Emerson Rosemount 4600 Quick Start Manual
Text of the manual
Quick Start Guide
00825-0100-4022, Rev HB
February 2019
Rosemount™ 4600 Oil & Gas Panel
Pressure Transmitter
Quick Start Guide
NOTICE
This guide provides basic guidelines for the Rosemount 4600 Oil & Gas Panel Pressure Transmitter. It does not
provide instructions for diagnostics, maintenance, service, troubleshooting, explosion-proof, flameproof, or
intrinsically safe (I.S.) installations. Refer to the Rosemount 4600 Reference Manual for more instr
Quick Start Guide
3
February 2019
1.0
Mount the transmitter
1.1
Electrical connection
1. Pull the leads through the threaded mounting hole in the panel wall.
2. Hand tighten the electrical connection into the mounting hole.
3. Using a wrench on the hex flat at the process connection, apply sufficient
torque to prevent transmitter vibration. Do not exceed 100
Quick Start Guide
2.1
Power supply
The dc power supply should provide power with less than two percent ripple.
The total resistance load is the sum of the resistance of the signal leads and the
load resistance of the controller, indicator, and related pieces. Note that the
resistance of intrinsic safety barriers, if used, must be included.
3.
Quick Start Guide
5
February 2019
4.0
Trim the transmitter
Note
Transmitters are shipped from Emerson™ fully configured per request or by the factory
default of full scale (span = upper range limit).
4.1
Zero trim
A zero trim is a single-point adjustment to compensate mounting position and
sealed gauge pressure effects. When performing a zero trim, ensure
Quick Start Guide
4.2
Using the Field Communicator
1. Vent the transmitter to atmosphere and connect Field Communicator.
2. At the main menu, input the Fast Key sequence.
3. Follow the commands to perform a zero trim.
4.3
Using the transmitter zero adjustment target
1. Vent the transmitter.
2. Set the 4 mA point by touching the magnetic end o
Quick Start Guide
7
February 2019
Configuration
Use any HART® compliant master to communicate with and verify configuration
of the Rosemount 4600.
User-selected damping will affect the transmitter’s ability to respond to
changes in the applied process. The damping value + response time must not
exceed the loop requirements.
Note
DCS or safety logic solver
Quick Start Guide
Proof test
This proof test will detect 90 percent of DU failures not detected by the
Rosemount 4600 automatic diagnostics.
1. Conduct a loop test. On Field Communicator enter the Fast Key sequence
1,2,2.
a. Enter the milliampere value representing a high alarm state and verify
that the analog current reaches that value.(1)
b