Mastervolt MASS 24/50-2 Installation Manual

Text of the manual

MASS 24/50-2; 24/75; 24/75 (120V);

24/100; 3-24/100; 48/25; 48/50 FULLY AUTOMATIC BATTERY CHARGER USER AND INSTALLATION MANUAL 10000001888/02 To download this manual in other languages, please visit our website: www.mastervolt.com

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

TABLE OF CONTENTS 1 GENERAL INFORMATION ........................................ 3 1.1 Use of this manual .............................................. 3 1.2 Validity of this manual ......................................... 3 1.4 Disclaimer ........................................................... 3 1.5 Identification label ............................................... 3 1.6 Correct disposal of this product .......................... 3 2 SAFETY INSTRUCTIONS .......................................... 4 2.1 General ............................................................... 4 2.2 Explosive gases .................................................. 4 2.3 Warnings regarding the use of batteries ............. 4 2.4 Warning regarding life support applications ........ 5 2.5 Guarantee specifications .................................... 5 3 PRODUCT DESCRIPTION ......................................... 6 3.1 The 3-step+ charge process ............................... 6 3.2 Dimensions ......................................................... 6 4 INSTALLATION .......................................................... 7 4.1 Location .............................................................. 7 4.2 Connections ........................................................ 7 4.3 Wiring 7 4.3.1 AC wiring ................................................. 7 4.3.2 AC safety grounding ................................ 7 4.3.3 DC wiring ................................................. 8 4.3.4 Connection of main batteries ................... 8 4.4 Battery capacity .................................................. 8 4.5 Battery isolator .................................................... 8 4.6 Connection of second battery (3A output) .......... 8 4.7 Temperature sensor ........................................... 8 4.8 Voltage sense ..................................................... 9 4.9 Alarm function ..................................................... 9 4.9.1 Standard alarm mode .............................. 9 4.9.2 DC alarm mode ....................................... 9 4.10 RJ12 splitter for enclosure C2 ............................. 9 4.11 Overview connection compartment ................... 10 4.12 Things you need ................................................ 10 4.13 Connection ........................................................ 11 4.14 Installation step-by-step..................................... 12 4.15 Commissioning after installation ........................ 13 4.15.1 General .................................................. 13 4.15.2 MasterBus .............................................. 13 4.16 Decommissioning .............................................. 13 4.17 Storage and transportation ................................ 13 5 DIP SWITCH SETTINGS ........................................... 14 5.1 DIP switch operation ......................................... 14 5.2 DIP switch functions .......................................... 14 6 OPERATION ............................................................. 15 6.1 Switching on/off ................................................. 15 6.2 Reset the Mass Charger.................................... 15 6.3 Equalize mode ................................................... 15 6.4 LED indicators ................................................... 15 7 MASTERBUS ............................................................ 16 7.1 About MasterBus ............................................... 16 7.2 Event based commands .................................... 16 7.3 How to set up a MasterBus network .................. 16 7.4 MasterBus Settings ........................................... 16 8 TROUBLE SHOOTING ............................................. 19 9 TECHNICAL DATA ................................................... 20 9.1 Specifications .................................................... 20 9.2 Characteristics ................................................... 22

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

3 1 GENERAL INFORMATION 1.1 Use of this manual This manual contains important safety and operating instructions for the safe and effective operation, maintenance and possible correction of minor malfunctions of the Mass Charger. It is therefore obligatory that every person who works on or with this product is completely familiar with the contents of this manual, and that he/she carefully follows the instructions and important safety instructions contained herein. 1.2 Validity of this manual All of the specifications, provisions and instructions contained in this manual apply solely to standard versions of the Mass Charger delivered by Mastervolt. This manual is valid for the following models: Part no Model Enclosure type 40020506 Mass 24/50-2 230V/50-60Hz C2 40020756 Mass 24/75 230V/50-60Hz C3 40120756 Mass 24/75 120V/60-50Hz C3 40021006 Mass 24/100 230V/50-60Hz C3 40031006 Mass 3-24/100 400V 3 phase C3 40040256 Mass 48/25 230V/50-60Hz C2 40040506 Mass 48/50 230V/50-60Hz C3 These models are further mentioned as “Mass Charger”. Mastervolt offers a wide range of products for your electrical installation. For an extensive overview of all our products, please visit our website www.mastervolt.com. 1.3 Liability Mastervolt can accept no liability for:  Consequential damage due to use of the Mass Charger.  Use that is inconsistent with the purpose of the product.  Possible errors in the manuals and their results. Disclaimer: Our products are subject to continual development and improvement. Therefore, additions or modifications to the products may cause changes to the technical data and functional specifications. No rights can be derived from this document. Please consult our most current Terms & Conditions of Sale. 1.4 Identification label Part number Serial number K201R0010 with device version “R” Figure 1. Identification label The identification label is located at the right-hand side of the Mass Charger. Important technical information required for service and maintenance can be derived from the identification label. CAUTION! Never remove the identification label. 1.5 Correct disposal of this product This product is designed and manufactured with high quality materials and components, which can be recycled and reused. When this crossed-out wheeled bin symbol is attached to a product, it means the product is covered by the European Directive 2012/19/EU. Please be informed about the local separate collection system for electrical and electronic products. Please act according to your local rules and do not dispose of your old products with your normal household waste. CERTIFICATES

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

2 SAFETY INSTRUCTIONS Read the entire manual before using the Mass Charger. Keep this manual in a secure place. WARNING This chapter describes important safety and operating instructions for use of a Mass Charger in residential, recreational vehicle (RV) and marine applications. 2.1 General 1 To reduce the risk of electric shock – Do not expose Mass Charger to rain, snow, spray, moisture, excessive pollution and condensing circumstances. To reduce risk of fire hazard, do not cover or obstruct the ventilation openings. Do not install the Mass Charger in a non-ventilated room, overheating may result. 2 Use of an attachment or spare part not recommended or sold by Mastervolt may result in a risk of fire, electric shock, or injury to persons. 3 The Mass Charger is designed to be permanently connected to an AC and DC electrical system. Installation of, and work on the Mass Charger, may be carried out only by a qualified, authorised and trained technician or electrician, consistent with the locally applicable standards and regulations. 4 Make sure that all wiring is properly installed and in good electrical condition; and that wire size is large enough for AC current rating of the Mass Charger. Check the wiring on a regular base, at least once a year. Do not use the Mass Charger when the wiring is undersized or damaged. 5 Do not operate the Mass Charger if it has received a sharp blow, been dropped, or otherwise damaged in any way; take it to qualified personnel. 6 Except for the connection compartment (see section Overview connection compartment4.11 on page 10), the Mass Charger may not be opened or disassembled. There are no serviceable parts inside the cabinet. Take it to qualified, authorized and trained service personnel when service or repair is required. Incorrect reassembly may result in a risk of electric shock or fire. Only qualified, electrician installers are authorized to open the connection compartment. 7 To reduce risk of electric shock, disconnect the Mass Charger from both AC and DC electrical system before attempting any maintenance or cleaning. Turning off controls will not reduce this risk. 8 The Mass Charger must be provided with an equipment-grounding conductor to the AC input ground terminal. Grounding and all other wiring must comply with local codes and ordinances. 9 Short circuiting or reversing polarity will lead to serious damage to batteries, Mass Charger, wiring as well as accessories. Fuses cannot prevent damage caused by reversed polarity and the warranty will be void. 10 In case of fire, you must use the fire extinguisher which is appropriate for electrical equipment. 11 If applied in a marine application in the United States, external connections to the Mass Charger shall comply with the United States Coast Guard Electrical Regulations (33CFR183, Sub part I). 2.2 Explosive gases 1 WARNING: risk of explosive gases. Working in vicinity of a lead-acid battery is dangerous. Batteries generate explosive gases during normal battery operation. For this reason, it is of utmost importance that each time before using the Mass Charger, you read this manual and follow the instructions exactly. 2 To reduce risk of battery explosion, follow these instructions and those published by battery manufacturer and manufacturer of any equipment you intend to use in vicinity of the battery. Review cautionary marking on these products. 3 DANGER: To reduce the risk of explosion – Never use the Mass Charger in situations where there is danger of gas or dust explosion or an area in which ignition-protected equipment is required. 2.3 Warnings regarding the use of batteries 1 Someone should be within range of your voice or close enough to come to your aid when you work near a lead-acid battery. 2 Have plenty of fresh water and soap nearby in case battery acid contacts skin, clothing, or eyes. 3 Wear complete eye protection and clothing protection. Avoid touching eyes while working near battery. 4 If battery acid contacts skin or clothing, wash immediately with soap and water. If acid enters eye, immediately flood eye with running cold water for at least 10 minutes and get medical attention immediately. 5 NEVER smoke or allow a spark or flame in vicinity of a battery or engine. 6 Do not short circuit batteries, as this may result in explosion and fire hazard! Be extra cautious to reduce risk of dropping a metal tool onto a battery. It might

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

5 spark or short-circuit battery or other electrical part and may cause explosion. 7 Remove personal metal items such as rings, bracelets, necklaces, and watches when working with a battery. A battery can produce a short-circuit current high enough to weld a ring or the like to metal, causing a severe burn. 8 Only use the Mass Charger for charging Lead-acid, NiCad and Li-ion batteries and the supply of users attached to these batteries, in permanent systems. Do not use the Mass Charger for charging dry-cell batteries that are commonly used with home appliances. These batteries may burst and cause injury to persons and damage to property. 9 NEVER charge a frozen battery. 10 Excessive battery discharge and/or high charging voltages can cause serious damage to batteries. Do not exceed the recommended limits of discharge level of your batteries. 11 If it is necessary to remove a battery, always remove the grounded terminal from the battery first. Make sure all accessories are off, so as not to cause an arc. 12 Be sure that the area around the battery is well ventilated while the battery is being charged. Refer to the recommendations of the battery manufacturer. 13 Batteries are heavy! It may become a projectile if it is involved in an accident! Ensure adequate and secure mounting and always use suitable handling equipment for transportation. 14 Study all battery manufacturer’s specific precautions while charging and recommended rates of charge. Note that the Mass Charger charge specifications are based on Mastervolt batteries. Specifications for a given chemistry of a different manufacturer may vary. If connecting batteries of a different manufacturer make sure the manufacturer's recommendations are met. 2.4 Warning regarding life support applications Mastervolt products are not designed to be used as component of medical equipment, unless negotiated in the form of a written agreement between customer and/or manufacturer and Mastervolt. Such agreement will require the equipment manufacturer either to contract additional reliability testing of the Mastervolt parts and/or to commit to undertake such testing as a part of the manufacturing process. In addition the manufacturer must agree to indemnify and not hold Mastervolt responsible for any claims arising from the use of the Mastervolt parts in the life support equipment. 2.5 Guarantee specifications Mastervolt guarantees that this unit has been built according to the legally applicable standards and specifications. Should work take place, which is not in accordance with the guidelines, instructions and specifications contained in this user manual, then damage may occur and/or the unit may not fulfil its specifications. All of these matters may mean that the guarantee becomes invalid. The guarantee is limited to the costs of repair and/or replacement of the product. Costs for installation labour or shipping of the defective parts are not covered by this guarantee.

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

3 PRODUCT DESCRIPTION The Mass charger is a fully automatic, high efficiency battery charger/rectifier. The Mass Charger not only charges batteries rapidly and safely, it supplies the connected consumers at the same time. In addition, the Mass Charger is secured against short circuit, overload and high temperatures in an industrial environment. 3.1 The 3-step+ charge process The Mass charger is equipped with an intelligent 3-step+ charge characteristic which takes care of an optimal charge of your batteries. See Figure 2 and Figure 9 (page 22) for more details. Figure 2. the 3-step+ charge process. 3.2 Dimensions C2 enclosure (Mass 24/50 and 48/25) C3 enclosure (other models)

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

7 4 INSTALLATION During installation and commissioning of the Mass Charger, the important safety instructions are applicable at all times. See chapter 2 on page 4. Please check the contents of the box before you start with the installation. The contents of the box need to be:  the Mass battery charger;  battery temperature sensor (incl. 6m cable);  a MasterBus terminator;  the user manual. If one of these items is missing, please contact your supplier. 4.1 Location Choosing a location to install:  Install the Mass Charger in a well-ventilated room protected against rain, snow, spray, vapour, bilge, moisture and dust.  Ambient temperature: 0…60°C/32°F…140°F; (power derating above 40°C/104°F to decrease the internal heat sink temperature).  Humidity: 0-95% non-condensing.  Never use the Mass Charger at a location where there is danger of gas or dust explosions  Mount the Mass Charger in such a way that obstruction of the airflow through the ventilation openings is prevented. No objects must be located within a distance of 10cm/4inch around the Mass Charger.  Mount the Mass Charger vertically, with the connecting cables downwards.  Do not install the Mass Charger in the same compartment as the batteries. Do not mount the Mass Charger straight above the batteries because of possible corrosive sulphur fumes. 4.2 Connections Before making the connection between the battery charger and the system, be sure that the AC and DC system are switched off. Remove the fuses in order to protect yourself against unexpected start up. 4.3 Wiring CAUTION! The wire and fuse sizes stated in this manual are given as example only. Prescribed wire and fuse sizes may be different due to local applicable regulations and standards. 4.3.1 AC wiring Check if the voltage of your mains source or generator corresponds with the AC input voltage of the battery charger as mentioned on the type number plate. See section 1.4 on page 3. It is important that the green/ yellow earth wire is ± 1 cm (0.4 inch) longer than the other wires. By accidentally pulling at the cable, the earth wire stays connected to the Mass Charger longer which offers additional safety. For a safe installation the correct wire cross section must be applied. Do not use a cross section that is smaller than indicated. See the following table to select the appropriate cross section for the AC wiring (up to 6m/20ft length): AC Current Minimum cross section: 6-12A 1.5mm² 14AWG 12-20A 2.5mm² 12AWG 20-32A 4.0mm² 10AWG Connection of AC wiring and recommended colours  230V [120V] installations: Wire colour Meaning Must be connected to: Brown or black [black] Phase L1 Blue [white] Neutral N Green/yellow [green] Earth PE/GND  400V installations (Mass 3-24/100): Wire colour Meaning Must be connected to: Brown/black/grey Phase L1, L2, L3 Green/yellow Earth PE/GND 4.3.2 AC safety grounding WARNING The ground wire offers protection only if the cabinet of the Mass Charger is connected to the safety ground. Connect the ground terminal (PE/GND) to the hull or the chassis. CAUTION! For safe installation it is necessary to insert a RCD (Residual Current Device; earth leakage switch) in the AC input circuit of the Mass Charger.

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

4.3.3 DC wiring Keep the cable connection between charger and batteries as short as possible. If available, use coloured battery cables. If this is not possible, mark the plus and the minus cables with coloured insulating tape (e.g. red for plus and blue/black for minus). Use the following diameters: Mass Charger Length <3 m Length 3-6 m Mass 24/50-2 MB 25mm² 35mm² Mass 24/75 MB 35mm² 50mm² Mass 24/75 (120V) MB 35mm² 50mm² Mass 24/100 MB 50mm² 70mm² Mass 3-24/100 MB 50mm² 70mm² Mass 48/25 MB 10mm² 16mm² Mass 48/50 MB 25mm² 35mm² 4.3.4 Connection of main batteries 1 Pull the cables through the cable glands of the Mass Charger. 2 Crimp on ring terminals to the cable:  ring M6 for 24/50-2 and 48/25;  ring M8 for 24/75, 24/75 (120V), 24/100, 48/50 and 3-24/100. 3 Connect the cables to the terminals of the Mass Charger. Pay attention to the polarity, positive on positive/negative on negative. 4 Integrate a suitable fuse (charger fuse) in the positive cable. When using a DC distribution with fuses, no additional fuse is necessary. 5 Cut the cables to length and crimp on the ring terminals. Connect the cable to the DC distribution or batteries. CAUTION! Reversing the positive and negative battery poles will severely damage the Mass Charger. Lay the positive and negative cables next to each other to limit the electromagnetic field around the cables. The negative cable should be connected directly to the negative post of the battery bank or the ground side of a current shunt. Do not use the hull or chassis frame as the negative conductor. 4.4 Battery capacity Always follow the instructions published by the battery manufacturer. Mass Charger Recommended battery capacity Mass 24/50-2 100Ah – 500Ah Mass 24/75 150Ah – 750Ah Mass 24/75 (120V) 150Ah – 750Ah Mass 24/100 200Ah – 1000Ah Mass 3-24/100 200Ah – 1000Ah Mass 48/25 50Ah – 250Ah Mass 48/50 100Ah – 500Ah 4.5 Battery isolator If one or more batteries or battery sets must be charged at the same time via one output, a battery isolator should be used. This isolates the different battery sets to prevent one discharging the other. Mastervolt offers several Battery Isolators. Please refer to www.mastervolt.com . A battery isolator causes a voltage drop of 0.6V. This can be compensated in two ways:  By changing DIP switch 4 to On (Diode enabled);  By using the voltage sense function (see section 4.8 on page 9); CAUTION! Never use both methods. Your batteries will be overcharged and severely damaged! If you use a ‘voltage drop free’ battery isolator, like the Mastervolt Battery Mate, no compensation is needed. For a proper installation, see the connection diagram that comes with the battery isolator. 4.6 Connection of second battery (3A output) The Mass 24/50-2 MB is standard equipped with a second charge output which can be used to give a maintenance charge to a small second battery set like a starter battery. The maximum charge current of the second output is 3A, which comes from the main output.  Use 2.5 to 4mm2 cable for the connection.  Connect the minus of the second battery to the minus of the main battery.  Connect the plus of the second battery to the +3A terminal of the Mass Charger (Figure 4 and Figure 5).  Integrate a 10A slow blow fuse in the plus cable. 4.7 Temperature sensor The standard temperature sensor is provided with 6m cable and a double-sided tape for easy installation. 1. Make sure that the side of the battery that you want to place the sensor, is clean and grease-free. 2. Remove the piece of paper from the tape and stick the sensor on the battery. 3. Plug the modular cable into the terminal at the right of the Mass Charger (see Figure 4 on page 10). For the C3 enclosure (refer to specifications) both "RS232" and "analog" are suitable. It is not necessary to shorten the cable. When you want to shorten it anyway please notice the polarity of the plug and use the old connector as an example. Now when the battery temperature is low, the charge voltage increases and when the battery temperature is high, the charge voltage is decreased. This prevents overcharge, and gassing, which increases the battery’s life time substantially.

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

9 Figure 3. Temperature compensated charging 4.8 Voltage sense If required, DC cable losses can be compensated by using the sense function. This will shorten the charge time. 1. Use 0,75mm2, preferably red and black wire and secure these with fuses of 2A slow blow. 2. Connect the wires with the two upper terminals of the green connector at the right side of the cabinet (see Figure 4 on page 10). Pay extra attention to the polarity of the wires, red on +S and black on -S. 3. Now connect the other side of the wires: black on the minus of the battery and red on the plus of the battery. 4.9 Alarm function To control external equipment, the charger is equipped with a potential free contacts alarm relay; see Figure 4 on page 10. The alarm function has two modes: standard (factory setting) and DC alarm mode (continuous mode). The maximum switch current of the relay is 1A. Exceeding the setpoints will activate the alarm (see page 17). 4.9.1 Standard alarm mode In this mode the relay responds to all fault conditions that the Mass Charger can detect such as: no AC input voltage, low DC voltage, voltage sense failure, temperature sense failure. 4.9.2 DC alarm mode To enable this mode a DIP switch setting needs to be changed (switch 1 and 2 at ON). The alarm now works as a DC alarm and responds to the battery voltage only. Note: In the DC alarm mode the electronics stay active permanently and drain a very small current of ±25mA, also when the Mass Charger is switched off. 4.10 RJ12 splitter for enclosure C2 The RJ12 connector (QRS232 communication port) can be used to connect the battery temperature sensor or the remote panel (not included). Use a RJ12-splitter to connect both at the same time (not included). Charge voltage (V) Battery temperature (°C)

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

4.11 Overview connection compartment C2 ENCLOSURE 1 Screw terminals AC input: L1, N, PE (24/100-3ph: L1, L2, L3, PE) 2 Earth stud 3 MasterBus connector 4 MasterBus connector 5 Output (battery) positive connector (maximum 3A) 6 RS232/Temperature sensor connector 7 Analog/Temperature sensor connector 8 Output (battery) positive connector 9 Output (battery) negative connector 10 Voltage sense/ potential free alarm contact C3 ENCLOSURE Figure 4. Overview connections Mass Charger 4.12 Things you need Make sure you have all the parts you need to install the Mass Charger: Product Quantity Mass Charger (included) 1 Battery temperature sensor with cable and plug (included) 1 DC cable to connect the positive DC connection (+) of the Mass Charger to the positive pole of the DC distribution; for specifications see section 4.3.3 on page 7 1 DC cable to connect the negative DC connection (–) of the Mass Charger to the negative pole of the DC distribution; for specifications see section 4.3.3 on page 7 1 DC fuse holder with a DC fuse, to be integrated in the positive DC cable 1 Screws/bolts (Ø 6mm) (with plugs) to mount the cabinet to a surface. Use mounting materials which are suitable to carry the weight of the Mass Charger 4 AC cable* to connect the AC input to an external power source (e.g. a shore connection or a generator set) 1 Batteries. See section 4.4 on page 8 for recommended capacity X Appropriate and reliable cable terminals, cable lugs, battery terminals and cord end terminals X * Double insulated three-wire cable with wire colours according to the locally applicable regulations. The applicable length and wire diameter depend on the electrical installation (see section 4.3.1 on page 7). We recommend as a minimum tool kit:  Socket wrench 13mm to fix the DC input (battery) cables  Flat blade screw driver 1.0 x 4.0mm to fix the screw terminals  Tools to fix the screws/bolts (Ø 6mm) with plugs to mount the cabinets to a surface  Philips screw driver to open the connection area of the Mass Charger  2mm flat blade screw driver for the sense terminal (see Figure 4, point 10).

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

11 4.13 Connection WARNING Let installation work be done by a licensed electrician. Before beginning with the connection of the wiring, make the AC distribution as well as the DC distribution voltage free. CAUTION! Too-thin cables and/or loose connections can cause dangerous overheating of the cables and/or terminals. Therefore tighten all connections well, in order to limit transition resistance as far as possible. Use cables of the correct size. Note: If the battery temperature remains within 15-25°C, the battery temperature sensor is optional. Note: The Mass Charger supports MasterBus and RS 232 compatible remote control panels. The following schematic illustrates the general placement of the Mass Charger. It is not meant to provide detailed wiring instructions for any particular electrical installation. Figure 5. Installation drawing of the Mass Charger BATTERY BANK 1 (main battery bank) Temperature sensor BATTERY BANK 2 Battery fuse Battery fuse Charger fuse L N PE/GND RCD

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

4.14 Installation step-by-step 1 Mark the position of the mounting spots using the drilling dimensions. 2 Place the four screws first and hang the Mass Charger over them. Then fix the Mass to the wall by securing the screws. 3 Open the connection compartment by loosening the two screws. 4 Feed the AC wiring through the cable gland and connect the wiring to the screw terminals. Tighten the cable gland firmly. 5 Connect the DC cabling of the house bank, positive to +, negative to – . + - + - 6 Option for model 24/50: Connect the DC wiring of the second battery bank (max. 3A). This bank has a common negative with the main battery. 7 Attach the battery temperature sensor to the casing of the main battery bank. Plug the temperature sensor cable into the “Temp.Sensor” jack. See also Figure 4 on page 10. 7 Option: Connect the Mass Charger to the MasterBus network. 8 The factory setting of the Mass Charger is optimal for most installations. Sometimes however, it is desirable to change these settings. See chapter 5 (page 14) and section 7.4 (page 16). 9 Check all wiring. If everything is all right, close the connection compartment by fixing the two screws. 10 Continue with section 4.15 for commissioning of the Mass Charger.

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

13 4.15 Commissioning after installation Note: When your Mass Charger is not new, you have to take into account that former users may have changed the settings. Reset the Mass Charger to factory settings when there is any doubt (see section 7.4 on page 16). 4.15.1 General The factory settings of the Mass Charger are optimal for most installations. With some applications however, it is desirable to change these settings. Therefore several adjustments can be made. See chapters 5 and 7.4. Note: The DIP switches must be adjusted prior to commissioning; all other settings can only be configured after commissioning. CAUTION! Check the polarity of all wiring before commissioning: positive connected to positive (red cables), negative connected to negative (black cables). If all wiring is OK, place the DC fuse(s) of the DC distribution to connect the batteries to the Mass Charger. WARNING When placing this fuse, a spark can occur, caused by the capacitors used in the Mass Charger. Now the Mass Charger is ready for operation. After switching on the AC power supply the Mass Charger will initiate the charging process. 4.15.2 MasterBus Adjustment of the settings of the Mass Charger can be made by means of DIP switches or via the MasterBus network (by means of an USB interface connected to a PC with MasterAdjust software). Some settings can only be changed via the MasterBus interface. See section 7.4 on page 16 for an overview of all available MasterBus settings. 4.16 Decommissioning If it is necessary to put the Mass Charger out of operation, follow the instructions in order of succession as described below: 1 Switch the Mass Charger to off. 2 Remove the DC fuse(s) of the DC distribution and/or disconnect the batteries. 3 Remove the AC fuse(s) of the AC input and/or disconnect the AC mains. 4 Open the connection compartment of the Mass Charger. 5 Check with a suitable voltage meter whether the inputs and the outputs of the Mass Charger are voltage free. 6 Disconnect all wiring. Now the Mass Charger can be demounted in a safe way. 4.17 Storage and transportation When not installed, store the Mass Charger in the original packing, in a dry and dust free environment. Always use the original packing for transportation. Contact your local Mastervolt Service Centre for further details if you want to return the apparatus for repair.

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

5 DIP SWITCH SETTINGS The Mass Charger settings can be adjusted in two ways:  By means of DIP switches;  Via the MasterBus network (by means of a remote control panel or an interface connected to a PC with MasterAdjust software); see section 7.4 on page 16. Note: Once a DIP switch has been set to On, MasterBus presets are disabled but people can still change the settings! CAUTION! Invalid settings of the Mass Charger can cause serious damage to your batteries and/or the connected load! Adjustments of settings may be undertaken by qualified personnel only! 5.1 DIP switch operation The Mass Charger has six DIP switches. These switches are operated by flipping the levers to the other position, using a small screw driver. Figure 6. DIP switches 5.2 DIP switch functions See the table for the functional overview of the DIP switches (Switch 5 and 6 are reserved for future use). Force Float (DIP switch 1) For special applications a fixed charge voltage can be required. The battery charger allows you to change the 3- step+ charge program to a single stage program by activating the function "Force Float", switching DIP switch 1 to "ON". The charge voltage will be fixed at 26.5V (24V charger) or 53V for a 48V charger. Traction setting (DIP switch 2) Setting for traction charging: +0.7/1.4V during bulk and +0.4/0.8V in absorption for 24/48V batteries. Gel/AGM batteries (DIP switch 3) Some Gel/AGM batteries need a higher float voltage for optimal charge. Changing the float voltage can be done by setting DIP switch 3 to "ON". The float voltage will increase to 27.6V (24V charger) or 55.2V for a 48V charger. Diode setting (DIP switch 4) Setting for +0.6V voltage compensation in case a battery isolator is used. DIP SWITCH 4 3 2 1 Standard 0 0 0 0 Diode 1 0 0 0 Gel/AGM 0 1 0 0 Diode + Gel/AGM 1 1 0 0 Traction 0 0 1 0 Traction + Diode 1 0 1 0 ContMon + Traction 0 1 1 0 ContMon + Traction + Diode 1 1 1 0 ForceFloat 0 0 0 1 ForceFloat + Diode 1 0 0 1 ForceFloat + Gel/AGM 0 1 0 1 ForceFloat + Diode + Gel/AGM 1 1 0 1 ContMon 0 0 1 1 ContMon + Diode 1 0 1 1 ContMon + Gel 0 1 1 1 ContMon + Diode + Gel/AGM 1 1 1 1 1 = On; 0 = Off ContMon: Continuous monitor mode. MasterBus, RS232 and DC alarm stay functioning at mains failure. Remote stays functioning if it has its own power source. Diode: Diode compensation on (+0.6V) Gel/AGM: Gel/AGM compensation on (during float +1.1V or 2.2V) Traction Traction charging (+0.7 or 1.4V during bulk and +0.4 or 0.8V in absorption). Force float: One step charge program with fixed float voltage.

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

15 6 OPERATION 6.1 Switching on/off Activate the Mass Charger by switching the main switch to the on position. When no error is present, the charger LED illuminates green and the Mass Charger starts charging. Move the switch to the off position to switch off the Mass Charger! 6.2 Reset the Mass Charger Set the main switch to off. 1. Switch on again. 2. The Mass Charger automatically resumes operation in Bulk stage after it was disconnected from an AC source. 6.3 Equalize mode An equalizing charge can be necessary after very deep discharges and/or inadequate charges. This has to be carried out according to the specifications of the battery manufacturer. WARNING! Equalization is ONLY applicable for flooded batteries and will damage Gel/AGM/Spiral type batteries! Incorrect use of the equalize mode may lead to hazardous situations. During equalizing the batteries are brought into the gas state and permitted load voltages may be exceeded (refer to Figure 10 on page 23 for characteristics). For these reasons the equalizing mode should only be used by trained technical engineers. The equalizing mode can only be started when the Mass Charger is in float operation. To start the equalize mode, select Equalize in the MasterBus device settings (see section 7.4 on page 16). 6.4 LED indicators Figure 7. Front panel of the battery charger During normal operation the charger LED (6) is green. When all charge process status LEDs (1 to 5) are on, the battery is fully charged. For details refer to Figure 9 on page 22. 1…5 Status LEDs charge process 6 Charger status LED: ˗ Green = on ˗ Off = off ˗ Red = fault condition: +: Battery sense error +: Charger temperature too high +: Short circuit indication, charger will reduce the charge current to 25% +: DC error, DC voltage too low or too high +: Temperature sense error 7 Status LED MasterBus communication: ˗ Green = MasterBus communication ˗ Off = no MasterBus communication 8 Main or on/off switch 9...13 Status LEDs charge current 13 5 4 3 2 1 7 6 8 9 10 11 12

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

7 MASTERBUS 7.1 About MasterBus All devices that are suitable for MasterBus are marked with the MasterBus symbol. MasterBus is a CAN based, fully decentralized data network for communication between Mastervolt devices. MasterBus is used as power management system for all connected equipment, such as the inverter, battery charger, generator and many more. Every device that is compatible with MasterBus is equipped with two data ports. The devices are simply chained together, forming a local data network. Monitoring panels such as the EasyView 5 can be used for monitoring and control of all connected MasterBus equipment. CAUTION! Never connect a non-MasterBus device to the MasterBus network directly! This will damage all connected MasterBus devices. 7.2 Event based commands With MasterBus a device can be programmed to initiate an action at another connected device. This is done by means of event based commands. 7.3 How to set up a MasterBus network  Connections between the devices are made by standard straight MasterBus cables. Mastervolt can supply these cables.  Up to 63 MasterBus devices can be connected together.  MasterBus needs a terminator on both ends of the network.  The electric power for the network comes from the connected devices according to the rule: 1 powering/3 non powering.  Do not make ring networks.  Do not make T-connections in the network. 7.4 MasterBus Settings Meaning Factory setting Adjustable range Device settings Language Language that is displayed on a monitoring device connected to the MasterBus. English EN, NL, DE, FR, ES, IT Name Name for the Mass Charger. CHG Mass+type* 0-12 characters Device Device name recognized by MasterBus. Mass Charger - Battery name Name for the main battery bank. House Bank 0-16 characters Factory settings Option to reset the Mass Charger to default settings. Not reset Not reset, reset Presets Diode compensate Option for charger diode +0.6V voltage compensation. If it is enabled, the compensation value is adjustable. Disabled Disabled, Enabled: 0-2.50V Forced float Option for Forced Float or constant voltage charging. If it is enabled, Forced Float voltage is adjustable. Disabled Disabled, Enabled Continuous mode Option to keep MasterBus powered by the battery when the Mass Charger is disabled. Disabled Disabled, Enabled Gel/AGM Gel/ AGM settings option. It includes fully adjustable Bulk, Absorption and Float settings. Disabled Disabled, Enabled Traction Traction settings option. See Traction settings. Disabled Disabled, Enabled NiCad NiCad settings option See NiCad settings. Disabled Disabled, Enabled Li-ion Li-ion settings option. See MLI settings. Disabled Disabled, Enabled Equalize Option to enable Equalizing. Shows only when no other battery type has been selected. Warning: Equalize is suitable for flooded batteries only! Do not use Equalize for other battery types! Disabled Disabled, Enabled

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

17 Meaning Factory setting Adjustable range General Max. current Maximum charge current, adjustable model dependent. (Max current)* 0 – Imax* Temp. compensate Charge voltage compensation for temperature (V/°C). -0.060/-0.120V/°C -1.000 – 1.000V/°C Bulk Bulk voltage Bulk voltage 28.50/57.00V 16.00-32.00/ 32.00-64.00V Max. bulk time Maximum bulk timer 480 min 0-600 min Min bulk time Minimum bulk timer 2 min 0-600 min Start bulk time Voltage at which to start the bulk timer. 27.60/55.20V 16.00-32.00/ 32.00-64.00V Bulk ret. volt. Return to Bulk voltage 25.60/51.20V 16.00-32.00/ 32.00-64.00V Bulk ret. time Adjustable Return to Bulk time after the Return to Bulk voltage has been reached. 30 sec 0-255 sec Absorption Abs. voltage Absorption voltage 28.50/ 57.00V 16.00-32.00/ 32.00-64.00V Max absorption Maximum absorption timer 240 min 0-600 min Min absorp. time Minimum absorption timer 15 min 0-180 min Return amps Return to Float current (in A) 6.0 %*I max 0-25% * I max Float Float voltage Float voltage 26.50/53.00V 16.00-32.00/ 32.00-64.00V Equalize voltage Equalize voltage 31.00/62.00V 16.00-32.00/ 32.00-64.00V Equalize time Equalize time 360 min 0-600 min Alarm set points DC Alrm high on Alarm DC High on 32.00/64.00V 16.00-32.00/ 32.00-64.00V DC Alrm high off Alarm DC High off 30.00/60.00V 16.00-32.00/ 32.00-64.00V DC Alrm low on Alarm DC low on 20.00/40.00V 16.00-32.00/ 32.00-64.00V DC Alrm low off Alarm DC low off 22.00/44.00V 16.00-32.00/ 32.00-64.00V DC Alrm delay Alarm delay time 30 sec 0-255 sec Traction settings Bulk voltage Bulk voltage 29.20/58.40V (read only) Max bulk time Maximum bulk time 360 min (read only) Min bulk time Minimum bulk time 4 min (read only) Start bulk time Start bulk time 27.60/55.20V (read only) Bulk ret. volt. Bulk return voltage 25.60/51.20V (read only) Bulk return time Bulk return time 30 sec (read only) Abs. voltage Absorption voltage 28.90/57.80V (read only) Max absorp. time Maximum absorption time 480 min (read only) Min absorp. time Minimum absorption time 15 min (read only) Return amps Return to Bulk current (in A) 6.0 %*I max (read only) Float voltage Traction float voltage 26.50/53.00V (read only) NiCad settings Bulk voltage Bulk voltage 29.00/58.00V (read only) Max bulk time Maximum bulk time 480 min (read only) Min bulk time Minimum bulk time 2 min (read only) Start bulk time Start bulk time 26.50/53.00V (read only) Bulk ret. volt. Bulk return voltage 10.00/20.00/40.00V (read only) Bulk return time Bulk return time 30 sec (read only) Abs. voltage Absorption voltage 29.00/58.00V (read only) Max absorp. time Maximum absorption time 480 min (read only) Min absorp. time Minimum absorption time 15 min (read only) Return amps Return to Bulk current (in A) 6.0 %*I max (read only) Float NiCad float voltage 26.00/52.00V (read only)

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

Meaning Factory setting Adjustable range MLI (Li-ion) settings Bulk voltage Bulk voltage 28.50/57V (read only) Max bulk time Maximum bulk time 480 min (read only) Min bulk time Minimum bulk time 2 min (read only) Start bulk time Start bulk time 26.50/53.00V (read only) Bulk ret. volt. Bulk return voltage 26.30/52.60V (read only) Bulk return time Bulk return time 240 sec (read only) Abs. voltage Absorption voltage 28.50/57V (read only) Max absorp. time Maximum absorption time 240 min (read only) Min absorp. time Minimum absorption time 15 min (read only) Return amps Return to Bulk current (in A) 6.0 %*I max (read only) Forced Float LI-ion forced float voltage 27/54V (read only) * Depending on model Events Event x source Event-based command. Mass Charger event that should result in an action by another device on the MasterBus network. Disabled See Event source list. Event x target Select a connected MasterBus device that should take action due to a Mass Charger event. Select… Selectable targets are system dependent. Event x command Action to be taken by the target device. Select… See command list in selected device manual Event x data Data is linked to the command. On changes the status to On at the first signal. Off changes the status to Off at the first signal. Copy lets the status follow the input. Copy Invert lets the status follow the opposite of the input Toggle changes the status at the 1st signal and back at the 2nd signal. It is used in combination with a pulse switch. Off Off, On, Copy, Copy Invert, Toggle. Event x+1 The next event appears after enabling Event x. Disabled See Event x. Mass Charger event source list (Mass Charger as event source) Charging Mass Charger state is On Bulk Charge stage is Bulk Absorption Charge stage is Absorption Float Charge stage is Float Failure Charger failure MasterBus alarm CSI Charger Status Interface MasterBus alarm to generate an audible alarm at charger failure Equalize Mass Charger is in Equalize mode TC Error Battery temperature sensor error Fan MasterBus signal for an external fan to start (at 50% load/50°C) LED Bulk LED Bulk illuminates LED 20-40 LED 2 illuminates (see Figure 7) LED Abs LED Abs illuminates LED 60-80 LED 4 illuminates (see Figure 7) LED Float LED Float illuminates LED Failure LED Failure illuminates Mass Charger event target list (Mass Charger as event target) Bulk Command to start the Bulk stage of charge Absorption Command to start the Absorption stage of charge Float Command to start the Float stage of charge On/ Standby Command to switch on the Mass Charger

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

19 8 TROUBLE SHOOTING In case of a failure, the Mass Charger display shows an error ‘code’ to help you find its source. See section 6.4 LED indicators, on page 15. If you cannot solve a problem using the following fault finding table, contact your supplier or Mastervolt. Make sure you have the part and serial number at hand (See section 1.4, on page 3). Malfunction Possible cause What to do No output voltage and/or current No AC input. Check AC wiring, check remote control panel. AC input voltage too low (< 180VAC). Check input voltage, check generator. AC input frequency out of range. Check input voltage, check generator. Output voltage too low, charger supplies maximum current Load that is connected to the batteries is larger than charger can supply. Reduce load taken from the batteries. Batteries not 100% charged. Measure battery voltage. After some time this will be higher. Charge current too low Batteries almost fully charged. Nothing, this is normal when the battery is almost fully charged. High ambient temperature. Nothing; if ambient temperature is more than 40°C the charge current is automatically reduced. Low AC input voltage. At lower AC input voltages the charge current is reduced. See Figure 8 on page 22. Check AC input voltage. Batteries not fully charged Charge current too low. See “Charge current too low”. Current to load is too high. Reduce load taken from the batteries. Charge time too short. Use a battery charger with higher capacity. Battery temperature too low. Use the battery temperature sensor. Defective or old battery. Check battery and replace if necessary. Batteries are discharged too fast Battery capacity reduced due to wastage or sulphation, stagnation. Charge and recharge a few times, this might help. Check battery and replace if necessary. Batteries are too warm, gassing Defective battery (short circuit in cell). Check battery and replace if necessary. Battery temperature too high. Use the battery temperature sensor. Charge voltage too high. Check settings (see section 7.4 on page 16).

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

9 TECHNICAL DATA 9.1 Specifications Model Mass 24/50-2 Mass 24/75 Mass 24/75 (120V) Product code 40020506 40020756 40120756 INPUT Mains voltage 230V, -10% + 15% 230V, -10% + 15% 120V, -10% + 15% Frequency 50-60Hz ± 5Hz 50-60Hz ± 5Hz 60-50Hz ± 5Hz Inrush current None, the battery charger is equipped with a soft start in accordance with IEC 1003-3 Input current 7A 12A 25A Power factor (Cos phi) 1 1 1 Maximum efficiency 89% 89% 89% Input power 1600W 2700W 2700W OUTPUT Nominal voltage 24VDC 24VDC 24VDC Max charge current (Imax)* 50A 75A 75A Outputs 1x50A + 1x3A 1 x 75A 1 x 75A Charge characteristic* 3-step+, fully automatic Battery types: Flooded lead acid, Gel/AGM lead acid, NiCd, Mastervolt MLI (see section 7.4 for settings) Default charge voltages at 25°C Absorption voltage* 28.5V 28.5V 28.5V Float voltage* 26.5V 26.5V 26.5V Voltage ripple max. 100mV RMS with resistive load @ full power Short circuit current (1/4 of Imax) 12.5A 18.75A 18.75A Wire gauge (up to 3m length) 25mm² 35mm² 35mm² Charger fuse (external) 63A 80A 80A ENVIRONMENTAL Ambient temperature -20 to 40°C** @ 100% output power, derated with 2,5%/°C above 40°C Cooling Forced air, by means of a ventilator with variable speed Humidity Maximum 95%RV, non-condensing MASTERBUS MasterBus powering capability Yes Yes Yes MasterBus menu languages English, Dutch, German, French, Spanish, Italian ENCLOSURE TYPE C2 C3 C3 Dimensions (hxwxd)mm See section 3.2 on page 6 See section 3.2 on page 6 See section 3.2 on page 6 Protection degree IP23 IP23 IP23 Weight 5kg 9kg 9kg * Adjustable, see chapter 5. ** The Mass 24/50-2 allows operation in ambient temperatures as high as 45°C. Specifications are subject to change without prior notice.

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

21 Model Mass 24/100 MB Mass 3-24/100 MB Mass 48/25 MB Mass 48/50 MB Product code 40021006 40031006 40040256 40040506 INPUT Mains voltage 230V, -10% + 15% 3 x 365...550V** 230V, -10% + 15% 230V, -10% + 15% Frequency 50-60Hz ± 5Hz 50-60Hz ± 5Hz 50-60Hz ± 5Hz 50-60Hz ± 5Hz Inrush current None, the battery charger is equipped with a soft start in accordance with IEC 1003-3 Current 16A 6.5A 8A 16A Power factor (Cos phi) 1 0.8 1 1 Efficiency 89% 89% 89% 89% Input power 3600W 3500W 1800W 3600W OUTPUT Nominal voltage 24VDC 24VDC 48VDC 48VDC Max charge current (Imax)* 100A 100A 25A 50A Outputs 1 x 100A 1 x 100A 1x25A 1x50A Charge characteristic* 3-step+, fully automatic Battery types: Flooded lead acid, Gel/AGM lead acid, NiCad, Mastervolt MLI (settings: section 7.10) Default charge voltages at 25°C Absorption voltage* 28.5V 28.5V 57V 57V Float voltage* 26.5V 26.5V 53V 53V Voltage ripple max. 100mV RMS with resistive load @ full power Short circuit current (1/4 of Imax) 25A 25A 6A 12.5A Cable size (within 3 m) 35mm² 35mm² 16mm² 25mm² Charger fuse (external) 125A 125A 32A 63A ENVIRONMENTAL Ambient temperature -20 to 40°C @ 100% output power, derated with 2,5%/°C above 40°C Cooling Forced air, by means of a ventilator with variable speed Humidity Maximum 95%RV, non-condensing MASTERBUS MasterBus powering capability Yes Yes Yes Yes MasterBus menu languages English, Dutch, German, French, Spanish, Italian ENCLOSURE TYPE C3 C3 C2 C3 Dimensions (hxwxd)mm See section 3.2 on page 6 Protection degree IP23 IP23 IP23 IP23 Weight 9kg 10kg 5kg 9kg * Adjustable, see chapter 5. ** For device versions up to J (see section 1.4 on page 3): 3x 365...440V Specifications are subject to change without prior notice.

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

9.2 Characteristics Figure 8. Charge current versus input voltage Figure 9. Charge characteristic of the 3-step+ charging method (at 25°C/77°F)

Mass Charger 24/50-2, 24/75, 24/75 (120V), 24/100, 3-24/100, 48/25, 48/50 – User and Installation Manual

23 Figure 10. Charge characteristic of the equalize charge cycle (at 25°C/77°F) Figure 11. Temperature compensation characteristic (charge voltage versus temperature)

1105 AN Amsterdam

The Netherlands Tel.: +31-20-3422100 Email: [email protected] Web: www.mastervolt.com Copyright © 2018 Mastervolt. All rights reserved. Reproduction, transfer, distribution or storage of part or all of the contents in this document in any form without the prior written permission of Mastervolt is prohibited.