System Sensor FAAST LT FL01 Series Quick Installation Manual
Text of the manual
The LT FL01 Series is part of the Fire Alarm Aspiration Sensing
Technology® (FAAST) family. FAAST is an advanced fire detection
system for use where early warning and very early warning are a
requirement. The system continuously draws air from the controlled
environment through a series of sampling holes to monitor th
Figure 4: How to Knock Out Cable
Gland Holes
Figure 3: Remove Backing to
Stick Cover Down
When label A is in place, remove the protector from the bottom of
the clear cover to stick the cover down, as shown in Figure 3:
Cable Access
Knock out cable gland holes where required. The
location of the cable gland holes is shown in Figure
Figure 7: Sequence (1 to 9) to Mount the Detector on the Bracket
Pipe Installation
1 2 3 4 5 6 7 8 9 10 1112131415161718
1 2 3 4 5 6 7 8 9
99 mm
41
1
2
mm
90 mm
4
3
0.00o
5
329 mm
6
7
7a
7b
7c
7d
8
9
2
1
Pipe Hole Configuration
Figure 8 below shows the pipe holes available on the unit. Each
unit has 2 pipe holes per channel connect
Power, Alarm and Control Connections
Figure 9: Inside the Detector
CHANNEL 2 FILTER
POWER AND
ALARM
CONNECTIONS
CHANNEL 1 FILTER
USB PORT
SENSOR COVER
POSITION FOR
TEST MAGNET
Exhaust Pipe
5
6
EARTH BAR
MOUNT
EARTH BAR
MOUNT
F-LT-EB
EARTH BAR
(OPTIONAL)
3
4
Note 1: All wiring should comply with local
requir
Table 2: Wiring Terminal Designations
(Note - Terminals marked CH2 will only be available on 2 channel
models)
Table 3: Relays
No.
Function
1
Ext Power In +
Primary PSU
T1
2
Ext Power In -
Primary PSU
3
Aux Power In +
Not used in default
4
Aux Power In -
Not used in default
5
NC Alarm Relay
CH1
T2
6
C Alarm Relay
CH1
7
NO Alarm Re
Figure 10: Front Panel Display
10b: FL0112E 1 Channel Detector (2 Sensors)
10a: FL0111E 1 Channel Detector (1 Sensor)
FRONT PANEL
The front panel will be different depending on which of the 3 FL01
models is being installed, and each is shown below.
The following information is displayed:
• Detector Status: Normal, Alarm, Fault
Table 4: Front Panel Indicators and Fault Descriptions
SENSOR
ASPIRATOR
ENSATION
E / INPUT
DISABLE
SOUNDER
FILTER
LOW FLOW
HIGH FLOW
INITIALIZATION
LEVEL 1
SMOKE
FAULT
FAULT
POWER
LEVEL 2
SMOKE
INITIALIZATION
ALARM
PREALARM
2
10
3
1
4
5
6
7
8
9
2
10
3
1
4
5
6
7
8
9
Figure 11: User Interface Buttons
Front Panel Buttons
The front pan
Password Sequence to Enter Maintenance Mode
Press and hold RESET; Left flow indicator will turn yellow, then
green.
Release RESET and FAULT indicator will switch on green. The
left flow indicator will blink green indicating the device is ready for
the first digit.
Press DISABLE to increment the LEDs 1…9; press TEST to select
a di