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.4
Operational safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.5
Electrostatic charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
1.6
Notes on safety conventions and symbols . . . . . . . . . . . 5
1.7
Symbols for certain types of information . . . . . . . . . . . 5
2
Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1
Device designation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.2
Order Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.3
Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
2.4
Certificates and approvals . . . . . . . . . . . . . . . . . . . . . . . 16
2.5
Registered trademarks . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.1
Incoming acceptance, transport, and storage . . . . . . . 17
3.2
Terms related to tank measurements . . . . . . . . . . . . . 18
3.3
Design and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 19
3.4
Necessary tools for installation . . . . . . . . . . . . . . . . . . 20
4
Displacer and measuring wire . . . . . . . . . . . . 21
4.1
Shape, diameter, and material . . . . . . . . . . . . . . . . . . . 21
5
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.1
Type of tanks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
5.2
Type of tank installation . . . . . . . . . . . . . . . . . . . . . . . . 24
5.3
Mounting without guide system . . . . . . . . . . . . . . . . . . 25
5.4
Mounting with a stilling well. . . . . . . . . . . . . . . . . . . . . 26
5.5
Mounting NMS5 with guide wire . . . . . . . . . . . . . . . . . 31
5.6
Alignment of NMS5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
5.7
Electrostatic charge . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
5.8
Mounting of the device . . . . . . . . . . . . . . . . . . . . . . . . . 35
6
Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.1
Wiring connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
6.2
Terminal assignment . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
6.3
Temperature input system. . . . . . . . . . . . . . . . . . . . . . . 48
7
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
7.1
Touch control and programming matrix . . . . . . . . . . . 50
7.2
HOME position. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
7.3
Access code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
7.4
Operation command and new operation status . . . . . 55
7.5
Operation of displacer . . . . . . . . . . . . . . . . . . . . . . . . . . 57
7.6
Calculation of level and densities . . . . . . . . . . . . . . . . . 58
8
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . .60
8.1
Initial settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
8.2
Settings for NMT 53x connections . . . . . . . . . . . . . . . .64
8.3
Settings for connection to NRF560 . . . . . . . . . . . . . . . .65
8.4
Liquid level calibration. . . . . . . . . . . . . . . . . . . . . . . . . . 66
8.5
Remote communications. . . . . . . . . . . . . . . . . . . . . . . . 69
8.6
Density and density profile measurements . . . . . . . . .75
8.7
Interface measurement . . . . . . . . . . . . . . . . . . . . . . . . . 82
8.8
Sealing of NMS5 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .83
9
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . .84
9.1
Exterior cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
9.2
Seals replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
9.3
Repairs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
9.4
Repairs to Ex-approved devices . . . . . . . . . . . . . . . . . . 84
9.5
Replacement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
10
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . .85
10.1
Calibration chamber . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
10.2
Power and control switch . . . . . . . . . . . . . . . . . . . . . . . 85
10.3
Ball valve NHV4A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .86
10.4
Reducing flange NHF4 . . . . . . . . . . . . . . . . . . . . . . . . . 86
11
Diagnosis and troubleshooting. . . . . . . . . . . . 87
11.1
Selection of diagnostic code and history . . . . . . . . . . 87
11.2
Error and status messages . . . . . . . . . . . . . . . . . . . . . . .88
11.3
Alarm history display. . . . . . . . . . . . . . . . . . . . . . . . . . . 90
11.4
List of alarm messages . . . . . . . . . . . . . . . . . . . . . . . . . 90
11.5
Flowcharts for diagnostics and troubleshooting . . . . .91
11.6
Setting after parts replacement . . . . . . . . . . . . . . . . . . .97
11.7
Intelligent function . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98
11.8
Return . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
11.9
Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
11.10 Software History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
12
Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
12.1
Sensor calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
12.2
Weight calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . .103
13
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . 106
14
Matrix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108
14.1
Programming Matrix . . . . . . . . . . . . . . . . . . . . . . . . . 108
14.2
Description of Programming Matrix . . . . . . . . . . . . . 118
15
Appendix. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 154
15.1
RS 485 MODBUS (COM- 5) terminator . . . . . . . . . . 154
15.2
Measurement wire replacement . . . . . . . . . . . . . . . . .156
Table of contents
Proservo NMS5 of intelligent tank gauge is designed for high-accuracy liquid level measurement in
storage and process applications.
NMS5 performs the tank inventory management, loss control, total cost saving, and safe operation.
NMS5 is designed for the purpose of single or multi-task installations, converting a wide range of mea-
surement functions.
1.2
Installation, commissioning, and operation
• Mounting, electrical installation, start-up, and maintenance of the instrument may only be per-
formed by trained personnel authorized by the operator of the facility.
• Personnel must read and understand these installation instructions before performing the proce-
dures.
• The instrument may only be operated by personnel who are authorized and trained by the operator
of the facility. All instructions in this manual must be observed.
• The installer must make sure that the measuring system is correctly wired according to the wiring
diagrams. The measuring system must be grounded.
• Observe all law and regulations applicable and valid for your country and pertaining to the opening
and repairing of electrical devices.
1.3
Product requirements
Power source
Check the voltage of the power supply before connecting it to the product. It should be the exact voltage
required for proper operation of the product.
Connection to other devices
It is possible to connect to other devices explained in this instruction. Refer to each operation instruc-
tion when connecting to devices.
Ground
Do not remove earth terminal or earth wire when the power is on.
Power cable
Use a power cable specified by our company. The product should be protectively grounded before it is
connected to a measurement object or an external control circuit.
1 Safety instructions
• Use the explosion proof type for measurement in areas where explosion hazards are present.
• Devices installed in areas having explosion hazards must not be opened when the power is on.
• Strict compliance with installation instructions and - ratings, as directed in this supplementary doc-
umentation, is mandatory.
• Device maintenance and repair is restricted to meet explosion proof regulations.
• Tighten the cable gland firmly.
• Devices employed in areas having explosion hazards should be installed and wired in keeping with
explosion proof regulations.
• Ensure that all personnel are properly qualified.
• Observe the certification requirements as well as national and local regulations.
Changes or modifications other than those expressly approved by Endress+Hauser are strictly prohib-
ited. Unauthorized modifications can cause malfunction or damage, resulting in serious injury or
death.
1.5
Electrostatic charge
Mounting with a stilling well is recommended for use in a tank which contains flammable liquid with
conductivity at 10-8 S/m or less.
In case of installation without a stilling well, allow enough stilling time according to the table below
before lowering the level gauge down to the liquid surface. When a stilling well is used, the stilling time
is shown as in column “<10” in the table below.
Conductivity
(S/cm)
Reference: Stilling time (min.)
Liquid volume in tank (m3)
≤10
10~50
50~100
≥5000
≥10-8
≥1
≥1
≥1
≥2
10-12 ~10-8
≥2
≥3
≥10
≥30
10-14~10-12
≥4
≥5
≥60
≥120
≤10-14
≥10
≥10
≥120
≥240
(Japan National Institute of Occupational Safety and Health)
WARNING
1 Safety instructions
Notes on safety conventions and symbols
To highlight safety-relevant or alternative operating procedures in this manual, the following conven-
tions have been used, each indicated by a corresponding symbol on the left.
1.7
Symbols for certain types of information
Symbol
Meaning
A0011189-EN
DANGER!
This symbol alerts you to a dangerous situation. Failure to avoid this situation will result in
serious or fatal injury.
A0011190-EN
WARNING!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
serious or fatal injury.
A0011191-EN
CAUTION!
This symbol alerts you to a dangerous situation. Failure to avoid this situation can result in
minor or medium injury.
A0011192-EN
NOTICE!
This symbol contains information on procedures and other facts which do not result in
personal injury.
Symbol
Meaning
A0011182
Allowed
Indicates procedures, processes or actions that are allowed.
A0011183
Recommendation
Indicates procedures, processes or actions that are recommended.
A0011184
Forbidden
Indicates procedures, processes or actions that are forbidden.
A0011193
Tip
Indicates additional information.
DANGER
WARNING
CAUTION
NOTICE
1 Safety instructions
The following technical data are given on the instrument nameplate:
Figure 1:
ATEX approval type Ex d/Ex d [ia]
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
��
NP- ### - # (*2)
XA00578G-A/08
Supply
Measuring range m
Displacer weight g
Displacer dia. mm�
Measure wire dia. mm�
Density range ~
Manufacturing date
Test date
Tester
Zero point of liquid level gauge is mm
under the reference point.
Only read level when indication "BAL" is present.
Certification no.
Tank ID
Ambient temperature: ~ +60°C
Process temperature: -200 ~ +200°C
KEMA 05 ATEX 2071
Ex d IIB T6...T3
ATEX II 1/2 G
Order code
Ser. no.
0044
PROSERVO NMS53
Made in Japan
Yamanashi 406-0846
Endress+Hauser Yamanashi Co.,Ltd.
IP67, NEMA 4X
Warning: Do not open the cover when energized.
*1: -20°C or -40°C is selected depending on the product
specification.
*2: NP-2514-X for -20°C, NP-2515-X for -40°C
1
Type code
2
Order code
3
Serial number
4
Power supply specification
5
Measuring range
6
Displacer weight
7
Displacer diameter
8
Measuring wire diameter
9
Density measurement lower limit
10
Density measurement upper limit
11
Date of manufacture
12
Date of manufacture test
13
Name of tester
14
Reference point (W&M)
15
Protection Class
16
NMi W&M Certificate number
17
PTB W&M Certificate number
18
PTB W&M Certificate number
2 Identification
ATEX approval type Ex d
Figure 3:
FM approval type XP
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
NP-2551-4
Order code
Ser. no.
0044
PROSERVO NMS53
Made in Japan
Yamanashi 406-0846
Endress+Hauser Yamanashi Co.,Ltd.
IP67, NEMA 4X
Supply
KEMA 05 ATEX 2071
Ex d IIC T6...T3
ATEX II 1/2 G
XA00578G-A/08
Certification no.
Tank ID
Ambient temperature: -20 ~ +60°C
Process temperature: -200 ~ +200°C
Measuring range m
Displacer weight g
Displacer dia. mm�
Measure wire dia. mm�
Density range ~
Manufacturing date
Test date
Tester
Zero point of liquid level gauge is mm
under the reference point.
Only read level when indication "BAL" is present.
Warning: Do not open the cover when energized.
Warning: Do not open the cover when an
exposive atmoaphere is present.
�
�
1
Type code
2
Order code
3
Serial number
4
Power supply specification
5
Measuring range
6
Displacer weight
7
Displacer diameter
8
Measuring wire diameter
9
Density measurement lower limit
10
Density measurement upper limit
11
Date of manufacture
12
Date of manufacture test
13
Name of tester
14
Reference point
15
NMi W&M Certificate number
16
PTB W&M Certificate number
17
PTB W&M Certificate number
NP-2346-4
Temperarure Class T4
APPROVED
F M
XP Class I, Div. 1, Gp. C, D
XP Class I, Zone 1, Gp. IIB
DIP Class II, III, Div. 1, Gp. E, F, G
Ambient temperature: -20 � +60�
NEMA 4X, IP67
Order code
Ser. no.
Input rated
Ambient temperature -20 ~
+60
Input
Output
Relay contact rated
30 V AC, 2A; 42 V DC, 2A, 60 W.
Measuring range m
Manufacturing date
Warning: Keep cover tight while circuits are alive.
Caution: Use supply wires suitable for 70� minimum.
Caution: A seal shall be installed within 50 mm of the enclosure.
PROSERVO NMS53
Made in Japan
Yamanashi 406-0846
Endress+Hauser Yamanashi Co.,Ltd.
4
5
6
3
2
1
2 Identification
1
Type code
2
Order code
3
Serial number
4
Input rating
5
Signal input specification
6
Signal output specification
FM approval type XP-AIS
Figure 5:
CSA approval type Ex d[ia]
Install: per drawing Ex421-439-
NP-2421-5
APPROVED
F M
Temperarure class T4
Ambient temperature: -20 � +60�
XP-AIS Class I, Div. 1, Gp. C, D
XP-AIS Class I, Zone 1, Gp. IIB
DIP Class II, III, Div. 1, Gp. E, F, G
XP-ANI Class I, Div. 2, Gp. C, D
Order code
Ser. no.
Input rated
Ambient temperature -20 ~
+60
Input
Output
Relay contact rated
30 V AC, 2A; 42 V DC, 2A, 60 W.
Measuring range m
Manufacturing date
Warning: Keep cover tight while circuits are alive.
Caution: Use supply wires suitable for 70� minimum.
Caution: A seal shall be installed within 50 mm of the enclosure.
PROSERVO NMS53
Made in Japan
Yamanashi 406-0846
Endress+Hauser Yamanashi Co.,Ltd.
4
5
3
2
1
6
�
1
Type code
2
Order code
3
Serial number
4
Input rating
5
Signal input specification
6
Signal output specification
7
XA version number
NP-2526-2
Ex d[ia] IIB T4; Class I, Zone 1;
Class I, Div. 1, Gp. C, D ; [Ex ia]
Clsss II, Div. 1, Gp. E, F, G ;
Class III
Ambient temperature: -20 � +60 �
MWP psi
R
216422
Type 4X, IP67
Intrinsically Safe Outputs when
installed per drawing Ex540-742
Order code
Ser. no.
Input rated
Input
Output
Relay contact rated
30 V AC, 2A; 42 V DC, 2A, 60 W.
Measuring range m
Manufacturing date
Warning: Keep cover tight while circuits are alive.
Caution: Use supply wires suitable for 70� minimum.
Caution: A seal shall be installed within 50 mm of the enclosure.
PROSERVO NMS53
Made in Japan
Yamanashi 406-0846
Endress+Hauser Yamanashi Co.,Ltd.
5
2
3
1
4
6
7
⑧
1
Type code
2
Order code
3
Serial number
4
Input rating
5
Signal input specification
6
Signal output specification
7
Measuring rage
8
XA version number
2 Identification
CSA approval type Ex d
Figure 7:
TIIS approval type Ex d
NP-2342-3
Order code
Ser. no.
Input rated
Ambient temperature: -20 � +60�
MWP psi
Exd IIB T4;
Class I, Divsion 1, Groups C, D ;
Clsss II, Divsion 1, Groups E, F, G ;
Class III
R
216422
Type 4X, IP67
Input
Output
Relay contact rated
30 V AC, 2A; 42 V DC, 2A, 60 W.
Measuring range m
Manufacturing date
Warning: Keep cover tight while circuits are alive.
Caution: Use supply wires suitable for 70� minimum.
Caution: A seal shall be installed within 50 mm of the enclosure.
PROSERVO NMS53
Made in Japan
Yamanashi 406-0846
Endress+Hauser Yamanashi Co.,Ltd.
1
2
3
4
5
7
6
1
Type code
2
Order code
3
Serial number
4
Input rating
5
Signal input specification
6
Signal output specification
7
Measuring rage
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�������Ex proof model :
�������Protection class :
�� / Rating
����
� Power supply:
���������/ Data communication: DC 48 V 300 mA�������
��������/ Contact input :� DC 30 V 0.6 W �������
������� / Contact output:� AC 250 V 1.5 A
�����������������������������������DC 30 V 9 W
�����/Ambient temperature: -20 � +60 �
� � � ��������������������������������
�����������������������������HIV�����0.05M��Km����
�������������������
Note: Be sure to cutt off the power and cool douwn this instrument befor opening
the cover.
In case of cunduit wiring method, shall be use HIV wire (insulation resistance
over 0.05M-ohm.Km)
Zero point of liquid level gauge is mm
under the reference point.
Only read level when indication "BAL" is present.
NP-2645-1
IP67
NEMA 4X
Order code
Ser. no.
PROSERVO NMS53
���������������
Yamanashi 406-0846
Made in Japan
Endress+Hauser Yamanashi Co.,Ltd.
BA 00401G/08
Measuring range m
Displacer weight g
Displacer dia. mm�
Measure wire dia. mm�
Density range ~
Manufacturing date
Test date
Tester
Certification no.
Tank ID
1
Type code
2
Order code
3
Serial number
4
Ex-proof model
5
Protection class
6
Power supply specification
7
Measuring range
8
Displacer weight
9
Displacer diameter
10
Measuring wire diameter
11
Density measurement lower limit
12
Density measurement upper limit
13
Date of manufacture
14
Date of manufacture test
15
Name of tester
16
NMi W&M Certificate number
17
PTB W&M Certificate number
18
PTB W&M Certificate number
2 Identification
IEC approval type Ex d -20°C
Figure 9:
IEC approval type Ex d -40°C
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
Ex d IIB T6...T3 Ga/Gb
IECEx KEM 09.0062
NP-2619-2
XA00582G-A/08
Ambient temperature: ~ +60°C
Process temperature: -200 ~ +200°C
Order code
Ser. no.
0044
PROSERVO NMS53
Made in Japan
Yamanashi 406-0846
Endress+Hauser Yamanashi Co.,Ltd.
IP67, NEMA 4X
Warning: Do not open the cover when energized.
Supply
Measuring range m
Displacer weight g
Displacer dia. mm�
Measure wire dia. mm�
Density range ~
Manufacturing date
Test date
Tester
Zero point of liquid level gauge is mm
under the reference point.
Only read level when indication "BAL" is present.
Certification no.
Tank ID
-20
1
Type code
2
Order code
3
Serial number
4
Power supply specification
5
Measuring range
6
Displacer weight
7
Displacer diameter
8
Measuring wire diameter
9
Density measurement lower limit
10
Density measurement upper limit
11
Date of manufacture
12
Date of manufacture test
13
Name of tester
14
Reference point
15
Protection class
16
NMi W&M Certificate number
17
PTB W&M Certificate number
18
PTB W&M Certificate number
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
Ex d IIB T6...T3 Ga/Gb
IECEx KEM 09.0062
XA00582G-A/08
Order code
Ser. no.
0044
PROSERVO NMS53
Made in Japan
Yamanashi 406-0846
Endress+Hauser Yamanashi Co.,Ltd.
IP67, NEMA 4X
Warning: Do not open the cover when energized.
Supply
Measuring range m
Displacer weight g
Displacer dia. mm�
Measure wire dia. mm�
Density range ~
Manufacturing date
Test date
Tester
Zero point of liquid level gauge is mm
under the reference point.
Only read level when indication "BAL" is present.
Certification no.
Tank ID
NP-2620-2
Ambient temperature: -40 ~ +60°C
Process temperature: -200 ~ +200°C
1
Type code
2
Order code
3
Serial number
4
Power supply specification
5
Measuring range
6
Displacer weight
7
Displacer diameter
8
Measuring wire diameter
9
Density measurement lower limit
10
Density measurement upper limit
11
Date of manufacture
12
Date of manufacture test
13
Name of tester
14
Reference point
15
Protection class
16
NMi W&M Certificate number
17
PTB W&M Certificate number
18
PTB W&M Certificate number
2 Identification
IEC approval type Ex d IIC
Figure 11:
NEPSI approval type IIB
�
�
�
�
�
�
�
�
�
�
�
�
�
�
Ex d IIC T6...T3 Ga/Gb
IECEx KEM 09.0062
NP-2621-2
XA00582G-A/08
Ambient temperature: -20 ~ +60°C
Process temperature: -200 ~ +200°C
Order code
Ser. no.
0044
PROSERVO NMS53
Made in Japan
Yamanashi 406-0846
Endress+Hauser Yamanashi Co.,Ltd.
IP67, NEMA 4X
Warning: Do not open the cover when energized.
Supply
Measuring range m
Displacer weight g
Displacer dia. mm�
Measure wire dia. mm�
Density range ~
Manufacturing date
Test date
Tester
Zero point of liquid level gauge is mm
under the reference point.
Only read level when indication "BAL" is present.
Certification no.
Tank ID
��
��
��
1
Type code
2
Order code
3
Serial number
4
Power supply specification
5
Measuring range
6
Displacer weight
7
Displacer diameter
8
Measuring wire diameter
9
Density measurement lower limit
10
Density measurement upper limit
11
Date of manufacture
12
Date of manufacture test
13
Name of tester
14
Reference point
15
NMi W&M Certificate number
16
PTB W&M Certificate number
17
PTB W&M Certificate number
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
��
Ex d IIB T6...T3 Ga/Gb
GYJ111093
NP-####-x(*2)
XA01257G-*/08
Ambient temperature: ~ +60°C
Process temperature: -200 ~ +200°C
Order code
Ser. no.
0044
PROSERVO NMS53
Made in Japan
Yamanashi 406-0846
Endress+Hauser Yamanashi Co.,Ltd.
IP67, NEMA 4X
Supply
Measuring range m
Displacer weight g
Displacer dia. mm�
Measure wire dia. mm�
Density range ~
Manufacturing date
Test date
Tester
Zero point of liquid level gauge is mm
under the reference point.
Only read level when indication "BAL" is present.
Certification no.
Tank ID
Warning: Do not open the cover when energized.
Warning: Do not open the cover when an
explosive atmosphere is present.
*1: -20°C or -40°C is selected depending on the product
specification.
*2: NP-2692 for -20°C, NP-2693 for -40°C
1
Type code
2
Order code
3
Serial number
4
Power supply specification
5
Measuring range
6
Displacer weight
7
Displacer diameter
8
Measuring wire diameter
9
Density measurement lower limit
10
Density measurement upper limit
11
Date of manufacture
12
Date of manufacture test
13
Name of tester
14
Reference point
15
Protection class
16
NMi W&M Certificate number
17
PTB W&M Certificate number
18
PTB W&M Certificate number
2 Identification
NEPSI approval type IIC
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
�
NP-2694
Order code
Ser. no.
0044
PROSERVO NMS53
Made in Japan
Yamanashi 406-0846
Endress+Hauser Yamanashi Co.,Ltd.
IP67, NEMA 4X
Supply
Ex d IIC T6...T3 Ga/Gb
GYJ111093
XA01257G-*/08
Ambient temperature: -20 ~ +60°C
Process temperature: -200 ~ +200°C
Measuring range m
Displacer weight g
Displacer dia. mm�
Measure wire dia. mm�
Density range ~
Manufacturing date
Test date
Tester
Zero point of liquid level gauge is mm
under the reference point.
Only read level when indication "BAL" is present.
Certification no.
Tank ID
Warning: Do not open the cover when energized.
Warning: Do not open the cover when an
explosive atmosphere is present.
1
Type code
2
Order code
3
Serial number
4
Power supply specification
5
Measuring range
6
Displacer weight
7
Displacer diameter
8
Measuring wire diameter
9
Density measurement lower limit
10
Density measurement upper limit
11
Date of manufacture
12
Date of manufacture test
13
Name of tester
14
Reference point
15
NMi W&M Certificate number
16
PTB W&M Certificate number
17
PTB W&M Certificate number
2 Identification
Drum Housing Pressure Rating; Material:
1
0… 200mbar/20kPa/2.9psi; Alu
2
0… 200mbar/20kPa/2.9psi; stainless ste>
4
0… 5.88bar/588kPa/85.28psi; Alu
5
0… 5.88bar/588kPa/85.28psi; stainless steel
6
0… 24.5bar/2.45MPa/355.34psi; stainless steel
9
Special version, TSP-no. to be spec.
020
Approval:
0
Weather proof, IP 67 NEMA 4X
1
TIIS Ex d IIB T4
5
FM XP Cl. I Div. 1 Gr. C-D
N
FM XP-AIS Cl. I Div.1 Gr. C-D
6
CSA Cl. I Div. 1 Gr. C-D
O
CSA Ex d[ia] Cl. I Div. 1 Gr. C-D
G
ATEX II 1/2G Ex d IIB T6...T3
Q
ATEX II 1/2G Ex d IIC T6...T3
S
ATEX II 1/2G Ex d IIB T6...T3, -40°C
J
ATEX II 1/2G Ex d (ia) IIB T6...T3
U
ATEX II 1/2G Ex d (ia) IIB T6...T3, -40°C
A
IEC Ex d ia IIB T6...T3 Ga/Gb
B
IEC Ex d IIB T6...T3 Ga/Gb
C
IEC Ex d IIC T6...T3 Ga/Gb
D
IEC Ex d ia IIB T6...T3 Ga/Gb, -40°C
E
IEC Ex d IIB T6...T3 Ga/Gb, -40°C
T
NEPSI Ex d ia IIB T6...T3
V
NEPSI Ex d IIB T6...T3
W NEPSI Ex d IIC T6...T3
X
NEPSI Ex d ia IIB T6...T3, -40°C
4
NEPSI Ex d IIB T6...T3, -40°C
9
Special version, TSP-no. to be spec.
030
Application:
A
Liquid Level
B
PTB (<1mm) type approval, liquid level
C
NMi (<1mm) type approval, liquid level
D
Multi measurement, liquid level, I/F level, bottom, density
E
PTB (<1mm) type approval, liquid level, I/F level, bottom, density
F
NMi (<1mm) type approval, liquid level, I/F level, bottom, density
G
Density profile multi measurement, liquid level, I/F level, bottom, density
H
PTB (<1mm)type approval, density profile, liquid level, I/F level, bottom, density
J
NMi (<1mm) type approval, density profile, liquid level, I/F level, bottom, density
Y
Special version, TSP-no. to be spec.
040
Output 1:
F
Not selected
A
2-way 2-wire (V1 protocol)
J
2-way 2-wire (MDP protocol)
B
2-way 2-wire (BBB protocol)
C
2-way 2-wire (MIC, RS232C protocol)
D
2-way 2-wire (MIC protocol)
G
HART active
H
HART passive
L
Whessmatic 550, overvoltage protection
M Mark Space
N
Enraf BPM
P
Modbus RS 485
Y
Special version, TSP-no. to be spec.
NMS5-
Product designation (Continued on next page)
2 Identification
4 x relay SPST
2
2 x 4-20mA
3
4 x relay SPST, 2 x 4 - 20mA
4
2 x relay SPST, Overspill prevention TÜV
5
4 x relay SPST, 1 x 4 - 20mA
9
Special version, TSP-no. to be spec.
060
Input:
0
HART (NMT5xx, NRF560, pressure transmitter)
1
1 x spot temperature Pt100, HART (NRF560, pressure transmitter)
2
2 x operation contact, HART (NMT5xx, NRF560, pressure transmitter)
3
1 x spot temperature Pt100, 2 x operation contact, HART
(NMT5xx, NRF560, pressure transmitter)
4
1 x status, HART (NMT5xx, NRF560, pressure transmitter)
5
1 x spot temperature Pt100, 1 x status, HART (NMT5xx, NRF560, pressure transmitter)
6
1 x spot temperature Pt100, 1 x status, 2 x operation contact, HART
(NMT5xx, NRF560, pressure transmitter)
9
Special version, TSP-no. to be spec.
070
Measuring Range; wire:
C
0 - 28m; SUS316L, 0.15mm
L
0 - 36m; SUS316L, 0.15mm
N
0 - 47m; SUS316L, 0.15mm
H
0 - 16m; PFA>SUS316, 0.4mm
K
0 - 16m; Alloy C, 0.2mm
M 0 - 22m; Alloy C, 0.2mm
Y
Special version, TSP-no. to be spec.
080
Cable Entry:
E
4 x thread G1/2
F
4 x thread G3/4
G
4 x thread NPT1/2
H
4 x thread NPT3/4
L
4 x thread M20
M
4 x thread M25
Y
Special version, TSP-no. to be spec.
090
Process Connection:
A
10K 80A RF, flange JIS B2220
C
10K 80A FF, flange JIS B2220
U
10K 150A RF, flange JIS B2220
E
20K 80A RF, flange JIS B2220
G
NPS 3" Cl.150 RF, flange ASME B16.5
J
NPS 3" Cl.300 RF, flange ASME B16.5
W NPS 4" Cl.300 RF, flange ASME B16.5
T
NPS 6" Cl.150 RF, flange ASME B16.5
L
DN80 PN10 B1, flange EN1092-1 (DIN2527 B)
N
DN80 PN25 B1, flange EN1092-1 (DIN2527 B)
Q
80A 150lbs RF, flange JPI 7S-15
S
80A 300lbs RF (apply for NMS5-6), flange JPI 7S-15
Y
Special version, TSP-no. to be spec.
100
Power supply:
3
85 - 264 VAC, 50/60 Hz
4
20 - 62 VDC, 20 - 55 VAC, 50/60 Hz
Y
Special version, TSP-no. to be spec.
NMS5-
Product designation (Continued on next page)
2 Identification
Cylindrical 30 mm, SUS316
K
Cylindrical 40 mm, SUS316
D
Cylindrical 50 mm, SUS316
W Cylindrical 30 mm, PTFE
V
Cylindrical 40 mm, PTFE
U
Cylindrical 50 mm, PTFE
T
Cylindrical 50 mm, AIloy C
B
Conical 50 mm, PTFE
R
Conical 70 mm, SUS316
S
Conical 110 mm, SUS316
Y
Special version, TSP-no. to be spec.
120
O-ring; chamber finishing:
0
NBR; not selected
1
Silicon rubber; not selected
5
Silicone rubber; FEP coated
3
PTFE (wire drum FKM); not selected
4
PTFE (Wire drum FKM); FEP coated
6
CR; not selected
2
FKM; not selected
7
FKM; FEP coated
8
FFKM; not selected
A FFKM; FEP coated
9
Special version, TSP-no. to be spec.
130
Options:
A
not selected
C
Rc3/8 cleaning nozzle
D
Rc3/8 gas purging nozzle
E
Guide wire installation
G
Relief valve
H
Relief valve, pressure gauge
J
Sunshade
L
Rc3/8 gas purging nozzle, sunshade
M Rc3/8 cleaning nozzle, sunshade
N
Rc3/8 gas purging nozzle, guide wire installation
P
Rc3/8 cleaning nozzle, guide wire installation
Q
Guide wire installation, sunshade
R
Relief valve, guide wire installation
S
Relief valve, pressure gauge, guide wire installation
T
Relief valve, sunshade
U
Relief valve, pressure gauge, sunshade
Y
Special version, TSP-no. to be spec.
NMS5-
Complete product designation
2 Identification
Scope of delivery
It is extremely important to follow the instructions concerning the unpacking, transportation and stor-
age of measuring instruments provided in the chapter “Incoming Acceptance, Transportation, Stor-
age”.
The scope of delivery consists of:
• Assembled Instrument
Accompanying documentation:
• Installation Instructions (this manual)
• Safety Instructions (XA)
• Functional Safety Manual (SD), Supplied with 4 to 20mA and Overspill Prevention Relay Output
2.4
Certificates and approvals
CE Mark, declaration of conformity
The device is designed to meet state-of-the-art safety requirements, has been tested and left the fac-
tory in a condition in which it is safe to operate. The device complies with the applicable standards and
regulations as listed in the EC declaration of conformity and thus complies with the statutory require-
ments of the EC directives. Endress+Hauser confirms the successful testing of the device by affixing to
it the CE mark.
2.5
Registered trademarks
HART®
Registered trademark of HART Communication Foundation, Austin, USA
FieldCare®
Registered trademark of the company Endress+Hauser Flowtec AG, Rheinach, CH
WARNING
2 Identification
Incoming acceptance, transport, and storage
3.1.1
Incoming acceptance
Check the packing and contents for any signs of damage.
Check the shipment, and make sure that nothing is missing and that the items match your order.
3.1.2
Transport
• Follow the safety instructions and conditions of transportation for instruments in excess of 18kg
(40 lbs.).
• Do not lift the measuring instrument by its housing during transportation.
3.1.3
Storage
Pack the measuring instrument so that it is protected against impacts during storage and transporta-
tion.
The original packing material provides the optimum protection for this.
The allowed storage temperature is -40 to +85°C (-40 to +185°F)
WARNING
3 Installation
Terms related to tank measurements
Figure 13:
Terms related to tank measurements
Lower layer
Middle layer
Upper layer
Upper interface
Lower interface
Liquid level
Nozzle
NMS5
Reference line
Dip-point offset
Upper limit stop level
Upper limit alarm
Ullage level
Gauge reference length
Tank height
Upper interface level
Lower interface level
Lower limit alarm
Lower limit stop level
Dipping reference point
(Dipping data place)
Liquid depth
(Innage level)
Measurement hatch
(Dipping reference)
Bottom of tank
3 Installation
Design and dimensions
Figure 14:
NMS5 dimension, unit
of measurement: mm (in)
*1: In case of 18mm (Flange thickness) at JIS10K80ARF
*2: In case of 20mm (Flange thickness) at JIS20K80ARF
8
7
6
11
3
9
10
2
1
5
C
D
NMS5 - 1/ NMS5 - 4
Max. 39.7 (1.56)
Travel distance of displacer
34.6 (1.36) for 28m (93.33ft)
Wire Ø0.15 (0.0059)
39.7 (1.56) for 36 (120ft)
Wire Ø0.15 (0.0059)
Displacer position at top of tank (center of flange)
Displacer position at bottom of tank
NMS5 - 2/ NMS5 - 5 / NMS5 - 6
Max. 41.6 (1.64)
Displacer position at top of tank (center of flange)
Displacer position at bottom of tank
8 Holes flange
8 Holes flange
95 (3.74)*1
289 (11.38)*1
316 (12.44)*2
99 (3.9)*2
321 (12.64)
351 (13.82)
301 (11.85)
338 (13.31)
4
A
B
5
D
1
C
3
11
9
10
2
6
7
8
4
A
B
Travel distance of displacer
34.6 (1.36) for 28m (93.33ft)
Wire Ø0.15 (0.0059)
39.7 (1.56) for 36 (120ft)
Wire Ø0.15 (0.0059)
41.6 (1.64) for 47m (156.67ft)
1
Electrical compartment
7
Measuring wire
2
Terminal box
8
Displacer
3
Display (LCD)
9
Calibration window
4
Cable entry (A, B, C, D)
10
Window cover
5
Wire drum housing
11
Touch control
6
Flange
NOTICE
3 Installation
Necessary tools for installation
The following tools are required when installing NMS5.
Figure 15:
Tools to be prepared, unit of measurement: mm (in)
Box end wrench
Crescent wrench
Allen wrench (Hex key)
Screw driver
� Flat head
� Phillips
Wire cutters or
terminal pliers
Wire terminal
Water pump pliers
Density calibration test weight
17 (0.669) and size matched
with flange size
350 (13.78)
3 (0.118)/5 (0.196)
M3
1.25sq, 2.0sq
Max. 6
(0.236)
3 Installation
Displacer and measuring wire
4.1
Shape, diameter, and material
4.1.1
Displacer
There are several types of displacer available for NMS5.
• The standard type has cylindrical shape and a diameter of 50 mm. Diameters from 30 to 50 mm are
optional.
• Cylindrical shape is used for viscous liquids. It is also effective if the stilling well is not smooth on its
interior surface.
Displacer weight and volume depend on the application. Thin displacers are suited for level measure-
ment, thicker ones for bottom level, interface level, and density measurement.
A counterweight is optional for heavy turbulence (inquire).
Displacers of three different materials are provided.
• The standard material is stainless steel SUS316.
• Alloy C and PFA are optional for corrosive liquids.
• Solid PFA, however, is not applied for flammable liquids.
The following size of displacer will be supplied, when you order custody transfer approval.
NMi (Netherlands).................Ø70 (2.76)
PTB (Germany).......................Ø110 (4.33)
4.1.2
Measuring wire
• The standard material of the measuring wire is stainless steel SUS316L.
• Alloy C and PFA coated stainless steel SUS316 are for corrosive liquids.
The following specification of measuring will be supplied when ordering the custody transfer approval.
• Select SUS316L (0.15mm) for NMi and PTB specifications.
• Refer to the separate "Techenical Information TI00452G" for displacer selection information and
Appendix "15.3 Displacer" in this chapter.
4 Displacer and measuring wire
Type of tanks
Depending on the type of tank and application, different installation procedures are recommended for
NMS5.
Type of tanks
Without guide system
With stilling well
With guide wires
fixed roof tank
Floating roof tank
Covered floating roof
tank
Pressurized or bullet
tank
Tank with agitator or
heavy turbulence
5 Installation
• A stilling well is required in a floating roof tank and a covered floating roof tank.
• Guide wires cannot be installed in a floating roof tank. When the measuring wire is exposed to free
space, it may break due to an external shock.
• Installing guide wires is not allowed in pressurized tanks because the wires would prevent closing
the valve for replacing the wire, wire drum, or displacer. NMS5 installation position is important for
applications without the guide wire system in order to prevent the measuring wire from being bro-
ken (refer to Alignment of NMS5 for details).
• Installing guide wires is not allowed in pressurized tanks because the wires would prevent closing
the valve for replacing the wire, wire drum, or displacer. NMS5 installation position is important for
applications without the guide wire system in order to prevent the measuring wire from being bro-
ken.
5 Installation
Type of tank installation
Figure 16:
Typical tank installation
A
Fixed roof tank
B
High pressure tank
C
Floating roof tank with stilling well
1
NMS5
2
Ball valve
3
Measuring wire
4
Displacer
5
Stilling well
6
Prothermo NMT539
B
2
3
4
5
6
1
4
5
6
A
1
3
3
4
5
C
6
1
5 Installation
Mounting without guide system
NMS5 is mounted on a nozzle of the tank roof without a guide system. Sufficient clearance inside the
nozzle is necessary to allow the displacer to move without hitting the inner walls.
Figure 17:
Mounting without guide system
D1
Inner Diameter of the tank nozzle
d
Diameter of the displacer
1
Displacer
D 1
1
d
5 Installation
Mounting with a stilling well
The stilling well diameter that is required to protect the measuring wire without disturbing its opera-
tion varies depending on the tank height. The stilling well could either be of constant diameter, or nar-
rower at its upper part and wider at its lower part. The following figure shows two examples of the lat-
ter case, namely a concentric stilling well and an asymmetric stilling well.
Figure 18:
Mounting with connection pipe
A
Front view
B
Side view
L1
Length from the center of the calibration window to the upper part of the stilling well
L2
Length from the center of the calibration window to the bottom of the stilling well
L3
Length from the center of the calibration window to the bottom of the flange
D1
Diameter of upper part of stilling well
D2
Diameter of stilling well
d
Diameter of displacer
p(Lx)
Longitudinal wire position from the center of the flange
r
Radial direction offset
L1
L2
L1
L2
A
B
L3
L3
D�
D�
d
r
D�
d
D�
p (Lx)
5 Installation
Mounting with asymmetric stilling well
A
Front view
B
Side view
L1
Length from the center of the calibration window to the upper part of the stilling well
L2
Length from the center of the calibration window to the bottom of the stilling well
L3
Length from the center of the calibration window to the bottom of the flange
D1
Diameter of upper part of stilling well
D2
Diameter of stilling well
d
Diameter of displacer
p(Lx)
Longitudinal wire position from the center of the flange
r
Radial direction offset
• L3: length from center of the calibration window to the bottom of the flange (99 mm (3.9 in) +
flange thickness). For JIS 10K 150A RF, the dimension is 99 mm (3.9 in) and the flange thickness
is 22 mm (0.87 in).
• When using an asymmetric stilling well, take into account the lateral shift of the displacer and fol-
low the NMS5 mounting direction as shown in the figure.
• To calculate the required stilling well diameters, the formula below should be used. The following
tables contain the necessary parameters in order to calculate the dimensions of the stilling well. Be
sure to have appropriate dimensions of the stilling well according to each dimension in the table.
• The radial direction offset is required for only the 47 m (154.2 ft) wire drum. For all other drums,
the offset is 0 mm/in.
L1
L2
L1
L2
A
B
L3
L3
D�
D�
d
r
D�
d
D�
p (Lx)
5 Installation
The following graph shows the lateral shift of the displacer depending on the measured distance
for the different wire drums.
Symbol
Description
P (Lx)
Longitudinal wire position from the center of the flange
r
Radial direction offset
s
Safety factor recommended; 5.0mm (0.20 in)
Feature: 070
Descriptions
r
N
0-47m: SUS316L, 0.15mm
6 mm (0.24 in)
Feature: 110
Descriptions
d
B
Conical 50mm, PTFE
50mm (1.97 in)
D
Cylindrical 50mm, SUS316
50mm (1.97 in)
K
Cylindrical 40mm, SUS316
40 mm (1.57 in)
N
Cylindrical 30mm, SUS316
30 mm (1.18 in)
R
Conical 70mm, SUS316
70 mm (2.76 in)
S
Conical 110mm, SUS316
110 mm (4.33 in)
T
Cylindrical 50mm, AlloyC
50mm (1.97 in)
U
Cylindrical 50mm, PTFE
50mm (1.97 in)
V
Cylindrical 40mm, PTFE
40 mm (1.57 in)
W
Cylindrical 30mm, PTFE
30 mm (1.18 in)
5 Installation
Lateral shift of displacer according to measurement range
a
0-16m: PFA>SUS316, 0.4mm
b
0-16m: Alloy C, 0.2mm
c
0-22m: Alloy C, 0.2mm
d
0-28m: SUS316L, 0.15mm
e
0-36m: SUS316L, 0.15mm
f
0-47m: SUS316L, 0.15mm
Upper diameter of stilling well
The dimension of D1 has to be the largest value of the dimensions D1a, D1b,D1c, and D1d according to the
following formula.
Example: L1 = 1 000 mm, L2 = 20 000 mm, d = 50 mm, s = 5.0, 28 m drum
D1 Dimension
(Example)
D1x dimension
Description
Formula
Example
Symbol
>68.1 mm
(2.68 in)
68.1mm (2.68in)
D1a
D1 dimension when the displacer
is in L1 = 0
= 2 x ( |p (0)|+ d/2 + s)
65.6mm (2.58in)
D1b
D1 dimension when the displacer
is in L1 length
= 2 x (|p (L1)|+ d/2 + s)
51.2mm (2.02in)
D1c
D1 dimension when the displacer
is in L2 length
= 2 x ( |p (L2)|+ s)
N/A
D1d
D1 dimension when the radial
direction offset is considered. This
calculation is used only with the
47 m (156.67 ft) wire drum (N in
Feature 70)
= 2 x (d/2 + r + s)
p (Lx) (mm) (in)
L�, L� (mm) (in)
a
de
c
b
-1.4 -1.3 -1.2 -1.1 -1.0 -0.9 -0.8 -0.7 -0.6 -0.5 -0.4 -0.3 -0.2 -0.1 0.0 0.1 0.2 0.3
-36
-32
-28
-24
-20
-16
-12
-8
-4
0
4
8
0
100
200
300
400
500
600
700
800
900
1000
1100
1200
1300
1400
1500
1600
1700
1800
0
2000
4000
6000
8000
10000
12000
14000
16000
18000
20000
22000
24000
26000
28000
30000
32000
34000
36000
38000
40000
42000
44000
46000
48000
f
5 Installation
Lower Diameter of stilling well
The dimension of D2 has to be the larger value of the dimensions D1 and D2b. See the graph above.
Concentric pipe
Example: L2 = 20 000 mm, d = 50 mm, s = 5.0, 28 m drum
Asymmetric pipe
Example: L2 = 20 000 mm, d = 50 mm, s = 5.0, 28 m drum
Recommendations for mounting stilling well
Follow the recommendations for mounting NMS5 with stilling well:
• Keep the pipe connection welds smooth.
• When drilling holes into the pipe, keep the interior surface of the holes clear of metal chips and
burrs.
• Coat or paint the interior surface of the pipe to prevent corrosion.
• Keep the pipe as vertical as possible. Check using a plumb bob.
• Install the asymmetric pipe under the valve and fit the centers of the NMS5 and the valve.
• Set the center of the lower part of the asymmetric pipe in the direction of the lateral motion.
• Observe the recommendations as per API MPMS chapter 3.1B.
• Confirm grounding between NMS5 and the tank nozzle.
D1 Dimension
(Example)
D1x dimension
Description
Formula
Example
Symbol
>101.2 mm
(3.98 in)
68.1mm (2.68in)
D1
Calculated D1 Value
N/A
101.2mm(3.98in)
D2b
D2 dimension when the displacer
is in L2 length
= 2 x (|p (L2)| + d/2 + s)
D1 Dimension
(Example)
D1x dimension
Description
Formula
Example
Symbol
>84.7 mm
(3.33 in)
68.1mm (2.68in)
D1
Calculated D1 Value
N/A
84.7mm(3.33in)
D2b
D2 dimension that the displacer
can pass through (Nth groove)
= |p (L2)| + d/2 + s + D1/2
5 Installation
Mounting NMS5 with guide wire
It is also possible to guide the displacer by a guide wire to prevent swinging.
Figure 21:
Mounting with guide wire, unit of measurement: mm (in)
No.
Description
A
Calibration chamber
B
Spring and sleeve
C
Guide wire sleeve
D
Crimp tool
1
NMS5
2
Reducer plate (for low pressure: 6mm (0.236 in))
Reduce flange (material is selectable from SS400 an SUS304.)
3
Spring, SUS304
4
Sleeve, SUS316
5
Calibration chamber for maintenance
NHC4HP for high pressure, SCS13 equivalent to SUS304
NHC4LP for low pressure, SCS13 equivalent to SUS304
6
Tank
7
Measuring wire
8
Guide wire, SUS316
9
Displacer
10
Anchor hook plate, SUS304
A
B
C
D
100
1
2
3
4
5
6
7
8
9
10
11
12
13
5 Installation
Guide wire installation procedure
1.
Install NMS5 [1] on the reducer plate.
2.
Perform calibration steps before the displacer [3] is attached to the guide wires.
• Make sure that the displacer does not touch the guide wires during calibration. This could be
done by mounting the NMS5 to the reducer plate [2] prior to fitting the guide wires [4].
Perform calibration steps so that displacer does not touch the guide wires if the guide wires are
already installed to the reducer plate.
3.
Secure the guide wires to the hooks of the springs [5].
4.
Secure the springs to the reducer plate.
5.
Put the guide wires through the displacer guide ring [6] and set the displacer.
This completes the guide wire installation procedure.
Figure 22:
Guide wire installation
1
NMS5
2
Reducer plate
3
Displacer
4
Guide wires
5
Springs
6
Displacer guide ring
11
Welding point
12
Ring, SUS316
13
Flange
No.
Description
2
3
1
5
6
4
5 Installation
Alignment of NMS5
5.6.1
Flange
Confirm that the size of the nozzle and the flange is matched prior to mounting NMS5 on the tank. The
flange size and the rating of NMS5 vary depending on the customer’s specifications.
• Check the flange size of NMS5.
• Mount the flange on the top of the tank. The deviation of the flange from the horizontal plane
should not exceed +/- 1 degree.
• When mounting NMS5 on a long nozzle, make sure that the displacer does not touch the inner wall
of the nozzle.
Figure 23:
Allowable inclination of mounting flange
1
Nozzle
When NMS5 is installed without a guide system, follow the recommendations below:
• Confirm the mounting nozzle is in the sector between 45 and 90 degrees (or -45 and -90 degrees)
away from the inlet pipe of the tank. This prevents heavy swinging of the displacer caused by waves
or turbulence from the inlet liquid.
• Confirm the mounting nozzle is 500 mm (19.69 in) or more away from the tank wall.
• Confirm the minimum measuring level is at 500 mm (19.69 in) or more above the top of the inlet
pipe by setting the low stop. This protects the displacer from direct flow of the inlet liquid.
• If a stilling well cannot be mounted in the tank due to the shape or condition of the tank, attaching
a guide system is recommended. Consult E+H services for further information.
+1°
-1°
1
5 Installation
Recommended position for mounting NMS5 and minimum measuring level
1
Inlet pipe
2
Tank nozzle
• Before pouring liquid into the tank, confirm that liquid flowing through the inlet of the pipe will not
contact the displacer directly.
• When discharging liquid out of the tank, ensure that the displacer will not get caught in the liquid
current and sucked into the outlet pipe.
5.7
Electrostatic charge
When liquid measured by NMS5 has a conductivity of 1 uS/m or less, it is quasinonconductive. In this
case, using a stilling well or guide wire is recommended. This releases the electrostatic charge on the
liquid surface.
�500
90°
-90°
0°
45°
-45°
1
1
�500
2
2
5 Installation
Mounting of the device
The NMS5 is delivered in two different packing styles depending on the mounting method of the dis-
placer.
• For the all-in-one method, the displacer is mounted on the measuring wire of NMS5.
• For the displacer shipped separately method, it is necessary to install the displacer on the measuring
wire inside NMS5.
5.8.1
Available installations
The following installation procedures are available for NMS5.
• Mounting without guide system
• Mounting with stilling well
• Mounting with guide wire
NMS5 is shipped as an all-in-one package when selected order codes meet all the following conditions:
• Feature 070: C or L
• Feature 090: A, C, E, G, J, L, N, Q or S
• Feature 110: D
• Feature 120: 0, 1, 2, 3, 6 or 8
• Feature 130: A, C, D, G, H, J, L, M, T or U
Mounting
option
Without guide system
(Free-space mounting)
With stilling well
With guide wire
Type of tanks
Type of
installations
• All-in one
• Displacer shipped sepa-
rately
• Displacer installation
through calibration win-
dow
• All-in one
• Displacer shipped sepa-
rately
• Displacer installation
through calibration win-
dow
Displacer shipped separately
5 Installation
Installation for all-in-one method
As NMS5 is protected by some packaging materials, remove them as follows prior to mounting NMS5.
Figure 25:
All-in-one method
1
Fixing band
2
Displacer holder
3
Tape
4
Wire drum stopper
5
Drum housing cover
Step
Procedure
Note
1
1.
Hold the gauge so that it stays horizontal against
the flange.
2.
Cut the fixing bands [1].
3.
Remove the displacer holder [2].
• Perform these steps before mounting NMS5
on the nozzle.
• Do not tilt NMS5 after removing the displacer
holder.
2
4.
Mount NMS5 on the nozzle.
• Make sure that the measuring wire hangs
vertically.
• Confirm that there are no kinks or other
defects in the measuring wire.
3
5.
Remove screws and M6 bolts (M10 bolts for
stainless steel housing) to remove the drum
housing cover [5].
6.
Loosen two screws and remove the wire drum
stopper [4].
• Be sure not to lose O-ring and fixed bolts for
the cover for the drum housing.
4
7.
Remove the tape [3] from the wire drum care-
fully.
• Remove the tape by hand to avoid damaging
the wire drum.
• Make sure that the measuring wire is wound
so that it fits correctly in the grooves.
5
8.
Mount the drum housing cover [5].
• Confirm that O-ring is in groove.
6
9.
Turn on the main power and confirm that NMS5
shows "STOP" and that level shows "16050
~16060mm".
10. Set "LEVEL" command, then set "STOP" where the
displacer stops 16000mm or less near the 15950
mm level.
11. Set "UP" command and the displacer will automat-
ically stop at 16000mm.
12. Set "STOP" command.
Sensor, reference, and drum calibration
steps are not required because they are all
performed prior to delivery.
1
2
3
4
5
5 Installation
Displacer shipped separately
It is necessary to install the displacer on the measuring wire inside NMS5.
Figure
Procedure
Figure 26:
Displacer installation 1
1.
Put NMS5 on the blocks or a pedestal.
2.
Confirm that there is enough space under NMS5.
Be careful not to drop NMS5.
Figure 27:
Displacer installation 2
3.
Remove screws and M6 bolts [5] (M10 bolts for stainless
steel housing).
4.
Remove the wire drum cover [3] and the bracket [2].
5.
Remove the wire drum [1] from the drum housing.
6.
Remove the tape [4] on the wire drum.
7.
Unwind the measuring wire approximately 250 mm
(9.84 in) so that the wire ring is positioned under the
flange.
8.
Mount the wire drum on NMS5.
9.
Mount the bracket.
• Handle the measuring wire with care. It may kink.
• Be sure that the wire is wound correctly in the grooves.
Figure 28:
Displacer installation 3
10. Hook the displacer [3] on the ring [2].
• Be sure that the wire is wound correctly in the grooves.
• If not, remove the displacer and the wire drum, and repeat
step 7.
Figure 29:
Displacer installation 4
11. Turn on the power of NMS5.
12. Perform sensor calibration
13. Secure the displacer [2] to the measuring wire [1] using
the securing wire [4].
14. Install the ground wire [3] of the displacer (for details,
refer to "5.2.7 Displacer ground wire installation".
15. Perform reference calibration.
16. Turn off the power.
17. Mount the wire drum cover [5].
For calibration, refer to "12 Adjustment".
200
130
���
200
130
1
2
3
4
5
1
2
3
1
2
4
5
3
5 Installation
Displacer installation 5
18. Mount NMS5 on the tank nozzle [1].
19. Confirm that the displacer does not touch the inner wall
of the nozzle.
20. Turn on the power.
21. Perform drum calibration.
For calibration, refer to "12 Adjustment".
Figure
Procedure
1
5 Installation
Installation through the calibration window
In the case of a 50 mm (1.97 in) diameter displacer, the displacer can be installed through
the calibration window.
It is only possible to install the following displacers through the calibration window: 50 mm SUS,
50 mm alloy C, 50 mm PTFE, Except 0.15mm, SUS measuring wire
Figure
Procedure
Figure 31:
Displacer installation 1
1.
Remove the calibration window cover [1].
Figure 32:
Displacer installation 2
2.
Remove M6 bolts [5].
3.
Remove the cover [4] and the bracket [3].
4.
Remove the wire drum [1] from the drum housing.
5.
Remove the tape [2] that is securing the wire.
Handling the measuring wire with care. It may kink.
Figure 33:
Displacer installation 3
6.
Holding the wire drum [1] with one hand, unwind the
measuring wire [3] approximately 500 mm (19.69 in).
7.
Secure the wire [3] temporarily with the tape [2].
8.
Insert the wire ring [4] into the drum housing.
9.
Pull the wire ring out through the calibration window.
Handle the measuring wire with care.
Figure 34:
Displacer installation 4
10. Insert the wire drum [4] temporarily into the drum
housing.
11. Hook the displacer [3] on the wire ring.
12. Secure the displacer to the measuring wire using the
securing wire [2].
13. Install the ground wire [1] for the displacer (for details,
refer to "5.2.7 Displacer ground wire installation".
Handle the measuring wire with care. It may kink.
1
2
1
2
3
4
5
1
2
3
4
1
2
3
4
5 Installation
Displacer installation 5
14. Hold the wire drum [1] up and place the displacer [2]
into the calibration window.
15. Remove the wire drum from the drum housing and
unwind the measuring wire approximately 500 mm
(19.69 in).
16. Hold the wire drum up and place the displacer into the
calibration window.
17. Hold the displacer at the center of the calibration win-
dow.
18. Hold the other hand (wire drum) up to add tension to
the measuring wire in order not to drop the displacer
rapidly.
Figure 36:
Displacer installation 6
19. Let go of the displacer [2].
20. Remove the tape from the wire drum [5].
21. Insert the wire drum into the drum housing.
22. Mount the bracket [4].
Be sure that the wire is wound correctly in the
grooves.
23. Turn on the power of NMS5 and move the displacer up
until the wire ring can be seen in the calibration win-
dow.
• Confirm that there are no kinks or other defects in the
measuring wire.
• Confirm that the displacer does not touch the inner wall
of the nozzle.
24. Perform sensor calibration.
25. Perform reference calibration.
26. Mount the drum housing cover [3] and the calibration
window cover [1].
27. Perform drum calibration.
For calibration, refer to "12 Adjustment".
Figure
Procedure
2
1
2
1
3
4
5
5 Installation
Displacer ground wire installation
Depending on the application and Ex requirements, electrical grounding of the displacer is required.
There are different procedures depending on the displacer type, which are described below.
Standard displacer installation
1.
Mount the displacer [3] on the wire ring [1].
2.
Wind the securing wire [4] on the wire hook.
3.
Wind the ground wire [2] between the washers [5] twice.
• If grounding is not required for non-explosion-proof applications, skip this step.
4.
Secure the nut [6] with a wrench [7].
This completes the displacer installation procedure.
Figure 37:
Displacer installation
1
Wire ring
2
Ground wire
3
Displacer
4
Securing wire
5
Washer
6
Nut
7
Wrench
PTFE displacer installation
1.
Remove the screw [1] using a flathead screwdriver.
2.
Mount the displacer [4] on the PFA covered ring [2].
3.
Remove the PFA cover approximately 10 mm (0.39 in) for conductivity.
4.
PTFE Wire: Install the ground wire [6] onto the displacer from the wire insertion slot [3] until the
ground wire touches to the wall of the screw hole [5].
5.
SUS Wire: Install the ground wire [6] onto the displacer from the wire insertion slot [3] until the
ground wire touches to the wall of the screw hole [5]. Then install the ground wire 10mm farther.
6.
Tighten the screw [1].
• Hold the ground wire with finger tips so that the wire does not come out from the slot.
7.
Lift the displacer using a screwdriver and confirm that the ground wire does not come out from
the slot.
This completes the PTFE displacer installation.
1
2
3
4
2
5
6
7
1.
2.
3.
4.
5 Installation
PTFE displacer installation; dimensions mm (in)
1
PFA covered ring
2
Wire insertion slot
3
Displacer
4
Screw hole
5
Ground wire
1.
2.
3.
4.
5.
7.
1
2
3
4
5
10 (0.39)
6.
5 Installation
The electrical connections of NMS5 are shown in "6.2 Terminal Assignment".
The power supply cable should have the following specifications:
• PVC, PE, or equivalently isolated
• 600 V insulation voltage or equivalent.
• Temperature rating 80 or high
The size of the core is defined by the core resistance, voltage drop, and required consumption. The
maximum power consumption of NMS5 is 50 VA/50W.
• Connect the ground terminal to the ground line inside or outside the terminal box.
• Use a wire 4mm2 or more for ground.
• Use cables and wires of sufficient and appropriate size and length to make a solid connection at each
terminal required.
• Do not stretch cables. This may lead to failure, loss of function, and/or damage to the device and
facility.
• Cut the trim cables for appropriate length. Do not leave the extra cables and wires in the electrical
compartment. This may lead to failure, loss of function, and /or damage to the device and facility.
CAUTION
WARNING
DANGER
6 Wiring
V1 Serial Signal, Modbus RS485, HART, Enraf BPM
Figure 39: Wiring sample 1
A
B
C
D
L
N
G
1
ARS
2
ARS
ARS
3
7
8
9
+
-
4
5
6
L
G
N
+
-
10
11
12
13
14
15
16
17
18
20
21
COM
19
+
-
+
-
+
-
22
23
24
25
26
A
B
b
A
B
b
Power supply
AC 85 to 264V 50/60Hz
or
DC 20 to 62V
AC 20 to 55V
Port_B +
Non IS HART to NRF
or others port_B -
Digital output
RS485,V1 serial pulse
or remote HART
Alarm Contact
Alarm contact
Alarm contact
Alarm contact
Operation
contact
input
4 to 20mA
Channel 1
4 to 20mA
Channel 2
Port_A +
local HART
port_A -
(see NOTICE.)
�����������������
Alarm contact
HOIST (CTR1)
HOIST (CTR2)
NOTICE
Ex ia local (slave) HART, or
Pt100 3 wire spot RTD (see NOTICE.)
terminals: 24 & 25
4 to 20mA output:
Terminals 20 & 21, 22 & 23
Terminals 22 & 23 will be used as “Status 1 Input”
when signal input from field unit
(Order code position 60) is: Order information: 060
4: HART and Status 1 input
5: HART, Pt100 Spot and Status 1 input
6: HART, Pt100 Spot temp.,
Operation contact, and Status 1 input
Ex d local (slave) HART
Terminals: 4 &5
Digital output: Terminals 6 & 7
V1 Serial Pulse, Modbus (RS485)
HART, Enraf BPM
Power supply
CAUTION
A
B
C
D
Cable entry descriptions
・ Terminal connection for Whessoe Matic 550 (WM550) and Mark Space, refer to the next few pages.
・ Terminals 4 & 5 and 24 & 25 for HART devices are inter - connected on Explosion proof (Ex d) certified version.
・ Terminals 24 & 25 (and 24, 25 & 26 for spot temp.) will be intrinsically safe (i.s.) device connection
only when intrinsically safe certified version is selected.
Ex d local (slave) HART
Terminal No.: 4 and 5
NRF and other HART communication devices
NOTICE
6 Wiring
Whessoe Matic 550
Figure 40: Wiring sample 2
A
B
C
D
L
N
G
1
ARS
2
ARS
ARS
3
7
8
9
+
-
4
5
6
L
G
N
10
11
12
13
14
15
16
17
18
20
21
COM
19
+
-
+
-
+
-
22
23
24
25
26
A
B
b
A
B
b
Power supply
AC 85 to 264V 50/60Hz
or
DC 20 to 62V
AC 20 to 55V
Local HART to NRF
Alarm Contact
Alarm contact
Alarm contact
Alarm contact
Operation
contact
input
WM550
Channel 1
Ex d Local HART
(See NOTICE.)
����������������������������
Alarm contact
HOIST (CTR1)
HOIST (CTR2)
NOTICE
Ex d local (slave) HART, or
Pt100 3 wire spot RTD (see NOTICE.)
terminals: 24 & 25
Ex d local (slave) HART
terminals: 4 &5
Power supply
A
B
C
D
Cable entry descriptions
NOTICE
WM550
Channel 2
Whessoe Matic (WM)output:
terminals 20 & 21, 22 & 23
WM550 is the current loop redundant data
transmission protocol.
Since these 4 terminals are occupied
by WM550 terminal connection,
4 to 20mA output and status 1 input function are
no longer available.
・ Terminals 4 & 5 and 24 & 25 for HART devices are inter - connected on Explosion proof (Ex d) certified version.
・ Terminals 24 & 25 (and 24, 25 & 26 for spot temp.) will be intrinsically safe (i.s.) device connection
only when intrinsically safe certified version is selected.
Normally the combination of WM550 and analog 4 to 20mA is prohibited.
Contact Endress+Hauser representatives if needed.
6 Wiring
Figure 41: Wiring sample 3
A
B
C
D
L
N
G
1
ARS
2
ARS
ARS
3
7
8
9
+
-
4
5
6
L
G
N
10
11
12
13
14
15
16
17
18
20
21
COM
19
+
-
+
-
+
-
22
23
24
25
26
A
B
b
A
B
b
Power supply
AC 85 to 264V 50/60Hz
or
DC 20 to 62V
AC 20 to 55V
Port_B+
Non IS HART to NMT
or other Port_B-
Alarm Contact
Alarm contact
Alarm contact
Alarm contact
Operation
contact
input
Mark/Space
�����������������
Alarm contact
HOIST (CTR1)
HOIST (CTR2)
NOTICE
Ex d local (slave) HART, or
�����������������������������������
terminals: 24 & 25
Ex d local (slave) HART
terminals: 4 &5
Power supply
A
B
C
D
Cable entry descriptions
NOTICE
Mark/Space
Port_A +
local HART
port_A -
�������������
M/S output:
terminals 20 &21, 22 & 23
M/S is the serial pulse digital data transmission
������������������������������������������
Since these 4 terminals are occupied by M/S
terminal connection, 4 to 20mA output and status 1
���������������������������������������
・ ���������������������������������������������������������������������������������������������������������������
・ ������������������������������������������������������������������������������������������������������
��������������������������������������������������������������
�������������������������������������������������������������������
�������������������������������������������������
6 Wiring
Using the external operation switch, ensure that the settings of the system are the same as shown in
the following logic setting table. This will allow user to input operation signals.
(Hoist-CTR1)(Stop-CTR2)
6.2.4
Input and output
Input signal
• Contact Switch
• HART
• Pt 100
Output signal
• V1
• WM550
• M/S
• ENRAF BPM
• MODBUS
• HART
• ANALOG 4-20mA
• Overspill Prevention (OSP)
• The cable used for input and/or output must be 24 AWG or more and must be screened or steel
armored. A twisted pair is required for HART and/or RS 485 signal.
• Two or three cores for mains, two cores for digital output and two cores for HART input are normally
used for the cabling of NMS5. The instrument has max. four cable entries.
• Check the cable size and the number of cables prior to ordering NMS5.
6.2.5
Cable gland
When there are extra cable entries not be used, mount threaded plugs for waterproof.
Refer to "Safety Instruction XA00578G-A".
When ordering TIIS Ex d specification, cable glands are attached with NMS5. Ensure to use the cable
glands.
CTR 1
CTR 2
OPERATION
OFF
OFF
LEVEL
ON
OFF
HOIST
OFF
ON
STOP
ON
ON
INTERFACE
DANGER
WARNING
6 Wiring
Temperature input system
There are two types of temperature input method and two types of Ex protection system as Ex d or Ex
[ia] in NMS5.
6.3.1
Ex d NMT input + HART input
Ex d HART sensor and NMT53x Ex d are connected in this system.
Figure 42:
Ex d NMT input and HART input
6.3.2
Ex d Pt100 Spot Temperature Input +HART Input
Ex d HART sensor and Ex d Pt100 sensor are connected in this system.
Figure 43:
Ex d Pt100 spot temperature input and HART input
26
4
24
25
J3
1A
1
3
5
J1
1B
Power
module
POW
Ex d
Ex d
HART
TCB CPU module
Terminal module
HART
sensor
Ex d
5
NRF
560
NMT
53x
Ex d
HART
sensor
Ex d
26
4
5
24
25
J3
1A
1
3
5
J1
1B
A
B
b
HART+
HART-
TCB CPU module
HART
sensor
Ex d
NRF
560
Ex d
Pt 100
Ex d
HART
HART
sensor
Ex d
Power
module
POW
Ex d
Spot
Temp.
module
6 Wiring
Ex ia NMT input + HART input
Ex d HART sensor and NMT53x Ex ia are connected in this system, excluding TIIS specification.
Figure 44:
Ex ia NMT input and HART input
6.3.4
Ex ia Pt100 Spot Temperature Input + HART Input
Ex d HART sensor and Ex ia Pt100 sensor are connected in this system, excluding TIIS specification.
Figure 45:
Ex ia Pt100 spot temperature input and HART input
26
4
5
24
25
J3
1A
1
3
5
J1
1B
Power
module
POW
Ex ia
TCB CPU module
Terminal module
Separation wall
Ex ia
HART
COM-4 module
Ex ia
Ex ia power feed
Ex d
power feed
Ex d
HART
sensor
Ex d
NRF
560
NMT
53x
Ex ia
Ex d
HART
26
4
5
24
25
J3
1A
1
3
5
J1
1B
Spot
Temp.
module
A
B
b
HART+
HART-
TCB -4 CPU module
Power
module
POW
Ex ia
Separation wall
Ex ia
Ex ia
Ex ia Power feed
Ex d power feed
Ex d
Plastic Case
Ex ia
HART
HART
sensor
Ex d
NRF
560
Ex ia
Pt 100
Ex d
HART
HART
sensor
Ex d
6 Wiring
Touch control and programming matrix
7.1.1
Display and operating elements
Display
During normal operation, NMS5 has an illuminated LCD that shows the level, the temperature, and the
status of the device at "HOME" position.
For the display of the other data and the programming of the parameters for operation, NMS5 uses a
convenient programming matrix.
Operating elements
NMS5 is operated by three visual operating elements, namely the keys "E", "+", and "-" . They are actuated
when the appropriate field on the protective glass of the front is touched with the finger ("touch con-
trol"). The corresponding transmitting and receiving diodes are not affected by external influences, e.g.
direct sunlight. The software and hardware installed in NMS5 rule out any malfunction that may be
caused in this way. Even in explosive hazardous areas, the explosion-proof housing of the touch control
ensures a safe access to the data.
Figure 46:
Display
7.1.2
Functions of operating elements
The programming matrix consists of matrix groups, namely one "static" matrix and additional "dynamic"
matrices. They are described in detail in Section "14 Matrix". The individual matrix groups, function
groups, and functions within the programming matrix can be selected by alternately touching the oper-
ating elements.
Figure 47:
Displays
Illuminated LCD
3 optical operating elements "Touch control"
Infrared receiver
Infrared
transmitter
LEVEL
U-D
0.0°C
LEVEL
U-D
0.0°C
LEVEL data
Temp. data
Displacer status symbol
Gauge status / Error
MORE FUNCTION
GVH: Position
Group message
Key guide
G:0
VH:3*
> GROUP SELECT < E
Enter matrix
Go
Back
HOME display
Function group display
Input number
Key guide
G:0
VH:39
ACCESS CODE
3
E
-
+
Measurement
data
G:0
VH:20
OPERATION
15955
LEVEL
Matrix display
Matrix display
14964.3mm
7 Operation
Figure 48: Matrix construction
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
Measured Value 1
0
0
Measured Value 2
1
1
Operation
2
Operation
2
More Function
3 Calibration
More Function
3 Device Data
Level Data
4
Contact Output 4
Calibration
5
Analog Out
5
Adjustment
6
Parts Data
6
Auto Wire Calib.
7
Input Signal
7
Auto Calib. Displ.
8
Communication
8
Display
9
Status
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
0
1
1
Operation
2
Operation
2
More Function
3 Service
More Function
3 Temperature
4
Temperature
Data
4
Gauge data
5
Element Temp. 5
System Data
6
Element Position
6
Service
7
NMT Adjustment 7
Sensor Value
8
Set Data NMT
8
Sensor Data
9
Device Data
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
0
1
1
Operation
2
Operation
2
More Function
3 HART Dev (1)
More Function
3 HART Dev (2)
Measured Value 4
Measured Value 4
P.V. Setting
5
P.V. Setting
5
Sensor Specific
6
Sensor Specific
6
Alarm
7
Alarm
7
Self Diagnostic
8
Self Diagnostic
8
Device Data
9
Device Data
9
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
0
0
1
1
Operation
2
Operation
2
More Function
3 Adjust Sensor
More Function
3 Tank Profile
Adjust Sensor
4
Profile Operation
4
HART Error Rate
5
Status/Data
5
Unit
6
Density 1-10
6
HART Line
7
Density 11-16
7
Interface Adjust 8
Position 1-10
8
9
Position 11-16
9
0
1
2
3
4
5
6
7
8
9
0
Static Matrix
Dynamic Matrix
1
Operation
2
More Function
3 Interface Profile
4
Status/Data
5
Density 1-10
6
Density 11-16
7
Position 1-10
8
Position 11-16
9
Meas. Wire &
Drum
Measured Value 1
Measured Value 2
Measured Value 1
Measured Value 2
Measured Value 1
Measured Value 2
Measured Value 1
Measured Value 2
Measured Value 1
Measured Value 2
Measured Value 1
Measured Value 2
Measured Value 1
Measured Value 2
Measured Value 1
Measured Value 2
7 Operation
LCD returns to HOME position when no key is touched for 10 minutes or more. Digits are incremented
or decremented using by + or - key. When touching + or - key continuously, then the minimum digit
changes first. After one cycle of the minimum, the second minimum changes. After one cycle of the
second follows the third minimum, and so on. When releasing a finger from the touch control, then
the procedure starts again from the minimum digit (Analogy of mechanical counter).
Figure 49:
Selection matrix groups, function groups, and functions with programming matrix
Key
Functions
• Access to the programming matrix (touch the key for 3 seconds or more).
• Return to HOME position (touch the key for 3 seconds or more).
• Move the status horizontally in the function group to select functions.
• Save parameters or access codes.
• Move the status vertically to select function groups.
• Selec or set parameters.
• Set access codes.
+ -
4
5
6
7
8
9
4
5
6
7
8
9
H
V
LCD ( HOME position)
When touching on the matrix for 3 seconds or longer,
the screen returns to HOME position.
1 CALIBRATION
3 SERVICE
4 TEMPERATURE
5 HART DEVICE (1)
6 HART DEVICE (2)
7 ADJ. SENSOR
8 TANK PROFILE
9 INTERFACE PROFILE
0
1
2
3
4
5
6
7
8
9
0
1
2
3
4
5
6
7
8
9
4
4
4
4
7 ADJ. SENSOR
3 SERVICE
4 TEMPERATURE
5 HART DEVICE(1)
6 HART DEVICE(2)
> 3 s
2 DEVICE DATA
MATRIX OF GVH030
4
2 DEVICE DATA
4
1 CALIBRATION
5
6
7
8
9
5
5
5
5
5
6
6
6
6
6
7
7
7
7
7
8
8
8
8
8
9
9
9
9
9
When touching
"E" on the matrix
for 3 seconds or
longer, the screen
moves to V0
position.
8 TANK PROFILE
9 INTERFACE PROFILE
7 Operation
After turning on the power, LCD shows the current data on HOME position.
Figure 50:
HOME position
The letters A, B, C and D stand for the areas where information on measured values and status of the
device are displayed:
The meanings of message appearing on LCD (display) is explained in the following table.
Area
Information
A
Current Level
B
Current Temperature
C
Displacer Status
D
Gauge Status
Gauge Status
Description
G - RE
Reference position for measuring
UP
The measuring wire is hoisted.
STOP
The measuring wire stops.
LIQU
The liquid is being measured.
U - IF
The upper interface level is being measured.
LIF
The lower interface level is being measured.
BOTM
The tank bottom level is being measured.
U - DE
The upper liquid density is being measured.
M - DE
The middle liquid density is being measured.
B - DE
The bottom liquid density is being measured.
CAN
Resetting RELE.OVER TENS (over tension error).
TEAC
Calibration is being measured.
blank
Measuring is not possible.
14964.3mm
0.0ºC
U-D
LEVEL
A
B
C
D
7 Operation
If no LCD operation, NMS5 will turn off the backlight of LCD 12 hour later. Touching LCD again after
this time will turn on the backlight.
Displacer
Status
Symbol
Meaning
BAL
Balance
The displacer is resting on the liquid surface or interface and in balanced
status.
T - B
Temporary Balance
Automatic weight calibration is being carried out.
U - U
Unbalance Up
The displacer is being hoisted and in unbalanced status.
U - D
Unbalance Down
The displacer is being lowered and in unbalanced status.
R - U
Balance Up
The displacer is being hoisted and in correction of balance.
R - D
Balance down
The displacer is being lowered and in correction of balance.
LOW
The displacer is resting at the lower stop.
7 Operation
The access code is to ensure the confidentiality of the setup data. Three security levels are available
along with access codes.
The higher levels include the lower ones. e.g. If access code 50 is specified for a function, then code 51
also enables editing. A function that requires access code 51, on the contrary, cannot be edited by code
50. However, 777 is only used to change I.S. terminal configuration.
Setting Access Code
7.4
Operation command and new operation status
7.4.1
Operation commands
Operation Commands can be sent the NMS5 from a host system. The following table explain the com-
mand codes.
Security Level
Access Code
0
None
1
For Operator
50
2
For Engineer
51/530/777
Item
Procedure
Remarks
Static Matrix
Figure 51:
Access Code
1.
At the static matrix "MORE FUNCTION",
select GVH039 "ACCESS CODE"
2.
The default value is "0". Touch the "+" key.
3.
The first digit increases to 9, then the sec-
ond digit increases. Stop touching "+" once
you reach "50".
4.
"50" is blinking. Gently touch "+" key again to
change the first digit from 0 to 1. Now you
have "51".
5.
Here touch "E"; "EDITING ENABLE" will be
displayed.
• When touching "E" while displaying an access
code except 0, 50, or 51 "EDITING LOCKED"
will appear.
• If an access code has not been selected before
performing any settings, the screen will
automatically change to show "ACCESS CODE"
• Operation Commands can be sent, and
displayed data read, by remote systems,
depending on your
NMS5 specification.
039
MORE
FUNCTION
ACCESS CODE
Code
Command
Remarks
0
LEVEL
1
UP
2
STOP
After weight calibration, STOP is set as a default operation command.
3
BOTTOM LEVEL
4
UPPER INTERF. LEVEL
5
MIDD.INTERF.LEVEL
6
UPPER DENSITY
7
MIDDLE DENSITY
8
DENSITY BOTTOM
9
REPEATABILITY
10
WATER DIP
7 Operation
New operation status
The following table shows the new operation status, which is available when "NEW NMS STATUS",
matrix position GVH272, is selected to "ENABLED".
Code
Meaning
NMS Display
0
No definition
-
1
Displacer at reference position
REFERENCE
2
Displacer hoisting up
UP
3
Displacer going down
DOWN
4
Displacer stop
STOP
5
Level measurement, balanced
LEVEL
6
Upper I/F level, balanced
UPPER INTERF. LEV.
7
Middle I/F level, balanced
MIDD. INTERF. LEV.
8
Bottom meas. Balanced
BOTTOM LEVEL
9
Upper density finished
UPPER DENSITY
10
Middle density finished
MIDDLE DENSITY
11
Bottom density finished
DENSITY BOTTOM
12
Release over tension
RELE. OVER TENS.
13
Calibration activated
CAL. ACTIVE
14
Seeking level
LEVEL SEEKING
15
Following level
LEVEL FOLLOWING
16
Seeking upper density
UPP.DEN.SEEKING
17
Seeking middle density
MID.DEN.SEEKING
18
Seeking bottom density
BOT. DEN. SEEKING
19
Seeking upper I/F level
UPP. INT. SEEKING
20
Following upper I/F level
UPP. INT. FOLLOWING
21
Seeking middle I/F level
MID.INT.SEEKING
22
Following middle I/F level
MID.INT.FOLLOWING
23
Seeking bottom level
BOTTOM SEEKING
24
Not initialized
NO INITIALIZE
25
Stopped at upper pos.
UPPER STOP
26
Stopped at lower pos.
LOWER STOP
27
Repeatability testing
REPEATABILITY
28
Seeking water level
WATER SEEKING
29
Water level, balanced
WATER LEVEL
30
Following water level
WATER FOLLOWING
31
Over-/under tension, Z-phase, ADC error
EMERGENCY ERROR
32
GVH157 SERVICE MODE = ON
MAINTENACE
7 Operation
Operation of displacer
The operation of the displacer for level, bottom level, interface level, and density measurement is pos-
sible by touch control.
Item
Procedure
Remarks
Figure 52:
Static matrix
Figure 53:
Touch control
1.
Select function groupGVH020 OPERA-
TION
2.
Select item OPERATION. The LCD shows
the
command given to NMS5and the dis-
placer position.
• Set access code to 50.
• If editing has previously been enabled by a
valid access code, then the request for the
code will not appear.
Figure 54:
Operation of displacer
3.
The following commands are available at
this position:
• LEVEL
• UP
• STOP
• BOTTOM LEVEL
• UPPER INTERF. LEV*
• MIDD.INTERF.LEV*
• UPPER DENSITY*
• MIDDLE DENSITY*
• DENSITY BOTTOM*
• WATER DIP*
• REPEATABILITY TEST
• Interface and density measurements are
not available unless
specifically requested.
• Density profile
measurement is explained in section "8.6
Density and Density Profile Measure-
ments".
• The optional operation commands are
available when such options are set.
OPERATION
OPERATION
Level
Bottom Level
Upper Interface
Level
Middle Interface
Level
Density Bottom
Water Dip
Middle Density
Upper Density
7 Operation
Calculation of level and densities
The section specifies the formula used by NMS5 to calculate levels and densities.
Figure 55:
Calculation of levels and densities
Surface and interface levels
While the measured surface or interface level is constant, the displacer rests at the balancing position.
The tension on the measuring wire is proportional to the displacer weight diminished by the buoyancy
forces in both layers:
A rise or fall of the level will increase or decrease the displacer volume. If this change exceeds the vol-
ume tolerance set at matrix position GVH345 "VOLUME TOLERANCE", then the corresponding change
will actuate the motor of the NMS5 till the balancing condition is fulfilled again.
Tank bottom level
For bottom level measurement, the balancing condition is defined as
T = W - (V + VB) ρb
Level
Formula
Liquid Level
T = W - Vвρu
Upper Surface
T = W - Vвρm - (V - Vв) ρu
Middle Surface
T = W - Vвρb - (V - Vв) ρm
Measuring Wire
Tension T
Gas
Density Negligible
Measured Displacer Weight W
Upper Liquid
����������
Measured Displacer Weight Wu
Middle Liquid
����������
����������������������������
�������������
����������
Measured Displacer Weight Wb
Balance
��������B
Displacer
��������
7 Operation
The upper, middle, and bottom densities are calculated by the following formulas.
• Upper density (Pu) and density profile
• Middle density (Pm)
• Bottom density (Pb)
Draft (distance from liquid surface to the bottom of displacer)
The draft varies depending on the shape of the displacer. For cylindrical shape, the draft is
where the variables and constants have the following meanings.
Figure 56:
Variables and constants for displacer
The surface or interface level should be within the cylindrical part of the displacer and approximately
in the middle of its total height.
ρu =
V
W - Wu
ρm =
V
Wu - Wm
ρu
+
ρb =
V
Wm - Wb
ρm
+
D = (V2 - V1) / A x 10 + h
= (V1 - V2 - V3) / A x 10 + h + h1
V1: Displacer Balance Volume (69ml)
V2: Displacer Lower Hemisphere Volume
V3: Displacer Bottom Stub Volume
A: Cross-section of Displacer
h : Height of Lower Cone
h1: Height of End of Cone
For example: standard displacer Ø50.8 (2) cylindrical shape
V1: Balance Volume (69ml)
V2: Volume of Lower Cone (24.46ml)
V3: Volume of End of Cone (0.12ml)
A: Cross-section of Displacer (20.26cm2)
h1: Displacer Bottom Stub Height (20mm (0.784in))
d
h
V2
D
h1
V3
Liquid Level
or Interface
7 Operation
All of the initial settings are required for NMS5 in most case. However, depending on NMS5 specifica-
tion, some settings may not be required. Set Access code 51 at GVH039 before applying the initial set-
tings.
8.1.1
System calendar/clock (GVH193 to 197)
Calendar/Clock values are set at factory (Japan Standard Time) prior to delivery. Change the data to
reflect local time.
8.1.2
Density values (GVH005 to 007)
Always set GVH005 Upper Density for actual density data, in LPG and any application where the actual
density is 0.7000 g/ml or less. failure to set this data may result in level gauge malfunction.
Density values for 3 liquid phases are set to 1.000 g/ml prior to delivery. Change the data to reflect
actual density values. For tanks with only one liquid phase, set Upper Density. For tanks with 2 or 3
clear phases, set Middle and Bottom densities too.
Minimum difference between phase settings should be at least 0.100 g/ml.
GVH005≤GVH006≤GVH007
Example:
• GVH005 Upper Density: 0.758/ml
• GVH006 Middle Density: 0.880/ml
• GVH007 Density Bottom: 1.000/ml
8.1.3
Tank height (GVH140)
Tank height value is set to default value at factory prior to delivery. Tank height is the reference height,
usually a gauging hatch on the tank that is used during manual level measurements. Change GVH140
to equal the reference height.
GVH141 "Dip Point Offset" will automatically change to reflect the difference in height between the ref-
erence height and the NMS5 reference position.
CAUTION
8 Commissioning
Upper and lower stop (GVH161/162)
Upper and Lower Stop determine the highest and lowest point of displacer movement. These data are
set to 16000mm and 0mm respectively at factory prior to delivery. Change these data to the desired
actual Upper and Lower limit values.
8.1.5
Communications address (GVH285)
Several types of digital output communication protocols are available when ordered from Endress +
Hauser. NMS5 is delivered with communications hardware and/or software installed. Only minimal
matrix parameter setting, Access code 51, is required.
Communications protocol is displayed and selected at GVH286 Protocol. NMS5 has been preset at fac-
tory, it is not necessary to change the setting.
At GVH285 select the desired device address for NMS5. Address range: 0 to 9, 00 to FF, or 1 to 247
for Modbus.
• FF is fixed for MIC protocol. WM550 and M/S address setting is done via dip switches on the com-
munications module inside NMS5.
• For Rackbus, termination resistors should be set on NMS5 at end of loop.
• Enraf BPM address range is 00 to 99. Refer to "8.5 Remote Communications".
Tank height
Dip point offset
(Difference between the
dipping hole height and
the reference line of
the calibration window)
8 Commissioning
Proactive safety function (GVH157/158/159)
Data range of safety level by output protocol
Matrix
Setting
GVH157
Service Mode: default = OFF.
Select OFF if GVH158 Prosafety = ON.
Select ON only when performing maintenance on NMS5.
Selecting ON disables the Proactive Safety function!
Access code 530
GVH158
Prosafety: default = ON.
Select OFF only if the Proactive Safety function will not be used.
Failure to confirm ON disables the Proactive Safety function!
Access code 530
GVH159
Safety Level: default = 65000.0mm (WM550.), or = 99999.0 mm (other protocols)
Possible data values depend on receiver specification (see table below)
Level value transmitted to the receiver if a fault occurs.
Access code 530
Protocol
Data Range
Data Format
Modbus
0.0 to 99999.0mm
Float
V1
0 to 99999.9mm
ASCII / 6 digit
MDP
0 to 99999mm
BCD / 5digit
WM550
0 to 65000mm
16bit
Mark/Space
19.999m/32.699m
20bit BCD / 5 digit
Enraf BPM
0 to 99999.9mm
6 or 7 byte
Rackbus
0 to 99999.9mm
Float
HART
0 to 99999.9mm
Float
WARNING
WARNING
8 Commissioning
Analogue output (GVH250 to 256)
When specified and ordered from Endress+Hauser, NMS5 is equipped with analogue output hardware
installed. Function settings may be changed as follows:
8.1.8
Contact relay alarm output (GVH240 to 247)
When specified and ordered from Endress+Hauser, NMS5 is equipped with contact relay alarm output
hardware installed. Function settings may be changed as follows:
Function
Setting
Assign Output 1
Assign level or temperature to channel 1 output.
Adjust 4mA
Set desired value at which level or temperature outputs 4 mA.
Adjust 20mA
Set desired value at which level or temperature outputs 20 mA
Assign Output 2
Assign level or temperature to channel 2 output.
Adjust 4mA
Set desired value at which level or temperature outputs 4 mA
Adjust 20mA
Set desired value at which level or temperature outputs 20 mA.
Device at Alarm
Select type of output for alarm
Function
Setting
Select Relay
Select relay number from 1, 2, 3 or 4.
Assign Relay
Select output definition from range of choices: None, Level, Liquid
Temperature, Caution, Warning, Emergency Error, Balance Signal.
Relay Function
Select High or Low.
Switching Point
Set value at which relay is activated.
Hysteresis
Set hysteresis value for selected relay.
Relay on Alarm
Select relay of Normal Open or Normal Closed.
When selecting Output2: "4: 2 x relay SPST, TUV with overspill prevention" at order
code 50, relay type is specified as only Normal Closed.
On Delay Time
Set time delay value for alarm output start.
Off Delay Time
Set delay value for alarm output stop.
NOTICE
8 Commissioning
Settings for NMT 53x connections
The following settings are required to display NMT 539 data on NMS5 screens.
By setting the HART retry number, it is possible to change the HART communication error detection
time of connected Prothermo to suit application needs.
When NMS5 cannot read data from Prothermo, it retries. The retry number can be set at the matrix
position GVH 773. It is possible to set the number of retries from 0 to 99 by the access code 530.
• The factory default HART retry number is 50. This value is suitable for a standard situation where
HART recommended cable is used. The detection time for a real error is approx. 17 minutes because
HART retry is executed 50 times to determine a real error.
• As the number decreases by 1, real errors can be detected faster by approximately 20 seconds.
When the HART retry number setting is 0, the detection time of real errors is approx. 40 seconds.
However, a false error may occur depending on the installation site conditions.
• As the number increases, false errors occur less. However, it takes longer to detect a real error. The
detection time for real errors is approx. 34 minutes when the number is set to 99.
Item
Procedure
Remarks
Figure 58:
Matrix group: service
Figure 59:
Static matrix
1.
In Static Matrix "MORE FUNCTION", invoke
GVH030 "MATRIX OF" and select "SERVICE".
2.
Invoke the Dynamic Matrix GVH362
"CONNECTION NMT" screen.
3.
Use the "+" and "-" keys to display "AVERAGE"
and press "E" to set data.
4.
Press "E" to return to
"SYSTEM DATA" and press the "-" key to
return to "MORE FUNCTION".
5.
Invoke Static Matrix "GVH030 MATRIX OF".
NMS5 matrix is divided into matrix groups.
Select "TEMPERATURE" from these groups.
6.
"EDITING ENABLED" is displayed on the
LCD.
7.
The average liquid
temperature is displayed on Dynamic
Matrix screen GVH440.
8.
The temperature of each contact is dis-
played on Dynamic Matrix screens GVH450
to GVH459.
030
362
MORE
FUNCTION
SYSTEM
DATA
MATRIX OF
CONNECTION NMT
030
MORE
FUNCTION
MATRIX OF
8 Commissioning
Settings for connection to NRF560
To connect NRF560, NMS5 requires the following settings.
Turn on the power to NMS5 first.
CAUTION
Item
Procedure
Remarks
Figure 60:
Matrix group: service
1.
In Static Matrix "MORE FUNCTION", invoke
GVH030 "MATRIX OF" and select "SERVICE".
2.
Invoke the Dynamic Matrix GVHH361
"CONNECTION NRF" screen.
3.
Use the "+" and "-" keys to select either "CON-
TACT 1" or "CONTACT 2".
• Set access code 51.
• CONTACT 1...
NRF 560
software version 1.6x and earlier (those NRF
560 that indicate no software version
correspond to connection type 1).
• CONTACT 2...
NRF 560
software version 1.8x and later.
030
361
MORE
FUNCTION
SYSTEM
DATA
MATRIX OF
CONNECTION NRF
8 Commissioning
Liquid level calibration
8.4.1
Opened tank
Preparation
Select LEVEL at GVH020 Operation. The displacer will descend to the liquid surface and balance.
When "BAL" is displayed, the displacer stopped moving.
When measuring the liquid level manually, use an approved method.
Set level (GVH150) for opening tank
Input the value at GVH150 after measuring the dipping level.
Figure 61:
Calibration Level (Manual Dipping Level)
When there is no liquid in the tank;
Figure 62:
Calibration level (empty tank), unit of measurement: mm (in)
When there is no liquid in the tank, level calibration is not 0mm on the measurement principle.
When 0mm level calibration is needed, refer to GVH004(BOTTOM LEVEL) or GVH142(DISPLAC.
DRAFT).
Manual
dipping
level
Draft
Calibration level
B
A
B=45(1.77)
Note: Ø50 (1.97) (Standard displacer)
140ml (Displacer volume)
70ml (Balance volume)
A= Depend on tank design
CAUTION
8 Commissioning
Level calibration procedure for closed tank
Closed tanks (e.g. LPG) cannot be hand-dipped. Follow the procedure shown below.
Figure 63:
Level calibration
1.
Check the NMS parameter
2.
Set the Level gauge at GVH020(BOTTOM)
Figure 64:
Draft level of displacer
3.
Check that the displacer is balance and LCD (display) shows Balance.
Matrix
Item
GVH005
UPPER DENSITY
GVH340
WIRE DRUM CIRC.
GVH342
DISPLACER WEIGHT
GVH343
DISPLACER VOLUME
GVH344
BALANCE VOLUME
CAUTION
0
45 (1.77)
45 (1.77)
BOTTOM plate (datum plate)
BALANCE position for displacer
8 Commissioning
Calculate the displacer balance position.
• In case of Ø50mm standard displacer, balance volume(GVH343) is reference value (a half of
displace volume)
• The balance point is 45mm from the bottom of the tank.
Refer to Appendix "14.3 Displacer".
Figure 65:
Level calibration
5.
Set Level Calibration to 45mm at GVH150 (SET LEVEL) in G1 MATRIX (Calibration). The bottom
is ZERO.
• If the bottom plate is not Zero (ex; X mm), adjust the level value by adding to the value.
LEVEL = X + 45(mm)
6.
Set level gauge at GVH020 (BOTTOM).
This completes the level calibration procedure.
8 Commissioning
The desired loop address for most digital protocols can be set at GVH285 (Address). The allowable
range for setting varies depending on the protocol installed in NMS5. The range has 0-9, 00-FF (FF is
fixed for MIC protocol), or 1-247 for Modbus.
• WM550 and Mark Space protocols addresses must be set by switches on the communications mod-
ule inside NMS5.
• Enraf BPM: Address range is 00-99. A-F is not available.
8.5.2
Whessoe Matic 550 (WM550) communication board setting
Jumper setting
Jumper settings for WM550 communication board
If software reset is required; J6 has to be short.
Polling address setting
Polling addresses are set by mechanically at SW1 on WM550 communication board (not by
accessing NMS programming matrix). Check all polling addresses before setting.
The following table shows about address setting.
For current loop setting, refer a operating manual for Whessoe 1098 or RTU 8130 operating manual.
Jumper
Function
Default Condition
J3 (Mode)
Use EPROM [IC4]->short
Short
J4 (Test)
Software testing
Short
J6 (Reset)
Reset
Open
J7 (Watch dog)
Watch dog setting
Short
Switch position
Value
1
1
2
2
3
4
4
8
5
16
6
COMPATIBILITY
MODE
WARNING
ON
1 2 3
4 5
6
Polling address = 1
ON
Polling address = 5
ON
Polling address = 9
ON
Polling address = 3
ON
Polling address = 7
Setting Sample
1 2 3
4 5
6
1 2 3
4 5
6
1 2 3
4 5
6
1 2 3
4 5
6
8 Commissioning
Mark/Space(M/S) communication board setting
Jumper Setting
Jumper settings for M/S communication board
Polling address setting
Polling addresses are set by mechanically at SW1 (1-8) and SW2(1-2) on Mark Space communication
board (not by accessing NMS programming matrix). Check all polling addresses before setting. The fol-
lowing table shows address setting.
Function setting
Each function is set at SW2-* shown as follows.
Jumper
Function
Default condition
J3 (Mode)
Use EPROM [IC4]->short
Short
J3 (Reset)
Reset
Open
J3 (WD)
Watch dog setting
Short
Switch Position
Value
SW1-1
1
SW1-2
2
SW1-3
4
SW1-4
8
SW1-5
16
SW1-6
32
SW1-7
64
SW1-8
128
SW2-1
256
SW2-2
512
Switch
Function
Default condition
SW2-3
ON: Data transmission under unbalanced condition
ON
SW2-4
ON: low baud rate setting
OFF
SW2-5
ON: Feet data OR 0-20m, OFF: 0-30m
OFF
SW2-6
ON: Measured data converted to feet
OFF
SW2-7
ON: Temperature data (57 bits)
ON
SW2-8
ON: Deg. F measured temperature unit, OFF: Deg. C
OFF
WARNING
ON
1
2
3
4
5
6
7
8
ON
1
2
3
4
5
6
7
8
SW - 1
SW - 2
Address Setting
Function Setting
Setting Example: 267
8 Commissioning
ENRAF BPM communication board (COM-3) setting
COM-3 Jumper setting
Communication setting
Select "V1/ENRAF BPM" at the matrix position GVH286.
Communication setting
Polling address is set at GVH285 "ADDRESS" of NMS5 matrix. The allowable range is from 00 to 99.
A to F for polling address can not use.
Communication setting
• Switch S1: Reset switch
• Connector J3: Communication port for debugging
Jumper
Function
Default Condition
JP1 (Mode)
ROM type setting
1-2 short: 27C4096
2-3 short: 27C1024
2-3 short
JP2 (Reset)
CPU mode setting (Fixed)
1-2 open
3-4 short
5-6 short
J3 (WD)
Baud rate setting
1-2 short: 1200 bps
1-2 open: 2400 bps
1-2 open
WARNING
8 Commissioning
Setting of analog output 4-20mA is available when ordered from Endress+Hauser. NMS5 is delivered
with analog output hardware installed. For the following matrix parameter settings, Access code 51,
is required.
If "LEVEL", confirm GVH158 (Prosafety) is "NO".
Matrix GVH
Item
Setting
250
Assign Output
Assign analog output (Level or Temperature) for channel 1.
251
Adjust 4mA
Set level or temperature value for 4mA output on channel 1.
Available only when GVH250= "Level" or "Liquid Temp"
Level: 0 to 99999mm
Temperature: -999 to 999°C
Default: 0mm / 0°C
252
Adjust 20mA
Set level or temperature value for 20mA output on channel 1. Available
only when GVH250 = "Level" or "Liquid Temp."
Level: 0 to 99999mm
Temperature: -999 to 999°C
Default: 0mm / 0°C
253
Assign Output 2
Assign analog output (Level or Temperature) for channel 2.
254
Adjust 4mA
Set level or temperature value for 4mA output on channel 2. Available
only when GVH253 = "Level" or "Liquid Temp."
Level: 0 to 99999mm
Temperature: -999 to 999°C
Default: 0mm / 0°C
255
Adjust 20mA
Set level or temperature value for 20mA output on channel 2. Available
only when GVH253 = "Level" or "Liquid Temp."
Level: 0 to 99999mm
Temperature: -999 to 999°C
Default: 0mm / 0°C
256
Device at Alarm
Select type of output for alarm. Select from OFF, HOLD current output,
Maximum value or Minimum value.
OFF: current does not apply when an error occurs.
HOLD: current which is applying is fixed when an error occurs.
MAX: 22mA current applies in stead of present current.
MIN: 2mA current applies in stead of present current.
Default: OFF
CAUTION
8 Commissioning
Contact relay alarm output
The specification of alarm for output contact relay is delivered as a part of NMS5. This specification
allows a maximum of 4 output contact relay settings. Set access code 51 in case of the following matrix
parameters.
Description of error message
Matrix GVH
Item
Setting
241
Select Relay
Use +/- and E keys to select to activate Contact Output Relays 1 to 4.
Default value = 1.
242
Assign Relay
Select output definition from range of choices: None, Level, Liquid Temp,
Caution, Warning, Emergency Error, and Balance Signal. Default value =
NONE.
243
Relay Function
Select High or Low function, available only when GVH241 = "Level" or
"Liquid Temp." Default value = HIGH.
244
Switching Point
Set level (0-99999 mm) at which relay is activated, available only when
GVH241 = "Level" or "Liquid Temp." Default value = 0 mm.
245
Hysteresis
Set hysteresis value (0-99999 mm) for selected relay, available only
when GVH241 = "Level" or "Liquid Temp." Default value = 0 mm.
When selecting Output2: "4: 2 x relay SPST, TUV with overspill
prevention" at order code 50, relay type is specified as only Normal
Closed.
246
Relay on Alarm
Select from Normal Open or Normal Closed, available only when
GVH241 = "Level" or "Liquid Temp." Default value = NORMAL OPENED.
247
On Delay time
Set delay time (0-999 seconds) for alarm output start, available only
when GVH241 = "Level" or "Liquid Temp." Default value = 0 seconds.
248
Off Delay Time
Set delay time (0-999 seconds) for alarm stop, available only when
GVH241 = "Level" or "Liquid Temp." Default value = 0 seconds.
Error type
Description
LEVEL
Liquid level exceeded the designated upper or lower limit.
LIQUID TEMPERATURE
Liquid temperature exceeded upper or lower limit.
CAUTION
Auto wire calibration error; Auto displacer calibration error
WARNING
Weight value exceeded the designated alarm sending limit (upper limit:
GVH162 or lower limit: GVH163). (e.g. local communication error, LCD error,
communication error, EEROM data error)
EMERGENCY ERROR
Z-phase no input error, ADC sensor error, communication IC error, A-phase no
input error, Driver error, power failure
NOTICE
8 Commissioning
I/O - 3
Alarm output, Standard
(Order Code position 050= 1,2,3 or 5)
4 relays with potential-free change-over contacts, freely assignable to
measured value
Hysteresis, Alarm output
Switch points and switching hysteresis freely adjustable, residual cur-
rent fail-safe mode: minimum or maximum, selectable
Operation output logic
Relay Condition
Initial Configuration
(Normal Status)
Open
Closed
On alarm
Closed
Open
On device error
Closed
Open
On abnormal power supply
(5% lower than, higher than
specified power supply
Custody Transfer
Closed
Custody Transfer
Open
Power outage
Hold last condition
Switching capacity, Alarm output
•
Max. 250VAC, 2A/62.5W
•
Max. 220VDC, 2A/60W
•
FM/CSA: 30VAC, 2A/42VDC, 2A, 60W
•
TIIS: 250VAC, 1.5A/30VDC, 9W
Alarm output,
Overspill prevention
(Order Code position 050=4)
2 relays with potential- free changeover contacts, assignable to Level
Hysteresis, Alarm output
Switch points and switching hysteresis freely adjustable, residual current fail-
safe mode: minimum or maximum, selectable
Operation output logic
Relay Condition
Initial Configuration (Normal Status)
Closed
On alarm
Open
On device error
Open
On abnormal power supply (5% lower
than, higher than specified power sup-
ply
Open
Power outage
Open
Switching capacity
•
Umax. 200VDC/200VppAC
•
Imax. 0.5AC, DC or peak AC
•
Pmax. 15W
Operation input
2 photocouplers, for external input from controller (tumbler switch, DCS, etc.)
Operation output logic
Gauge Status
CTR1
CTR2
Level
0 (OFF)
0 (OFF)
UP
1 (ON)
0 (OFF)
STOP
0 (OFF)
1 (ON)
Interface Level
1 (ON)
1 (ON)
Input voltage
15VDC, active circuit (supplied by NMS5)
Input current
Approximately 5mA
8 Commissioning
Density and density profile measurements
Two different types of density measurement are available when ordered from Endress+Hauser.
• Spot density measurement for up to 3 liquid phases
• Density profile measurement
1.
Tank profile for up to 16 points for total liquid height.
2.
Tank profile for upper phase liquid only.
3.
Tank profile based on a manually entered profile parameter.
8.6.1
Spot density measurement
Spot measurement for up to 3 liquid phases is an option that is available when ordered from
Endress+Hauser.
The following preconditions are required in order to assure safe and accurate operation.
• NMS5 must be configured for Spot density measurement as ordered from Endress+Hauser. For
information regarding upgrading your NMS5, contact Endress+Hauser representatives.
• Density values:
Figure 66:
Density measurement
• Density values can be viewed and changed at the following matrix positions:
GVH005: Upper Density
GVH006: Middle Density
GVH007: Density Bottom
• The displacer is balanced at liquid level and the liquid surface is not moving.
For spot density measurement, the following parameters can be set or selected. However the factory
default settings also can be used.
Matrix
Item
Setting
GVH143
Displacer Raise
Density
Set distance (0-300mm) for displacer to rise the level position above during
measuring density. Default setting = 150 mm. Observe the rule: GVH143 +
GVH144 = 300 n, where n = integer.
GVH144
Displacer
Submerge
Density
Set distance (0-300mm) for displacer to submerge the level position above
during measuring density. Default setting = 150 mm. Observe the rule:
GVH143 + GVH144 = 300 n, where n = integer.
e.g. 0.760 g/ml
e.g. 0.880 g/ml
e.g. 0.1000 g/ml
Upper density < Middle density
Select the measurement of the density desired from UPPER DENSITY, MIDDLE DENSITY, or DENSITY
BOTTOM at GVH020 "OPERATION". NMS5 raises the displacer up out of the liquid, measures its
weight, and sends the displacer down to measure the density. After density is measured, the displacer
remains at that position until UP or LEVEL command are selected at GVH020.
Figure 67:
Density measurement
8.6.2
Density profile measurement
Tank profile density measurement
In addition to the preconditions, the following additional preconditions are required in order to assure
safe and accurate operation for the density measurement of the tank profile.
Access Code 51 is required to edit parameters.
• NMS5 must be configured for Spot & Profile density measurement as ordered from Endress+Hauser.
Contact Endress+Hauser for the information regarding upgrading NMS5.
• The standard tank bottom level (GVH004) is zero. If not, the formula used for calculating the inter-
val between profiles is GVH000 / GVH841. The displacer touches the bottom of the tank before
measuring a lower level (e.g. 884mm).
• If Bottom Level is not 0 mm, select Manual I/F Profile at GVH840. Set GVH843 I/F Manual Level =
actual bottom level e.g. 884mm. In this case, the intervals will be calculated based on GVH000 -
GVH843/GVH841.
• The density profile can be operated when the liquid is still in the tank. However, depending on the
height of liquid level, it may take 1 hour or more to operate the density profile.
Additional matrix parameter settings are required for remote communications via WM550 communi-
cations protocol. Refer to Section "14 Matrix, (Dynamic Matrix, Device Data: G2), WM550 DENS. SEL.".
Matrix
Item
Setting
GVH154
SAFE DENSITY
Select the desired resultant condition when density profile measurement
fails due to displacer reaching the low-limit for density profile operation
(set in GVH155). Selecting "ON" will result in STOP operation. Selecting
"IGNOR" will result in "LEVEL" operation, displacer will return to liquid level.
Selecting "OFF" will leave the displacer at the position where density profile
measurement failed, and in "DENSITY" operation.
GVH155
DEN. OPE.
LEVEL
Set the lower limit for displacer movement during density profile operation
Default setting = 300 mm.
Upper layer (Gas or liquid)
Lower layer
(Liquid)
A
B
8 Commissioning
• A. Tank profile for up to 16 points for total liquid height
GVH840 Ope Select: Select 1: Tank Profile.
• B. Tank profile for upper phase liquid only
GVH840 Ope Select: Select 2: I/F Profile.
• C. Tank profile for based on a manually entered profile parameter.
GVH840 Ope Select: Select 3: MANU.I/F Profile.
When choosing A, B, and C above, the following parameters can be set or select. The factory default
settings also can be used.
Initial setting of tank profile (density profile) measurement
All of necessary set up can be done at "G8 Tank Profile" matrix. There are six factors to configured prior
to the actual operation.
GVH840 OPE. SELECT
Matrix
Item
Setting
GVH841
Ope Point
Set the number of measurement points (2-16) for Tank Profile
measurement. Default setting = 2.
GVH843
I/F Manu. Level
Manually set the water interface level (0-99999.9mm) to be referenced
during the tank profile measurement. Default setting = 0 mm. Only used
with C, tank profile for based on a manually entered profile parameter.
GVH844
Bal. Level
Set the allowance for level movement (1.0 -99.9 mm) prior to Tank
Profile operation. If the level movement exceeds this value, profile
operation is canceled. Setting 99.9mm allows Profile measurement to
proceed, regardless of level movement. Default setting = 2.0 mm.
GVH845
Up Wait Time
Set waiting time (1-31 minutes) for displacer weight to be measured in
air, when making the weight table at start of profile operation. Default
setting = 1 minute.
GVH846
Liq Wait Time
Set the time (1-31 minutes) for displacer to stop at each measurement
position during profile operation. Default setting = 1 minute.
GVH847
Ope Wait Time
Set maximum waiting time (1-31 minutes) for conditions in GVH844
(Bal Level) to be satisfied before profile operation begins. E.g. if the level
movement exceeds setting at GVH844, NMS5 is in "standby" for the time
set in this matrix. After the maximum time elapses, profile operation is
canceled. Default setting = 1 minute.
Item
Procedure
Remarks
Figure 68:
GVH840
1.
Select GVH030 "MATRIX OF" in the row
"MORE FUNCTION" on Static Matrix, then
select "Tank profile".
• Set access code to 50.
2.
Select function group "PROFILE OPE" and
GVH840 "OPE SELECT".
• The row of PROFILE OPE is the only
function group that needs
configuration for the density profile
operation.
3.
Select 1: "TANK PROFILE" by pressing + or -
key.
4.
Press E to configure.
• Selection of "0: SPOT" enables Upper
Density measurement instead of
Density Profile measurment.
Matrix Group�TANK PROFILE
Static
Matrix
GVH = 30
GVH = 840
MORE
FUNCTION
Matrix
of
Dynamic
Matrix
Function
Group
TANK
PROFILE
PROFILE
OPE.
STATUS
DATA
DENSITY
1-10
DENSITY
11-16
POSITION
1-10
POSITION
11-16
OPE.
SELECT
8 Commissioning
GVH841 OPE. POINT
GVH844 BAL. LEVEL
GVH845 UP WAIT TIME
Item
Procedure
Remarks
Figure 69:
GVH841
1.
Select GVH841 "OPE POINT " to determine
number of density measuring points.
• Set access code to 51. Default value is 2
points and selectable up to 16 points.
2.
Enter required number by pressing + or - key,
and select E to enter.
• Whatever the number of measuring point is
selected, the measuring interval & point
between each point are automatically
calculated within the liquid level.
Function
Group
Matrix Group: TANK PROFILE
PROFILE
OPE.
OPE.
POINT
GVH841
Item
Procedure
Remarks
Figure 70:
GVH844
1.
Select GVH844 "BAL LEVEL" to determine the
liquid stability range in order to start the
operation.
• Set access code to 51. NMS software has a
function to scan & record the liquid level
every 5 minutes.
2.
Enter desired value by pressing + or - key and
select E to enter. Input value of 99.9mm rep-
resents that the measuring procedure starts
regardless of level condition.
• NMS5 only starts the actual measurement
when the liquid level is within the entered
value compared to the recorded level data 5
minutes ago. This function ensures the safe
operating condition to avoid filling or
draining liquid from the tank.
Function
Group
GVH844
Matrix Group : TANK PROFILE
TANK
PROFILE
BAL.
LEVEL
Item
Procedure
Remarks
Figure 71:
GVH845
1.
Select GVH845 "UP WAIT TIME" to determine
the displacer weight calibration interval in air.
• Set access code to 51. The displacer raises
approximately 500mm above liquid surface
after confirming the stability of liquid level
within "BAL LEVEL" function.
2.
Enter desired waiting time by pressing + or -
key, and select E to enter.
• The displacer weight is calibrated at 8
different positions in air and the interval
between those positions are adjustable
within this function to allow excess liquid to
drip off the displacer to achieve higher
accuracy.
Function
Group
GVH845
Matrix Group : TANK PROFILE
TANK
PROFILE
UP.WAIT
TIME
8 Commissioning
GVH846 LIQ. WAIT TIME
GVH847 OPE. WAIT TIME
Item
Procedure
Remarks
Figure 72:
GVH846
1.
Select GVH846 "LIQ. WAIT TIME" to deter-
mine the displacer weight calibration interval
between each measuring point in the liquid.
• Set access code to 51. A small turbulence
made by the movement of displacer itself
may cause the liquid surrounding displacer
to be unstable for the accurate
measurement.
2.
Enter desired waiting time by pressing + or -
key, and select E to enter.
• This function allows displacer to hold in
each calculated position before actual
measurement is proceeded based on the
entered value.
Function
Group
GVH846
Matrix Group : TANK PROFILE
TANK
PROFILE
LIQ. WAIT
TIME
Item
Procedure
Remarks
Figure 73:
GVH847
1.
Select GVH847 "OPE. WAIT TIME".
• Set access code to 51.
2.
Enter desired waiting time by pressing + or -
key, and select E to enter.
• This function determines how long for the
NMS to wait if "BAL. LEVEL" can not be
established before quitting entire operation.
Function
Group
GVH847
Matrix Group : TANK PROFILE
TANK
PROFILE
OPE. WAIT
TIME
8 Commissioning
Operation of tank profile (density profile) measurement
After all the initial settings are completed, the actual operation can be proceeded by one simple com-
mand. The operation status regarding this function is displayed at GVH850 and the liquid level condi-
tion is also displayed at GVH851. Terms of status display and descriptions are listed below.
Operations status (GVH850, OPE. STATUS)
Level condition status (GVH851, LEVEL CONDITION)
Status
Contents
0: Accepting
Accepting density profile command
1: Standby
Ready to execute density profile command
2: In operation
Executing density profile command
3: OPR. END
Density profile operation completed successfully
4: UN_BALANCE ERR
Fail: Required conditions for density profile operation not satisfied
5: IPR. ERR. STOP
Fail: Abnormal conditions occurred during density profile operation
Status
Contents
0: Off Level Meas.
Active operation is not LEVEL (Profile cannot start).
1: Stable
Liquid level/surface is stable (Profile can start).
2: Unstable
Liquid level/surface is unstable (Profile cannot start).
3: Ignore condition
Ignores liquid level/surface condition (profile cannot start).
Item
Procedure
Remarks
Figure 74:
Static matrix
1.
Select GVH020 "OPERATION" in the Static
Matrix and select "UPPER DENSITY".
• Set access code to 50.
• The operation command "UPPER DENSITY" is
shared between spot and Tank Profile
density measurement depends on GVH840
configuration.
2.
Press E to start the operation.
• The operation must start when the NMS is
in Level measuring mode.
3.
Unless there is any incompatible circum-
stances during the displacer automatically
returns to the level measurement after the
last measuring point.
• To minimize the risk of safe operation, the
displacer immediately returns to the Level
measurement regardless of completing
various data process.
Static matrix
GVH020
LEVEL
UP
STOP
BOTTOM LEVEL
MIDDLE INTER LEVEL
UPPER DENSITY
MIDDLE DENSITY
DENSITY BOTTOM
REPEATABILITY
WATER DIP
OPE.
OPE.
8 Commissioning
Density profile operation diagram
Figure 75:
Density profile
Operation procedure
1.
Set NMS5 so that it can measures the liquid level.
2.
Raises the displacer and measure each weight of 8 measuring points in the air.
3.
Measure the density at the setting position in the liquid level.
4.
Return to level measurement.
5.
Save the data in G8 matrix accordingly.
This completes the operation procedure.
The average density and temperature data regarding density profile function (G8 Matrix) are com-
pletely different from the data on G0 static matrix which displays the conventional upper density (spot)
and temperature (continuously scanned) data.
8 points of air weight measurement
(within 300 (11.81) circumference
of wire drum)
Nozzle
First displacer weight calculation line
(Approximately 500 (19.69) from liquid level)
No. 1 Measuring point
No. 2 Measuring point
No. 3 Measuring point
No. 4 Measuring point
No. 5 Measuring point
No. 6 Measuring point
No. 7 Measuring point
If required density measuring points are 7, the method to calculate
each point from liquid level in NMS with ver 4.25 software is:
(7 points +1)
Liquid level
x Measuring point number
Ex. if the liquid level is 4,000 (157.48)
and needs to determine the position of No. 5 measuring point from the liquid surface;
(7 +1)
4,000 (157.48)
x 5 = 2,500 (98.43)
Interface profile
(upper layer)
Max.16 point
Tank profile
(liquid level to tank bottom)
Max.16 point
Liquid level
WARNING
8 Commissioning
NMS5 can measure interface levels via the following operations.
• Upper Interface Level: returns the level data for the interface between top 2 liquid phases. Displacer
remains at interface level in UPPER INTERFACE operation.
• Middle Interface Level: returns the level data for the interface between bottom 2 liquid phases. Dis-
placer remains at interface level in MIDDLE INTERFACE operation.
• Water Dip: returns the level data for the interface between top 2 liquid phases. Displacer returns to
liquid level in LEVEL operation.
The following preconditions are required in order to assure safe and accurate operation.
• Density values:
Figure 76:
Interface measurement
Density values can be viewed and changed at the following matrix positions:
• GVH005: Upper Density
• GVH006: Middle Density
• GVH007: Density Bottom
Additional matrix parameter settings are required for remote communications via WM550 communi-
cations protocol. Refer to Section "14 Matrix, (Dynamic Matrix, Device Data : G2), WM550 ALM.
SELECT.".
Operation:
After confirming the above pre-conditions, use the "+" or "-" keys to select the desired operation at
matrix position GVH020 OPERATION. When the desired operation is displayed, press the "E" key.
e.g. 0.760 g/ml
e.g. 0.880 g/ml
e.g. 0.1000 g/ml
Upper density < Middle density
Sealing of NMS5
NMS5 can be sealed, and data can be made unchangeable for custody transfer purposes as follows.
Sealing of NMS5 procedure
1.
Set OPE. DENSITY at GVH278 as the liquid density (if the density is expected to change during
operation, set the average value.).
2.
Turn off the power supply, open NMS5.
3.
Turn the micro switch to the "on position" on the printed circuit board TCB (see figure below).
NMS5 will then enter "write-protect" mode and not accept any further level, weight, or density
data changes.
This completes the sealing of NMS5 procedure.
Figure 77:
Printed circuit board TCB
2
20
9
1
6
1
13
1
1
CNB
CN5
CN7
CN6
CN4
SW1
U1
4
1
5
4
1
5
8
5
8
1
4
5
8
1
4
U20
U19
U15
U13
U10
14
1
15
28
1
16
8
9
1
7
8
U14
U9
U21
U7
U4
U11
U12
1
14
7
8
1
16
U24
U6
9
8
C16
C8
C7
U2
DC-DC Converter
C35
U3
C38
ON
OFF
CN9
CN2
CN3
TCB
CD_L423
Protect switch
8 Commissioning
NMS5 measuring instrument requires no special maintenance.
9.1
Exterior cleaning
When cleaning the exterior of measuring devices, always use cleaning agents which will not cause cor-
rosion or other damage to the housing surface seals.
9.2
Seals replacement
NMS5 O-rings may need to be replaced periodically, and more frequently in extreme climates. The
period between changes will depend on climate severity, ambient temperatures and process.
9.3
Repairs
The Endress+Hauser repair policy is based on the fact that the measuring devices have a modular
design and that customers are able to undertake repairs themselves. Spare parts are contained in cor-
responding kits along with their related replacement instructions. Endress+Hauser provides spare
parts for repairs of NMS5. Contact Endress+Hauser service representatives for further assistance
regarding service and spare parts.
9.4
Repairs to Ex-approved devices
When performing repairs on Ex-approved devices, note the following:
• Repairs of Ex-approved devices may only be performed by trained personnel or by Endress+Hauser
Service.
• Comply with the prevailing standards, national Ex-area regulations, safety instructions (XA) and
other relevant rules.
• Only use original spare parts provided by Endress+Hauser.
• When ordering spare parts, note the device information on the nameplate. Replace parts only with
parts that have the same device information.
• Perform repairs according to the instructions. When completing repairs, perform the specified rou-
tine test on the device.
• Only Endress+Hauser service representatives may convert a certified device into a different certified
variant.
• Document all repair work and conversions.
9.5
Replacement
After replacing NMS5 or electronic module, the adjustment of a new sensor is required.
9 Maintenance
NHC4HP: high pressure version
NHC4LP: low pressure version
The following figure shows dimensions of NHC4LP, 10K 150A RF, SUS304 version. For the other spec-
ifications, contact Endress + Hauser representatives.
Figure 78:
Calibration chamber, unit of measurement: mm (in)
10.2
Power and control switch
Figure 79:
Power and Control Switch NHS8, Unit of Measurement: mm (in)
Flange
8 Holes
Ø150 (5.91)
222.5 (8.76)
450 (17.72)
Flange
Rated Voltage
Rated Current
Housing
Terminal Box
Structure
No. of Certificate
Connection Diagram
Power supply
NMS
Term. No
NHS8
Term. No.
1
2
3
4
5
6
7
Handle
position
Wiring
LIFT
INST
STOP
OFF
7
6
4
3
5
2
1
OFF
STOP
INSTLIFT
Cable entry
PF (G) 3/4
PF (G)1
h (mm)
B
20
24
140
145
Cable entry
193 (7.6)
113 (4.45)
65 (2.56)
Grounding
LIFT
STOP
OFF
2 - Ø7 (0.27)
120 (4.72)
B
INST
h
Power L
Power N
COM
CRT1
CRT2
AC110/220V
6A/5A
Aluminum alloy casting
Iron casting
Ex. Proof D3aG5
T3875
Specifications
1
2
16
17
18
10 Accessories
Ball valve NHV4A
NHV4A: Standard ball valve with ASME flanges
NHV4J: Standard ball valve with JIS flanges
The following figure shows dimensions of NHV4J, 10K 150A RF, SUS304 version. For the other spec-
ifications, contact Endress + Hauser representatives.
Figure 80:
Ball Valve, Unit of Measurement: mm (in)
10.4
Reducing flange NHF4
Figure 81:
Reducing flange, unit of measurement: mm (in)
Ball
Body cap
Body
340 (13.39)
295 (11.61)
1000 (39.37)
Low pressure (JPI example)
High pressure (ASME example)
Stud bolt
Flange
Stud bolt
Flange
Ø90
Ø90
8-Ø23 (0.9)
P.C.D = Ø241.3 (9.5)
4-UNC 5/8
9 (0.35)
Ø317.5 (12.5)
38.2 (1.5)
3/4 8-UNC
P.C.D = 168.1 (6.62)
12-Ø22.4 (0.9)
P.C.D =Ø269.7 (1062)
Ø279 (10.98)
10 Accessories
Diagnosis and troubleshooting
NMS5 has a superb self-diagnosis function which monitors its operation. If an error is occurred, the
corresponding message is displayed on the LCD. The selected matrix position and the error message
are displayed every few seconds alternatively. Data can be accessed while the selected matrix position
is displayed. The error messages are stored in the memory of NMS5. Matrix position GVH037 provides
the diagnostic history.
11.1
Selection of diagnostic code and history
Item
Procedure
Remark
Figure 82:
Static matrix
Figure 83:
Touch control
1.
On "MORE FUNCTION" , select item GVH036
"DIAGNOSTIC CO."
2.
Previous static matrix records are sequentially
displayed in Static Matrix screen GVH037,
starting with the latest record. Up to 100
alarm records can be saved. If the number of
records exceeds 100, it is sequentially over-
written
starting with the oldest record. For example,
973192238 2402 means that an error
occurred at 22:38 on March 19, 1997, when
the instrument temperature was 24 oC and
this is the second error since NMS5 was
installed. Display includes the year, month,
day, hour, minute, instrument temperature,
and an error sequential number, in this order.
• Item GVH037 only shows error message,
calendar, and pointer, but no label on the
LCD.
MORE
FUNCTION
DIAGNOSTIC CO
(Erroneous Message)
0 3 6
0 37
11 Diagnosis and troubleshooting
Error and status messages
Message
Cause
Remedy
Error Code
-49.5 ºC
Indication of shorted element in NMT
temperature sensor
Check GVH450 through GVH459 to see element.
358.0 ºC
Element is not enabled, or not installed
in NMT temperature sensor .
Check GVH482 Total number of elements
359.0 ºC
Indication of open element in NMT
temperature sensor
Check GVH450 through GVH459 to see element.
ADC/SENSOR ERROR
The signal from the A/D converter is
out of range.
Consult E+H Service.
107
ADJ. XXXCOUNTER
(X=A, I, Z or
combination)
Error of level data check by A, I, and/or
Z phase encoder.
If the message appears frequently, then consult E+H Service.
A PHASE NO INPUT
The input of the A phase signal from
the encoder is not available.
Replace the detector unit. Consult E+H Service.
122
BELOWBOT. POINT
Indicates NMS displacer position is
below lowest of NMT temperature
sensor.
DEVICE ERROR: DEV 1
(or 2)
The HART device 1 (or 2) gives an error
signal.
Check the HART device 1 (or 2) .
130, 131
DEVICE ERROR: NMT
NMT53x gives an error signal.
Check the connection of NMT53x. Check the register of the
temperature sensor at position GVH362 "CONNECTION
NMT."
250
DEVICE ERROR: NMT
NMT53x temperature sensor is not
available.
Check NMT53x. Error messages are available in NMT53x
manual.
233
DEVICE ERROR: NRF
NRF560 gives an error signal.
Check NRF560. Error messages are available in NRF560
manual.
240
DISPL CALIB ERROR
The deviation of automatic weight
calibration exceeds its set limit.
Check build-up or deposit on the displacer.
120
ELEM 0 RANGE OVER
Indicates the reference resistance
element (ºC) on NMT electronics is out-
of- tolerance.
IMPOSSIBILITY
Operation is impossible because there
is no weight table.
LOCAL ERROR: DEV1
(or 2)
NMS5 cannot access the local HART
device 1 (or 2).
Check the connection of the HART device to NMS5. Check
the registration of the device(s) in matrix group G5/6.
232
LOCAL ERROR: NMT
The signal from NMT53x temperature
sensor is not available.
Check the connection of NMT53x. Check the register of the
temperature sensor at position GVH362 "CONNECTION
NMT."
111
LOCAL ERROR: NRF
NMS5 cannot access NRF 560.
Check the connection of NRF560 and register of the tank
side monitor at position GVH361 "CONNECTION NRF."
113
MINTENANCE
GVH157 Service Mode = ON
Set GVH157 = OFF
199
MEM. ERROR
Defect in the memory that is specially
used for custody transfer sealing.
Replace the CPU board. Consult E+H Service.
201
MPU RESET
Power to the CPU module fell below
minimum value.
MPU: START ACT*
Power to NMS5 was turned OFF/ON.
If the message occurs frequently, then consult E+H
Service.
OVERTENSION
The tension on the measuring wire
exceeds the upper limit set at
position GVH162 "OVER TENS. SET."
Check if the displacer motion is blocked by clogging or
sticking.
To release overtensioning, access position GVH371 "RELE.
OVER TENS."
101
POWER FAILURE
The supply voltage falls below the
allowed value.
Check the power source.
124
11 Diagnosis and troubleshooting
These error histories are available (Erroneous Message) at position GVH037.
RAM FAILURE
CPU RAM failure
ROM ERROR
EEPROM
Consult E+H Service.
132
SIFA ERROR
Error between communication board
and CPU board for digital output.
Replace the CPU board. Consult E+H service.
114
TEMP BELOW RANGE
Indicates the measured temperature
data is below the fixed range of the
NMT temperature sensor.
TEMP COM OPEN
Indicates an open common line in the
NMT temperature sensor
TEMP COM SHORT
Indicates a shorted common line in the
NMT temperature sensor
TEMP OVER RANGE
Indicates the measured temperature
data is higher than the fixed range of
the NMT temperature sensor.
UNDERTENSION
The tension on the measuring wire falls
below the lower limit set at
position GVH163 "UNDER TENS. SET."
Check if the measuring wire is cut or the displacer is lost. In
this case, check the installation of the NMS5.
102
WIRE CALIB ERROR
The deviation of automatic wire
calibration exceeds its set limit.
Check wire and wire drum.
115
Z PHASE NO INPUT
The input of the Z phase signal from
the encoder is not available.
Replace the detector unit. Consult E+H
Service.
106, 112
MPU:XXXX*
(XXXX=text)
CPU error
The error might happen occasionally and might be registered
in GVH037 (Erroneous Message).
However, it is normally negligible. If it occurs frequently,
then consult E+H Service.
OPE.CODE ERROR
An illegal operation command is
accessed.
If the message occurs frequently, then consult E+H Service.
LCD CHECK
Error between LCD (touch control) unit
and CPU board for digital
output.
Replace the touch control.
121
GAUGE TEMP.
The temperature inside the gauge
exceeds the limit.
Check if the ambient temperature stays within the limit.
If the application is a high temperature tank, then take
measures to avoid heat transfer from the tank to NMS5.
DRIVER ERROR
A motor driver error has occurred
Consult E+H Service
Message
Cause
Remedy
Error Code
11 Diagnosis and troubleshooting
Alarm history display
11.4
List of alarm messages
Item
Procedure
Remarks
Figure 84:
Device data
Figure 85:
LCD (Display)
1.
Bring up Static Matrix GVH034 (ALARM
CONTACT)."
Figure 86:
Static matrix
2.
Previous static matrix records are sequentially displayed in Static
Matrix screen GVH035, starting with the latest record.
• Up to 100 alarm records can be saved. If the number of records
exceeds 100, it is sequentially overwritten starting with the oldest
record.
• The display includes the year, month, day, hour, minute, instrument
temperature, and an error sequential number, in this order. For
example, 97 3192238 2402 means that an error occurred at 22:38
on March 19, 1997, when the instrument temperature was 24 oC
and this is the second error since NMS5 was installed.
MORE
FUNCTION
ALARM CONTACT
0 3 4
MORE
FUNCTION
Alarm Message
0 3 5
Message
Cause of alarm
UPPER LIMIT LEVEL
The level has risen above the set alarm operation value.
LOWER LIMIT LEVEL
The level has fallen below the set alarm operation value.
UPPER LIMIT TEMP.
The temperature has risen above the set alarm operation value.
LOWER LIMIT TEMP.
The temperature has fallen below the set alarm operation value.
11 Diagnosis and troubleshooting
Flowcharts for diagnostics and troubleshooting
For up to 10 elements,
check GVH450 to 459 to
find shorted element.
For 10 or more elements,
select element at
GVH470 and check
data at GVH473.
(Level display)
-49.5 ºC
Display shows
358.0ºC.
ADJ(A, I, Z) COUNTER
YYMMDDhhmm TT ##
Meaning:
Shorted element in NMT
temperature
Meaning:
NMT can not measure
liquid or gas average
temperature for some
reasons because all
elements are in gas or
liquid phase.
This shows special
situation of application,
not an error code.
Diagnostic : -49.5ºC
Diagnostic : 358.0ºC
Diagnostic : 359.0ºC
Level display shows
359.0ºC
Meaning:
Open element in NMT
temperature sensor
Diagnostic : ADC SENSOR ERROR
ADC SENSOR ERROR
YYMMDDhhmm TT ##
Meaning:
The A/D signal output from
the detector unit, or input to
CPU, is abnormal.
Replace TCB or detector
unit.
Reconnect CN5 and CN7.
TCB CN5, CN7 loose?
Diagnostic : ADJ A, I or Z COUNTER
Abnormal condition in
filed application due to
turbulence of gage head
or extreme changes of
level. Contact Endress+
Hauser representatives.
Diagnostic : A PHASE NO INPUT
A PHASE NO INPUT
YYMMDDhhmm TT ##
Meaning:
Despite the motor (liquid level)
moving 15 mm (0.59 in) or
more, A phas e input signal
was not inputted from
rotary encoder.
TCB CN5, CN7 loose?
Meaning:
Level adjustment is required
at calender time by automatic
configuration unit.
Yes
No
Yes
No
Yes
No
For up to 10 elements,
check GVH450 to H9 to
find open element.
For 10 or more elements,
select element at
GVH470,view
temperature at GVH473.
Check connectors of
NMT. Recover the wiring
if necessary. Check
element resistance.
When connector is
broken, record the data of
the malfunction at G4
matrix,and return the
device to Endress+ Hauser.
Observed for a while
Frequent ?
Replace detector unit.
Frequent ?
Yes
No
Observed for a while
Replace TCB or detector
unit.
Reconnect CN5 and CN7.
Check internal wiring
connectors of NMT.
Correct any abnormality.
Check element resistance.
If the element is short-
circuited, record all the
data of the malfunction at
G4 matrix, and return the
device to Endress+ Hauser.
11 Diagnosis and troubleshooting
Adjust position data of the
lowest element at GVH486
in the range of 0 to
500 mm (19.69 in).
This prevents error
occurrence when the level
is low; however, it might
cause detection of gas
temperature so that liquid
temperature may not
always be correctly measured.
Meaning:
Liquid level is positioned at
the lowest point. Due to below
the element, temperature
can not be measured.
Measuring:
An error arose in HART device
and HART fails to function.
Refer to operating manual
of HART device.
Diagnostic : BELOW BOT. POINT
Diagnostic : DEVICE ERROR: DEV1 (2)
Diagnostic : DEVICE ERROR : NRF
Diagnostic : ELEM 0 RANGE OVER
Record temperature data
matrix and replace
module.
NMT module connector
OK?
SW v 4.20 or Later ?
Set GVH498 = ON
Error is reset and
temperature shows
3580ºC.
If displacer position goes
lower than (Elem 0 position
+ GVH486), BELOW BOT.
POINT will display.
Device error: DEV1 or 2
Meaning:
An error arose in NMT
temperature sensor.
Check current error code at
GVH480. Check previous
error. Refer to operating
manual of NMT for details
of error.
Diagnostic : DEVICE ERROR: NMT
Device Error: NMT
Diagnostic : IMPOSSIBILITY
Meaning:
Operation is impossible
due to invalid weight table.
Adjust hall sensors.
Perform weight calibration.
Impossible Operation
Yes
No
No
Yes
Display shows
358.0ºC.
CAUTION
Device Error: NRF
Refer to operating manual
of HART device.
Meaning:
An error arose in NRF tank
side monitor.
Diagnostic : DISPL CALIB ERROR
Increase setting value at
GVH185, calibrate hall
sensor, or perform weight
calibration.
Meaning:
Displacer weight exceeds
allowable range, which disable
measuring temperature.
Foreign matter at
displacer ?
Clean displacer, wire, wire,
and drum.
Adjust hall sensor.
Perform weight calibration.
Yes
No
Data is flashing
Element 0 Range Over
Reconnect NMT module.
11 Diagnosis and troubleshooting
HART sensor breakage or
HART circuit or power
malfunction
Repair is required.
Local Error Device 1 or 2
Meaning:
HART communication error
arose in HART sensor 1 or 2.
Diagnostic : LOCAL ERROR DEV1(2)
Diagnostic : LOCAL ERROR NRF
Check HART bus wiring,
NMS HART module, TCB
NRF HART module, and
FCB
Meaning:
An error arose in NRF tank
side monitor.
HART connection OK?
Sensor is disconnected
when GVH549 and 649
= ON.
Perform GVH549 and 649
= 0.
Meaning:
An error has occurred at the
NMT temperature sensor.
Check NMT error.
Refer to NMT operation
manual.
Diagnostic : LOCAL Error NMT
Local Error: NMT
Local Error: NRF
G3V6H1 correct ?
Correct the data of
GVH361.
Yes
No
Yes
No
HART terminal voltage
is 16V or less?
Check G3V6H1:
NRF > = v 1.82, CONTACT2
NRF < v 1.82, CONTACT1
HART is within
DC16.5 to 25.5V?
No
Yes
No
Meaning:
CPU went out of control by
external noise and watch
dog functioned to restart
the program.
Diagnostic : MPU : RESET
CPU might be influenced
by noise.
Check how it functions.
MEM. ERROR
YYMMDDhhmm TT ##
Frequent ?
Check that the gauge has
been correctly grounded.
Check the cause of external
noise and take
countermeasures.
Replace CPU TCB and check
how it functions.
No
Yes
Set the communication
address as follows.
GVH591 = 4
GVH691 = 5
No
HART terminal voltage
is 16V or less?
HART sensor breakage or
HART circuit or power
malfunction
Repair is required.
When sensor is
disconnected GVH362
status is not OFF.
Diagnostic : LOCAL Error NMT
Maintenance
YYMMDDhhmm TT ##
This shows NMS status
is on maintenance
at GVH157.
Check NMS HART module,
TCB, NRF HART module,
and FCB.
Yes
11 Diagnosis and troubleshooting
Check the NMS local
power supply if frequent.
MPU: START ACT
YYMMDDhhmm TT ##
Meaning:
Power supply is turned off
and on at the recorded
calender time.
Diagnostic : MPU: START ACT
Meaning:
Tension of measuring wire
is exceeding setting value at
GVH162.
Set Operation = STOP
Set G3V7H1 = ON
Diagnostic : OVERTENSION
Overtension
Diagnostic : TEMP. BELOW RAMGE
Check NMT specification.
Check temperature of
each point at GVH450 to
459, and check the
temperature inside the
tank at the same time.
Overtension arose.
Check how it works.
No
Meaning:
Malfunction of NMT
temperature element
common wiring
Diagnostic : TEMP. COM. OPEN
Common wiring is
free of damage?
No
Overtension
occurs when hoisting
the wire?
Check the cause of
overtension and recover it.
Yes
Diagnostic : POWER FAILURE
POWER FAILURE
YYMMDDhhmm TT ##
Check local power supply.
Meaning:
Power voltage is not within
the standard value at the
recorded calender time.
Diagnostic : RAM FAILURE
Replace CPU module TCB
RAM FAILURE
YYMMDDhhmm TT ##
Meaning: CPU RAM failure
Data below range ?
Record temperature
matrix data and replace
temperature module.
This is normal operation.
When the temperature
returns to the specified
range, the error goes away.
Meaning:
Measured temperature
value is exceeding allowable
range.
Display is flashing.
Yes
No
Yes
Diagnostic : ROM ERROR
Replace CPU module TCB
ROM Error
YYMMDDhhmm TT ##
Meaning:
CPU ROM fetch error
Display is flashing.
Record temperature
matrix data and replace
temperature module.
Repair the damaged
wiring.
11 Diagnosis and troubleshooting
Diagnostic : TEMP. COM. SHORT
Diagnostic : UNDERTENTION
Stop the gauge operation.
Measuring wire cut ?
Check the weight measuring
function. If an error occurs,
replace CPU TCB and
detector unit TCC-3.
Check cause of cut and
replace wire, and adjust
hall sensor and perform
calibration.
Meaning:
Measured weight is smaller
than the setting at GVH163
Undertention
Yes
No
Common wiring is
free of short?
No
Record temperature
matrix data and replace
temperature module.
Meaning:
Malfunction of NMT
temperature element
common wiring
Yes
Repair the shorted
wiring.
Diagnostic : TEMP. OVER RANGE
Data over range ?
Yes
Data is flashing.
Check NMT specification.
Check temperature of
each point at GVH450 to
459, and check the
temperature inside the
tank at the same time.
Record temperature
matrix data and replace
temperature module.
NMT operates correctly.
When temperature returns
to allowable range, error
goes away.
Meaning:
Measured temperature
value is exceeding allowable
range.
No
Data is flashing.
Diagnostic : WIRE CALIB ERROR
No
Increase setting value at
GVH185, calibrate hall
sensor, or perform weight
calibration.
Meaning:
Level position is below the
lowest point, which disable
measuring temperature.
Foreign matter at
displacer ?
Clean displacer, wire,
and wire drum. Adjust
hall sensor and perform
weight calibration.
Yes
Data is flashing.
Meaning:
Abnormal Z-phase signal
output from the encoder,
or input to CPU.
Diagnostic : Z PHASE NO INPUT
TCB CN5, CN7 are
loose?
Replace detector unit.
No
Z PHASE NO INPUT
YYMMDDhhmm TT ##
Yes
Check connectors.
11 Diagnosis and troubleshooting
Diagnostic : Calibration unsuccessful
After calibration, measured value shows 0.0g at GVH370.
Diagnostic : No response to OPERATION
GVH020 = LEVEL, GVH021 � LEVEL
0.0g
Measured Weight
G3V4H0, H1, H2
correct?
Input correct values for
circumference, wire, and
displacer weight.
Adjust hall sensors.
Perform weight calibration.
Adjust Hall sensors
(refer to 12.1 Sensor
Adjustment).
If the specified value can
not be obtained, replace the
detector unit.
No
No
Yes
Replace detector unit.
Adjust hall sensor.
Perform weight calibration.
Yes
Hall sensor
adjustment OK?
Level Operation
Yes
Replace CPU module TCB.
Adjust hall sensor.
Perform weight calibration.
Yes
GVH020
GVH021
Not Level Operation
Perform level operation
at tank side monitor
NRF560.
Set OPERATION = LEVEL by
using tank gauge system
or host CPU.
GVH024 = LEVEL ?
No
No
GVH025 = LEVEL ?
11 Diagnosis and troubleshooting
Setting after parts replacement
After any part of NMS5 is replaced, and before starting NMS5 calibration, specify the data on the fol-
lowing equipment.
• Circumferential length of wire drum (indicated on face of wire drum)
• Weight of displacer (indicated on the body of the displacer)
• Volume of displacer (indicated on the body of the displacer)
• Balance volume (indicated on the body of the displacer or 50% of volume)
• Density of measured liquid (up to three phases)
• Height of tank with NMS5 mounted on it (refer to Section "8 Commissioning").
Item
Procedure
Remarks
Matrix group: SERVICE
1.
In Static Matrix "MORE FUNCTION" bring up
GVH030 "MATRIX OF" and select "SERVICE.
2.
Select Dynamic Matrix GVH340 "WIRE
DRUM CIRC." Check whether the displayed
value is equal to the value marked on the
wire drum.
• If not, adjust the displayed value.
• Set the access code at 51.
Figure 87:
Dynamic matrix.
Figure 88:
Displacer
3.
Select the Dynamic Matrix screen GVH341.
4.
Set Dynamic Matrix GVH342 "DISPLACER
WEIGHT" at the value marked on the dis-
placer.
5.
Set Dynamic Matrix GVH343 "DISPLACER
VOLUME" to the value marked on the dis-
placer.
6.
Set Dynamic Matrix GVH344 "BALANCE
VOLUME" at half the value set in "DIS-
PLACER VALUME." "This setting is provided
to the approximate position of the displacer
when it becomes
7.
stationary in the liquid.
• The weight and volume of the displacer are
marked on its bottom
• The balance volume is the volume of that
part of the displacer that is immersed in the
liquid when the displacer is balanced in the
liquid.
• For calculation methods of the draft position.
MORE
FUNCTION
DISPLACER WEIGHT
MATRIX OF
DISPLACER VOLUME
BALANCE VOLUME
MEAS. WIRE
& DRUM
030
344
343
342
11 Diagnosis and troubleshooting
Maintenance prediction function
The history of maintenance is displayed at matrix screen GVH265 (Parts Overused Date) LCD screen
displays the following contents.
• Total operation time for parts managed according to this value
• Total number of rotations of the wire drum for parts managed according to this value
11.8
Return
The measuring device must be returned if repairs or a factory calibration are required, or if the wrong
measuring device has been ordered or delivered. According to legal regulations, Endress+Hauser, as an
ISO-certified company, is required to follow certain procedures when handling returned products that
are in contact with medium. To ensure swift, safe and professional device returns, please read the
return procedures and conditions on the Endress+Hauser website at www.services.endress.com/
return-material
11.9
Disposal
Observe the following notes during disposal:
• Observe valid federal/national regulations.
• Ensure proper separation and reuse of the device components.
Reference part
management value
Display
Part
Reference
(conducting time/
number of rotations)
1) POWER UNIT
2) DISPLAY UNIT
3) MOTOR UNIT
4) WIRE UNIT
5) BEARINGS UNIT
6) SHAFT UNIT
Power supply unit
LCD indicator
Motor/driver unit
Measuring wire
Drum bearing metal
Drum shaft
43,800 hours (about 5 years)
61,300 hours (about 7 years)
43,800 hours (about 5 years)
240,000 rotations
145,000 rotations
240,000 rotations
11 Diagnosis and troubleshooting
Software Version / Date
Software Changes
Documentation
Changes
V2.13, from 9.96
Original Release
BA001N/08/en/09.98
V2.20, from 10.97
T2:TCB-2, Modified V1: R&S command
BA001N/08/en/11.97
V4.06, from 04.98
HART master, T4:TCB-4
V4.06, from 04.98
HART master T&W, T4:TCB-4
V4.08X, from 08.98
upper stop speed reduction 3-step
V4.20, from 08.98
WM550, Commuwin II display, elem. Error fix
BA001N/08/en/12.99
V4.20, from 09.98
T&W
BA001N/08/en/12.99
V4.22, from 05.00
HART line selection add to static matrix: gas temp.
minus data remote communication level 6 digit data
processing memory clear volume calculation matrix
deleted
V4.23B, from 09.00
standard release, alarm output modify, NMT level
selection
V4.24, from 04.01
standard release
BA001N/08/en/03.01
V4.24 OSP, from 06.01
Over Spill protection
V4.24T&W, from 07.01
T&W spec.
V4.24 T2, from 02.02
TCB-2 CPU, NMT, V1 level measurement
V4.25, from 09.02
Density profile function
BA001N/08/en/02.02
V4.27, from 09.04
Level hold matrix, Error display on Home screen only
BA001N/08/en/11.04
V4.27 T6/T&O, from11.05
W&M and Overspill prevention
BA001N/08/en/03.06
V4.27 A, from 05.07
standard release
V4.27 B, from 09.08
standard release
BA1001N/08/en/12.08
V4.27 C, from 04.09
Proactive Safety function
BA1001N/08/en/04.09
V4.27 E, from 03.10
DTM support
BA00401G/08/en/
01.11
V4.27 F, from 05.11
SIL
BA00401G/08/en/
02.11
V4.27 G, from 05.12
4-20mA long range support
BA00401G/08/en/
03.13
V4.27G1, from 04.15
Extend density measurement range. Enable 4-20 mA
output assignment on upper I/F measurement. Send
the gauge status code "1: Reference" on Modbus
protocol.
BA00401G/08/en/
07.15
V4.27G2, from 03.16
NMT HART retry number setting function
BA00401G/08/en/
08.16
11 Diagnosis and troubleshooting
After exchanging CPU module, detector unit, wire drum, measuring wire (all or part), it is necessary to
adjust the hall sensors and make new weight table calibration.
1.
Move the displacer to the side of calibration window or the maintenance chamber window (top
of the tank) or put the displacer on a work bench so that the displacer can be touched.
Figure 89:
Sensor calibration 1
2.
Confirm that NMS5 is level and no vibration or other disturbance occurred.
3.
Set access code to 530 at GVH039.
4.
Set operation command to STOP at GVH020.
5.
Select ADJ.SENSOR at GVH030.
6.
Record sensor count (Wa2) at GVH741.
Figure 90:
Sensor calibration 2
Do not let wire fall off the wire drum.
7.
Lift the displacer so that the weight of the measuring wire shows 0 until the sensor count is stable
and record the value of sensor count (Wa1). Use the following formula to get the difference
between Wa2 and Wa1.
• |Wa2 - Wa1 | = 10000 (+/-100)?
8.
If Yes, go to step 7 "GVH740 A Zero".
530
ACCESS CODE
GVH039
STOP
OPERATION
ADJ. SENSOR
MATRIX OF
GVH020
GVH030
29XX 25000
ADJ. A SPAN
Index
count
Sensor
count
(Ex. Wa2= 25000)
29XX 15000
ADJ. A SPAN
(Ex. Wa1= 15000)
WARNING
12 Adjustment