Johnson Controls T25 Installation Instructions Manual

Specifications

Brand: Johnson Controls
Category: Thermostat
Model: T25 (Installation Instructions Manual), prN9LHP7MTpbI
File Type: PDF
File Size: —
Pages: 6 pages

Download Document

Get a high-quality, printable PDF version of this manual for offline use.

Download PDF Manual (6 pages)

⚠️ Download Safety: This PDF is completely safe to download (last scan date: 04/04/2026).

Read Online

Read the Johnson Controls T25 Installation Instructions Manual online using the built-in PDF viewer.

T25 Installation Instructions Manual: Key Pages of Document

Installation Instructions T25

Issue Date 05/27/14 T25 Two-Stage Room Thermostat Application Requirements T25 thermostats are for line- or low-voltage service requiring accurate control of two operating functions. There are two stages of control for heating and cooling with automatic changeover on three- and four-pipe fan coil installations and similar applications. Typical uses are for compressor controls, relays, valves, fan coils, and other applications where low differentials and accurate sensing are required. Installation IMPORTANT: Use this T25 Two-Stage Room Thermostat only as an operating control. Where failure or malfunction of the thermostat c ...

Two Mounting Holes

0.28 (7.1) 0.15 (3.8) x 2.84 (72) 1.44 (37) Figure 1: T25A Dimensions, in. (mm) Mounting Plate Studs High Temperature Stop Set Point Knob Figure 2: Inside View of T25 Wall Box Mounting To mount the thermostat to an electrical conduit box, proceed as follows: 1. Remove the external adjustment knob, when furnished, by loosening the knob set screw using the provided Allen wrench. Slide the knob from the adjustment shaft. 2. Remove the cover by loosening the Allen-head screws at the top and bottom of the thermo ...

8. Secure the thermostat to the adaptor plate with the

two machine nuts referred to in Step 3. 9. Refer to the Wiring section to connect the terminals on the Pennswitches. 10. If a high temperature stop is desired, proceed to the Setup and Adjustments section. Wall Surface Mounting To mount the thermostat directly to an interior wall surface (no electrical box) proceed as follows: 1. At the desired thermostat location, make an opening in the wall approximately 1/2 in. in diameter, and pull the wires through it. 2. Plug the rest of the wall opening to prevent drafts from affecting the operation of the thermostat (when applicable). 3. Remove the adjustin ...

Note: RB , RY indicates

HI-TEMP. RB , RY indicates LO-TEMP. D represents differential between stages. H represents High. L represents Low. H H H Figure 3: Two-stage Control Switching Action Hot Hot or Neutral Power Supply Cooling Equipment Heating Equipment Hot (240 VAC) or Neutral (120 VAC) YH YL BH BL RH RL Figure 4: Typical Wiring for One-stage Heating and One-stage Cooling Hot Hot or Neutral Power Supply 2nd Stage Cooling Hot (240 VAC) ...

Setup and Adjustments

The indicator line on models with knobs denotes the thermostat dial setting. Concealed adjustment models have internal adjustment dials. Adjust concealed dial models (with the cover removed) by turning the dial and lining up the desired dial setting at a 9 o’clock position when the thermostat is vertical. Calibration The T25 thermostats are factory calibrated. Do not attempt field calibration. Set Screw High Temperature Stop Set Point Knob Figure 9: Setting the High Temperature Stop Commissioning the High Temperature Stop If a high temperature stop is desired, refer to Figure 9 and follow the procedure described below. 1. Turn t ...

Table 1: Electrical Ratings

Motor Ratings 120 V 208 V 240 V 277 V AC Full Load Amperes 6.0 3.5 3.0 - AC Locked Rotor Amperes 36.0 21.0 18.0 - Non-inductive Amperes 10.0 9.2 8.0 7.2 Pilot Duty—125 VA 24 to 277 VAC Note: When used as a two-circuit switch, the total connected load must not exceed 2,000 VA. Technical Data Product T25 Two-Stage Room Thermostat Output Single Pole, Double Throw (SPDT) Switches Two Enclosed Pennswitches Cover Cold Rolled Steel with “Tawny Silver” Finish Differential (Mechanical) Each Stage 0.7F° (0.4C°) Approximately Between Stages 3F° (1.7C°) Non-Adjustable Supply Voltage 24 V, 120 V, 208 V, 240 V, 277 V Mounting Wi ...

Thermostat PDF Instructions

Evosense public
MMA Evosense public
31.05.2026 2 pages

AB Markaryds Metallarmatur Tel. +46 (0)433 737 00 www.mma.se Installationsanvisning Assembly instruction Montageanleitung Instructions pour l’installation Instrucciones de uso Installasjonsveiledning Asennusohjeet Evosense public 4 8282 132_rev.1 170105 sid Device user manual for the MMA Evosense public Thermostat. It provides technical information on system configuration, installation guides, diagnostic information.

Uni-Kit 4350 Series
Robertshaw Uni-Kit 4350 Series
07.09.2026 2 pages

INSTALLATION DATA 4350 SERIES COMMERCIAL thERMOStAt BJ unI-kIt® DESCRIPTION The Robertshaw® 4350 Series Commercial Thermostat Uni-Kit® is designed specifically for heavy-duty commercial oven and griddle “applications. The High-Temperature thermostats wi Installation reference manual for the Robertshaw Uni-Kit 4350 Series Thermostat. It details operating modes and safety, troubleshooting, product specifications, operating guidelines.

WavePRO T2500
Peco WavePRO T2500
18.08.2026 20 pages

Benefi ts: • Reduced installation time • Reduced wiring costs • Energy cost savings • Scalability of network • Flexibility in fl oor planning • Ideal for building renovation PECO WavePRO™ Wireless System INSTALLATION GUIDE: T2500 THERMOSTAT AND Product usage manual for the Peco WavePRO T2500 Thermostat. It explains troubleshooting and device operation tips, wiring diagrams, hardware instructions, software updates.

33CS220-FS
Carrier 33CS220-FS
20.03.2026 8 pages

Setup and usage guide for the Carrier 33CS220-FS Thermostat. The guide focuses on installation, device calibration, daily usage.