Siemens SQM5 Technical Instructions
Text of Siemens SQM5 Technical Instructions
Document No. 155-517P25
Rev. 1, July, 2000
Reversing Actuators
ISO 9001
REGISTERED FIRM
®
EA0511R1
Siemens Building Technologies, Inc.
Description
SQM5... reversing actuators are used for the positioning of flow control valves, butterfly
valves, dampers, or any application requiring rotary motion. The SQM5… actuators
accommodate control input signals of 4-20 mA, 0-135 Ω, 0-10 Vdc, 0-20 mA, position
proportional and float
Document No. 155-517P25 Rev. 1, July, 2000
Page 2
Siemens Building Technologies, Inc.
Features, Continued
•
Connections for both base and face mounting
•
Low hysteresis actuator and potentiometer gearing
•
Externally visible position indication
•
Selection of input and output signals
•
Zero and span adjustment
•
Field exchangeable circuit boards and potentiometers
•
Electronic damper linearization function
•
Split ran
SQM5… Reversing Actuators
Technical Instructions
155-517P25
Rev. 1, July, 2000
Siemens Building Technologies, Inc.
Page 3
Application
SQM5… actuators are uniquely suited for both industrial and commercial applications.
The high level of accuracy permits precise modulating control of industrial process and
process heating applications, often significantly enhancing performance and product
quality.
In commercial and industrial burner applications requiri
Document No. 155-517P25 Rev. 1, July, 2000
Page 4
Siemens Building Technologies, Inc.
Table 2. Product Numbers for Accessories.
Electronic circuit boards
AGA56.1A97
24-250 Vac (A) board for SQM5x.xxxxxAx
AGA56.9A87
24 Vac
(Z) board for SQM5x.xxxxxZx
AGA56.9A17
120 Vac
(Z) board for SQM5x.xxxxxZx
AGA56.9A27
220 Vac
(Z) board for SQM5x.xxxxxZx
AGA56.41A87
24 Vac
(G) board for SQM5x.xxxxxGx
AGA56.41A17
110 Vac
(G) board for SQM5x.xxxxx
SQM5… Reversing Actuators Technical Instructions
155-517P25
Rev. 1, July, 2000
Siemens Building Technologies, Inc.
Page 5
Product Number Identification Legend
For actuator identification only. To select product numbers for ordering, see Table 1.
SQM5
0
.
4
8
0
R
1
Z
3
Actuator family
Torque in-lb @ 60 (50) Hz.
0
90 for 8 (10) sec. running time
0
140 for 12 (15), 25 (30), 37 (45) sec.
3
200 for 25 (30) sec.
6
310 for 37 (45) sec.
6
400 for 50 (60), 7
Document No. 155-517P25 Rev. 1, July, 2000
Page 6
Siemens Building Technologies, Inc.
Installation and
Operation
Instructions
SQM5… actuators are generally shipped without the shaft installed. To install the
selected shaft:
1. Loosen the two screws on the actuator cover corners. See Figure 2.
2. Lift the screws and raise the cover. See Figure 3.
Shaft Installation
EA0564R1
Figure 2.
EA0568R1
Figure 3.
3. Each shaft is supplied wit
SQM5… Reversing Actuators Technical Instructions
155-517P25
Rev. 1, July, 2000
Siemens Building Technologies, Inc.
Page 7
8. Place the second washer onto the “insert end” of the shaft. Using spreading pliers,
install the “C” clip.
Rotational Direction
Verification
Most SQM5… actuators are factory configured for counterclockwise (ccw), minimum to
maximum rotation when facing the gear end of the actuator, or clockwise (cw) rotation
when facing t
Document No. 155-517P25 Rev. 1, July, 2000
Page 8
Siemens Building Technologies, Inc.
Switch Adjustment,
continued
NOTE:
SQM5x.xxxxxAx actuators may be adjusted between 0° and 160°.
SQM5x.xxxxxx3 actuators have a 90° potentiometer and the switches must be
adjusted only between 0 and 90°. SQM5x.xxxxxx4 actuators have a 135°
potentiometer and the switches must be adjusted only between 0 and 135°.
Shaft Adjustment
See Figure 6.
SQM5… Reversing Actuators Technical Instructions
155-517P25
Rev. 1, July, 2000
Siemens Building Technologies, Inc.
Page 9
Wiring, continued
A
L
Z
N
AGA56.1A97
SW1
MAN
AUTO
SW 2
1
2
1
2
13
11
21
M
I
II
III
IV
V
II
III
I
IV...VIII
"economy"
minimum
maximum
auxilliary
12
22
13
23
14
15
24
25
ASZ...
3
4
5
EA0555R2
Figure 7. Basic Functional Diagram of AGA56.1…
0
A
Z
L
AUTO.
MAN.
AGA56.1A97
EA0554R2
Figure 8. AGA56.1A97 Terminal/Auto-Manual Board.
AGA56.4
Document No. 155-517P25 Rev. 1, July, 2000
Page 10
Siemens Building Technologies, Inc.
MAX
MIN
OPE
MAX
MIN
A
L
Z
LR
AGA56.4...
N
REG
MAX
MIN
MIN
MAX
Y
SW1
MAN
AUTO
SW 2
Y
M
Y-
Y+ AGA56.41...
(4...20 mA)
AGA56.42...
(0...135 Ohm)
AGA56.43...
(0...10 V)
(+2 V)
0...2 V
135 Ohm
M
Y
U
1
2
3
13
11
21
12
22
13
23
M
I
II
III
IV
V
II
III
I
IV...VIII
"economy"
minimum
maximum
auxilliary
ASZ...
(1000 Ohm)
4
5
14
15
24
25
EA0556R2
13
ZL
51
N
Fig
SQM5… Reversing Actuators Technical Instructions
155-517P25
Rev. 1, July, 2000
Siemens Building Technologies, Inc.
Page 11
AGA56.9… circuit boards.
See Figures 11 and 12.
1. Connect line voltage to terminal L. Terminal L must be powered at all times.
2. Connect neutral to terminal N.
3. Connect ground to the terminal located to the right of the auto/manual switch.
4. For applications where terminals Z, ZL and A are not used, bridge terminals L1 and
L.
Document No. 155-517P25 Rev. 1, July, 2000
Page 12
Siemens Building Technologies, Inc.
M
U4
Y1
Y2
Y3
Y0
0
MAN.
AUTO.
L
Z
A
L1
ZL
N
P
3-POSITION
SWITCH
JUMPERS
OPE
MAX
MIN
1
2
J1
LIN
1
2
J2
U1...U3
MAX POS MIN
POT. METERS
AGA56.9A...
U1
2
3
M
ZF
M
U
U
EA0558R2
Figure 12. AGA56.9… Terminal and Trim Potentiometer/ Jumper Board.
Commissioning
Power Actuator
Set the auto/manual switch in the manual position and apply power to
SQM5… Reversing Actuators Technical Instructions
155-517P25
Rev. 1, July, 2000
Siemens Building Technologies, Inc.
Page 13
Example of limit switch I and III
and trim potentiometer settings
Switch III setting
Switch I setting
0 deg.
EA0562R1
MIN trim potentiometer setting
MAX trim potentiometer setting
90 deg.
Figure 13. Switch cam and trim
potentiometer setting.
NOTE:
The actual minimum and maximum
modulating range is determined either
by the setting of
Document No. 155-517P25 Rev. 1, July, 2000
Page 14
Siemens Building Technologies, Inc.
Features of
SQM5x.xxxxxZx
Actuators
SQM5xx.xxxxxZx actuators contain the AGA56.9A… multi function circuit board. This
circuit board provides the following features:
Multiple Input Signals
The AGA56.9A… circuit board accepts the following input signals:
Line voltage
•
Power to A drives the actuator open to the setting of switch cam I (Maximum
SQM5… Reversing Actuators Technical Instructions
155-517P25
Rev. 1, July, 2000
Siemens Building Technologies, Inc.
Page 15
maximum signal is present on Y0, Y1, Y2, or Y3, then the actuator will modulate through
the full rotational range in response to a 4 to 12 mA signal applied at ZF. (Maximum
signal can be easily achieved by bridging terminals U4 and Y0.)
See Figure 16.
NOTE:
It is possible to configure the actuator for split range operation 12 to 4 mA
Document No. 155-517P25 Rev. 1, July, 2000
Page 16
Siemens Building Technologies, Inc.
Features of
SQM5x.xxxxxAx
Actuators
Input Signals
The AGA56.1A97… circuit boards accept the following additional input signal:
Line voltage
•
Power to A drives the actuator open to the setting of switch cam I (Maximum).
•
Power to Z drives the actuator closed to the setting of switch cam II (Economy).
•
Power to switch III, terminal 3 dri
SQM5… Reversing Actuators Technical Instructions
155-517P25
Rev. 1, July, 2000
Siemens Building Technologies, Inc.
Page 17
6. Reconnect the brown wire to the left terminal and the blue wire to the right terminal.
The black wire remains connected to the middle terminal.
7. See Figure 6. Remove the white plastic actuator position-indicating dial by gently
pulling while rotating in the clockwise direction.
8. The actuator position indicating pointer, locate
Document No. 155-517P25 Rev. 1, July, 2000
Page 18
Siemens Building Technologies, Inc.
AGA56.41/42/43
Circuit Board
Installation
1. Remove the AGA56.41/42/43… circuit
board from the packaging. The circuit
board is shipped as one board.
2. Separate the board at the perforation
by holding the circuit board at both
ends and gently bending the board
until it separates.
3. Move the terminal section containing
the auto/manual switch to t
SQM5… Reversing Actuators Technical Instructions
155-517P25
Rev. 1, July, 2000
Siemens Building Technologies, Inc.
Page 19
AGA56.41/42/43
Circuit Board
Installation, continued
9. Make the following connections to the
actuator: See Figure 22.
a. Connect the black wire, marked “1”
from the circuit board to switch I,
terminal 1.
b. Connect the yellow wire, marked
“2” from the circuit board to switch
II, terminal 2.
c. Connect the white wire, marked
Document No. 155-517P25 Rev. 1, July, 2000
Page 20
Siemens Building Technologies, Inc.
AGA56.9A…
Circuit Board
Installation, continued
4. Guide the base circuit board from the
switch housing side of the actuator into
the bottom of the circuit board mounting
bracket. See Figure 23.
5. Re-install the actuator motor capacitor.
See Figure 24.
6. Connect the blue neutral wire, shipped
loose with the AGA56.9A…, to the
spade connector