Siemens 3AH Instructions, Installation, Operation, Maintenance
Text of the manual
Vacuum Circuit Breaker
Operator Module
Type 3AH
4.16kV to 38kV
Instructions
Installation
Operation
Maintenance
SGIM-9918
Medium-Voltage
Equipment
The information contained herein is general in nature and not intended for
specific application purposes. It does not relieve the user of responsibility
to use sound practices in application, installation, operation, and mainte-
nance of the equipment purchased. Siemens reserves the right to make
changes in the specifications shown herein or to m
Table of Contents
Vacuum Circuit Breaker Operator Module
1
Introduction and Safety ........................................................3
Introduction ..............................................................................3
Qualified Person .......................................................................3
Signal Words ....
Introduction and Safety
Introduction
The 3AH family of vacuum circuit breakers is designed to
meet all the applicable ANSI, NEMA and IEEE standards.
Successful application and operation of this equipment
depends as much upon proper installation and mainte-
nance by the user as it does upon the careful design and
fabrication by Siemens.
The purpose of this In
Receiving, Handling and Storage
Introduction
This manual covers the Receiving, Handling and Storage
instructions for Type 3AH vacuum circuit breakers shipped
separately from the switchgear. This section of the manual
is intended to help the user identify, inspect and protect
the circuit breaker prior to its installation.
Receiving Procedure
Make a physical
Installation Checks and Initial Functional Tests
Introduction
This section provides a description of the inspections,
checks and tests to be performed on the circuit breaker
module only.
Inspections, Checks and Tests without Control Power
Vacuum circuit breakers are normally shipped with their
primary contacts open and their springs discharged. How-
ever, i
The Type 3AH vacuum circuit breaker operator is intended
for application in a drawout truck for use in medium volt-
age metal-clad switchgear. The 3AH circuit breaker con-
forms to the requirements of ANSI Standards, including
C37.20.2, C37.04, C37.06, C37.09 and C37.010.
3AH circuit breakers consist of three va
The operating principle of the 3AH vacuum interrupter is
simple. Figure 3 is a cutaway view of a typical vacuum
interrupter. The entire assembly is sealed after a vacuum
is established. The interrupter stationary contact is con-
nected to the upper disconnect stud of the circuit breaker.
The interrupt