Text of Alstom MX3EG1A Technical Manual

atic c Sy

Synch nchron roniz izer er TECHNICAL L MANUAL MDE/A133 3 2295 5 001 ABCD

MDE/A133 2295 001

MDE/A133 2295 001 MX3EG1A MX3EG1A SUMMARY SUMMARY 1. 1. TECHNICAL TECHNICAL DATA DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 2. 2. GENERAL GENERAL CHARACTERI
MDE/A133 2295 001 MX3EG1A 6. LCD MENU STRUCTURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 6.1 MAIN READING MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14 6.1.1 Changing dialogue language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
MDE/A133 2295 001 MX3EG1A 1. TECHNICAL DATA The device belongs to the Modulex 3 line, and processes with a numerical technique two phase voltages to provide the automatic synchronization besides several additional functions. The user's interface is available locally through the presence of a display unit and remotely through a LONWORKS(TM)b bus with a control and monitoring system. It is furthermore capable of dialoguing with a Personal Computer thr
MDE/A133 2295 001 MX3EG1A Voltage regulator parameters voltage regulation mode CPU: CONT-PULSE voltage regulation pulse time tupu: 0.10 ÷ 9.99 s voltage regulation pause time tupa: 0.10 ÷ 9.99 s by steps of 0.01 s ADDITIONAL SETTINGS bar TV primary rated voltage: 100 ÷ 1000000 V generator TV primary rated voltage: 100 ÷ 1000000 V by steps of: 1 V rated frequency fn: 50 o 60 Hz Auxiliary power supply versions MX3EG1A.1
MDE/A133 2295 001 MX3EG1A 2. GENERAL CHARACTERISTICS The device features a mechanical casing that is 4U in height and as wide as to allow up to 4 pieces to be accommodated in a 19" rack in addition to normal flush-mounting. The casing is made of hot-galvanized PVC-coated plate frame inside which the movable part that carries all the electronic circuits and the local interface slides on guides. The pull-out action is facilitated by special 'handles',
MDE/A133 2295 001 MX3EG1A 3.4 Load pulse and parallel command When none of the following thresholds: DUb, DUg, DU, Dfb, Dfg, Df, Dp is tripping, the protection sends a parallel command with a pulse duration equal to tc; the command is sent with a n advance time equal to tr (breaker trip time) compared to the expected Dp=0 phase difference instant: this to allow the breaker to be closed just when the voltages are in phase with each other. If after th
MDE/A133 2295 001 MX3EG1A 3.5.3 DB dead-bar mode ON-CHECK The device checks that the generator frequency and voltage lie within the limits defined by Dfb and DUb: if these do not lie within the mentioned limits, the device carries out all the adjusting operations necessary to make them lie within the range of values defined. The 'parallel breaker closing' command will be then sent. 3.6 Main and spare settings The device can store two groups of setti
MDE/A133 2295 001 MX3EG1A 4.3 LED signalling circuits The signalling circuits are made up of twelve LEDs (see fig. 3). Four LEDs are strictly assigned to previously established signalling functions: - green LED (Uaux) ON in the presence of power supply and correct feeder output voltage values - green LED (RUN) ON with fixed light in normal conditions and blinking light during setting change or test operations - red LED (RUN) ON with fixed light whe
MDE/A133 2295 001 MX3EG1A 4.13 Serial communication on LONWORKS (TM) bus In the version including the bus board, the device can communicate with a central monitoring and control system at a speed of 1.2 5 Mbaud. The connection to the field bus is made through terminals: 43 and 45. The communication board, which can even be added afterwards, is enabled only if the special jumper is provided in S6, and is disabled when the mentioned jumper is placed