PREV. SAFETY GROUND MUST BE CONNECTED OUT TEMP PROVE /DHW STAGE A STAGE B MENU FUNCTIONS SELECT enters menus or accepts changes ADJUST selects menu items or changes settings BACK returns to previous menu PREV./NEXT steps through stage status STAGE HELP NEXT PRESS TO SELECT BACK SYS= 125oF OD= 31oF ADJUST A1 A2 A3 A4 A5 A6 A7 A8 A9 A10 A11 A12 STAGE C DO NOT APPLY ANY VOLTAGE TO SENSOR TERMINALS B1 B2 B3 B4 B5 B6 NETWO ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

HT# 059299-00 A Content Content . . . . . . . . . . . . . . . . . . . . . . . . . 2 Multi-MOD Platinum Overview . . . . . . . . . . . . . . 3 Standard Features . . . . . . . . . . . . . . . . . . 3 Optional Features . . . . . . . . . . . . . . . . . . . 4 Modulat ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

3 HT# 059299-00 A Multi-MOD Platinum Overview The Multi-MOD Platinum is a multi-boiler modulating control. It uses PID logic in addition to overlapping the lead and lag boiler modulation, its patent logic, to achieve a smooth modulation and efficient system performance. It is capable of modulating 4 on board boilers. When used with extensions panels it can connect to a total o ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

HT# 059299-00 A Optional Features Internet Communication: The Internet communication option gives remote access to the control from any computer with a web browser. The access is through Heat-Timer ICMS web site. Internet ready controls have the capability to connect to a large number of network sensors. These sensors can be space, temperature, pressure, oil tank levels, a ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

5 HT# 059299-00 A Purge Boiler B 20% 100% 20% 20% 24% 20% Lead Boiler A remain at 20% until System Sensor exceeds Target Lag Boiler B remains at Ignition % while Lead Boiler A modulates down Decrease Modulation Boiler A Boiler B Normal Modulation Decrease When the load is reduced, the control will gradually decrease the lag boiler's modulation until it reaches its lowest firing ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

HT# 059299-00 A The starting reset ratio for most systems is the 1.00 (OD):1.00 (SYS) (Outdoor Temperature : Heating Water Temperature) ratio. This means that for every degree the outdoor temperature drops, the temperature of the heating water will increase one degree. The starting point of the ratio is adjustable, but comes factory set to 70°F Outdoor Temperature and 100°F ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

7 HT# 059299-00 A Initial Pilot Program Setting an Initial Pilot Program eases the installation and configuration of the Multi-MOD Platinum and gives the opportunity to use many of the energy saving features while providing comfort. The program should consist of the following: • Select the features that your system can utilize, • Making sure you are ordering the right co ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

HT# 059299-00 A Multi-MOD Platinum Function Chart MULTI-MOD Platinum MADE IN U.S.A. PREV. SAFETY GROUND MUST BE CONNECTED OUT TEMP PROVE /DHW STAGE A STAGE B MENU FUNCTIONS SELECT enters menus or accepts changes ADJUST selects menu items or changes settings BACK returns to previous menu PREV./NEXT steps through stage status STAGE HELP NEXT PRESS TO SELECT BACK SYS= 125oF ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

9 HT# 059299-00 A Multi-MOD Platinum Back Chart N 5V 8V CPU Board Battery Ethernet RS485 Main Board Control Stages A & B Control Stages C & D A1 G1 B1 A2 G2 B2 RS485 Communication Board (HT# 900234-20-XXX) Fuse Battery HT#020002-00 Ethernet (RJ45) connects to: • Internet • BACnet IP Green RS485 connects to: • MSI HUB interface RS485 connects to Extensions only. Cables are ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

HT# 059299-00 A ENCLOSED ENERGY MANAGEMENT EQUIPMENT LISTED 99RA LOCKOUT INPUTS B1 B2 B3 B4 B5 B6 B7 B8 B9 B10 B11 B12 B13 B14 B15 B16 E F G H I J K L MODUALTION OUTPUTS MODUALTION OUTPUTS C1 C2 C3 C4 C5 C6 C7 C8 C9 C10 C11 C12 C13 C14 C15 C16 C17 C18 C19 C20 C21 C22 C23 C24 - + + - + + - + + - + + MADE IN U.S.A. SAFETY GROUND MU ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

11 HT# 059299-00 A 1 2 3 4 5 6 7 8 On Control Stages 1 & 2 Control Stages 3 & 4 Control Stages 5 & 6 Control Stages 7 & 8 Modulating Output Cards: • 135Ω Output Card (HT# 900203-135) • Current and Volt Output Cards (HT# 900203-C/V) Fuse RS485 connects to (MMOD, HWRQ, or MPCQ Platinum) Dip Switches determine Extension number EXT1 Dip1=ON, DIP2=ON EXT2 Dip1=OFF, DIP2=ON Ex ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

HT# 059299-00 A Installation Mounting the Enclosure • Select a location near the equipment to be controlled. • The surface should be flat, sufficiently wide, and strong enough to hold the Multi-MOD. • Installation location should be away from extreme heat, cold, or humidity. • Remove the control from its enclosure by removing the top center screw and loosening ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

13 HT# 059299-00 A • The RS485 cable length must not exceed 3500 feet. • The RS485 cable must use one of the Platinum control’s enclosure side knockouts. Do not use bottom knockouts for communication cabling. • Connect the RS485 cable coming from the BACnet MSTP or Modbus network to the Black RS485 communication socket on the back of the control’s Communication ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

HT# 059299-00 A System Output Wiring (Terminals 3, 4) • The System output can be used to activate a pump, a pump starter, a combustion air damper, or other equipment. • The Multi-MOD Platinum activates the System output whenever there is a call for any of the stages. The System output remains energized whenever a stage is active. • The System output does not sour ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

15 HT# 059299-00 A Stage Output and Boiler Pump Wiring • To have the Multi-MOD Platinum operate the boilers and their pumps, use SPDT relays (Single-Pole Double-Throw) and TDR relays (Time-Delay relay). • The SPDT relay sends the activation signal from the Multi-MOD Platinum stage activation output to the boiler Interlock (TT) and its pump. • The TDR relay receives t ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

HT# 059299-00 A • Terminals C2, C5, C8, and C11 on the Multi-MOD Platinum must be connected to the modulation Signal (+) terminals on the burners. • Terminals C1, C4, C7, and C10 on the Multi-MOD Platinum must be connected to the modulation Common terminals on the burners. MADE IN U.S.A. SAFETY GROUND MUST BE CONNECTED B STAGE C B4 B5 B6 ROUTE SENSOR AND AUXILIARY WIR ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

17 HT# 059299-00 A Input Wiring Outdoor sensor • An outdoor sensor must be used when selecting Reset °F or Reset °C. The sensor is used to calculate the system target. In addition it is used in the outdoor Cutoff. See "Sensor Type" on page 26 and "Outdoor Cutoff Temperature" on page 32. • If an outdoor sensor is installed in any of the set point options, it will onl ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

HT# 059299-00 A • Attach the sensor wires to the Out Temp terminals (A11 and A12). Temperature sensors have no polarity. • Connect the shield to terminal A12 with one of the other sensor wires. Do not connect the shield at the sensor end. • The sensor wires can be extended up to 500’ using shielded 2-conductor cable (#18/2). MULTI-MOD Platinum MADE IN U.S.A. PR ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

19 HT# 059299-00 A Prove Wiring (Terminals A3, A4) Dry-Contact • The System Prove feature is provided to check the system component operation status before activating any stages. Prove must be selected from the Prove/DHW Startup option. See "Prove/DHW Mode" on page 28. • A typical use of this feature is to check for water flow before firing any boiler stages. When the ...

Multi-MOD Platinum with Space and Scheduling Installation and Operation Manual

HT# 059299-00 A Setback Wiring (EMS Input Terminals +, Signal) Dry-Contact • The Setback is used to reduce the system target when less load is required during the night or on the weekends when a building is unoccupied, but a minimum level of heat is still required. • To use the Setback, the EMS Input mode must be set to Setback. See "EMS Input Mode" on page 27. Also, ...