Quick Start Guide

00825-0100-4022, Rev HB February 2019 Rosemount™ 4600 Oil & Gas Panel Pressure Transmitter

Quick Start Guide

NOTICE This guide provides basic guidelines for the Rosemount 4600 Oil & Gas Panel Pressure Transmitter. It does not provide instructions for diagnostics, maintenance, service, troubleshooting, explosion-proof, flameproof, or intrinsically safe (I.S.) installations. Refer to the Rosemount 4600 Reference Manual for more instr

Quick Start Guide

3 February 2019 1.0 Mount the transmitter 1.1 Electrical connection 1. Pull the leads through the threaded mounting hole in the panel wall. 2. Hand tighten the electrical connection into the mounting hole. 3. Using a wrench on the hex flat at the process connection, apply sufficient torque to prevent transmitter vibration. Do not exceed 100

Quick Start Guide

2.1 Power supply The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller, indicator, and related pieces. Note that the resistance of intrinsic safety barriers, if used, must be included. 3.

Quick Start Guide

5 February 2019 4.0 Trim the transmitter Note Transmitters are shipped from Emerson™ fully configured per request or by the factory default of full scale (span = upper range limit). 4.1 Zero trim A zero trim is a single-point adjustment to compensate mounting position and sealed gauge pressure effects. When performing a zero trim, ensure

Quick Start Guide

4.2 Using the Field Communicator 1. Vent the transmitter to atmosphere and connect Field Communicator. 2. At the main menu, input the Fast Key sequence. 3. Follow the commands to perform a zero trim. 4.3 Using the transmitter zero adjustment target 1. Vent the transmitter. 2. Set the 4 mA point by touching the magnetic end o

Quick Start Guide

7 February 2019 Configuration Use any HART® compliant master to communicate with and verify configuration of the Rosemount 4600. User-selected damping will affect the transmitter’s ability to respond to changes in the applied process. The damping value + response time must not exceed the loop requirements. Note DCS or safety logic solver

Quick Start Guide

Proof test This proof test will detect 90 percent of DU failures not detected by the Rosemount 4600 automatic diagnostics. 1. Conduct a loop test. On Field Communicator enter the Fast Key sequence 1,2,2. a. Enter the milliampere value representing a high alarm state and verify that the analog current reaches that value.(1) b