IDEC SMARTRELAY Operation & User’s Manual
Read Online
Read the IDEC SMARTRELAY Operation & User’s Manual online using the built-in PDF viewer.
Text of the manual
IDEC SmartRelay Manual
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
i
Legal information - Warning notice system
Legal information
Warning notice system
This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent
damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert
symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are
graded according to the degree of danger.
If more than one degree of danger is present, the warning notice representing the highest degree of danger will
be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to
property damage.
Qualified Personnel
The product/system described in this documentation may be operated only by personnel qualified for the specific
task in accordance with the relevant documentation, in particular its warning notices and safety instructions.
Qualified personnel are those who, based on their training and experience, are capable of identifying risks and
avoiding potential hazards when working with these products/systems.
Proper use of IDEC products
Note the following:
Copyright © IDEC CORPORATION All rights reserved
The reproduction, distribution or use of this document or its contents is not permitted without express written
authority. Offenders will be liable for damages. All rights reserved, in particular in the event of patents being
granted or the registration of a utility model or design.
Disclaimer of Liability
We have reviewed the contents of this publication to ensure consistency with the hardware and software
described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the
information in this publication is reviewed regularly and any necessary corrections are included in subsequent
editions.
DANGER
indicates that death or severe personal injury will result if proper precautions are not taken.
WARNING
indicates that death or severe personal injury may result if proper precautions are not taken.
CAUTION
indicates that minor personal injury can result if proper precautions are not taken.
NOTICE
indicates that property damage can result if proper precautions are not taken.
WARNING
IDEC products may only be used for the applications described in the catalog and in the relevant technical
documentation. If products and components from other manufacturers are used, these must be recommended
or approved by IDEC. Proper transport, storage, installation, assembly, commissioning, operation and
maintenance are required to ensure that the products operate safely and without any problems. The permissible
ambient conditions must be complied with. The information in the relevant documentation must be observed.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
ii
Preface
With IDEC SmartRelay you have acquired a logic module that meets the stringent quality
requirements of ISO 9001.
You can use IDEC SmartRelay in many fields of applications. Due to its high functionality and
easy operation, IDEC SmartRelay offers you the utmost efficiency for almost any application.
Purpose of this manual
This IDEC SmartRelay manual provides you with information about the creation of circuit
programs, about the installation and use of Base Modules with more enhanced features, the
FL1F-RD1 (Text Display with Ethernet interfaces), and IDEC SmartRelay expansion modules.
IDEC SmartRelay's place in information technology
The wiring information in your IDEC SmartRelay manual is also found in the IDEC
SmartRelay Product Info included with all devices. For further information on programming
the IDEC SmartRelay on your PC, refer to the Online Help for WindLGC.
WindLGC is IDEC SmartRelay programming software for PCs. It runs under Windows®
(including Windows XP®, Windows 7®, and Windows 8®). It helps you to get started with
IDEC SmartRelay and to write, test, print out and archive your programs, independent of
IDEC SmartRelay.
Guide
The manual contains the following chapters:
•
Getting started with IDEC SmartRelay
•
IDEC SmartRelay installation and wiring
•
Programming IDEC SmartRelay
•
IDEC SmartRelay functions
•
Web server
•
UDF (User-Defined Function)
•
Data Log
•
Configuring IDEC SmartRelay
•
Using memory cards
•
Security
•
IDEC SmartRelay software
•
Applications
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
iii
The manual also includes appendices A - F, which follow the chapters.
Valid range of this manual
The manual applies to devices of series FL1F.
New features of the IDEC SmartRelay
The following features are new for the IDEC SmartRelay FL1F devices:
•
Ethernet communication support by all Base Modules
Each Base Module is equipped with an RJ45 interface and a two-color status LED for
Ethernet communication.
•
New text display (FL1F-RD1) with enhanced features
–
The Text Display module is available with two Ethernet interfaces. These two Ethernet
interfaces can also function as a two-port switcher. You can connect the Text Display
with a Base Module, a PC, or another Text Display through the Ethernet interfaces.
Text Display can connect with different Base Modules through IP address selection.
–
Text Display provides a three-pin (P1, P2, and FE) terminal for power connection.
–
Text Display has three main menu commands available, respectively for the IP address
selection of a Base Module, the remote settings of the connected Base Module, and
the independent configuration of the Text Display.
•
Support of 6-line display and three backlight colors
Both the IDEC SmartRelay onboard display and Text Display support a 6-line character
display and three backlight colors (white/amber/red). The IDEC SmartRelay onboard
display can display a maximum of 16 Western European characters or 8 Asian characters
per line. Text Display can display a maximum of 20 Western European characters or 10
Asian characters per line.
•
Increased maximum I/O connections
IDEC SmartRelay supports a maximum of 24 digital inputs, 20 digital outputs, 8 analog
inputs and 8 analog outputs.
•
Built-in Web server in Base Modules
IDEC SmartRelay provides you with easy access through Internet browsers. With the Web
server function, you can access the Base Module using a connected device (PC, tablet or
smart phone) by entering the IP address of the IDEC SmartRelay module in the Web
browser of the connected device.
•
Enhanced functions added to special function blocks
–
Message texts: The IDEC SmartRelay support a 6-line message text display and
ticking messages, as well as message text display on the Web server. You can enble
the tick setting for each display line by setting the block parameters.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
iv
Preface
•
More memory markers for the creation of the circuit program
The IDEC SmartRelay supports 64 digital memory markers and 64 analog memory
markers. Some new special markers are described as follows:
–
M28: Enables the Display amber backlight
–
M29: Enables the Display red backlight
–
M30: Enables the Text Display amber backlight
–
M31: Enables the Text Display red backlight
•
Extended menu commands for diagnostics
With the extended menu commands for diagnostics, the IDEC SmartRelay provides a
facility for diagnosing software and hardware errors and viewing the error logs. You can
use these menu commands to troubleshoot and debug the IDEC SmartRelay system.
•
Curve representation of analog value changes
IDEC SmartRelay supports the graphical display of analog value changes in the form of a
trend curve on the onboard display. You can easily monitor each analog I/O in use by
means of the trend curves when IDEC SmartRelay is in RUN mode.
•
Micro SD card support
IDEC SmartRelay supports micro SD (Secure Digital) cards that support FAT32 file
system format. You can store and copy-protect a circuit program, with or without the data
log of process data, from IDEC SmartRelay to an SD card, or copy a circuit program from
the card to IDEC SmartRelay. The maximum capacity of micro SD card is 32 GB.
•
Enhanced Data Log function
IDEC SmartRelay supports a maximum of 20000 lines for each data log file stored on the
micro SD card. IDEC SmartRelay automatically creates a new data log file with a new
name on the micro SD card when the number of lines in the current file exceeds the
maximum number of lines.
Compatibility with previous IDEC SmartRelay series
IDEC SmartRelay device series are incompatible with any previous device series such as
FL1E series.
WindLGC version 8.0 or later is required to use IDEC SmartRelay FL1F. IDEC SmartRelay
FL1F cannot be programmed with WindLGC prior than version 8.0.
The circuit programs used with prior versions of IDEC SmartRelay, such as IDEC SmartRelay
FL1E, can be transferred to IDEC SmartRleay FL1F using WindLGC.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
v
Security information
IDEC provides products and solutions with industrial security functions that support the
secure operation of plants, solutions, machines, equipment and/or networks. They are
important components in a holistic industrial security concept. With this in mind, IDEC’
products and solutions undergo continuous development. IDEC recommends strongly that
you regularly check for product updates.
For the secure operation of IDEC products and solutions, it is necessary to take suitable
preventive action (e.g. cell protection concept) and integrate each component into a holistic,
state-of-the-art industrial security concept. Third-party products that may be in use should
also be considered.
Note
To protect WindLGC from any undesired manipulation when your PC suffers malicious
attacks from the Internet, IDEC strongly recommends you to install a whitelist tool such as
McAfee Application Control 6.1 on the PC.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
vi
Preface
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
vii
Preface......................................................................................................................................................... ii
1
Getting started with IDEC SmartRelay ........................................................................................................1
2
IDEC SmartRelay installation and wiring ..................................................................................................13
2.1
Modular IDEC SmartRelay setup............................................................................................... 15
2.1.1
Maximum IDEC SmartRelay network setup .............................................................................. 15
2.1.2
Maximum setup with expansion modules .................................................................................. 17
2.1.3
Setup with different voltage classes .......................................................................................... 18
2.1.4
Compatibility .............................................................................................................................. 19
2.2
Installing/removing IDEC SmartRelay ....................................................................................... 20
2.2.1
DIN rail mounting ....................................................................................................................... 21
2.2.2
Wall-mounting ............................................................................................................................ 23
2.2.3
Mounting the Text Display ......................................................................................................... 25
2.2.4
Labeling IDEC SmartRelay ........................................................................................................ 26
2.3
Wiring IDEC SmartRelay ........................................................................................................... 26
2.3.1
Connecting the power supply .................................................................................................... 27
2.3.2
Connecting the Text Display power supply ................................................................................ 29
2.3.3
Connecting IDEC SmartRelay inputs ......................................................................................... 29
2.3.4
Connecting outputs .................................................................................................................... 39
2.3.5
Connecting the Ethernet interface ............................................................................................. 43
2.4
Putting into operation................................................................................................................. 44
2.4.1
Powering on IDEC SmartRelay ................................................................................................. 44
2.4.2
Operating states ........................................................................................................................ 47
3
Programming IDEC SmartRelay ...............................................................................................................49
3.1
Connectors ................................................................................................................................ 50
3.2
Blocks and block numbers......................................................................................................... 52
3.3
From circuit diagram to IDEC SmartRelay program .................................................................. 55
3.4
The four golden rules for operating IDEC SmartRelay .............................................................. 57
3.5
Configuring menu access protection for IDEC SmartRelay....................................................... 59
3.6
Overview of IDEC SmartRelay menus....................................................................................... 61
3.7
Writing and starting the circuit program..................................................................................... 63
3.7.1
Selecting programming mode .................................................................................................... 63
3.7.2
The first circuit program ............................................................................................................. 64
3.7.3
Circuit program input ................................................................................................................. 65
3.7.4
Assigning a circuit program name ............................................................................................. 69
3.7.5
Password for circuit program protection .................................................................................... 70
3.7.6
Switching IDEC SmartRelay to RUN mode ............................................................................... 74
3.7.7
Second circuit program .............................................................................................................. 78
3.7.8
Deleting a block ......................................................................................................................... 83
3.7.9
Deleting block groups ................................................................................................................ 84
3.7.10
Correcting programming errors .................................................................................................. 86
3.7.11
Selecting analog output values for RUN/STOP transition ......................................................... 86
3.7.12
Defining the type of analog outputs ........................................................................................... 88
3.7.13
Setting the power-on delay of IDEC SmartRelay ....................................................................... 89
3.7.14
Clearing the circuit program and password ............................................................................... 89
Table of contents
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
viii
Table of contents
3.7.15
Summertime/wintertime conversion .......................................................................................... 90
3.8
Configuring additional functions for IDEC SmartRelay.............................................................. 94
3.8.1
Configuring network settings ..................................................................................................... 94
3.8.2
Configuring a UDF (User-Defined Function) ............................................................................. 96
3.8.3
Configuring the Data Log ........................................................................................................... 96
3.8.4
Viewing network inputs/outputs ................................................................................................. 97
3.8.5
Changing IDEC SmartRelay to master/slave mode .................................................................. 98
3.8.6
Diagnosing errors from IDEC SmartRelay ............................................................................... 100
3.9
Memory space and circuit program size.................................................................................. 105
4
IDEC SmartRelay functions ....................................................................................................................111
4.1
Constants and connectors....................................................................................................... 111
4.2
Basic functions list - GF........................................................................................................... 116
4.2.1
AND ......................................................................................................................................... 117
4.2.2
AND with edge detection ......................................................................................................... 118
4.2.3
NAND (not AND) .................................................................................................................... 118
4.2.4
NAND with edge detection ...................................................................................................... 119
4.2.5
OR ........................................................................................................................................... 120
4.2.6
NOR (not OR) ......................................................................................................................... 121
4.2.7
XOR (exclusive OR) ................................................................................................................ 122
4.2.8
NOT (Negation, Inverter) ......................................................................................................... 122
4.3
Special functions ..................................................................................................................... 123
4.3.1
Designation of the inputs ......................................................................................................... 123
4.3.2
Time response ......................................................................................................................... 124
4.3.3
Backup of the real-time clock .................................................................................................. 125
4.3.4
Retentivity ................................................................................................................................ 125
4.3.5
Parameter protection ............................................................................................................... 125
4.3.6
Calculating the gain and offset of analog values ..................................................................... 126
4.4
Special functions list - SF ........................................................................................................ 127
4.4.1
On-delay .................................................................................................................................. 132
4.4.2
Off-delay .................................................................................................................................. 136
4.4.3
On-/off-delay ............................................................................................................................ 138
4.4.4
Retentive on-delay ................................................................................................................... 140
4.4.5
Interval time-delay relay/Pulse output ..................................................................................... 142
4.4.6
Edge-triggered interval time-delay relay .................................................................................. 144
4.4.7
Asynchronous pulse generator ................................................................................................ 146
4.4.8
Random generator ................................................................................................................... 148
4.4.9
Stairwell light switch ................................................................................................................ 150
4.4.10
Dual-function switch ................................................................................................................ 152
4.4.11
Seven-day time switch ............................................................................................................. 155
4.4.12
Twelve-month time switch ....................................................................................................... 158
4.4.13
Astronomical clock ................................................................................................................... 163
4.4.14
Stopwatch ................................................................................................................................ 166
4.4.15
Up/down counter ..................................................................................................................... 168
4.4.16
Operating hours counter .......................................................................................................... 171
4.4.17
Frequency trigger .................................................................................................................... 175
4.4.18
Analog trigger .......................................................................................................................... 178
4.4.19
Analog differential trigger ......................................................................................................... 181
4.4.20
Analog comparator .................................................................................................................. 183
4.4.21
Analog watchdog ..................................................................................................................... 188
4.4.22
Analog amplifier ....................................................................................................................... 191
4.4.23
Latching relay .......................................................................................................................... 193
4.4.24
Current impulse relay .............................................................................................................. 194
4.4.25
Message texts ......................................................................................................................... 196
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Table of contents
IDEC SmartRelay Manual
ix
4.4.26
Softkey ..................................................................................................................................... 205
4.4.27
Shift register ............................................................................................................................. 207
4.4.28
Analog multiplexer ................................................................................................................... 209
4.4.29
Analog ramp control ................................................................................................................. 212
4.4.30
PI controller .............................................................................................................................. 216
4.4.31
Pulse width modulator (PWM) ................................................................................................. 221
4.4.32
Analog Math ............................................................................................................................ 224
4.4.33
Analog Math error detection .................................................................................................... 227
4.4.34
Analog filter .............................................................................................................................. 229
4.4.35
Max/Min ................................................................................................................................... 231
4.4.36
Average value .......................................................................................................................... 235
5
Web server ..............................................................................................................................................237
5.1
Enabling the Web server ......................................................................................................... 237
5.2
Logging on to the Web server.................................................................................................. 238
5.3
Viewing IDEC SmartRelay system information........................................................................ 240
5.4
Operating the virtual module on the Web server ..................................................................... 240
5.5
Viewing and editing variable memory tables ........................................................................... 245
5.6
Logging off from the Web server ............................................................................................. 245
6
UDF (User-Defined Function) .................................................................................................................247
7
Data log ...................................................................................................................................................251
8
Configuring IDEC SmartRelay ................................................................................................................253
8.1
Selecting parameter assignment mode ................................................................................... 253
8.1.1
Parameters .............................................................................................................................. 255
8.1.2
Selecting the parameters ......................................................................................................... 255
8.1.3
Modifying parameters .............................................................................................................. 256
8.2
Setting the default values for IDEC SmartRelay...................................................................... 258
8.2.1
Setting the time of day and date .............................................................................................. 259
8.2.2
Setting the display contrast and backlight choice .................................................................... 261
8.2.3
Setting the menu language ...................................................................................................... 263
8.2.4
Setting the number of AIs in IDEC SmartRelay ....................................................................... 264
8.2.5
Setting the start screen ............................................................................................................ 265
9
Using memory cards ...............................................................................................................................267
9.1
Formatting micro SD cards...................................................................................................... 267
9.2
Inserting and removing the card from IDEC SmartRelay......................................................... 269
9.3
Copying data from IDEC SmartRelay to the card.................................................................... 270
9.4
Copying data from the card to IDEC SmartRelay.................................................................... 271
10
Security ...................................................................................................................................................273
10.1
Network access security.......................................................................................................... 273
10.2
Program access security ......................................................................................................... 275
10.2.1
Program password protection .................................................................................................. 275
10.2.2
Program copy protection .......................................................................................................... 275
10.3
Menu access security .............................................................................................................. 276
11
IDEC SmartRelay software .....................................................................................................................277
11.1
IDEC SmartRelay software...................................................................................................... 277
11.2
Connecting IDEC SmartRelay to a PC .................................................................................... 280
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
x
Table of contents
12
Applications .............................................................................................................................................281
A
Technical data .........................................................................................................................................283
A.1
General technical data............................................................................................................. 283
A.2
Technical data: FL1F-B12RCC/H12RCC ................................................................................ 285
A.3
Technical data: FL1F-M08C2R2 ............................................................................................. 287
A.4
Technical data: FL1F-H12SCD ............................................................................................... 289
A.5
Technical data: FL1F-M08B1S2.............................................................................................. 290
A.6
Technical data: FL1F-H12RCA/B12RCA ................................................................................ 292
A.7
Technical data: FL1F-M08D2R2 ............................................................................................. 294
A.8
Technical data: FL1F-B12RCE/H12RCE, FL1F-M08B2R2..................................................... 296
A.9
Switching capacity/service life of the relay outputs ................................................................. 298
A.10
Technical data: FL1F-J2B2 ..................................................................................................... 299
A.11
Technical data: FL1F-K2BM2.................................................................................................. 300
A.12
Technical data: IDEC SmartRelay Power 24 V ....................................................................... 301
A.13
Technical data: FL1F-RD1 (Text Display with Ethernet interfaces)......................................... 301
B
Determining the cycle time ......................................................................................................................303
C
IDEC SmartRelay without display
("IDEC SmartRelay Pure") ......................................................................................................................305
D
IDEC SmartRelay menu structure ...........................................................................................................307
D.1
Base Module............................................................................................................................ 307
D.1.1
Menu overview ........................................................................................................................ 307
D.1.2
Main menu ............................................................................................................................... 307
D.1.3
Programming menu ................................................................................................................. 308
D.1.4
Card menu ............................................................................................................................... 308
D.1.5
Setup menu ............................................................................................................................. 309
D.1.6
Network menu ......................................................................................................................... 310
D.1.7
Diagnostics menu .................................................................................................................... 310
D.1.8
Start menu ............................................................................................................................... 311
D.2
Text Display............................................................................................................................. 312
D.2.1
Menu overview ........................................................................................................................ 312
D.2.2
Main menu ............................................................................................................................... 313
D.2.3
BM selection menu .................................................................................................................. 314
D.2.4
BM settings menu .................................................................................................................... 314
D.2.5
Text Display settings menu ..................................................................................................... 316
E
Type numbers .........................................................................................................................................319
F
Abbreviations ..........................................................................................................................................321
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Table of contents
IDEC SmartRelay Manual
xi
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
1
Getting started with IDEC SmartRelay
Here's IDEC SmartRelay
IDEC SmartRelay is a universal logic module made by IDEC that integrates:
•
Controls
•
Operator and display panel with background lighting
•
Power supply
•
Interface for expansion modules
•
Interface for a micro SD card
•
Interface for an optional text display (TDE) module
•
Pre-configured standard functions, for example, on- and off-delays, current impulse relay
and softkey
•
Timers
•
Digital and analog memory markers
•
Inputs and outputs, according to the device type
IDEC SmartRelay additionally integrates the following components:
•
Interfaces for Ethernet communication
•
FE (Functional Earth) terminal for connecting to earth ground
•
One LED for indicating Ethernet communication status
What IDEC SmartRelay can do for you
IDEC SmartRelay offers solutions for domestic and installation engineering applications such
as stairwell lighting, external lighting, sun blinds, shutters, shop window lighting and more. It
can also offer solutions for switch cabinet engineering, as well as for mechanical and
apparatus engineering such as gate control systems, air-conditioning systems, and rainwater
pumps.
You can also use IDEC SmartRelay to implement special control systems in conservatories or
greenhouses, for control signal processing and for distributed local controlling of machines
and processes.
Special versions without operator panel and display unit are available for series production
applications in installation engineering.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Getting started with IDEC SmartRelay
IDEC SmartRelay Manual
2
Which devices are available?
Base Modules are available in two voltage classes:
•
Class 1 ≤ 24 V, i.e. 12 VDC, 24 VDC, 24 VAC
•
Class 2 > 24 V, i.e. 100 VAC/VDC to 240 VAC/VDC
Base Modules are available in two versions:
•
Base Modules (version with display): 8 inputs and 4 outputs
•
Base Modules (version without display): 8 inputs and 4 outputs
Each module has an expansion interface and an Ethernet interface and provides 44 pre-
configured standard and special function blocks for the creation of your circuit program.
Which expansion modules are available?
•
FL1F-M08... digital modules are available for operation with 12 VDC, 24 VAC/VDC and
100 VAC/VDC to 240 VAC/VDC, and are equipped with four inputs and four outputs.
•
IDEC SmartRelay analog modules are available for operation with 24 VDC and some with
12 VDC, depending on the specific module. Each is equipped with two analog inputs or
two analog outputs.
Each digital/analog module has two expansion interfaces for connecting additional modules.
Which display modules are available?
•
Base Modules
•
Text Display
Features of the Text Display
The Text Display is available for the Base Modules. It provides an additional display that is
wider than the Base Module. It has four function keys that you can program in your circuit
program as inputs. Like the IDEC Base Module, it has four cursor keys, an ESC key and an
Enter key that you can also program in your circuit program and use for navigation on the
Text Display.
You can create and download a power-up screen for the Text Display from WindLGC. This
screen displays briefly when you initially power on the Text Display. You can also upload the
power-up screen from the Text Display to WindLGC.
The Text Display provides three main menu commands, respectively for the IP address
selection of a Base Module, the remote settings of the connected Base Module, and the
independent configuration of the Text Display. The menus for the Text Display are shown in
Appendix "Text Display (Page 312)".
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
3
Getting started with IDEC SmartRelay
It's your choice
The various Base Modules, expansion modules, and Text Display offer you a highly flexible
and adaptive system to suit your specific tasks.
The IDEC SmartRelay system offers you many solutions for small domestic installations,
simple automation tasks, and even complex engineering tasks involving its integration into a
bus system.
Note
You can only use expansion modules of the same voltage as the Base Module. Mechanical
encoding pins in the housing prevent you from connecting devices of a different voltage
class.
Exception: The interface on the left side of an analog module is galvanically isolated. These
types of expansion modules can therefore be connected to devices of a Setup with different
voltage classes (Page 18).
A Text Display has two Ethernet interfaces. You can connect each interface to a Base
Module, a PC, or another Text Display.
Each Base Module supports the following connections for the creation of the circuit program,
regardless of the number of connected modules:
•
Digital inputs I1 to I24
•
Analog inputs AI1 to AI8
•
Digital outputs Q1 to Q20
•
Analog outputs AQ1 to AQ8
•
Digital memory markers blocks M1 to M64:
–
M8: Startup marker
–
M25: Backlight marker: onboard display white
–
M26: Backlight marker: Text Display white
–
M27: Message text character set marker
–
M28: Backlight marker: onboard display amber
–
M29: Backlight marker: onboard display red
–
M30: Backlight marker: Text Display amber
–
M31: Backlight marker: Text Display red
•
Analog memory markers blocks: AM1 to AM64
•
Shift register bits: S1.1 to S4.8 (32 shift register bits)
•
4 cursor keys
•
Blank outputs: X1 to X64
IDEC SmartRelay additionally supports the display of the following network digital/analog
inputs and outputs if you have previously configured them in the circuit program in WindLGC
V8.0 and downloaded the program to the IDEC SmartRelay:
•
64 network digital inputs: NI1 to NI64
•
32 network analog inputs: NAI1 to NAI32
•
64 network digital outputs: NQ1 to NQ64
•
16 network analog outputs: NAQ1 to NAQ16
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Getting started with IDEC SmartRelay
IDEC SmartRelay Manual
4
The IDEC SmartRelay structure
Power supply
ཱ
Inputs
ི
Outputs
ཱི
FE terminal
ུ
R-45 interface, for connection to Ethernet (10/100 Mbit/s)
ཱུ
Ethernet communication status LED
ྲྀ
Micro SD card slot
ཷ
LCD (only for version with display) (Note 1)
ླྀ
Control panel (only for version with display)
ཹ
Expansion interface
ེ
Mechanical coding sockets
ཻ
Standard DIN rail
ོ
Version number
(Example:
represents Version 1.)
H1:
Version with display: 55 mm
Version without display: 53 mm
H2:
Version with display: 60 mm
Version without display: 58 mm
Note 1:
For version without display, LCD is replaced by RUN/STOP LED.
,'(&6PDUW5HOD\)/)
)/)+5&&
+
+
ESC
OK
AC/DC 100...240V INPUT
Q1
L1
1
2
1
2
1
2
1
2
I1
I2
I3
I4
I5
I6
I7
I8
N
Q2
Q3
Q4
IE(LAN)
MAC ADDRESS
OUTPUT 4xRELAY/10A
LAN
$OOGLPHQVLRQVLQPP
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
5
Getting started with IDEC SmartRelay
Power supply
ཱ
Inputs
ི
Outputs
ཱི
RUN/STOP LED
ུ
Expansion interface
ཱུ
Mechanical coding pins
ྲྀ
Mechanical coding sockets
ཷ
Slide
ླྀ
Standard DIN rail
ཹ
Version number
Power supply
ཱ
Inputs
ི
Outputs
ཱི
RUN/STOP LED
ུ
Expansion interface
ཱུ
Mechanical coding pins
ྲྀ
Mechanical coding sockets
ཷ
Slide
ླྀ
Standard DIN rail
ཹ
Version number
)/)0&5
OUTPUT 4x RELAY/5A
AC/DC 100...240V INPUT 4xAC/DC
RUN/STOP
L1
I1
I2
I3
I4
N
1
2
1
2
1
2
1
2
Q1
Q2
Q3
Q4
$OOGLPHQVLRQVLQPP
)/)0%5
OUTPUT 4x RELAY/5A
DC 12/24V INPUT 4x DC
RUN/STOP
L+
I1
I2
I3
I4
M
1
2
1
2
1
2
1
2
Q1
Q2
Q3
Q4
$OOGLPHQVLRQVLQPP
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Getting started with IDEC SmartRelay
IDEC SmartRelay Manual
6
FL1F--2B2
FL1F-.2BM2 (0 ... 10 VDC or 0/4 ... 20 mA)
Power supply
ཱ
Inputs
ི
RUN/STOP LED
ཱི
Expansion interface
ུ
Mechanical coding pins
ཱུ
Mechanical coding sockets
ྲྀ
Slide
ཷ
FE terminal
ླྀ
Standard DIN rail
ཹ
Version number
Power supply
ཱ
Outputs
ི
RUN/STOP LED
ཱི
Expansion interface
ུ
Mechanical coding pins
ཱུ
Mechanical coding sockets
ྲྀ
Slide
ཷ
FE terminal
ླྀ
Standard DIN rail
ཹ
Version number
INPUT 2x (0...10V/0...20mA)
DC 12/24V
RUN/STOP
L+
I1
I2
M1
M2
U1
U2
L+
M
M
$OOGLPHQVLRQVLQPP
OUTPUT 2x (0...10V or 0/4...20mA)
DC 24V
RUN/STOP
L+
U1+
U2+
M1
M2
I1
I2
L+
M
M
$OOGLPHQVLRQVLQPP
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
7
Getting started with IDEC SmartRelay
FL1F-RD1
The Text Display includes a wider display area than onboard display. It includes four
programmable cursor keys, four programmable function keys, an ESC key, and an ENTER
key. You use the Ethernet cable to connect from the Ethernet interface on the right side of the
Text Display to the Ethernet interface on the Base Module.
How to identify the IDEC SmartRelay
The IDEC SmartRelay identifier informs you of various properties.
Base module
FL1F- ①②③④⑤
①B: Base module without display
H: Base module with display
②Number of Inputs and Outputs
③R: Relay output
S: Tr. (source) output
④C: With clock
⑤D: 24V DC
E: 12/24V DC
A: 24V AC/DC
C: 100...240V AC/DC
Expansion module
Digital module
FL1F-M ①②③④
①Number of Inputs and Outputs
②B1: 24V DC B2: 12/24V DC
C2: 100...240V AC/DC D2: 24V AC/DC
③S: Tr. (source) output R: Relay output
④Terminal type 2: non-removable terminal
①
Power supply
②
Ethernet interfaces
ཱ
$OOGLPHQVLRQVLQPP
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Getting started with IDEC SmartRelay
IDEC SmartRelay Manual
8
Analog input module
FL1F-J ①②③
①Number of Inputs
②Resolution B: 10bit
③Terminal type 2: non-removable terminal
Analog output module
FL1F-K ①②③④
①Number of Outputs
②Resolution B: 10bit
③M: 0 ... 10V, 0/4 ... 20 mA
④Terminal type 2: non-removable terminal
Text Display
FL1F- ①②
①RD: Remote Display
②Version type
Symbols
Version with display unit is equipped with 8 inputs, 4 outputs and 1 Ethernet interface.
Version without display unit is equipped with 8 inputs, 4 outputs and 1 Ethernet interface.
The digital module is equipped with 4 digital inputs and 4 digital outputs.
The analog module is equipped with 2 analog inputs or 2 analog outputs, according to the
device type.
The Text Display module is equipped with 2 Ethernet interfaces.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
9
Getting started with IDEC SmartRelay
Versions
The following IDEC SmartRelay versions are available:
Expansion modules
The following expansion modules can be connected to IDEC SmartRelay:
Symbol
Designation
Supply voltage
Inputs
Outputs
Properties
FL1F-H12RCE
12/24VDC
8 digital 1)
4 relays
(10 A)
FL1F-H12RCC
100 VAC/VDC to
240 VAC/VDC
8 digital
4 relays
(10 A)
FL1F-H12SCD
24 VDC
8 digital 1)
4 solid state
24 V/0.3 A
FL1F-H12RCA 3)
24 VAC/VDC
8 digital
4 relays
(10 A)
FL1F-B12RCE
12/24 VDC
8 digital 1)
4 relays
(10 A)
no display unit
no keyboard
FL1F-B12RCA 3)
24 VAC/VDC
8 digital
4 relays
(10 A)
no display unit
no keyboard
FL1F-B12RCC 2)
100 VAC/VDC to
240 VAC/VDC
8 digital
4 relays
(10 A)
no display unit
no keyboard
1)
Of those can be used alternatively: 4 analog inputs (0 V to 10 V) and 4 fast digital inputs.
2)
100-240 VAC/VDC versions: AC input group has two groups consisting of 4 inputs each. Each input
within a group must be connected to the same phase. It is possible to interconnect groups with a
different phase.
3) The digital inputs can be operated with P or N action.
Symbol
Name
Power supply
Inputs
Outputs
FL1F-M08B2R2
12/24 VDC
4 digital
4 relays (5 A)
FL1F-M08B1S2
24 VDC
4 digital
4 solid state 24 V/0.3 A
FL1F-M08D2R2 3)
24 VAC/VDC
4 digital
4 relays (5 A)
FL1F-M08C2R2
100 VAC/VDC to
240 VAC/VDC
4 digital 1)
4 relays (5 A)
FL1F-J2B2
12/24 VDC
2 analog
0 V to 10 V or
0/4 mA to 20 mA 2)
None
FL1F-K2BM2
24 VDC
None
2 analog
0 VDC to 10 VDC or
0/4 mA to 20 mA 4)
1) Different phases are not allowed within the inputs.
2) 0 V to 10 V, 0/4 mA to 20 mA can be connected optionally.
3) Digital inputs can be operated either with P or with N action.
4) 0 V to 10 V, 0/4 mA to 20 mA can be connected optionally.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Getting started with IDEC SmartRelay
IDEC SmartRelay Manual
10
Text display module
The following FL1F-RD1 module is available:
Certification and approvals
IDEC SmartRelay is certified to UL/c-UL and FM.
•
UL/c-UL Haz. Loc.
Underwriters Laboratories Inc. (UL) to
- UL 508 (Industrial Control Equipment)
- CSA C22.2 No. 142 (Process Control Equipment)
- ANSI/ISA 12.12.01 (Hazardous Location)
- CSA C22.2 No.213 (Hazardous Location)
APPROVED for use in
Class I, Division 2, Group A, B, C, D
Class I, Zone 2, Group IIC
•
FM Approval (US Approval and Canada Approval)
FM approvals (FM) to
- Approval Standard Class Number 3611, 3600, 3810
- CSA C22.2 No. 94
- CSA C22.2 No. 213
- CSA C22.2 No. 1010-1
- CSA C22.2 No. 60529
APPROVED for use in
- Class I, Division 2, Groups A, B, C, D
- Class I, Zone 2, Groups IIC
IDEC SmartRelay is issued with the CE certification of conformity. It is compliant with
following standards:
•
EN 61131-2
•
61000-6-1, -2, -3, -4
•
EN 50581
Marine certification has been requested. (As of September, 2015)
•
ABS (American Bureau of Shipping)
•
BV (Bureau Veritas)
•
DNV (Det Norske Veritas)
•
GL (Germanischer Lloyd)
•
LRS (Lloyds Register of Shipping)
•
Class NK (Nippon Kaiji Kyokai)
IDEC SmartRelay modules are therefore suitable for use in industrial and residential areas.
Use in Class I, Division 2, Group A, B, C and D locations or in non-hazardous locations is
supported.
Symbol
Name
Supply voltage
Display
FL1F-RD1
24 VAC/VDC
12 VDC
LCD (160 x 96)
6-row display
Note
You will find current approvals on the rating plate of the relevant module.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
11
Getting started with IDEC SmartRelay
Marine certification requires following conditions.
•
All 12/24VDC modules are only to be used with 24VDC power supply.
•
24V power supply line are to be protected by surge protective device ((order No. 918 402/
918 422 manufactured by DEHN+SÖHNE GmbH CO.) or equivalent).
•
When using IDEC SmartRelay FL1F in bridge and deck zones with filter ((B84113-C-B-30
manufactured by EPCOS AG) or equivalent).
Please contact us if there are any questions such as about the environment in which IDEC
SmartRelay is used.
ID for Australia
Recycling and Disposal
You can fully recycle IDEC SmartRelay devices due to their low-pollutant equipment. Contact
a certified electronic waste disposal center for environmentally acceptable recycling and
disposal of your old devices.
Our products carrying the label shown at the side are compliant with AS/NZS
CISPR11:2011.
WARNING
Explosion hazard
Do not disconnect equipment while the circuit is live or unless the area is konwn to be free of
ignitable concentrations.
Substitution of any components can impair suitability for Class I, Division 2. Combinations of
equipment are subject to investigation by the local authority having jurisdiction at the time of
the installation.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Getting started with IDEC SmartRelay
IDEC SmartRelay Manual
12
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
13
IDEC SmartRelay installation and wiring
General guidelines
Note the following guidelines for installing and wiring your IDEC SmartRelay:
•
Always ensure that the wiring of your IDEC SmartRelay is compliant with current rules and
standards. Also, conform with all national and regional regulations when you install and
operate the devices. For information on standards and regulations that apply to your
specific case, contact your local authorities.
•
Always switch off power before you wire or install/remove a module.
•
Always use cables with appropriate conductor cross-sections for the relevant current. You
can wire IDEC SmartRelay with cable conductor cross-sections (Page 26) from 1.5 mm2 to
2.5 mm2.
•
Do not exceed the screw torque of the terminals. Range of torques: 0.5 Nm to 0.6 Nm.
•
Keep the cabling as short as possible. If longer cables are necessary, use shielded
versions. Always route your cables in pairs; that it, one neutral conductor plus one phase
conductor or signal line.
•
Always keep separate:
–
The AC wiring
–
High-voltage DC circuits with high-frequency switching cycles
–
Low-voltage signal wiring
•
Install wires with appropriate strain relief.
•
Provide a suitable lightning surge arrester for cables installed in hazardous areas.
•
Do not connect an external power supply in parallel to the output load of a DC output. This
could develop a reverse current at the output if you have not installed a diode or similar
barrier device.
•
Be sure to use only certified components to ensure reliable functioning of equipment.
Note
Only skilled personnel who are familiar with and follow general engineering rules, relevant
regulations and standards must install IDEC SmartRelay devices.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
IDEC SmartRelay Manual
14
What you must note when installing
IDEC SmartRelay is designed for fixed and enclosed installation in the housing or the control
cabinet.
Safety of electronic control equipment
Introduction
The notes below apply regardless of the type or manufacturer of the electronic control.
Approach for reliability
Maximum reliability of IDEC SmartRelay devices and components is achieved by
implementing extensive and cost-effective measures during development and manufacture.
This includes the following:
•
Use of high-quality components
•
Design of all circuits for worst-case scenarios
•
Systematic and computer-aided testing of all components
•
Burn-in of all large-scale integrated circuits (for example, processors and memory)
•
Prevention of static charge when handling MOS ICs (Metal Oxide Semiconducor
Integrated Circuits)
•
Visual checks at different stages of manufacture
•
Continuous heat-run test at elevated ambient temperature over a period of several days
•
Careful computer-controlled final testing
•
Statistical evaluation of all returned systems and components to enable the immediate
initiation of suitable corrective measures
•
Monitoring of major control components, using online tests (cyclic interrupt for the CPU, etc.)
These measures are referred to as basic measures.
WARNING
IDEC SmartRelay is designed for installation in a cabinet. Do not install IDEC SmartRelay
outside a cabinet. If IDEC SmartRelay is installed outside a cabinet, severe personal injury or
death or damage to equipment may be caused due to unexpected operations.
You can operate IDEC SmartRelay from the front panel at any time.
2.1 Modular IDEC SmartRelay setup
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
15
IDEC SmartRelay installation and wiring
2.1 Modular IDEC SmartRelay setup
Carrying out tests
You must ensure safety in your plant.
Before finally commissioning a system, carry out complete functional testing as well as all the
necessary safety testing.
Also, test for any predictable faults that can occur. This means that you will avoid any danger
to the plant or to people during operation.
Risks
In all cases where the occurrence of failures can result in material damage or injury to persons,
take special measures to enhance the safety of the installation - and the application. System-
specific and special regulations exist for such applications. Follow these regulations exactly
when installing the control system (for example, VDE 0116 for burner control systems).
For electronic control equipment with a safety function, the measures that you must take to
prevent or rectify faults are based on the risks involved in the installation. Beyond a certain
degree of hazard the basic measures mentioned above are not sufficient and you must take
additional safety measures for the controller.
Important information
Follow the instructions in the operating manual exactly. Incorrect handling can render measures
intended to prevent dangerous faults ineffective, or generate additional sources of danger.
2.1
Modular IDEC SmartRelay setup
2.1.1
Maximum IDEC SmartRelay network setup
Maximum IDEC SmartRelay network setup
IDEC SmartRelay supports FL1F Communication over a 10/100 Mbit/s TCP/IP Ethernet
network.
An IDEC SmartRelay can support the following network connections:
•
A maximum of 16 TCP/IP-based FL1F Communication connections with the following
devices:
–
Additional IDEC SmartRelay
There are two types of connections available for FL1F Communication, static connection
and dynamic connection. For the static connection, the server reserves the required
resources for the connected client to ensure stable data transfer. For the dynamic
connection, the server responds to a communication request only when free resources are
available. You can configure the static/dynamic connections as required, for example, n
static connections and 16-n dynamic connections. IDEC SmartRelay supports a maximum
of eight static connections.
•
A maximum of one TCP/IP Ethernet connection with the Text Display. A Text Display
module can connect with different Base Modules through IP address selection, but can not
communicate with more than one Base Module at the same time.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.1 Modular IDEC SmartRelay setup
IDEC SmartRelay Manual
16
ವ
A maximum of one TCP/IP Ethernet connection between a Base Module and a PC with
:indLGC V8.0 installed.
A typical IDEC SmartRelay network setup is shown below:
Note
IDEC SmartRelay Manual
17
IDEC SmartRelay installation and wiring
2.1 Modular IDEC SmartRelay setup
2.1.2
Maximum setup with expansion modules
IDEC SmartRelay supports a maximum of Getting started with IDEC SmartRelay (Page 1).
You can achieve the maximum setup in different ways as shown below:
Maximum setup of an IDEC SmartRelay with analog inputs onboard - four in use
Base Module, 4 digital modules and 6 analog modules (example)
Maximum setup of an IDEC SmartRelay with analog inputs onboard - two in use
Base Module, 4 digital modules and 7 analog modules (example)
Maximum setup of an IDEC SmartRelay without analog inputs onboard (FL1F-H12RCA/B12RCA and
FL1F-H12RCC/B12RCC)
Base Module, 4 digital modules and 8 analog modules (example)
For FL1F-H12RCE/B12RCE and FL1F-H12SCD modules, you can configure whether the
module uses zero, two or four of the four possible analog inputs. AI inputs are numbered
consecutively depending on how many you configure the IDEC SmartRelay Base Module to
use. If you configure two inputs, they are numbered AI1 and AI2, and correspond to the I7 and
I8 input terminals. Subsequent AI expansions modules would begin numbering at AI3. If you
configure four inputs, they are numbered AI1, AI2, AI3, and AI4, and correspond to I7, I8, I1,
and I2 in that order. Subsequent AI expansions modules would begin numbering at AI5. See
topics "Constants and connectors (Page 111)" and "Setting the number of AIs in IDEC
SmartRelay (Page 264)".
$,$,$,$,
,,,,,,
)/)
.%0
$4$4
)/)
.%0
$4$4
)/)
.%0
$4$4
44
)/)
0
)/)
0
)/)
0
)/)
0
44
44
44
,,
,,
,,
,,
)/)
-%
$,$,
$,$,
)/)
-%
)/)
.%0
$4$4
44
,'(&6PDUW
5HOD\%DVH
0RGXOH
,,,,,,
$,$,
)/)
.%0
$4$4
)/)
.%0
$4$4
)/)
.%0
$4$4
44
)/)
-%
)/)
0
)/)
0
)/)
0
)/)
0
44
44
44
,,
,,
,,
,,
)/)
-%
$,$,
$,$,
$,$,
)/)
-%
)/)
.%0
$4$4
44
,'(&6PDUW
5HOD\%DVH
0RGXOH
)/)
.%0
$4$4
)/)
.%0
$4$4
)/)
.%0
$4$4
44
,,
)/)
-%
)/)
-%
)/)
0
)/)
0
)/)
0
)/)
0
44
44
44
,,
,,
,,
,,
)/)
-%
$,$,
$,$,
$,$,
$,$,
)/)
-%
)/)
.%0
$4$4
44
,'(&6PDUW
5HOD\%DVH
0RGXOH
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.1 Modular IDEC SmartRelay setup
IDEC SmartRelay Manual
18
High-speed/optimal communication performance
For optimal and high-speed communication performance between the Base Module and the
various modules, install the digital modules first, then the analog modules (as the examples
above show). (The special function PI controller is an exception: the AI used for the value PV
should be on the Base Module or an analog input module adjacent to the Base Module).
You install the Text Display module separately and connect it to the Base Module with the
Ethernet interface.
2.1.3
Setup with different voltage classes
Rules
You can only connect digital modules to devices of the same voltage class.
You can connect analog modules to devices of any voltage class.
Overview: Connecting an expansion module to the IDEC SmartRelay Base Module
In the following tables, "X" means that the connection is possible; "-" means that the
connection is not possible.
IDEC SmartRelay Base Module
Expansion modules
FL1F-
M08B2R2
FL1F-
M08B1S2
FL1F-
M08D2R2
FL1F-
M08C2R2
FL1F-
J2B2/K2BM2
FL1F-H12RCE
x
x
x
-
x
FL1F-H12RCC
-
-
-
x
x
FL1F-H12SCD
x
x
x
-
x
FL1F-H12RCA
x
x
x
-
x
FL1F-B12RCE
x
x
x
-
x
FL1F-B12RCA
x
x
x
-
x
FL1F-B12RCC
-
-
-
x
x
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
19
IDEC SmartRelay installation and wiring
2.1 Modular IDEC SmartRelay setup
Overview: Connecting an additional expansion module to an expansion module
2.1.4
Compatibility
All of IDEC SmartRelay FL1F modules are compatible with FL1F series only.
You cannot connect IDEC SmartRelay FL1F Base Modules to old expansion modules such
as FL1E series.
You cannot connect IDEC SmartRelay FL1F expansion modules to old Base Modules such
as FL1E series.
You cannot connect IDEC SmartRelay FL1F text display to old Base Modules such as FL1E
series.
You can only use the Text Display module with equipment series FL1F.
The Text Display provides two Ethernet ports for network connection and six-line text display
specifically for the IDEC SmartRelay FL1F device.
IDEC SmartRelay supports micro SD cards only.
You cannot edit message texts from the Base Module that contain any of the following
parameters:
•
Par
•
Time
•
Date
•
EnTime
•
EnDate
•
Analog input
•
Digital I/O status
•
Special characters (for example: ±, € )
You can only edit such message texts from WindLGC.
Expansion module
Additional expansion modules
FL1F-
M08B2R2
FL1F-
M08B1S2
FL1F-
M08D2R2
FL1F-
M08C2R2
FL1F-
J2B2/K2BM2
FL1F-M08B2R2
x
x
x
-
x
FL1F-M08B1S2
x
x
x
-
x
FL1F-M08D2R2
x
x
x
-
x
FL1F-M08C2R2
-
-
-
x
x
FL1F-J2B2/K2BM2
x
x
x
-
x
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.2 Installing/removing IDEC SmartRelay
IDEC SmartRelay Manual
20
2.2
Installing/removing IDEC SmartRelay
Dimensions
The IDEC SmartRelay installation dimensions are compliant with DIN 43880.
IDEC SmartRelay can be snap-mounted to 35 mm DIN rails according to EN 60715 or
mounted on the wall with two M4 screws.
IDEC SmartRelay width:
•
Text Display has a width of 128.2 mm.
•
Base Modules have a width of 71.5 mm.
•
Expansion Modules have a width of 35.5 mm (FL1F-M08...)
Note
The figures below show you an example of the installation and removal of an FL1F-
H12RCE and a digital module. The measures shown apply to all other Base Module
versions and expansion modules.
WARNING
Risk to life when you touch live parts
Death or serious injury can result when you touch live parts.
Always switch off power before you remove or insert an expansion module.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
21
IDEC SmartRelay installation and wiring
2.2 Installing/removing IDEC SmartRelay
2.2.1
DIN rail mounting
Mounting
To mount a Base Module and a digital module onto a DIN rail, follow these steps:
1. Hook the Base Module onto the rail.
2. Push down the lower end to snap it on. The mounting interlock at the rear must engage.
3. On the right side of the Base Module/Expansion Module, remove the connector cap.
4. Place the digital module onto the DIN rail on the right-hand side of the Base Module.
5. Slide the digital module towards the left until it contacts the Base Module.
6. Using a screwdriver, push the interlock to the left. In its end position the slide interlock
engages in the Base Module.
Repeat the digital module steps to mount further expansion modules.
Note
Be sure to cover the expansion interface on the last expansion module.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.2 Installing/removing IDEC SmartRelay
IDEC SmartRelay Manual
22
Removal
To remove IDEC SmartRelay if you have installed only one Base Module, follow these steps:
1. Insert a screwdriver into the eyelet at the bottom of the slide interlock and move the latch
downward.
2. Swing the Base Module off the DIN rail.
To remove IDEC SmartRelay if you have connected at least one expansion module to the
Base Module, follow these steps:
1. Using a screwdriver, push the integrated slide interlock to the right.
2. Slide the expansion module off towards the right.
3. Insert a screwdriver into the eyelet at the bottom of the slide interlock and lever it downward.
4. Swing the expansion module off the profile rail.
Repeat steps 1 to 4 for all other expansion modules.
5. After removing all expansion modules, remove the base module.
Note
When removing modules, be sure to disengage the slide interlock of the module that
connects it to the next module. When removing multiple modules, it is easier to start with the
last module on the right side.
$
%
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
23
IDEC SmartRelay installation and wiring
2.2 Installing/removing IDEC SmartRelay
2.2.2
:all-mounting
Follow the instructions below to wall-mount IDEC SmartRelay by means of two mounting
slides and two M4 screws (tightening torTue 0.8 Nm to 1.2 Nm).
Note
:hen you do not wall-mount IDEC SmartRelay, always keep the mounting hooks in the
factory default positions, that is, within the data area given in the illustration above
otherwise, the mounting hooks may deform if they are exposed to hot and humid
surroundings for a long term.
0RXQWLQJKRRNV
)DFWRU\GHIDXOWSRVLWLRQ
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.2 Installing/removing IDEC SmartRelay
IDEC SmartRelay Manual
24
Drilling template for wall-mounting
Before you can wall-mount IDEC SmartRelay, you need to drill holes using the template
shown below:
All dimensions in mm
Bore hole for M4 screw, tightening torque 0.8 Nm to 1.2 Nm
①Base Module
② Expansion Modules
98 +/– 0.3
1
2
2
2
+0.2
53.5–0.0
+0.2
35.5–0.0
+0.2
n x 35.5–0.0
,'(&
6PDUW5HOD\
)/)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
25
IDEC SmartRelay installation and wiring
2.2 Installing/removing IDEC SmartRelay
2.2.3
Mounting the Text Display
To prepare the mounting surface for the optional Text Display and mount it, follow these
steps:
1. Cut a 119 mm × 78.5 mm (tolerance: +0.5 mm) hole in the mounting surface.
2. Place the included gasket on the frontplate of the Text Display.
3. Fit the Text Display into the cutout you made in the mounting surface.
4. Attach the mounting brackets (included) to the Text Display
5. Tighten the mounting screws on the mounting brackets to 0.2 Nm torque to secure the
Text Display.
You can then connect the Text Display to the Base Module through the Ethernet interface.
Note
Make sure you mount the Text Display vertically on a flat surface of an IP 65 or Type 4X/12
enclosure.
① Mounting brackets
② Mounting screws
③ Gasket
④ Cabinet door or control panel
(Thickness: 1.5 mm to 4 mm)
ི
ཱ
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.3 :iring IDEC SmartRelay
IDEC SmartRelay Manual
26
2.2.4
Labeling IDEC SmartRelay
The rectangular areas on the IDEC SmartRelay modules are intended for labeling.
In the case of expansion modules, you can use the rectangular areas for labeling the inputs
and outputs, for example. In this connection, you can enter a delta factor of 8 for the inputs
or 4 for the outputs if the Base Module already has 8 inputs or 4 outputs.
2.3
:iring IDEC SmartRelay
:ire IDEC SmartRelay using a screwdriver with a 3 mm blade.
mm2@
A:G
Phoenix Contact
Ferrule type No.
NIC HIFU
Blade Terminals
type No.
NIC HIFU
Insulated Pin Terminals
type No.
0.3
22
AI0,5-10:H
BT1.25-10-1
-
0.5
20
AI0,5-10:H
TGN-TC-1.25-11T
0.75
18
AI0,75-8G<
1.25
18
AI1,5-8B.
BT1.25-10-1
BT2-9-1
2.0
16
AI2,5-8BU
BT2-9-1
-
Recommended
crimping tool
CRIMPFO; =A 3
NH1
NH61
NH11
NH32
NH65
AC/DC 100...240V INPUT 8xAC/DC
X10
L1
I1
I2
I3
I4
I5
I6
I7
I8
N
5HFWDQJXODUDUHD
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
27
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
For 2-cable connection
2.3.1
Connecting the power supply
The 100-240 VAC/VDC versions of IDEC SmartRelay are suitable for operation with rated
voltages of 100 VAC/VDC and 240 VAC/VDC. The IDEC SmartRelay 24 V and 12 V versions
can be operated with a 24 VDC, 24 VAC or 12 VDC power supply. For information on
permissible voltage tolerances, line frequencies and power consumption, refer to the
installation instructions in the Product Information supplied with your device and to the
technical data in Appendix A.
The Text Display must be supplied with a voltage of 12 VDC or 24 VAC/VDC.
Cross-section
[mm2]
AWG
Phoenix Contact
Ferrule type No.
0.3
22
AI-TWIN2X0,5-8WH
0.5
20
AI-TWIN2X0,5-8WH
0.75
18
AI-TWIN2X0,75-8GY
1.25
18
AI-TWIN2X1,5-8BK
Recommended
crimping tool
CRIMPFOX ZA 3
Note
Always cover the terminals after you have completed the installation. To protect IDEC
SmartRelay adequately from impermissible contact to live parts, comply with local standards.
CAUTION
Expansion modules FL1F-M08C2R2 must be operated with the same type of power supply
(DC or AC) as for the connected 100-240 VAC/VDC version of the Base Module. The same
supply output "+/- "on DC power supplies or "N/L" on AC power supplies must connect to the
same phase on both the expansion module FL1F-M08C2R2 and the connected FL1F-
H12RCC/B12RCC. Failure to follow the instructions could result in personal injury.
Note
A power failure might cause an additional edge triggering signal at the special functions. The
stored data will be from the last uninterrupted cycle.
When using different power supplies, supply power to the base module and expansion
modules at the same time, or supply power to expansion modules before the base module.
When supplying power to expansion modules after the base module, expansion modules
may not be recognized by the base module.
When using different power supplies, the fast transient/burst immunity (IEC61000-4-4) will be
1kV (power supply).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
IDEC SmartRelay Manual
28
Connecting IDEC SmartRelay
Connect IDEC SmartRelay to the power supply as shown below, depending on whether your
power supply is DC or AC:
Circuit protection with AC voltage
To suppress voltage peaks on the power supply lines, you can install a metal oxide varistor
(MOV). Make sure the operating voltage of the varistor (MOV) used lies at least 20% above
the rated voltage.
Circuit protection with DC voltage
To suppress voltage peaks on the power supply lines, install a protection device.
Note
IDEC SmartRelay is a double-insulated switchgear. You must connect its FE terminal to
earth ground.
/
0
1
/
/
0
,
,
,
,
/
1
,
,
,
,
,'(&6PDUW5HOD\
ZLWK'&SRZHUVXSSO\
,'(&6PDUW5HOD\
ZLWK$&SRZHUVXSSO\
3URWHFWLRQZLWKVDIHW\IXVH
LIUHTXLUHGUHFRPPHQGHGIRU
)/)+5&(
$
)/)+6&'
$
7RVXSSUHVVVXUJHYROWDJHVLQVWDOO
YDULVWRUV029ZLWKDQRSHUDWLQJ
YROWDJHDWOHDVWDERYHWKHUDWHG
YROWDJH
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
29
IDEC SmartRelay installation and wiring
2.3 :iring IDEC SmartRelay
2.3.2
Connecting the Text Display power supply
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
IDEC SmartRelay Manual
30
Sensor characteristics for IDEC SmartRelay
Sensor connections
Connecting glow lamps and two-wire proximity switches (Bero) to FL1F-H12RCC/B12RCC or
FL1F-M08C2R2 (AC)
The figure below shows how you connect a switch with a glow lamp to IDEC SmartRelay. The
current that flows through the glow lamp allows IDEC SmartRelay to detect a "1" signal even
though the switch contact is not closed. If, however you use a switch that has the glow lamp
fitted with a power supply, this response does not occur.
FL1F-H12RCE
FL1F-B12RCE
FL1F-H12SCD
FL1F-H12RCA
FL1F-B12RCA
FL1F-H12RCC
FL1F-B12RCC
I3 ~ I6
I1,I2,I7,I8
I3 ~ I6
I1,I2,I7,I8
AC
DC
AC
DC
Input voltage (Signal 0)
Input current (Signal 0)
< 5 V DC
< 0.88mA
< 5 V DC
< 0.07mA
< 5 V DC
< 0.9mA
< 5 V DC
< 0.07mA
< 5 V AC
< 1.2mA
< 5 V DC
< 1.2mA
< 40 V AC
< 0.05mA
< 30 V DC
< 0.06mA
Input voltage (Signal 1)
Input current (Signal 1)
> 8.5 V DC
> 1.5mA
> 8.5 V DC
> 0.12mA
> 12 V DC
> 2.1mA
> 12 V DC
> 0.18m
> 12 V AC
> 2.6mA
> 12 V DC
> 2.6mA
> 79 V AC
> 0.08 mA
> 79 V DC
> 0.13mA
FL1F-M08B2R2
FL1F-M08B1S2
FL1F-M08D2R2
FL1F-M08C2R2
AC
DC
AC
DC
Input voltage (Signal 0)
Input current (Signal 0)
< 5 V DC
< 0.88mA
< 5 V DC
<0.88mA
< 5 V AC
< 1.1mA
< 5 V DC
< 1.1mA
< 40 V AC
< 0.05mA
< 30 V DC
< 0.06mA
Input voltage (Signal 1)
Input current (Signal 1)
> 8.5 V DC
> 1.5mA
> 12 V DC
> 2.1mA
> 12 V AC
> 2.63mA
> 12 V DC
> 2.63mA
> 79 V AC
> 0.08 mA
> 79 V DC
> 0.13mA
Note
FL1F-H12RCC/B12RCC contains two groups of four inputs, for a total of eight. Within each
group, you must operate all inputs on the same phase. Different phases are only possible
between the groups.
Example: I1 to I4 on phase L1, I5 to I8 on phase L2.
You must not connect the inputs of the FL1F-M08C2R2 to different phases.
/
1
&
/
1
,
,
,
,
;;W\SHFDSDFLWRUQ)9$&
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
31
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
Take into account the quiescent current of any two-wire proximity switches that you use. The
level of the quiescent current of some two-wire proximity switches is high enough to trigger a
logical "1" signal at the IDEC SmartRelay input. You should therefore compare the quiescent
current of the proximity switches with the Technical data (Page 283).
Remedy
To suppress this response, use an X1/X2-type capacitor rated at 100 nF and 275 VAC. In a
destructive situation, this type of capacitor safely disconnects. You must choose the voltage
level for which the capacitor is rated such that it is not destroyed in the case of overvoltage!
At 230 VAC, the voltage between N and an input I(n) must not be greater than 40 V to
guarantee a "0" signal. You can connect approximately ten glow lamps to the capacitor.
Restrictions
Signal status transitions 0 → 1/1 → 0
After a 0 to 1 or 1 to 0 transition, the signal must remain constant at the input at least for the
duration of one program cycle, so that IDEC SmartRelay can detect the new signal status.
The size of the circuit program determines the program execution time. The appendix
"Determining the cycle time (Page 303)" contains a benchmark test routine that you can use
to determine the current scan cycle time.
Special features of FL1F-H12RCE/B12RCE and FL1F-H12SCD
Fast digital inputs: I3, I4, I5 and I6
These modules include fast digital inputs (up/down counters, frequency triggers). The
restrictions mentioned earlier do not apply to these fast digital inputs.
Analog inputs: I1 and I2, I7 and I8
You can use the inputs I1, I2, I7 and I8 of IDEC SmartRelay versions FL1F-H12RCE/B12RCE
and FL1F-H12SCD as either digital inputs or analog inputs. The IDEC SmartRelay circuit
program defines the input mode (digital or analog).
The inputs I1, I2, I7 and I8 provide digital inputs, and the inputs AI3, AI4, AI1 and AI2 provide
analog inputs, as described in the topic "Constants and connectors (Page 111)". AI3
corresponds to the input terminal I1; AI4 corresponds to I2; AI1 corresponds to I7; AI2
corresponds to I8. The use of AI3 and AI4 is optional. You configure your IDEC SmartRelay to
use either two or four analog inputs as the topic "Setting the number of AIs in IDEC
SmartRelay (Page 264)" describes.
When using inputs I1, I2, I7 and I8 as analog inputs, only the range from 0 to 10 VDC is
available.
Note
Expansion modules do not have fast digital inputs.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
IDEC SmartRelay Manual
32
Connecting a potentiometer to inputs I1, I2, I7 and I8
To allow you to achieve 10 V as the maximum value when you completely turn the
potentiometer once, you must connect a series resistor on the potentiometer's input side
regardless of the input voltage (see figure below).
We suggest the following sizes of potentiometers and associated series resistors:
When using a potentiometer and 10 V input voltage as the maximum value, you must ensure
that with a connected input voltage of 24 V, 14 V must release via the series resistor to
ensure a maximum supply of 10 V when you turn the potentiometer one full rotation. With a
voltage of 12 V, you can neglected this.
Sensor connections
Connect sensors to IDEC SmartRelay as shown below.
FL1F-B12RCE/H12RCE and FL1F-B12RCA/H12RCA/H12SCD
Voltage
Potentiometer
Series Resistor
12 V
5 kΩ
-
24 V
5 kΩ
6.6 kΩ
Note
The FL1F-J2B2 expansion module provides additional analog inputs.
Always use shielded cables for analog signals, and keep these as short as possible.
The inputs of these devices are not isolated
and therefore require a common reference
potential (chassis ground).
With FL1F-H12RCE/B12RCE and FL1F-
H12SCD modules, you can tap analog
signals between the supply voltage and
chassis ground (* = series resistor (6.6 kΩ)
at 24 VDC).
0
/
,
,
,
,
,
/
0
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
33
IDEC SmartRelay installation and wiring
2.3 :iring IDEC SmartRelay
Connection example
FL1F-B12RCC/H12RCC
The inputs of these devices are in two
groups, each consisting of four inputs.
Different phases are only possible between
groups, but not within the groups.
1
09
1
9$&9'&
/
/
,,
%
AC/DC 24V INPUT 8xAC/DC
Q1
P1
1
2
1
2
1
2
1
2
I1
I2
I3
I4
I5
I6
I7
I8
P2
Q2
Q3
Q4
IE(LAN)
MAC ADDRESS
OUTPUT 4xRELAY/10A
LAN
RUN/STOP
PD[$
9$&
/
/
/
1
1
/
,
,
,
,
,
,
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.3 :iring IDEC SmartRelay
IDEC SmartRelay Manual
34
Connection example
:ARNING
Current safety regulations (VDE 0110, ... and IEC 61131-2, ... as well as UL 508) do not
permit the connection of different phases to an AC input group (I1 to I4 or I5 to I8) or to the
inputs of a digital module.
1
09
1
9$&9'&
/
/
,,
%
ESC
OK
AC/DC 100...240V INPUT 8xAC/DC
Q1
L1
1
2
1
2
1
2
1
2
I1
I2
I3
I4
I5
I6
I7
I8
N
Q2
Q3
Q4
IE(LAN)
MAC ADDRESS
OUTPUT 4xRELAY/10A
LAN
OUTPUT 4x RELAY/5A
AC/DC 115...240V INPUT 4xAC/DC
RUN/STOP
L1
I1
I2
I3
I4
N
1
2
1
2
1
2
1
2
Q1
Q2
Q3
Q4
1
/
/
/
,,
,,
ESC
OK
AC/DC 100...240V INPUT 8xAC/DC
Q1
L1
1
2
1
2
1
2
1
2
I1
I2
I3
I4
I5
I6
I7
I8
N
Q2
Q3
Q4
IE(LAN)
MAC ADDRESS
OUTPUT 4xRELAY/10A
LAN
7ZRSKDVHFRQQHFWLRQRIWKH
%DVH0RGXOH
7KUHHSKDVHFRQQHFWLRQRIWKH%DVH0RGXOH
ZLWKDQH[SDQVLRQPRGXOH
PD[$
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
35
IDEC SmartRelay installation and wiring
2.3 :iring IDEC SmartRelay
FL1F--2B2
The illustration above shows an example of four-wire current measurement and two-wire
voltage measurement.
Connecting a two-wire sensor to the FL1F--2B2
:ire up the two-wire sensor
s connecting wires as follows:
1. Connect the sensor
s output to connection U (0 V to 10 V voltage measurement) or to
connection I (0/4 mA to 20 mA current measurement) of the FL1F--2B2 module.
2. Connect the plus connector on the sensor to the 24 V supply voltage (L).
3. Connect the ground connection of the current output M (on the right side of the sensor, as
shown in the figure above) to the corresponding M input (M1 or M2) on the FL1F--2B2
module.
FE terminal for connecting earth and
shielding the cable
ི
Shielded cable
ཱ
Earth
ཱི
Standard DIN rail
Note
Fluctuating analog values can occur if you do not mount/correctly mount the screening on the
connecting wire from the analog valuator device to the analog FL1F--2B2 expansion module
(encoder wire).
To avoid fluctuating analog values when using these expansion modules, take the following
measures:
ವ
Use only shielded cable.
ವ
Shorten the cable as much a possible. The cable must not be more than 10 meters long.
ವ
Clamp the cable on one side only and clamp it only to the FE terminal on the FL1F--2B2/
.2BM2 expansion module.
ವ
Connect the earth to the FE terminal on the expansion module.
INPUT 2x (0...10V/0...20mA)
DC 12/24V
RUN/STOP
L+
I1
I2
M1
M2
U1
U2
L+
M
M
/
0
/
/
0
0
0
9
2
3
4
1
9ROWDJHPHDVXUHPHQW
&XUUHQWPHDVXUHPHQW
5HIHUHQFH
&XUUHQW
&XUUHQW
P$
6HQVRU
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
IDEC SmartRelay Manual
36
Input Internal Circuit
FL1F-H12RCC / FL1F-B12RCC
Digital AC/DC Input
FL1F-M08C2R2
Digital AC/DC Input
When using the AC two-wire sensor
390kΩ
120nF
43kΩ
180kΩ
270kΩ
I1 ~ I8
Internal
N
Circuit
390kΩ
120nF
43kΩ
180kΩ
270kΩ
I1 ~ I4
N
Internal
Circuit
AC
2-wire
Sensor
I1 ~ I8
L1
N
100 ~ 240V AC
R1
~
(I1 ~ I4)
Note : Bleeder resistance (R1) calcuation
The voltage drop across the load (R1) must be less than 40V while the
sensor is turned off.
R1 must satisfy the following three conditions.
Condition 1: R1 (Ω) ≤
Maximum input OFF voltage (= 40V AC)
Maximum sensor leakage current (A)
Condition 2: R1 (Ω) ≤
Sensor power voltage (V)
Minimum sensor load current (A)
Condition 3: PR1 (W) ≥
× 3 (3: recommended allowance)
{Sensor power voltage (V)}2
R1 resistance (Ω)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
37
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
FL1F-H12RCA / FL1F-B12RCA
Digital AC/DC Input
FL1F-M08D2R2
Digital AC/DC Input
When using the AC two-wire sensor
FL1F-H12RCE / FL1F-B12RCE / FL1F-H12SCD
Digital DC Input
I1 ~ I8
P2
4.3kΩ
100nF
510Ω
Internal
Circuit
I1 ~ I4
P2
4.3kΩ
100nF
510Ω
Internal
Circuit
AC
2-wire
Sensor
I1 ~ I8
L1
N
24V AC
R2
~
Note : Bleeder resistance (R2) calcuation
The voltage drop across the load (R2) must be less than 5V while the
sensor is turned off.
R3 must satisfy the following three conditions.
Condition 1: R2 (Ω) ≤
Maximum input OFF voltage (= 5V AC)
Maximum sensor leakage current (A)
Condition 2: R2 (Ω) ≤
Sensor power voltage (V)
Minimum sensor load current (A)
Condition 3: PR2 (W) ≥
× 3 (3: recommended allowance)
{Sensor power voltage (V)}2
R2 resistance (Ω)
I3 ~ I6
4.3kΩ
47nF
1.5kΩ
4.7kΩ
M
Internal
Circuit
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
IDEC SmartRelay Manual
38
FL1F-M08B2R2/FL1F-M08B1S2
Digital DC Input
FL1F-H12RCE / FL1F-B12RCE / FL1F-H12SCD
Analog Input (0-10V)
FL1F-J2B2
Analog Input (0-10V)
FL1F-J2B2
Analog Input (0-20mA)
I1 ~ I4
4.3kΩ
47nF
1.5kΩ
4.7kΩ
M
Internal
Circuit
I1,I2,I7,I8
36kΩ
10nF
18kΩ
M
1nF
18kΩ
Internal
Circuit
U1, U2
57kΩ
10nF
19kΩ
+3.3V
M1, M2
Internal
Circuit
I1,I2
M1,M2
Max.55Ω
10nF
124Ω
Internal
Circuit
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
39
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
2.3.4
Connecting outputs
FL1F-H12RCA/B12RCA/H12RCC/B12RCC/H12RCE/B12RCE
The FL1F-H12RCA/B12RCA/H12RCC/B12RCC/H12RCE/B12RCE version includes relay
outputs. The potential of the relay contacts is isolated from the power supply and the inputs.
Requirements for relay outputs
You can connect various loads to the outputs; e.g., lamps, fluorescent lamps, motors,
contactor relays, etc. For information on the properties required for the loads connected to
FL1F-H12RCA/B12RCA/H12RCC/B12RCC/H12RCE/B12RCE, refer to the General technical
data (Page 283).
Connecting
Connect the load to FL1F-H12RCA/B12RCA/H12RCC/B12RCC/H12RCE/B12RCE as shown
below:
//
4
4
4
4
10
3URWHFWLRQZLWKDXWRPDWLFFLUFXLWEUHDNHUPD[$FKDUDFWHULVWLFV%
/RDG
/RDG
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.3 :iring IDEC SmartRelay
IDEC SmartRelay Manual
40
IDEC SmartRelay with transistor outputs
= 5 kΩ
I1, I2:
0/4 ... 20 mA
R2:
<= 250 Ω
0
/
ཱ
R2
0 ... 10 V
0/4 ... 20 mA
R1
L+
U1+ M1
M2 I2
I1 U2+
'&9
M
L+
M
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
41
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
Output Internal Circuit
FL1F-H12RCA / FL1F-B12RCA / FL1F-H12RCC / FL1F-B12RCC / FL1F-H12RCE / FL1F-B12RCE /
FL1F-M08B2R2 / FL1F-M08C2R2 / FL1F-M08D2R2
Relay Output
FL1F-H12SCD / FL1F-M08B1S2
Transister Output (Source)
+V
1
2
Q1 ~ Q4
Internal
Circuit
U+
U+
IN
OUT
+24V
Q1 ~ Q4
M
10nF
100kΩ
Internal
Circuit
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
IDEC SmartRelay Manual
42
FL1F-K2BM2
Analog Output (0-10V)
FL1F-K2BM2
Analog Output (0/4 ... 20mA)
U1+,U2+
M1,M2
+15V
10Ω
100nF
+
-
Internal
Circuit
I1,I2
M1,M2
+15V
22Ω
10nF
Internal
Circuit
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
43
IDEC SmartRelay installation and wiring
2.3 Wiring IDEC SmartRelay
2.3.5
Connecting the Ethernet interface
Base modules and text display are equipped with a 10/100 Mbit/s Ethernet RJ45 interface.
Requirements for the network cable
Use a shielded Ethernet cable to connect to the Ethernet interface. To minimize
electromagnetic interference, make sure you use a standard Category 5 shielded twisted-pair
Ethernet cable with a shielded RJ45 connector on each end.
Connecting
You connect the FE terminal to earth ground, and connect a network cable to the Ethernet
interface.
Ethernet status LED
①
②
③
Earth ground
Ethernet cable, for connecting to the Ethernet interface
Ethernet status LED
LED type
Color
Description
Status LED
Flashing orange
IDEC SmartRelay is receiving/sending data across Ethernet.
Steady green
IDEC SmartRelay is already connected to Ethernet.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.4 Putting into operation
IDEC SmartRelay Manual
44
2.4
Putting into operation
2.4.1
Powering on IDEC SmartRelay
IDEC SmartRelay does not have a power switch. The reaction of IDEC SmartRelay during
startup depends on the following:
•
Whether a circuit program is stored in IDEC SmartRelay
•
Whether a micro SD card is inserted
•
Whether this is an IDEC SmartRelay version without display unit (FL1F-B12RCE/
B12RCA/B12RCC)
•
Whether IDEC SmartRelay is in RUN mode or STOP mode at the time of power failure
To ensure that the expansion module on IDEC SmartRelay changes to RUN mode, check the
following:
•
Has the sliding contact between IDEC SmartRelay and the expansion module snapped
into place properly?
•
Is the power supply connected to the expansion module?
•
In addition, always ensure that you switch on the power supply to the expansion module
first before activating the power supply to the Base Module (or activate both power
supplies at the same time); if you do not do this, the system does not detect the expansion
module when you start up the Base Module.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
45
IDEC SmartRelay installation and wiring
2.4 Putting into operation
The following illustration shows all possible reactions of IDEC SmartRelay:
IDEC SmartRelay installation and wiring
2.4 Putting into operation
IDEC SmartRelay Manual
46
1. If neither IDEC SmartRelay nor the inserted card contains a circuit program, the Base
Module displays the following:
2. IDEC SmartRelay automatically copies the circuit program on the card to memory and
overwrites the existing circuit program.
3. If there is a circuit program in IDEC SmartRelay or on the card, IDEC SmartRelay adopts
the operational state it had prior to power-off. Versions without a display unit (FL1F-
B12RCE/B12RCA/B12RCC) automatically change from STOP to RUN (LED changes
from red to green).
4. If you have enabled retentivity for at least one function, or a function is permanently
retentive, IDEC SmartRelay retains the current values at power-off.
Note
When a power failure occurs while you are entering a circuit program, the program in IDEC
SmartRelay is missing after power is returned.
Before you modify the circuit program, save a backup copy of your original to a card or to a
computer using WindLGC.
(PSW\SURJUDP
(UURU
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
47
IDEC SmartRelay installation and wiring
2.4 Putting into operation
2.4.2
Operating states
Base Module operating states
Base Modules (Version with and without LCD Display) have two operating states: STOP and
RUN.
IDEC SmartRelay expansion modules, operating states
Expansion modules have three operating states. The color of the LED (RUN/STOP) indicates
one of three operating states for expansion modules.
STOP
RUN
•
The display shows that the program is
empty when you start the program
(except for FL1F-B12RCE/B12RCA/
B12RCC devices)
•
Switching IDEC SmartRelay to
programming mode
(except for FL1F-B12RCE/B12RCA/
B12RCC devices)
•
LED is red
(only for FL1F-B12RCE/B12RCA/
B12RCC devices)
•
Display: Screen mask for monitoring I/O and
messages (after START in the main menu) or for
the parameter assignment menu
(except for FL1F-B12RCE/B12RCA/B12RCC
devices)
•
Switching IDEC SmartRelay to parameter
assignment mode
(except for FL1F-B12RCE/B12RCA/B12RCC
devices)
•
LED is green
(only for FL1F-B12RCE/B12RCA/B12RCC devices)
Action of IDEC SmartRelay:
•
The input data is not read.
•
The circuit program is not executed.
•
The relay contacts are permanently open
or the transistor outputs are switched off.
Action of IDEC SmartRelay:
•
IDEC SmartRelay reads the status of the inputs.
•
IDEC SmartRelay uses the circuit program to
calculate the status of the outputs.
•
IDEC SmartRelay switches the relay/transistor
outputs on or off.
Note
After switching the power on, the system briefly switches through the outputs on the FL1F-
H12SCD. With an open circuit, a voltage of > 8 V can occur for up to approximately 100 ms;
when the circuit is loaded, this time reduces to a matter of microseconds.
Green (RUN)
Red (STOP)
Orange/Yellow
The expansion module
communicates with the device to
the left.
The expansion module does not
communicate with the device to
its left.
Initialization phase of the
expansion module
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay installation and wiring
2.4 Putting into operation
IDEC SmartRelay Manual
48
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
49
Programming IDEC SmartRelay
Getting started with IDEC SmartRelay
Programming refers to creating a circuit program from the Base Module.
In this chapter you will learn how to use IDEC SmartRelay to create the IDEC SmartRelay
circuit programs for your application.
WindLGC is the IDEC SmartRelay programming software that you can use on your PC to
quickly and easily create, test, modify, save and print the circuit programs. The topics in this
manual, however, relate only to the creation of circuit programs on the actual IDEC SmartRelay
Base Module. The programming software WindLGC contains extensive online help.
A small example in the first part of this chapter introduces the operating principles of IDEC
SmartRelay:
•
You will learn the meaning of two basic terms, namely the connector and the block.
•
As the next step, you will create a circuit program based on a simple conventional circuit.
•
Lastly, you will enter this program directly in IDEC SmartRelay.
It will take you only a few pages of this manual to store your first executable circuit program in
the IDEC SmartRelay device. With suitable hardware (switches etc.), you will then be able to
carry out initial tests.
Note
IDEC SmartRelay versions without a display unit, that is, the FL1F-B12RCE, FL1F-B12RCA
and FL1F-B12RCC versions, do not have an operator panel and display unit. These devices
are ideal for use in small machine and process equipment engineering systems for series
production.
You do not program FL1F-B12RCE/B12RCA/B12RCC versions directly on the device.
Instead, you download a program to the device from WindLGC or from memory cards with
the program you created on another IDEC SmartRelay device.
IDEC SmartRelay versions without a display cannot write data to memory cards.
See Chapters "Using memory cards (Page 267)", "IDEC SmartRelay software (Page 277)"
and the Appendix "IDEC SmartRelay without display ("IDEC SmartRelay Pure") (Page 305)"
for more information.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Programming IDEC SmartRelay
3.1 Connectors
IDEC SmartRelay Manual
50
3.1
Connectors
IDEC SmartRelay is eTuipped with inputs and outputs
Example of a configuration with several modules:
The illustration shows the conceptual usage of the inputs, not the actual physical markings on
the module.
The letters I followed by numerals identify the inputs. :hen you look at IDEC SmartRelay
from the front, you can see the input terminals at the top. Only analog input modules FL1F-
-2B2 has the inputs at the bottom.
The letters 4 followed by numerals (on FL1F-.2BM2) identify the outputs. In the figure, you
can see the output terminals at the bottom.
Note
IDEC SmartRelay can recognize, read and switch the I/O of all expansion modules
regardless of their type. The I/O numbers follow the installation order of the modules.
For IDEC SmartRelay FL1F series, the following I/O and memory markers blocks are
available for creating your circuit program from IDEC SmartRelay:
ವ
I1 to I24, AI1 to AI8, 41 to 420, A41 to A48, M1 to M64, and AM1 to AM64
ವ
32 shift register bits S1.1 to S4.8
ವ
4 cursor keys C , C , C and C
ವ
four function keys on the FL1F-RD1: F1, F2, F3, and F4
ವ
64 blank outputs ;1 to ;64
If you have previously configured any of the network digital or analog inputs/outputs NI1 to
NI64, NAI1 to NAI32, N41 to N464, and NA41 to NA416 in your circuit program from
:indLGC, after downloading the circuit program to IDEC SmartRelay, these network digital
or analog inputs/outputs are available in the IDEC SmartRelay however, you can not edit the
rest of the program from the IDEC SmartRelay, except for the Par parameter.
See the Constants and connectors (Page 111) topic for more details.
The following applies to inputs I1, I2, I7 and I8 of FL1F-B12RCE/H12RCE and FL1F-
H12SCD versions: If you use I1, I2, I7 or I8 in the circuit program, this input signal is digital. If
you use AI3, AI4, AI1, or AI2, the input signal is analog. The numbering of the analog inputs
is significant: AI1 and AI2 corresponded to I7 and I8. :ith the addition of two new analog
inputs, these modules optionally use I1 for AI3 and I2 for AI4. See the graphical
representation in the topic on Maximum setup with expansion modules (Page 17). Also
note that you can also use I3, I4, I5, and I6 as fast digital inputs.
$QDORJRXWSXWV
$QDORJLQSXWV
2XWSXWV
,QSXWV
,
287387[9RUP$
8 M1
,1387[9P$
8
0
,
8
0
1 2 1 2
4
4
,
,
,
,
0
/
1 2 1 2 1 2 1 2
4
4
4
4
,
,
,
,
,
,
,
,
0
/
,
4
4
1 2 1 2
/$1
0
/
0
/
0
/
0
/
'&9,1387['&
5816723
5816723
5816723
'&9
287387[5(/$<$
,, $,$,9
,, $,$,9
'&9,1387['&
'&9
0$&$''5(66
287387[5(/$<$
(/$1
, 8 0
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
51
Programming IDEC SmartRelay
3.1 Connectors
IDEC SmartRelay's connectors
The term connector refers to all connections and states in IDEC SmartRelay .
The digital I/O status can be '0' or '1'. Status '0' means that the input does not carry a specific
voltage. Status '1' means that the input does carry a specific voltage.
The 'hi' and 'lo' connectors make it easier for you to create the circuit program. 'hi' (high) is
assigned the status '1', and 'lo' (low) is assigned the status '0'.
You do not have to use all of the connectors of a block. The circuit program automatically
assigns the unused connectors a status that ensures proper functioning of the relevant block.
For information on the meaning of the term "block", refer to the topic on "Blocks and block
numbers (Page 52)".
IDEC SmartRelay has the following connectors :
Connectors
Inputs
FL1F-H12RCC
FL1F-B12RCC
FL1F-H12RCA
FL1F-B12RCA
Two groups:
I1 to I4 and
I5 to I8
I9 to I24
AI1 to AI8
none
FL1F-H12RCE
FL1F-B12RCE
FL1F-H12SCD
I1, I2, I3-I6, I7, I8
AI3, AI4 ...
AI1, AI2
I9 to I24
AI5 to AI8
Outputs
Q1 to Q4
Q5 to Q20
none
AQ1 to AQ8
lo
Logical '0' signals (off)
hi
Logical '1' signals (on)
Memory markers
Digital memory markers: M1 to M64
Analog memory markers: AM1 to AM64
Shift register bits
S1.1 to S4.8
Network inputs 1)
NI1 to NI64
Network analog inputs 1)
NAI1 to NAI32
Network outputs 1)
NQ1 to NQ64
Network analog outputs 1)
NAQ1 to NAQ16
DM: Digital module
AM: Analog module
1) To make these four connectors available in an IDEC SmartRelay module, you must configure them
in the circuit program with WindLGC V8.0 and download the circuit program to the IDEC SmartRelay.
,'(&6PDUW5HOD\)/)
)/)0
)/)-%
)/).%0
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Programming IDEC SmartRelay
3.2 Blocks and block numbers
IDEC SmartRelay Manual
52
3.2
Blocks and block numbers
This chapter shows you how to use IDEC SmartRelay elements to create complex circuits
and how blocks and I/O are interconnected.
In the topic "From circuit diagram to IDEC SmartRelay program (Page 55)" you will learn how
to transform a conventional circuit into an IDEC SmartRelay circuit program.
Blocks
A block in IDEC SmartRelay represents a function that is used to convert input information
into output information. Previously you had to wire the individual elements in a control cabinet
or terminal box. When you create the circuit program, you interconnect the blocks.
Logic operations
The most elementary blocks are the logic operations:
•
AND
•
OR
•
...
These special functions offer you significantly greater performance:
•
Current impulse relay
•
Up/down counter
•
On-delay
•
Softkey
•
....
The chapter entitled "IDEC SmartRelay functions (Page 111)" gives a full list of the IDEC
SmartRelay functions.
,
,
,Q
,Q
25
ุ
4
,QSXWV,DQG,FRQQHFWWRWKH25EORFN7KH
ODVWWZRLQSXWVRIWKHEORFNUHPDLQXQXVHG
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
53
Programming IDEC SmartRelay
3.2 Blocks and block numbers
Block representation on the IDEC SmartRelay onboard display
The figure below shows a typical view of the IDEC SmartRelay onboard display. As you can
see, it can show only one block at a time. IDEC SmartRelay shows the block number on the
top of the display by default if you assign no name to this block. The block numbers help you
check the circuit structure. Alternatively, you can also choose to display a customized block
name instead of the block number. For more information about assigning a block name, refer
to Section "Circuit program input (Page 65)".
Assigning a block number
IDEC SmartRelay automatically assigns each new block in a circuit program a block number.
IDEC SmartRelay uses these block numbers to indicate the block interconnections. This
means that these numbers are mainly an aid to your orientation in the circuit program.
The figure above shows you three views of the IDEC SmartRelay onboard display, which
represent the circuit program. As you can see, IDEC SmartRelay interconnects the blocks
using their numbers. To scroll the circuit program, use the keys or .
%
,Q
,Q
25
%
4
,
ุ
9LHZRIWKH,'(&6PDUW5HOD\GLVSOD\
%ORFNQXPEHUDVVLJQHG
E\,'(&6PDUW5HOD\
$QRWKHUEORFNLV
FRQQHFWHGDWWKLVSRLQW
8QXVHGFRQQHFWRU
2XWSXW
%ORFN
,QSXW
%
,Q
,
25
,
%
,
ุ
%
,Q
,
25
,
%
,
ุ
%
,Q
,Q
25
%
4
%
ุ
%
4
%ORFNQXPEHUV
7KHVHEORFNV
DUHLQWHUFRQ
QHFWHG
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Programming IDEC SmartRelay
3.2 Blocks and block numbers
IDEC SmartRelay Manual
54
Advantages of block numbers
You can connect almost any block to an input of the current block by means of its block
number. In this way, you can reuse the interim results of logical or other operations, reduce
programming effort, save memory space and clean up your circuit layout. To do so, however,
you need to know how IDEC SmartRelay has named the blocks.
Note
An organizational program chart can be a valuable aid when you create the circuit program
because you can enter in this chart all the block numbers that IDEC SmartRelay assigns.
By using the WindLGC software to program IDEC SmartRelay, you can directly create a
function chart of your circuit program. WindLGC also allows you to assign 12-character
names to up to 100 blocks, and to view these on the IDEC SmartRelay onboard display in
parameter assignment mode. See the topic "The four golden rules for operating IDEC
SmartRelay (Page 57)".
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
55
Programming IDEC SmartRelay
3.3 From circuit diagram to IDEC SmartRelay program
3.3
From circuit diagram to IDEC SmartRelay program
View of a circuit diagram
The following illustration shows a typical circuit diagram that represents the circuit logic:
Creating this circuit with IDEC SmartRelay
In IDEC SmartRelay you create a circuit logic by interconnecting blocks and connectors:
To create a new circuit logic in IDEC SmartRelay, start at the circuit output.
The output is the load or relay that is to be switched.
Convert the circuit logic into blocks by working through the circuit, starting at the output and
ending at the input:
Note
Although you have four inputs available for Basic functions list - GF (Page 116), most of the
views only show three inputs for reasons of clarity. You program this fourth input and assign
parameters just like you do with the other three inputs.
6
6
6
.
(
.
7KHVZLWFKHV6256$1'6
DFWLYDWHWKHUHOD\.DQGVZLWFK
RQWKHORDGDW(
/
1
66
,
,
,
4
ุ
/
1
,
,
,
,
4
4
4
:LULQJRIWKHLQSXWV
&LUFXLWSURJUDPLQ,'(&6PDUW5HOD\
:LULQJRIWKHRXWSXWV
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Programming IDEC SmartRelay
3.3 From circuit diagram to IDEC SmartRelay program
IDEC SmartRelay Manual
56
Step 1: Connect the normally open contact S3 in series with another circuit element to output
Q1. A series connection corrsponds to the AND block:
Step 2: Use an OR block to connect S1 and S2 in parallel. A parallel circuit corresponds to the
OR block:
Unused inputs
The circuit program automatically assigns the unused connectors a status that ensures
proper functioning of the relevant block.
In our example we shall use only two inputs of the OR block and two inputs of the AND block;
the third and fourth inputs are unused.
Now connect the I/O to IDEC SmartRelay.
Wiring
Connect the switches S1 to S3 to the screw terminals of your IDEC SmartRelay :
•
S1 to connector I1 of IDEC SmartRelay
•
S2 to connector I2 of IDEC SmartRelay
•
S3 to connector I3 of IDEC SmartRelay
The output of the AND block controls the relay at output Q1. The load E1 connects to output Q1.
,
4
,
,
,
4
ุ
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
57
Programming IDEC SmartRelay
3.4 The four golden rules for operating IDEC SmartRelay
Wiring example
The following figure shows you the wiring, based on a 100-240 VAC/VDC version of IDEC
SmartRelay.
3.4
The four golden rules for operating IDEC SmartRelay
Rule 1: Changing the operating mode
•
You create the circuit program in programming mode. After power is on, and when the
program is empty in IDEC SmartRelay, IDEC SmartRelay selects the programming mode
by default.
•
You can edit timer and parameter values of an existing circuit program in both parameter
assignment mode and programming mode. During parameter assignment IDEC
SmartRelay is in RUN mode; that is, it continues executing the circuit program (see the
topic "Configuring IDEC SmartRelay (Page 253)"). To work in programming mode, you
need to terminate the circuit program.
•
Select the menu command
on the main menu to set RUN mode.
•
When the system is in RUN mode, you can return to parameter assignment mode by
pressing the ESC key.
•
When parameter assignment mode is open and you want to return to programming mode,
select the menu command
from the parameter assignment menu to
set STOP mode.
For more details on operating modes, refer to the Appendix topic "IDEC SmartRelay menu
structure (Page 307)".
/
1
,
,
,
,
4
4
4
/
1
6
6
6
/
1
2XWSXWZLULQJ
/RDG
,QSXWZLULQJ
6WDUW
6WRS
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Programming IDEC SmartRelay
3.4 The four golden rules for operating IDEC SmartRelay
IDEC SmartRelay Manual
58
Rule 2: Outputs and inputs
•
Always create your circuit program by working from the output to the input.
•
You can connect an input to several outputs, but not the same output to several inputs.
•
Within the same program path you cannot connect an output to an upstream input. You
can use markers or outputs for such internal recursions.
Rule 3: Cursor and cursor movement
The following applies when you edit a circuit program:
•
You can move the cursor when it appears as a solid square:
–
Press , , or to move the cursor in the circuit program.
–
Press OK to change to select connector/block.
–
Press ESC to exit programming mode.
•
You select a connector/block when the cursor appears as a solid square:
–
Press or to select a connector or a block.
–
Confirm with OK.
–
Press ESC to return to the previous step.
Rule 4: Planning
•
Before you start to create a circuit program, first create a design on paper or program
IDEC SmartRelay directly using WindLGC.
•
IDEC SmartRelay can only save complete and faultless circuit programs.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
59
Programming IDEC SmartRelay
3.5 Configuring menu access protection for IDEC SmartRelay
3.5
Configuring menu access protection for IDEC SmartRelay
IDEC SmartRelay provides two access levels, administrator and operator, to limit access to
specific menus in programming mode. As an administrator, you can access all menu
commands while as an operator, some specific menu commands are not visible (see section
Overview of IDEC SmartRelay menus (Page 61)). IDEC SmartRelay
s default setting is
administrator at delivery, and you can switch to operator at any time. :hen switching from
operator to administrator, you need to enter a valid password (IDEC by default). IDEC
SmartRelay always saves its access level before power-off.
Switching IDEC SmartRelay from administrator to operator
To switch IDEC SmartRelay
s access level from administrator to operator, follow these steps:
1. Move the cursor to on the main menu of programming mode: Press or
2. Confirm : Press O.
3. Move the cursor to ཱ: Press or
4. Confirm ཱ: Press O.
IDEC SmartRelay now switches to the access level of operator and returns to the main menu.
Note
The access level of the Text Display is operator by default, and you can switch it to
administrator with the password IDEC.
The Text Display saves its access level before power-off if it connects to the same Base
Module after power-on. If you connect a different Base Module to it, however, the Text
Display restores its access level to operator after power-on.
The access level setting on the Text Display is independent of that on the Base Module.
1HWZRUN
'LDJQRVWLFV
&DUG
3URJUDP
6WDUW
6HWXS
0VJ&RQILJ
6WDUW6FUHHQ
&ORFN
3RZHURQ'HOD\
$4
%0$,180
ႣႭ
/&'
0HQX/DQJXDJH
&ORFN
6WDUW6FUHHQ
0VJ&RQILJ
6ZLWFKWR23
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Programming IDEC SmartRelay
3.5 Configuring menu access protection for IDEC SmartRelay
IDEC SmartRelay Manual
60
Switching IDEC SmartRelay from operator to administrator
To switch IDEC SmartRelay
s access level from operator to administrator, follow these steps:
1. Move the cursor to on the main menu of programming mode: Press or
2. Confirm : Press O.
3. Move the cursor to ཱ: Press or
4. Confirm ཱ: Press O.. The display appears as follows:
5. Press or to move up and down the alphabet to select your letters (for example, IDEC).
6. Confirm the password: Press O.
IDEC SmartRelay now switches to the access level of administrator and returns to the
main menu.
'LDJQRVWLFV
1HWZRUN
6HWXS
/&'
0HQX/DQJXDJH
6WDUW6FUHHQ
0VJ&RQILJ
6ZLWFKWR$'0,1
$'0,13DVVZRUG
$'0,13DVVZRUG
,'(&
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
61
Programming IDEC SmartRelay
3.6 Overview of IDEC SmartRelay menus
3.6
Overview of IDEC SmartRelay menus
The following illustration shows an overview of IDEC SmartRelay menus:
These menu commands are visible only with the access level of administrator.
For more details on the menus, refer to the Appendix Base Module (Page 307).
The following illustration shows an overview of Text Display menus:
2.
(6&
2.
(6&
2.
(6&
ႣႭ
2.
(6&
2.
(6&
7UDQVIHUPHQX
&OHDU3URJ
3URJ3DVVZRUG
0HPRU\8VDJH
3URJ1DPH
6HW3DUDPHWHU
(GLW3URJ
1HWZRUN
'LDJQRVWLFV
&DUG
6HWXS
3URJUDP
6WDUW
&RS\3URWHFW
/RDG3URJ&DUG
6DYH3URJ!&DUG
6HW060RGH
,3$GGUHVV
3URJUDPPLQJPRGH
3URJUDPPLQJPHQX
0DLQPHQX
6HWXSPHQX
1HWZRUN
'LDJQRVWLFV
6HWXS
3URJUDP
6WRS
3DUDPHWHUDVVLJQPHQWPHQX
3DUDPHWHUDVVLJQPHQWPRGH
1RWH7KHಯ%0$,180ರVHOHFWLRQ
LVRQO\DYDLODEOHRQ%DVH0RGXOHV
WKDWVXSSRUWIRXUDQDORJLQSXWV
1HWZRUNFRQILJXUDWLRQPHQX
'LDJQRVWLFVPHQX
&ORFN
6WDUW6FUHHQ
0VJ&RQILJ
3RZHURQ'HOD\
$4
%0$,180
/&'
0HQX/DQJXDJH
&ORFN
6WDUW6FUHHQ
0VJ&RQILJ
6ZLWFKWR23
7RJJOH
7RROV
+DUGZDUH
6RIWZDUH
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Programming IDEC SmartRelay
3.6 Overview of IDEC SmartRelay menus
IDEC SmartRelay Manual
62
The Text Display provides three menus as follows:
ವ
The Base Module selection menu
IDEC SmartRelay Manual
63
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
3.7
:riting and starting the circuit program
The example below shows how to create a program for your circuit design in IDEC
SmartRelay.
3.7.1
Selecting programming mode
:hen you connect IDEC SmartRelay to the power supply and switch it on, the display shows
you the main menu of the programming mode:
The first line is highlighted. Press and to move the highlight bar up and down. Move it to
and confirm with O.. IDEC SmartRelay opens the programming menu.
The IDEC SmartRelay
s programming menu is as shown below:
Here you can also move the highlight bar by pressing and . Move the highlight bar to ཱ
and confirm with O..
Programming IDEC SmartRelay
3.7 Writing and starting the circuit program
IDEC SmartRelay Manual
64
3.7.2
The first circuit program
The following parallel circuit consists of two switches.
Circuit diagram
The corresponding circuit diagram shows as follows:
Translated into an IDEC SmartRelay circuit program, you use an OR block to control relay K1
at output Q1.
Circuit program
Switch S1 connects to input I1 and switch S2 connects to input I2. Inputs I1 and I2 connect to
the OR block connectors.
The corresponding layout of the circuit program in IDEC SmartRelay shows as follows:
Note
Because you have not yet saved a password for the circuit program in IDEC SmartRelay, you
can directly enter editing mode. When you select to edit the program after you have saved a
password-protected circuit program, IDEC SmartRelay prompts you to enter a password and
to confirm it with OK. You can only edit the program after you have entered the correct
Password for circuit program protection (Page 70).
If you have created your circuit program in IDEC SmartRelay, you can view it in the circuit
program window by moving cursor on the blocks. IDEC SmartRelay can display a maximum
of 31*31 blocks in the circuit program window.
6
6
.
(
.
7KHVZLWFK6256WXUQVRQ
WKHORDG,'(&6PDUW5HOD\
LQWHUSUHWVWKLVSDUDOOHOFLUFXLWDV
DQ
25
ORJLFEHFDXVH625
6VZLWFKHVRQWKHRXWSXW
25
,
,
4
ุ
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
65
Programming IDEC SmartRelay
3.7 Writing and starting the circuit program
Wiring
The corresponding wiring shows as follows:
S1 switches input I1, while S2 switches input I2. The load connects to the relay Q1.
3.7.3
Circuit program input
You can now write the circuit program, starting at the output and working towards the input.
IDEC SmartRelay initially shows the output:
You will see a solid square at Q1, which is the cursor. The cursor indicates your current
position in the circuit program. You can move the cursor by pressing the , , and keys.
Now press the key. The cursor moves to the left.
/
1
,
,
,
,
,
,
,
,
4
4
4
4
/
1
6
6
/
1
4
,Q
4
7KHILUVW,'(&6PDUW5HOD\RXWSXW
4
4
,Q
7KHFXUVRULQGLFDWHV\RXUFXUUHQW
SRVLWLRQLQWKHFLUFXLWSURJUDP
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Programming IDEC SmartRelay
3.7 Writing and starting the circuit program
IDEC SmartRelay Manual
66
At this point you enter only the first (OR) block. Press OK to select editing mode.
The cursor now appears as a flashing solid square. IDEC SmartRelay offers you various
options here.
Select GF (basic functions) by pressing the key until GF appears, and confirm with OK.
IDEC SmartRelay now shows the first block from the list of basic functions:
Press OK to select editing mode, which causes IDEC SmartRelay to display the cursor as a
flashing solid square. Now press or until the OR block appears on the display:
Press OK to confirm your entries and exit the dialog.
You have now entered the first block. IDEC SmartRelay automatically assigns a block
number to each new block. If you assign a name to the block, IDEC SmartRelay shows the
block name instead of the block number. You can assign a block name as required:
Press to move the cursor to "B1".
Press OK and the cursor is now displayed as a flashing solid square. Now you can press
and to list the alphabet, numbers and special characters, either in ascending or descending
order. For more information on the available character set, refer to Section "Assigning a
circuit program name (Page 69)".
4
4
,
7KHFXUVRULVGLVSOD\HGDVD
IODVKLQJVROLGVTXDUH\RXFDQQRZ
VHOHFWDFRQQHFWRURUDEORFN
%
$1'
4
,Q
,Q
,Q
,Q
7KH$1'LVWKHILUVWEORFNRIWKHEDVLF
IXQFWLRQOLVW7KHVROLGVTXDUHFXUVRU
SURPSWV\RXWRVHOHFWDEORFN
%
25
4
,Q
,Q
,Q
,Q
ุ
7KHIODVKLQJVROLGVTXDUHFXUVRUVWLOO
DSSHDUVRQWKHEORFN
%
25
4
,Q
,Q
,Q
,Q
ุ
4
%
ุ
IDEC SmartRelay Manual
67
Programming IDEC SmartRelay
3.7 Writing and starting the circuit program
After you complete the change, press OK to confirm.
You then connect the block inputs as follows:
Press to position the cursor on In1 and press OK to select editing mode.
Press or to select the digital input list. The first element of the digital input list is the "Input
1", namely "I1". You can press to move the cursor to the input number, and then use or
to select the desired input (I1 to I24).
After selecting I1, the display now shows as follows:
Press OK to confirm. You have now connected I1 to the input of the OR block.
Now you connect input I2 to the input of the OR block:
1. Move the cursor to In2: Press or
2. Switch to editing mode: Press OK
3. Select the digital input list: Press or
4. Move the cursor to the input number: Press
5. Select I2: Press or
6. Apply I2: Press OK
Note
Inputs F1, F2, F3, and F4 correspond to the four function keys on the optional Text Display.
More shift register bits (S1.1 to S4.8), blank connectors (X1 to X64) and analog memory
markers (AM1 to AM64) are available in the FL1F device series.
Network digital inputs (NI1 to NI64), network analog inputs (NAI1 to NAI32), network digital
outputs (NQ1 to NQ64), and network analog outputs (NAQ1 to NAQ16) are available for the
FL1F device series. IDEC SmartRelay does not include these inputs and outputs until you
configure them in a circuit program in WindLGC V8.0 and download the program to your
IDEC SmartRelay.
%
25
4
,
,Q
,Q
,Q
ุ
7KHGLVSOD\QRZVKRZV
%
25
4
,
,Q
,Q
,Q
ุ
%
25
4
,
ุ
4
%
ุ
,
,Q
,Q
,Q
Programming IDEC SmartRelay
3.7 Writing and starting the circuit program
IDEC SmartRelay Manual
68
You have now connected I2 to the second input of the OR block:
To invert an input, move the cursor to the relevant position, for example:
Confirm with OK.
Now press or to invert this input:
Next, press ESC.
You can review your first circuit program by pressing or to move the cursor through the
circuit program.
To exit circuit programming mode and return to the programming menu, press ESC
Note
You can invert individual inputs of the basic and special functions; that is, if an input carries a
logical "1" signal, you can cause the circuit program to output a logical "0". You can also
cause IDEC SmartRelay to invert a logical "0" signal to a logical "1".
Note
IDEC SmartRelay has now saved your circuit program to nonvolatile memory. The circuit
program remains in the IDEC SmartRelay memory until you explicitly delete it.
You can save the actual values of special functions in the case of a power outage assuming
that these functions support the "Retentive" parameter and that the necessary program
memory is available. By default, IDEC SmartRelay deactivates the "Retentive" parameter
when you insert a function; to use it, you must enable this option.
%
25
4
,
,
ุ
4
%
ุ
,
,Q
,
,Q
IDEC SmartRelay Manual
69
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
3.7.4
Assigning a circuit program name
?
@
A
B
C
^
_
`
ฏ
a
b
c
d
e
f
g
h
i
M
k
l
m
n
o
p
T
r
s
t
u
v
w
x
y
z
1HWZRUN
'LDJQRVWLFV
&DUG
6HWXS
6WDUW
3URJUDP
&OHDU3URJ
0HPRU\8VDJH
6HW3DUDPHWHU
(GLW3URJ
3URJ3DVVZRUG
3URJ1DPH
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
IDEC SmartRelay Manual
70
IDEC SmartRelay Manual
71
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
4. Confirm ཱ: Press O.
5. Press or to move up and down the alphabet to select your letters. Because Base
Module only provides uppercase letters for the password, you can Tuickly access letters
at the end of the alphabet (in this example, English) by using the button:
Press once to select =
Press twice to select <, etc.
The display appears as follows:
To enter a password of AA, for example, the procedure is the same as for entering the
name of the circuit program.
6. Select A: Press
7. Move to the next letter: Press
8. Select A: Press
The display now appears as follows:
9. Confirm the password: Press O.
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
IDEC SmartRelay Manual
72
Changing the password from Base Module
IDEC SmartRelay Manual
73
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
Deactivating the password from Base Module
To deactivate the password to allow, for example, another user to edit your circuit program,
you must know your current password (in our example ==).
To deactivate the password, follow these steps in the programming menu:
1. Move the cursor to : Press or
2. Confirm : Press O.
Enter your current password as described in steps 5 to 7 above. Confirm your entries with
O..
3. Move the cursor to ཱ: Press or
4. Confirm ཱ: Press O.
The display now shows:
Alternatively, you can also select ི and clear the password by leaving the input box
blank.
5. Press any key and IDEC SmartRelay returns to the programming menu.
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
IDEC SmartRelay Manual
74
Password: :rong Password
If you enter the wrong password and confirm the input with O., Base Module does not open
editing mode, and the display shows as follows:
In this case, press any key and IDEC SmartRelay returns to the programming menu. This
repeats itself over and over again until you enter the correct password.
3.7.6
Switching IDEC SmartRelay to RUN mode
To switch IDEC SmartRelay to RUN mode, follow these steps:
1. Return to the main menu: Press ESC
2. Move the cursor to : Press or
3. Confirm : Press O.. The display now shows:
4. Press to move the cursor to ཱ and press O..
IDEC SmartRelay runs the circuit program and shows the following display:
The start screen of IDEC SmartRelay displays one of the following:
ವ
Date and current time-of-day (only for versions with real-time clock). This element flashes
if you have not set the date and time.
ವ
Digital inputs
ವ
Parameter assignment menu
IDEC SmartRelay Manual
75
Programming IDEC SmartRelay
3.7 Writing and starting the circuit program
,
:HG
Ⴇ
Ⴑ
Ⴇ
Ⴑ
Ⴇ
Ⴑ
Ⴇ
Ⴑ
4
$,
$,
'LVSOD\ILHOGRI,'(&6PDUW5HOD\LQ581PRGH
6WDUWVFUHHQ
,QSXWV,WR,
,QSXWV,WR,
2XWSXWV4WR4
2XWSXWV4WR4
,QSXWV,WR,
2XWSXW4
$QDORJLQSXWV$,WR$,
$QDORJLQSXWV$,WR$,
3UHVV
3UHVV
3UHVV
3UHVV
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Programming IDEC SmartRelay
3.7 Writing and starting the circuit program
IDEC SmartRelay Manual
76
Viewing the analog value changes
You can view the value changes of each analog I/O in the form of a trend curve when IDEC
SmartRelay is in RUN mode. For example, to view the value changes of AI3, follow these
steps:
1. Switch IDEC SmartRelay to RUN mode.
2. Scroll the display to the AI screen form (3/9): Press or
3. Move the cursor to AI3: Press or
Ⴇ
Ⴑ
Ⴇ
Ⴑ
Ⴇ
Ⴑ
$4
$4
0
Ⴇ
Ⴑ
Ⴇ
Ⴑ
0
(6&&
$QDORJRXWSXWV$4WR$4
$QDORJRXWSXWV$4WR$4
3UHVV
3UHVV
3UHVV
3UHVV
3UHVV
0HPRU\PDUNHUV0WR0
0HPRU\PDUNHUV0WR0
0HPRU\PDUNHUV0WR0
0HPRU\PDUNHUV0WR0
0HPRU\PDUNHUV0WR0
FXUVRUNH\VIRUPDQXDOLQWHUYHQWLRQLQ
WKHFLUFXLWSURJUDP(6&NH\
0HPRU\PDUNHUV0WR0
0HPRU\PDUNHUV0WR0
$,
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
77
Programming IDEC SmartRelay
3.7 Writing and starting the circuit program
4. Press OK to confirm your selection. The display now shows the AI3 value changes in the
form of a curve, for example:
The display refreshes continuously and the curve shifts to the left of the display bit by bit.
You can press or to move the screen form to the left/right in order to view the earlier/
later value changes.
What is meant by: "IDEC SmartRelay is in RUN"?
In RUN mode, IDEC SmartRelay executes the circuit program. IDEC SmartRelay first reads
the status at the inputs, determines the status of the outputs by means of the circuit program,
and switches these on or off according to your settings.
This is how IDEC SmartRelay indicates the I/O status:
In this example, only the inputs I1and I15 and the outputs Q8 and Q12 are set "high".
Status indication on the display
Using the example, you can see how IDEC SmartRelay displays the input and output states:
$,
,
4
,QSXWRXWSXWVWDWXVLV
,
4
/
6
6
,
,
4
1
:KHQVZLWFK6LVFORVHGWKHVWDWXV
DWLQSXW,LVKLJK
,'(&6PDUW5HOD\FRPSXWHVWKH
RXWSXWVWDWHVE\PHDQVRIWKHFLUFXLW
SURJUDP
2XWSXW4 ಯರLQWKLVFDVH
:KHQ4 ಯರ,'(&6PDUW5HOD\
VHWVUHOD\4DQGWKHORDGFRQQHFW
HGWR4LVVXSSOLHGZLWKYROWDJH
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
IDEC SmartRelay Manual
78
3.7.7
Second circuit program
Up to this point, you have successfully created your first circuit program, assigned it a name,
and optionally a program password. In this section you will learn how to modify existing circuit
programs and how to use the special functions.
Using this second circuit program, you will learn how to perform the following tasks:
ವ
Add a block to an existing circuit program
ವ
Select a block for a special function
ವ
Assign parameters
Modifying circuits
IDEC SmartRelay Manual
79
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
3. Confirm : Press O.. The display now shows:
4. On the programming menu, move the cursor to ཱ: Press or
5. Confirm ཱ: Press O.. If reTuired, enter your password at the prompt and confirm with
O..
6. In the circuit program window, press O. to activate the cursor as a solid sTuare.
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
IDEC SmartRelay Manual
80
:hen you select a special or basic function block, IDEC SmartRelay shows you the relevant
function block and positions the solid sTuare cursor on the block. Press O. to enter the
editing mode, and the cursor appears as a flashing solid sTuare. Press or to select the
reTuired block.
Select your block (off-delay, see the next figure), and then press O.:
Press to move the cursor to Trg, and then press O..
Press or to select B1 and confirm with O..
IDEC SmartRelay automatically connects the uppermost input of the new block to B1, which
you had previously connected to 41. Note that you can only interconnect digital inputs with
digital outputs or analog inputs with analog outputs. IDEC SmartRelay otherwise removes the
old
block.
The off-delay block has two inputs and a parameter. At the top is the trigger input (Trg) you
use to start the off-delay time. In our example, the OR block B1 triggers the off-delay.
IDEC SmartRelay Manual
81
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
2. Switch to editing mode: Press O.
3. Press and to position the cursor.
4. Press and to modify the value at the relevant position.
5. Confirm your entries with O..
Setting the time
Set the time T 12:00 minutes:
1. Move the cursor to the first digit: Press or
2. Select the digit 1: Press or
3. Shift the cursor to the second digit: Press or
4. Select digit 2: Press or
5. Move the cursor to the unit: Press or
6. Select the timebase m (for minutes): Press or
7. Confirm your entries with O..
Showing/hiding parameters - the parameter protection mode
If you want to show/hide the parameter and allow/prevent its modification in parameter
assignment mode, follow these steps:
1. Move the cursor to -/: Press or
2. Switch to editing mode: Press O.
3. Select the protection mode: Press or
The display should now show:
4. Confirm your entries with O..
%
7 P
%
7 P
:KHQWKHSURWHFWLRQPRGHVKRZV
\RXFDQPRGLI\WKHWLPH7LQ
SDUDPHWHUDVVLJQPHQWPRGH
:KHQWKHSURWHFWLRQPRGHVKRZV
\RXFDQQRWPRGLI\WKHWLPH7
LQSDUDPHWHUDVVLJQPHQWPRGH
RU
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
IDEC SmartRelay Manual
82
Enabling/disabling retentivity
To decide whether you want to retain your current data after a power failure or not, follow
these steps:
1. Move the cursor to -/: Press or
2. Switch to editing mode: Press O.
3. Move the cursor to the retentivity setting: Press or
4. Select the retentivity setting: Press or
The display now shows:
5. Confirm your entries with O..
Verification of the circuit program
IDEC SmartRelay Manual
83
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
Closing the programming mode
:hen you finish programming, you can exit the programming mode by following these steps:
1. Return to the programming menu: Press ESC
2. Return to the main menu: Press ESC
3. Move the cursor to : Press or
4. Confirm : Press O.
IDEC SmartRelay is back in RUN mode:
3.7.8
Deleting a block
Consider the case where you want to delete the block B2 from your circuit program and
connect B1 directly to 41.
To delete this block, follow these steps:
1. Switch IDEC SmartRelay to programming mode.
(As a reminder, refer to the topic The four golden rules for operating IDEC SmartRelay
(Page 57)).
2. Select : Press or
1HWZRUN
'LDJQRVWLFV
&DUG
6HWXS
3URJUDP
6WDUW
:HG
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
IDEC SmartRelay Manual
84
3. Confirm : Press O.
4. Select ཱ: Press or
5. Confirm ཱ: Press O.
(If reTuired, enter your password and confirm with O..)
6. Press O. in the circuit program window, and the cursor now appears as a solid sTuare.
7. Move the cursor to the 41 block and then press O..
8. Move the cursor to B2, the input of 41, and confirm with O..
9. Now replace block B2 with block B1 at output 41.
ದ
Move the cursor to the 2 in B2: Press
ದ
Select
B1
: Press
ದ
Apply
B1
: Press O.
Result: IDEC SmartRelay deletes block B2 from the circuit and connects the output of B1
directly to output 41.
3.7.9
Deleting block groups
Consider the case where you want to delete blocks B1 and B2 from the second circuit
program example (refer to the Second circuit program (Page 78) topic).
To delete these two blocks from that program, follow these steps:
3URJ1DPH
&OHDU3URJ
0HPRU\8VDJH
3URJ3DVVZRUG
6HW3DUDPHWHU
(GLW3URJ
4
4
%
25
2II'HOD\
3DU
,
,
5
4
ุ
%
%
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
IDEC SmartRelay Manual
85
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
1. Switch IDEC SmartRelay to programming mode.
(As a reminder, refer to the topic The four golden rules for operating IDEC SmartRelay
(Page 57)).
2. To select : Press or
3. To confirm : Press O.
4. To select ཱ: Press or
5. To confirm ཱ: Press O.
(If reTuired, enter your password and confirm with O..)
6. Press O. in the circuit program window, and the cursor now appears as a solid sTuare.
7. Move the cursor to the 41 block and then press O..
8. Move the cursor to B2, the input of 41, and confirm with O..
9. Now set the blank connector at output 41 instead of block B2:
ದ
Select the blank connector: Press or
ದ
Apply the blank connector: Press O.
Result: IDEC SmartRelay deletes block B2 and all blocks that connect to B2 (in this case,
block B1) from the circuit.
1HWZRUN
'LDJQRVWLFV
&DUG
6HWXS
6WDUW
3URJUDP
3URJ1DPH
&OHDU3URJ
0HPRU\8VDJH
3URJ3DVVZRUG
6HW3DUDPHWHU
(GLW3URJ
4
4
%
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
IDEC SmartRelay Manual
86
3.7.10
Correcting programming errors
IDEC SmartRelay Manual
87
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
Programming IDEC SmartRelay
3.7 :riting and starting the circuit program
IDEC SmartRelay Manual
88
3.7.12
Defining the type of analog outputs
Analog outputs can be either 0..10V/0..20mA, which is the default, or 4..20mA.
To define the type of analog outputs, follow these steps starting from the programming menu:
1. Move the cursor to : Press or
2. Select : Press O.
3. Move the cursor to A4: Press or
4. Select A4: Press O.
5. Move the cursor to ཱ: Press or
6. Select ཱ: Press O.
IDEC SmartRelay shows the following display:
7. Move the cursor to the desired A4, and press O..
IDEC SmartRelay indicates the defined type for the analog channel by a circle with a dot.
8. Select either 0..10V/0..20mA (default) or 4..20mA: Press or
9. Confirm your selection: Press O..
1HWZRUN
'LDJQRVWLFV
&DUG
3URJUDP
6WDUW
6HWXS
$4LQ6WRS
$47\SH
$47\SH
$47\SH
$47\SH
$47\SH
$47\SH
$47\SH
$47\SH
$47\SH
$47\SH
$47\SH
$47\SH
ႣႭ
$47\SH
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]