TouchStar Evolution Installation And Maintenance Manual

Text of the manual

EVOLUTION DOOR CONTROLLER

(RS-485 VERSION) INSTALLATION AND MAINTENANCE GUIDE MAN069-01 OCTOBER 2018

IMPORTANT SAFETY INFORMATION

This door controller has been designed to meet international safety standards but, like any electrical equipment, care must be taken if safety is to be assured. Read these safety instructions before installation and operation of the door controller. Retain this installation guide for future use.  DO DO DO

IMPORTANT SAFETY INFORMATION

2 POWER REQUIREMENT 2 INTRODUCTION INTRODUCTION 4 SITING THE DOOR CONTROLLER LOCATING THE DOOR CONTROLLER 5 CABLING 5 DIMENSIONS 5 DOOR CONTROLLER PCB CONNECTIONS PCB WIRING AND LINKS DIAGRAM PCB249ASX 6 CONNECTING A READER READERS 7 PIN PAD 7 CONNECTING A LOCK FAIL OPEN LOCK 8 RELAY CONTACTS 8 FAIL

This guide provides the information necessary to install a door controller. It includes

mounting and cabling requirements and instructions to enable the device to be commissioned. This door controller (as opposed to the standard Evolution door controller) communicates over RS RS RS RS----485 485 485 485 They are connected via 2 wire communicat

SITING THE DOOR CONTROLLER

LOCATING THE DOOR CONTROLLER... The door controller should be located in a position away from extremes of heat, dust vibration and fumes. It should be protected from excessive condensation, hosing and direct sunlight. Choose a location as near as possible to both Reader and the device to be operated, that will allow room for main

DOOR CONTROLLER PCB CONNECTIONS

Reader Power Lock RTE Button PCB249ASX with PCB251ASX fitted Sounder Reader

CONNECTING A READER

READERS... The main type of reader that the door controller is designed to use is proximity. However, it will also work with standard clock/data interface, magnetic stripe and barcode readers. Our most common readers are listed below together with connection details. NOTES: If wiegand input is required then LK9 LK9 LK9 LK9 is made and t

CONNECTING A LOCK

The relay contacts have in built protection against transient spikes but when using a pure inductive load with no back EMF protection, extra protection must be fitted. This can be in the form of a metal-oxide varistor (MOV) or diodes (supplied). The positive (+) supply of an inductive load should be connected to the cathode of the diode

CONNECTING A LOCK

FAIL CLOSED LOCK... The fail closed lock requires power to be applied to open it. If power fails, the door will be fail locked. The door controller applies power to the lock when a valid card is swiped. The lock is released and the door can be opened. This type of lock is suitable for the external doors of a building, although it should b

CONNECTING SWITCHES & I/O

OUTPUTS... These are open collector transistors which can drive a load connected to the internal 12V 12V 12V 12V supply or an external supply of up to 12V 12V 12V 12V. When the output is ON ON ON ON it can sink a current of 100mA 100mA 100mA 100mA. This example shows a siren connected to the internal 12V 12V 12V 12V supply. To us