Document No. 155-517P25

Rev. 1, July, 2000 Reversing Actuators ISO 9001 REGISTERED FIRM ® EA0511R1 Siemens Building Technologies, Inc. Description SQM5... reversing actuators are used for the positioning of flow control valves, butterfly valves, dampers, or any application requiring rotary motion. The SQM5… actuators accommodate control input signals of 4-20 mA, 0-135 Ω, 0-10 Vdc, 0-20 mA, position proportional and float
Document No. 155-517P25 Rev. 1, July, 2000 Page 2 Siemens Building Technologies, Inc. Features, Continued • Connections for both base and face mounting • Low hysteresis actuator and potentiometer gearing • Externally visible position indication • Selection of input and output signals • Zero and span adjustment • Field exchangeable circuit boards and potentiometers • Electronic damper linearization function • Split ran

SQM5… Reversing Actuators

Technical Instructions 155-517P25 Rev. 1, July, 2000 Siemens Building Technologies, Inc. Page 3 Application SQM5… actuators are uniquely suited for both industrial and commercial applications. The high level of accuracy permits precise modulating control of industrial process and process heating applications, often significantly enhancing performance and product quality. In commercial and industrial burner applications requiri
Document No. 155-517P25 Rev. 1, July, 2000 Page 4 Siemens Building Technologies, Inc. Table 2. Product Numbers for Accessories. Electronic circuit boards AGA56.1A97 24-250 Vac (A) board for SQM5x.xxxxxAx AGA56.9A87 24 Vac (Z) board for SQM5x.xxxxxZx AGA56.9A17 120 Vac (Z) board for SQM5x.xxxxxZx AGA56.9A27 220 Vac (Z) board for SQM5x.xxxxxZx AGA56.41A87 24 Vac (G) board for SQM5x.xxxxxGx AGA56.41A17 110 Vac (G) board for SQM5x.xxxxx
SQM5… Reversing Actuators Technical Instructions 155-517P25 Rev. 1, July, 2000 Siemens Building Technologies, Inc. Page 5 Product Number Identification Legend For actuator identification only. To select product numbers for ordering, see Table 1. SQM5 0 . 4 8 0 R 1 Z 3 Actuator family Torque in-lb @ 60 (50) Hz. 0 90 for 8 (10) sec. running time 0 140 for 12 (15), 25 (30), 37 (45) sec. 3 200 for 25 (30) sec. 6 310 for 37 (45) sec. 6 400 for 50 (60), 7
Document No. 155-517P25 Rev. 1, July, 2000 Page 6 Siemens Building Technologies, Inc. Installation and Operation Instructions SQM5… actuators are generally shipped without the shaft installed. To install the selected shaft: 1. Loosen the two screws on the actuator cover corners. See Figure 2. 2. Lift the screws and raise the cover. See Figure 3. Shaft Installation EA0564R1 Figure 2. EA0568R1 Figure 3. 3. Each shaft is supplied wit
SQM5… Reversing Actuators Technical Instructions 155-517P25 Rev. 1, July, 2000 Siemens Building Technologies, Inc. Page 7 8. Place the second washer onto the “insert end” of the shaft. Using spreading pliers, install the “C” clip. Rotational Direction Verification Most SQM5… actuators are factory configured for counterclockwise (ccw), minimum to maximum rotation when facing the gear end of the actuator, or clockwise (cw) rotation when facing t
Document No. 155-517P25 Rev. 1, July, 2000 Page 8 Siemens Building Technologies, Inc. Switch Adjustment, continued NOTE: SQM5x.xxxxxAx actuators may be adjusted between 0° and 160°. SQM5x.xxxxxx3 actuators have a 90° potentiometer and the switches must be adjusted only between 0 and 90°. SQM5x.xxxxxx4 actuators have a 135° potentiometer and the switches must be adjusted only between 0 and 135°. Shaft Adjustment See Figure 6.
SQM5… Reversing Actuators Technical Instructions 155-517P25 Rev. 1, July, 2000 Siemens Building Technologies, Inc. Page 9 Wiring, continued A L Z N AGA56.1A97 SW1 MAN AUTO SW 2 1 2 1 2 13 11 21 M I II III IV V II III I IV...VIII "economy" minimum maximum auxilliary 12 22 13 23 14 15 24 25 ASZ... 3 4 5 EA0555R2 Figure 7. Basic Functional Diagram of AGA56.1… 0 A Z L AUTO. MAN. AGA56.1A97 EA0554R2 Figure 8. AGA56.1A97 Terminal/Auto-Manual Board. AGA56.4
Document No. 155-517P25 Rev. 1, July, 2000 Page 10 Siemens Building Technologies, Inc. MAX MIN OPE MAX MIN A L Z LR AGA56.4... N REG MAX MIN MIN MAX Y SW1 MAN AUTO SW 2 Y M Y- Y+ AGA56.41... (4...20 mA) AGA56.42... (0...135 Ohm) AGA56.43... (0...10 V) (+2 V) 0...2 V 135 Ohm M Y U 1 2 3 13 11 21 12 22 13 23 M I II III IV V II III I IV...VIII "economy" minimum maximum auxilliary ASZ... (1000 Ohm) 4 5 14 15 24 25 EA0556R2 13 ZL 51 N Fig
SQM5… Reversing Actuators Technical Instructions 155-517P25 Rev. 1, July, 2000 Siemens Building Technologies, Inc. Page 11 AGA56.9… circuit boards. See Figures 11 and 12. 1. Connect line voltage to terminal L. Terminal L must be powered at all times. 2. Connect neutral to terminal N. 3. Connect ground to the terminal located to the right of the auto/manual switch. 4. For applications where terminals Z, ZL and A are not used, bridge terminals L1 and L.
Document No. 155-517P25 Rev. 1, July, 2000 Page 12 Siemens Building Technologies, Inc. M U4 Y1 Y2 Y3 Y0 0 MAN. AUTO. L Z A L1 ZL N P 3-POSITION SWITCH JUMPERS OPE MAX MIN 1 2 J1 LIN 1 2 J2 U1...U3 MAX POS MIN POT. METERS AGA56.9A... U1 2 3 M ZF M U U EA0558R2 Figure 12. AGA56.9… Terminal and Trim Potentiometer/ Jumper Board. Commissioning Power Actuator Set the auto/manual switch in the manual position and apply power to
SQM5… Reversing Actuators Technical Instructions 155-517P25 Rev. 1, July, 2000 Siemens Building Technologies, Inc. Page 13 Example of limit switch I and III and trim potentiometer settings Switch III setting Switch I setting 0 deg. EA0562R1 MIN trim potentiometer setting MAX trim potentiometer setting 90 deg. Figure 13. Switch cam and trim potentiometer setting. NOTE: The actual minimum and maximum modulating range is determined either by the setting of
Document No. 155-517P25 Rev. 1, July, 2000 Page 14 Siemens Building Technologies, Inc. Features of SQM5x.xxxxxZx Actuators SQM5xx.xxxxxZx actuators contain the AGA56.9A… multi function circuit board. This circuit board provides the following features: Multiple Input Signals The AGA56.9A… circuit board accepts the following input signals: Line voltage • Power to A drives the actuator open to the setting of switch cam I (Maximum
SQM5… Reversing Actuators Technical Instructions 155-517P25 Rev. 1, July, 2000 Siemens Building Technologies, Inc. Page 15 maximum signal is present on Y0, Y1, Y2, or Y3, then the actuator will modulate through the full rotational range in response to a 4 to 12 mA signal applied at ZF. (Maximum signal can be easily achieved by bridging terminals U4 and Y0.) See Figure 16. NOTE: It is possible to configure the actuator for split range operation 12 to 4 mA
Document No. 155-517P25 Rev. 1, July, 2000 Page 16 Siemens Building Technologies, Inc. Features of SQM5x.xxxxxAx Actuators Input Signals The AGA56.1A97… circuit boards accept the following additional input signal: Line voltage • Power to A drives the actuator open to the setting of switch cam I (Maximum). • Power to Z drives the actuator closed to the setting of switch cam II (Economy). • Power to switch III, terminal 3 dri
SQM5… Reversing Actuators Technical Instructions 155-517P25 Rev. 1, July, 2000 Siemens Building Technologies, Inc. Page 17 6. Reconnect the brown wire to the left terminal and the blue wire to the right terminal. The black wire remains connected to the middle terminal. 7. See Figure 6. Remove the white plastic actuator position-indicating dial by gently pulling while rotating in the clockwise direction. 8. The actuator position indicating pointer, locate
Document No. 155-517P25 Rev. 1, July, 2000 Page 18 Siemens Building Technologies, Inc. AGA56.41/42/43 Circuit Board Installation 1. Remove the AGA56.41/42/43… circuit board from the packaging. The circuit board is shipped as one board. 2. Separate the board at the perforation by holding the circuit board at both ends and gently bending the board until it separates. 3. Move the terminal section containing the auto/manual switch to t
SQM5… Reversing Actuators Technical Instructions 155-517P25 Rev. 1, July, 2000 Siemens Building Technologies, Inc. Page 19 AGA56.41/42/43 Circuit Board Installation, continued 9. Make the following connections to the actuator: See Figure 22. a. Connect the black wire, marked “1” from the circuit board to switch I, terminal 1. b. Connect the yellow wire, marked “2” from the circuit board to switch II, terminal 2. c. Connect the white wire, marked
Document No. 155-517P25 Rev. 1, July, 2000 Page 20 Siemens Building Technologies, Inc. AGA56.9A… Circuit Board Installation, continued 4. Guide the base circuit board from the switch housing side of the actuator into the bottom of the circuit board mounting bracket. See Figure 23. 5. Re-install the actuator motor capacitor. See Figure 24. 6. Connect the blue neutral wire, shipped loose with the AGA56.9A…, to the spade connector