Toshiba BACnet BCN001Z Function Manual
File Specifications
| Brand: | Toshiba |
| Category: | Inverter |
| Model: | BACnet BCN001Z (Function Manual), prK9pzXnKXoco |
| File Type: | |
| File Size: | — |
| Pages: | 19 pages |
Download PDF
Download Toshiba BACnet BCN001Z Manual (19 pages)Read Online:
Read the Toshiba BACnet BCN001Z Function Manual online using the built-in PDF viewer.
Key Pages of Document
BACnet® Option unit Function Manual BCN001Z NOTICE 1. Make sure that this instruction manual is delivered to the end user of BACnet® Option unit. 2. Read this manual before installing or operating the BACnet® Option unit. Keep it in a safe place for reference. 3. All information contained in this manual are subje ...
inverter. Before using BACnet® Option unit, carefully read this function manual in order to completely and correctly utilize its excellent performance. After reading this function manual, please keep ii handy for future reference. For details of its g ...
1. OVERVIEW ........................................................................................................................................... 3 2. NAMES AND FUNCTIONS ................................................................................................................... 3 2.1. Outline ................. ...
network. BCN001Z is applicable for VF-PS1 software version V620 or later. 2. Names and functions The drawing below shows names and functions of main parts. 2.1. Outline Connector to the inverter 0 Don't use this connecter ---+ Don't use t ...
The LED shows the present status of the network and error. •Layout of LED COM 2.1 ERR 2.2 2.3 2.4 2.5 I> COM (Green) __ O~F~F~--11--~0~F~F--11 ON JUUL_[ JUUUl !< 2s )« 1s) OFF OFF ERR (Red) 1s :- -: JlIU1Ilflf JUUL_[ _fl____Jl 11 __ 0=F'-'-F ___ 11.---00c.c.F'-F _ ic 2s )!C 1s3! 'c 1s 3; OFF A B c D E F G State LEDs Com ...
~ ID 0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 The DIP switch on the circuit board of the option is used to set a MSfTP MAC address. Each DIP switch is ON when it is flipped to the lower position. The MAC address must be unique and not match any other device on a network se ...
96 OFF ON ON OFF OFF OFFJOFF OFF 65 OFFi ON OFFIOFF OFF OFF OFF ON 97 OFF ON ON OFF OFFIOFFIOFFI ON 66 OFF! ON OFFiOFFiOFF OFF. ON OFF 98 OFF ON ON OFF OFF I OFF I ON !OFF 67 OFF ON OFFlOFF'OFFiOFF ON. ON 99 OFF ON ON OFF OFF I OFF I ON ON 68 OFFi ON IOFFlOFFIOFFI ...
3.1. Communication parameters ·!!:' Set up the inverter parameters as follows. To update, reset of inverter. If these parameters are not set to correct value, this unit can not work normally. Title Function Description Factory setting 0: AUTO adaptive, 1: 9600bps,2: 19200bps, f831 Network Baudrate (*1) (*2) 3: 38400bps ...
Set the network baudrate to F 8 3 1 . Set the same baudrate in the network. If set AUTO baudrate. the option unit detects network baudrate automatically. 3.3. Network error detection (f832, f851, f852) Set the network communication loss action time to r 8 3 2. The network loss detection starts from the first rece ...
4.1. Object I Property support Matrix This option board supports below table objects and properties. Object Type Property Device Binary Binary Binary Analog Analog Analog Input Output Value Input Output Value Object Identifier ,/ ,/ ,/ ,/ ,/ ,/ ,/ O ...