WEG SSW-07 Operation & User’s Manual
Read Online
Read the WEG SSW-07 Operation & User’s Manual online using the built-in PDF viewer.
Text of the manual
Motors | Automation | Energy | Transmission & Distribution | Coatings
User's Manual
Manual del Usuario
Manual do Usuário
all-guides
com
Document: 0899.5832 / 14
English - Español - Português
SOFT-STARTER
USER’S MANUAL
MANUAL DEL
USUARIO DEL
ARRANCADOR
SUAVE
MANUAL DO
USUÁRIO DA
SOFT-STARTER
Español
English
Português
Summary of revisions / Sumario de las revisiones / Sumário das revisões
Español
English
Português
The information below describes the revisions in this manual.
Revision
Description
Chapter
1
First Edition
-
2
General Revision
-
3
General Revision
-
4
Size 4 Included
-
5 and 6
Table 3.1 and 8.2 corrected
3 and 8
7
Revision after the Size 4 UL certification.
Changed: item 3.2.3; 3.2.4.1; 3.2.4.2; 3.2.7;
4.8; 5.2; E77 in the table 6.1; table 8.1
3, 4, 5, 6
and 8
8
Included new functions of
software version V1.4x
3,4
and 5
9
General Revision
-
10
Change in table 7.1
7
11
General Revision
-
12
General Revision
-
13
E19 Included in the table 6.1
6
14
Changes in item 3.2.4
3
La información abajo describe las revisiones ocurridas en este manual.
A informação abaixo descreve as revisões ocorridas neste manual.
Revisão
Descrição
Capítulo
1
Primeira Edição
-
2
Revisão Geral
-
3
Revisão Geral
-
4
Inclusão da mecânica 4
-
5 e 6
Correções das tabelas 3.1 e 8.2
3 e 8
7
Correção depois da certificação UL da
Mecânica 4. Alterado: item 3.2.3; 3.2.4.1;
3.2.4.2; 3.2.7; 4.8; 5.2; E77 na tabela 6.1;
tabela 8.1
3, 4, 5,
6 e 8
8
Inclusão das novas funções da versão
de software V1.4x
3, 4 e 5
9
Revisão Geral
-
10
Alteração na tabela 7.1
7
11
Revisão Geral
-
12
Revisão Geral
-
13
Inclusão de E19 na tabela 6.1
6
14
Alterações no item 3.2.4
3
Revisión
Descripción
Capítulo
1
Primer Edición
-
2
Revisión General
-
3
Revisión General
-
4
Inclusión Mecánica 4
-
5 y 6
Correción de las tablas 3.1 y 8.2
3 y 8
7
Corrección luego de la certificación UL de la
Mecánica 4. Modificado: ítem 3.2.3; 3.2.4.1;
3.2.4.2; 3.2.7; 4.8; 5.2; E77 en la tabla 6.1;
tabla 8.1
3, 4, 5, 6
y 8
8
Inclusión de las nuevas funciones de la
version de software V1.4x
3, 4 y 5
9
Revisión General
-
10
Alteración en la tabla 7.1
7
11
Revisión General
-
12
Revisión General
-
13
Inclusión E19 en la tabla 6.1
6
14
Modificaciones en el ítem 3.2.4
3
1.1 Safety Notices in the Manual ................................................5
1.2 Safety Notices on the Product ..............................................5
1.3 Preliminary Recommendations .............................................5
CHAPTER 2
General Information
2.1 About this Manual ................................................................7
2.2 About the Soft-Starter SSW-07 ............................................7
2.3 Soft-Starter SSW-07 Identification Plate ............................8
2.4 Receiving and Storage .......................................................11
CHAPTER 3
Installation and Connection
3.1 Mechanical Installation .......................................................12
3.1.1 Environmental Conditions ............................................12
3.1.2 Soft-Starter SSW-07 Dimensions ................................12
3.1.3 Mounting Specifications ...............................................13
3.1.3.1 Mounting Inside a Panel .....................................14
3.1.3.2 Mounting on Surface ..........................................15
3.2 Electrical Installation ...........................................................15
3.2.1 Power Terminals ...........................................................16
3.2.2 Location of the Grounding, Control and Power
Connections ..................................................................17
3.2.3 Recommended Power and Grounding Cables ............18
3.2.4 Power Supply Connection to the Soft-Starter SSW-07 18
3.2.4.1 Short Circuit Capacity, Fuses, ................................
Circuit Breaker – UL ............................................19
3.2.4.2 Input Circuit Breakers and Fuses – IEC ..............20
3.2.4.3 Control Fuse ........................................................21
3.2.5 Soft-Starter SSW-07 Connection to the Motor .............22
3.2.5.1 Standard Three-Wire Connection .......................23
3.2.6 Grounding Connections ...............................................23
3.2.7 Control and Signal Connections ...................................24
3.3 Recommended Set-ups ......................................................25
3.3.1 Recommended Set-up with Command via Two-wire
Digital Inputs and Isolation Contactor ..........................26
3.3.2 Recommended Set-up with Command via Three-wire
Digital Inputs and Circuit-Breaker ................................26
3.3.3 Recommended Set-up with Command via Two-wire
Digital Inputs and Direction of Rotation .......................27
3.3.4 Recommended Set-up with Command via Two-wires
Digital Inputs and DC-Braking .....................................28
3.3.5 Symbols .......................................................................29
Setting the SSW-07
4.1 Control Type Setting ...........................................................30
4.2 Kick Start ............................................................................31
4.3 Initial Voltage Setting ..........................................................31
4.4 Current Limit Setting ...........................................................32
4.5 Acceleration Ramp Time Setting ........................................31
4.6 Deceleration Ramp Time Setting ........................................31
4.7 Motor Current Setting .........................................................32
4.8 Motor Electronic Overload Protection ................................33
4.9 Reset ..................................................................................36
4.10 DI2 Digital Input Setting ....................................................36
4.11 Output Relay Operation ....................................................37
4.12 Relay Output RL1 Programming ......................................37
CHAPTER 5
Programming Information and Suggestions
5.1 Applications and Programming ...........................................38
5.1.1 Voltage Ramp Starting .................................................39
5.1.2 Current Limit Starting ...................................................40
5.1.3 Starting with Pump Control (P202 = 2) ........................40
5.1.4 Programming the control type in pump control ............42
5.2 Protections and Programming ............................................43
5.2.1 Suggestion on How to Program the Thermal Class .....43
5.2.2 Service Factor ..............................................................45
CHAPTER 6
Solution and Troubleshooting
6.1 Faults and Possible Causes ...............................................49
6.2 Troubleshooting ..................................................................52
6.3 Preventive Maintenance .....................................................53
CHAPTER 7
Options and Accessories
7.1 IP20 Kit ...............................................................................54
CHAPTER 8
Technical Characteristics
8.1 Nominal Powers and Currents According to UL508 ...........55
8.2 Nominal Powers and Currents for Standard IP55,
IV Pole Weg Motor .............................................................55
8.3 Power Data .........................................................................56
8.4 Electronics and Programming Data ....................................56
This Manual contains the necessary information for the correct use
of the Soft-Starter SSW-07.
It was written to be used by qualified personnel with suitable training
or technical qualifications to operate this type of equipment.
The following safety notices will be used in the text.
DANGER!
The nonobservance of the procedures recommended in this warning
can lead to death, serious injuries and considerable material damage.
ATTENTION!
Failure to observe the recommended procedures in this notice may
lead to material damage.
NOTE!
The text intents to supply important information for the correct
understanding and good operation of the product.
The following symbols may be attached to the product as a safety
notice.
High Voltages.
Components are sensitive to electrostatic discharge.
Do not touch them.
Mandatory connection to ground protection (PE).
DANGER!
Only personnel with suitable qualification and familiar with the
Soft-Starter SSW-07 and associated equipment should plan or
implement the installation, start-up, operation and maintenance of
this equipment.
These personnel must follow all safety instructions in this manual
and/ or defined by local regulations.
Failure to follow these safety instructions may result in personnel
injury and/or equipment damage.
1.3 PRELIMINARY
RECOMMENDATIONS
CHAPTER 1 - SAFETY INSTRUCTIONS
6
English
NOTE!
In this Manual, qualified personnel are those trained to:
1. Install, ground, power-up, and operate the Soft-Starter SSW-07
according to this manual and the required safety procedures;
2. Use protection equipment according to established regulations;
3. Give First Aid.
DANGER!
Always disconnect the general power supply before touching any
electrical component associated to the Soft-Starter SSW-07.
High voltage may be present even after the power supply is
disconnected. Wait at least 3 minutes for the total discharge of the
capacitors.
Always connect the equipment’s heatsink to the protection ground
(PE), at the proper connection point.
ATTENTION!
All electronic boards have components that are sensitive to
electrostatic discharges. Do not touch these components or
connectors directly.
If necessary, first touch the grounded metallic heatsink or use a
suitable grounded wrist strap.
Do not apply any high voltage test on the Soft-Starter SSW-07!
If necessary, contact the manufacturer.
NOTE!
Soft-Starters SSW-07 may interfere with other electronic equipment.
Follow the measures in Chapter 3 to reduce these effects.
NOTE!
Read this manual completely before installing or operating the
Soft-Starter SSW-07.
NOTE!
For using this product in elevator applications be aware that it meets
elevator duty only in the USA market.
ATTENTION!
When in operation, electric energy systems – such as transformers,
converters, motors and cables – generate electromagnetic fields
(EMF), posing a risk to people with pacemakers or implants who
stay in close proximity to them. Therefore, those people must stay
at least 2 meters away from such equipment.
This manual presents the Soft-Starter installation, how to start it up,
its main technical characteristics and how to identify and correct the
most common problems. The manuals listed next must be consulted
in order to get more information regarding the functions, accessories
and working conditions:
�Programming Manual, with a detailed description of the
parameters and its functions;
�RS232 / RS485 Communication Manual.
�DeviceNet Communication Manual.
These manuals are supplied in electronic format on the CD-ROM
that accompanies the Soft-Starter, or can be obtained at WEG’s
web site: http://www.weg.net.
The Soft-Starter SSW-07 is a high performance product that permits
the start control of the three phase AC induction motors. Thus, it
prevents mechanical shocks on the load and current peaks in the
supply line.
para Ajustes
Tampa para
Trifásica
Opcionais Plug-In
Ajustes e Habilitar as
Proteções
DIP Swith para
Trimpots
Ajustes da
LED's para Indicação
DIP Switch para
Entrada de Alimentação
Reset (DI2 e DI3)
de Status da SSW-07
Classe Termica
Alimentação da Eletrônica
(A1 e A2)
Comanda Aciona/Desaciona
Motor (DI1) e
Saída para Motor
Saida a Relé
(13,14/23 e 24)
Three-phase
Power Supply
DIP Switch for
Soft-Starter adjustment
and protection enabling
Status Indication LEDs
of the SSW-07
Lid for optional Plug-in
Modules
Relay Output
(13, 14/23 and 24)
Motor Output
Electronic Power Supply
(A1 and A2)/
Start/Stop Command
of the Motor (D1) and
Reset (DI2 and DI3)
DIP switch to adjust
the Thermal Class
Trimpots to adjust
Figure 2.1 - Frontal view of the SSW-07
2.1 ABOUT THIS
MANUAL
2.2 ABOUT THE
SOFT-STARTER
SSW-07
CHAPTER 2
CHAPTER 2 - GENERAL INFORMATION
8
English
Figure 2.2 - Soft-Starter SSW-07 block diagram
2.3 SOFT-STARTER SSW-07 IDENTIFICATION PLATE
Figure 2.3 - Soft-Starter SSW-07 identification plate
Three-Phase
Power Supply
Control
Power Supply
Programmable
Digital Inputs
Programmable Digital
Outputs
Digital Signal
Processor
DSP
Three-Phase Motor
PE
R
S
T
A1
A2
Dl2
Dl3
13
14/23
24
Dl1
3 x
2 x
RL1
RL2
U
V
W
SSW-07 Model
Input Data (Voltage,
Number of Phases,
Current and Frequency)
Control Power Supply
Data (Voltage, Frequency)
Serial Number
Software
Version
Manufacturing date
(14 corresponds to
week and H to year)
WEG Stock
Item Number
CHAPTER 2 - GENERAL INFORMATION
9
English
Position of the Identification Plate on the Soft-Starter SSW-07:
Figure 2.4 - Location of the labels
X
VISTA FRONTAL
VISTA DE X
FRONTAL VIEW
X VIEW
CHAPTER 2 - GENERAL INFORMATION
10
English
EX
SSW-07
0017
T
5
S
_ _
_ _
_ _
Z
Market
BR = Brazil
EX = Export
WEG Soft-
Starter
Series
SSW-07
SSW-07
Nominal Current
0017 = 17 A
0024 = 24 A
0030 = 30 A
0045 = 45 A
0061 = 61 A
0085 = 85 A
0130 = 130 A
0171 = 171 A
0200 = 200 A
0255 = 255 A
0312 = 312 A
0365 = 365 A
0412 = 412 A
Three-
Phase
Power
Supply
220-575 Vac
Optional:
S = Standard
O = with
Optional
Degree of
Protection
Blank =
Standard
IP=IP20 (1)
Special
Hardware
Blank =
Standard
H1 = Electronics
supply: 110 to
130 Vac (2)
H2 = Electronics
supply: 208 to
240 Vac (2)
Special
Software
Blank =
Standard
S1 = Special
Software
End of
Code
HOW TO SPECIFY THE SSW-07 MODEL:
NOTE!
The option field (S or O) defines if the Soft-Starter SSW-07 will be a standard version or if it will include any optional. If standard, the
code ends here.
Always put the letter Z at the end. For example:
EXSSW070017T5SZ = Standard Soft-Starter SSW-07 with 17 A and 220 V to 575 V to three-phase input with the User’s Guide in
English, Spanish and Portuguese.
If there is any optional, the fields must be filled out in the correct sequence until the code is completed with the letter Z.
The standard product as defined by this code is described as:
�Degree of Protection: IP20 from 17 A to 85 A and IP00 from 130 A to 412 A.
(1) Only for models 130 A to 412 A.
(2) Only for the 255 A to 412 A models.
CHAPTER 2 - GENERAL INFORMATION
11
English
The Soft-Starter SSW-07 is supplied in a cardboard box. On the
outside of the package there is an identification plate which is
identical to the one placed on the Soft-Starter SSW-07.
To open the package:
1- Put it on a table;
2- Open the package;
3- Take out the Soft-Starter.
Check if:
The Identification plate of the Soft-Starter SSW-07 matches the
model purchased:
Damage has occurred during transport. If so, contact the carrier
immediately.
If the Soft-Starter SSW-07 is not installed immediately, store it in
its package in a clean and dry place with temperature between
-25 °C (-13 °F) and 65 °C (149 °F). 1 hour at -40 °C (-40 °F) is
permitted.
SSW-07
Model
Height
H
mm
(in)
Width
L
mm
(in)
Depth
P
mm
(in)
Volume
cm3
(in3)
Weight
kg
(lb)
17 A
24 A
30 A
221
(8.70)
180
(7.09)
145
(5.71)
5768
(352.2)
1.65
(3.64)
45 A
61 A
85 A
260
(10.24)
198
(7.80)
245
(9.65)
12613
(770.8)
3.82
(8.42)
130 A
171 A
200 A
356
(14.02)
273
(10.75)
295
(11.61)
28670
(1750)
8.36
(18.43)
255 A
312 A
365 A
412 A
415
(16.34)
265
(10.43)
320
(12.6)
35192
(2147)
12.8
(28.2)
Table 2.1 - Dimensions of the package in mm (in)
Figure 2.5 - Dimensions of the package
2.4 RECEIVING
AND STORAGE
INSTALLATION AND CONNECTION
This chapter describes the procedures for the electrical and
mechanical installation of the Soft-Starter SSW-07. The guidelines
and suggestions must be followed for the correct operation of the
Soft-Starter SSW-07.
The location of the Soft-Starters SSW-07 is an important factor to
assure the correct operation and high product reliability.
Avoid:
�Direct exposure to sunlight, rain, high moisture and sea air ;
�Exposure to explosive or corrosive gases and liquids;
�Exposure to excessive vibration, dust or any metallic and/or oil
particles in the air.
Allowed Environmental Conditions:
Surrounding air Temperature: 0 ºC to 55 ºC (32 ºF to 131 ºF) -
nominal conditions.
Relative air moisture: 5 % to 90 %, with no-condensation.
Maximum altitude: 1,000 m (3,300 ft) above sea level - nominal
conditions.
From, 1,000 m to 4,000 m (3,300 ft to 13,200 ft) above sea level -
current reduction of 1 % for each 100 m (330 ft) above 1,000 m
(3,300 ft).
From 2000 m to 4000 m (6,600 ft to 13,200 ft) above sea level -
voltage reduction of 1.1 % for each 100m (330 ft) above 2,000 m
(6,600 ft).
Pollution degree: 2 (according to the UL508).
Normally, only non conductive pollution. Condensation must not
cause conduction in the particles in the air.
The external dimensions and mounting holes are shown in figure
3.1 and table 3.1 below.
C
A
B
D
P
H
L
A
L
P
C
D
B
H
Figure 3.1 - SSW-07 dimensions
3.1 MECHANICAL
INSTALLATION
3.1.1 Environmental
Conditions
CHAPTER 3
3.1.2 Soft-Starter
SSW-07
Dimensions
CHAPTER 3 - INSTALLATION AND CONNECTION
13
English
Table 3.1 - Installation data with dimensions in mm (in)
To install the Soft-Starter SSW-07 leave at least the free spaces
surrounding the Soft-Starter as in figure 3.2 below. The dimensions
of these free spaces are described in table 3.2.
SSW-07 Model
A
mm
(in)
B
mm
(in)
C
mm
(in)
17 A
24 A
30 A
50
(2)
50
(2)
30
(1.2)
45 A
61 A
85 A
80
(3.2)
80
(3.2)
30
(1.2)
130 A
171 A
200 A
100
(4)
100
(4)
30
(1.2)
255 A
312 A
365 A
412 A
150
(6)
150
(6)
30
(1.2)
Table 3.2 - Recommended free spaces
Install the Soft-Starter SSW-07 in the vertical position according to
the following recommendations:
1) Install on a reasonably flat surface;
2) Do not put heat sensitive components immediately above the
Soft-Starter SSW-07.
ATTENTION!
If a Soft-Starter SSW-07 is installed on top of another use the
minimum distance A + B and diverge from the top Soft-Starter the
hot air that comes from the one beneath it.
3.1.3 Mounting
Specifications
* IP20 with optional.
SSW-07
Model
Height
H
mm
(in)
Width
L
mm
(in)
Depth
P
mm
(in)
A
mm
(in)
B
mm
(in)
C
mm
(in)
D
mm
(in)
Mounting
Screw
Weight
kg
(lb)
Degree
of
Protection
17 A
24 A
30 A
162
(6.38)
95
(3.74)
157
(6.18)
85
(3.35)
120
(4.72)
5
(0.20)
4
(0.16)
M4
1.3
(2.9)
IP20
45 A
61 A
85 A
208
(8.19)
144
(5.67)
203
(7.99)
132
(5.2)
148
(5.83)
6
(0.24)
3.4
(0.13)
M4
3.3
(7.28)
IP20
130 A
171 A
200 A
276
(10.9)
223
(8.78)
220
(8.66)
208
(8.19)
210
(8.27)
7.5
(0.3)
5
(0.2)
M5
7.6
(16.8)
IP00 *
255 A
312 A
365 A
412 A
331
(13.0)
227
(8.94)
242
(9.53)
200
(7.87)
280
(11.0)
15
(0.59)
9
(0.35)
M8
11.5
(25.4)
IP00 *
CHAPTER 3 - INSTALLATION AND CONNECTION
14
English
For Soft-Starters SSW-07 installed in panels or closed metallic
boxes exhaustion/cooling is required so the temperature does not
exceed the maximum allowed. Refer to dissipated nominal power
in table 3.3.
3.1.3.1 Mounting
Inside a Panel
Table 3.3 - Dissipated power for ventilator panel dimensioning
Figure 3.2 - Free spaces for ventilation
ATTENTION!
Independent conduits or cable trays must be planned for physic
separation of signal, control and power cables. (Refer to item 3.2
Electrical Installation).
C
SAIDA
FLUXO DE AR
B
A
ENTRADA
FLUXO DE AR
Air Flow
Inlet
Air Flow
Outlet
A
B
C
SSW-07
Model
Dissipated Power
in the electronics
(W)
Average Power
dissipated
10 starts/h
3 x In @ 30 s
(W)
Total Average Power
dissipated
10 starts/h
3 x In @ 30 s
(W)
17 A
12
15.3
27.3
24 A
12
21.6
33.6
30 A
12
27
39
45 A
12
41
53
61 A
12
55
67
85 A
12
77
89
130 A
12
117
129
171 A
12
154
166
200 A
12
180
192
255 A
12
230
242
312 A
12
281
293
365 A
12
329
341
412 A
12
371
383
CHAPTER 3 - INSTALLATION AND CONNECTION
15
English
Figure 3.3 shows the installation of the Soft-Starter SSW-07 on the
surface of a mounting plate.
3.1.3.2 Mounting on
Surface
Figure 3.3 - Installation procedures of the Soft-Starter SSW-07 on a surface
3.2 ELECTRICAL
INSTALLATION
DANGER!
The Soft-Starter SSW-07 cannot be used as an emergency stop
device.
DANGER!
Be sure that the AC input power is disconnected before making any
terminal connection.
ATTENTION!
The information below may be used as a guide to achieve a proper
installation. Follow also the applicable local standards for electrical
installations.
ATTENTION!
If a power isolating contactor or circuit breaker with minimum voltage
coil is not used at the first power on, then power up the electronics
first, adjust the trimpots that are necessary to put the SSW-07 into
operation and only after this energize the power section.
CHAPTER 3 - INSTALLATION AND CONNECTION
16
English
The power terminal blocks vary in size and configuration, depending
on the SSW-07 soft-starter model, as can be observed at the figures
3.5 and 3.6.
Terminals:
R / 1L1, S / 3L2 and T / 5L3: AC supply line.
U / 2T1, V / 4T2 and W / 6T3: Motor connection.
3.2.1 Power
Terminals
Figure 3.4 - Standard power/grounding connections
Line
Circuit-breaker
Fuses
R
S
T
R/1L1 S/3L2 T/5L3
U/2T1 V/4T2 W/6T3 PE
PE
PE
CHAPTER 3 - INSTALLATION AND CONNECTION
17
English
Figure 3.5 - Power terminals
Table 3.4 - Maximum torque for power connection
3.2.2 Location of the Grounding, Control and Power Connections
Figure 3.6 - Location of the grounding, control and power connections
Models 17 A to 85 A
Models 130 A to 412 A
Dimensions in mm (in).
SSW-07
Model
Enclosure
Size
Line / Motor
Grounding
Screw/
Terminal
Torque
Nm
(in lb)
Screw
Torque
Nm
(in lb)
17 A
24 A
30 A
Size 01
Terminal
3
(27)
M4
(5/32”)
4.5
(40)
45 A
61 A
85 A
Size 02
Terminal
5.5
(49)
M5
(3/16”)
6
(53)
130 A
171 A
200 A
Size 03
M8
(5/16”)
19
(168)
M6
(1/4”)
8.3
(73)
255 A
312 A
365 A
412 A
Size 04
M10
(3/8”)
37
(328)
Terminal
0.5
(4.5)
BORNE DE SAIDA
POTENCIA
BORNE DE ENTRADA
POTENCIA
BORNE DE ENTRADA
POTENCIA
BORNE DE SAIDA
POTENCIA
Output Power
Terminal
Input
Power Terminal
Output
Power Terminal
Input
Power Terminal
R/1L1
S/3L2
T/5L3
U/2T1
V/4T2
W/6T3
R/1L1 S/3L2 T/5L3
ATERRAM EN TO
ATERRAM EN TO
ATERRAM EN TO
C O N TRO LE
C O N TRO LE
C O N TRO LE
C O N TRO LE
ATERRAM EN TO
62.8
(2.48)
36.3
(1.43)
84,8
(3.34)
13.3
(0.52)
114
(4.48)
148
(5.81)
56.3
(2.22)
60.5
(2.38)
22.7
(0.89)
39.7
(1.56)
25.1
(0.99)
197
(7.75)
32.7
(1.29)
14.8
(0.59)
14.8
(0.59)
33.0
(1.30)
39.0
(1.54)
39.0
(1.54)
48.2
(1.90)
63.0
(2.48)
75.5
(2.97)
75.5
(2.97)
63.0
(2.48)
Grounding
Control
Control
Control
Control
Grounding
Grounding
Grounding
CHAPTER 3 - INSTALLATION AND CONNECTION
18
English
The described specifications in table 3.5 are valid only for the
following conditions:
�Copper wires for 70 ºC (158 ºF) with PVC insulation for ambient
temperature of 40 ºC (104 ºF), installed in perforated and not
agglomerated conduits.
�Naked or silver coated copper busbars with round edges with 1
mm radius with ambient temperature of 40 ºC (104 ºF) and bus
temperature of 80 °C (176 °F).
NOTE!
For correct cable dimensioning, consider the installation condition
and the maximum permitted line voltage drop.
SSW-07
Model
Power Cable
Grounding Cable
(mm2)
AWG
(mm2)
AWG
17 A
4
12
4
12
24 A
6
10
6
10
30 A
6
10
6
10
45 A
10
8
6
10
61 A
16
6
10
8
85 A
25
4
10
8
130 A
50
1
25
4
171 A
70
2/0
35
2
200 A
95
3/0
50
1
255 A
120
250 kcmil
2.5
14
312 A
185
350 kcmil
2.5
14
365 A
240
500 kcmil
2.5
14
412 A
300
600 kcmil
2.5
14
Table 3.5 - Minimum cable gauge specification
DANGER!
The AC input must be compatible with the voltage range of the
Soft-Starter SSW-07.
DANGER!
Provide a power supply disconnecting switch for the Soft-Starter
SSW-07. This disconnecting switch must disconnect the AC input
voltage to the Soft-Starter SSW-07 whenever necessary (for
example: during maintenance services).
If a disconnected switch or a contactor is inserted in the motor supply
line never operate these devices with the motor running or when
the Soft-Starter SSW-07 is enabled.
ATTENTION!
The overvoltage control in the line that feeds the soft-starter must
be done using overvoltage suppressors with a clamping voltage of
680 Vac (phase-to-phase connection) and an energy absorption
capability of 40 joules (17 A to 200 A models) and 80 joules (255 A
to 412 A models).
3.2.3 Recommended
Power and
Grounding
Cables
3.2.4 Power Supply
Connection to
the Soft-Starter
SSW-07
CHAPTER 3 - INSTALLATION AND CONNECTION
19
English
3.2.4.1 Short Circuit
Capacity,
Fuses, Circuit
Breaker – UL
NOTE!
Use the wire sizes and fuses recommended in tables 3.5 and 3.7.
The connector tightening torque is indicated in table 3.4. Use only
copper wires 70 °C (158 °F).
Table 3.6 presents the short circuit capacity, Standard Fault, of
the power supply (symmetric Arms) at which the SSW-07 can be
installed, provided that protected by means of regular fuses or circuit
breakers, used in the UL tests.
SSW-07
Model
Nominal
Rating
Short Circuit
Rating
≤ 600V
Circuit Breaker
(CB) - UL489
Any MCCB
Ultra-fast Fuses
Ferraz Shawmut/
Mersen
Flush End Contacts
Ultra-fast Fuses
Cooper Bussmann
Bolted Contacts
17 A
17 A
5 kA
< 30A
6.6URD30TTF0050
170M2611
24 A
24 A
5 kA
< 40A
6.6URD30TTF0080
170M1366
30 A
30 A
5 kA
< 40A
6.6URD30TTF0080
170M1366
45 A
45 A
5 kA
< 150A
6.6URD30TTF0100
170M1367
61 A
61 A
5 kA
< 150A
6.6URD30TTF0125
170M1368
85 A
85 A
10 kA
< 150A
6.6URD30TTF0200
170M1370
130 A
130 A
10 kA
< 225A
6.6URD31TTF0325
170M1372
171 A
171 A
10 kA
< 250A
6.6URD32TTF0450
170M3170
200 A
200 A
10 kA
< 250A
6.6URD32TTF0500
170M3171
255 A
255 A
18 kA
< 400A
6.6URD32TTF0400
170M5158
312 A
312 A
18 kA
< 400A
6.6URD33TTF0500
170M3171
365 A
365 A
18 kA
< 600A
6.6URD33TTF0550
170M5161
412 A
412 A
18 kA
< 600A
6.6URD33TTF0700
170M6161
Table 3.6 - Short circuit capacity – UL Standard Fault
The fuses in table 3.6 used in the SSW-07 UL tests are of the ultra-
fast (aR) type, which also reduce the risk of SCRs being burned by
over current transients.
Table 3.7, presents the short circuit capacity, High Fault, of the power
supply (symmetric Arms) at which the SSW-07 can be installed
within a closed panel, provided that protected by means of circuit
breakers, used in the UL tests.
CHAPTER 3 - INSTALLATION AND CONNECTION
20
English
SSW-07
Model
Nominal
Rating
Short
Circuit
Rating
≤ 480V
Circuit Breaker
(DIVQ)
Short Circuit
Rating
≤ 600V
Circuit Breaker
(DIVQ)
Minimum
Enclosure
Dimensions
(WxHxL) (mm)
17 A
17 A
65 kA
WEG ACW125W-FTU25-3 or
UBW225H-FTU30-3A or
HFD3030L
18 kA
UBW225H-FTU40-
3A or HFD3040L
800
600
300
24 A
24 A
65 kA
WEG ACW125W-FTU30-3
18 kA
UBW225H-FTU40-
3A or HFD3040L
800
600
300
30 A
30 A
65 kA
WEG ACW125W-FTU40-3
18 kA
UBW225H-FTU40-
3A or HFD3040L
800
600
300
45 A
45 A
65 kA
WEG ACW125W-FTU60-3
or UBW225H-FTU150-3A or
HFD3150L
18 kA
UBW225H-FTU40-
3A or HFD3040L
800
600
300
61 A
61 A
65 kA
WEG ACW125W-FTU60-3
or UBW225H-FTU150-3A or
HFD3150L
18 kA
UBW225H-FTU150-
3A or HFD3150L
800
600
300
85 A
85 A
65 kA
WEG ACW125W-FTU60-3
or UBW225H-FTU150-3A or
HFD3150L
18 kA
UBW225H-FTU150-
3A or HFD3150L
800
600
300
130 A
130 A
65 kA
WEG ACW250W-FTU250-3
or UBW225H-FTU225-3A or
HFD3225L
18 kA
UBW225H-FTU150-
3A or HFD3150L
800
600
300
171 A
171 A
65 kA
WEG ACW250W-FTU250-3 or
UBW250H-FTU250-3A
or HJD3250
30 kA
UBW225H-FTU225-
3A or HFD3225L
800
600
300
200 A
200 A
65 kA
WEG ACW250W-FTU250-3 or
UBW250H-FTU250-3A
or HJD3250
30 kA
UBW250L-FTU250-
3A or JDC3250
800
600
300
255 A
255 A
65 kA
WEG ACW400W-FTU400-3
or UBW400H-FTU400-3A or
HKD3400
30 kA
UBW250L-FTU250-
3A or JDC3250
1000
600
400
312 A
312 A
65 kA
WEG ACW400W-FTU400-3
or UBW400H-FTU400-3A or
HKD3400
30 kA
UBW400H-FTU400-
3A or HKD3400
1000
600
400
365 A
365 A
65 kA
WEG ACW800W-FTU800-3 or
UBW600H-FTU600-3A
or HLD3600
42 kA
UBW400H-FTU400-
3A or HKD3400
1000
600
400
412 A
382 A
65 kA
WEG ACW800W-FTU800-3 or
UBW600H-FTU600-3A
or HLD3600
42 kA
UBW600L-FTU600-
3A or LDC3600
1000
600
400
Table 3.7 - Short circuit capacity – UL High Fault
Ultra-fast fuses (aR), regular fuses or circuit breakers:
For Coordination Type 1, regular fuses or circuit breakers can be
used, according to IEC 60947-4-2, which will protect the installation
against short circuits, however, the SCRs will not be protected.
Circuit breakers of the table 3.6 and table 3.7.
For Coordination Type 2, the fuses to be used in the input must be
for protection of semiconductors, ultra-fast type (aR), according
to IEC 60947-4-2. They reduce the risk of the SCRs to burn out
because of overcurrent transients.
3.2.4.2 Input Circuit
Breakers and
Fuses – IEC
CHAPTER 3 - INSTALLATION AND CONNECTION
21
English
SSW-07
Model
I²t SCR
(A²s)
FNH aR
Blade Contacts
17 A
720
FNH1-63-K-A
24 A
4000
FNH00-80-K-A
30 A
4000
FNH00-100-K-A
45 A
8000
FNH00-125-K-A
61 A
10500
FNH00-160-K-A
85 A
51200
FNH00-250-K-A
130 A
97000
FNH1-400-K-A
171 A
168000
FNH2-500-K-A
200 A
245000
FNH2-630-K-A
255 A
90000
FNH3-500-K-A
312 A
238000
FNH3-710-K-A
365 A
238000
FNH3-710-K-A
412 A
320000
2 x FNH3-500-K-A
Table 3.8 - I²t of the SCR and aR Weg fuses
Ultra-fast fuses (aR), with l²t smaller than or equal to 75 % of the
value of the SCR indicated (A²s) in table 3.8.
NOTE!
The maximum I²t of the fuse of the SSWs varies according to the
design of the SCR used; therefore, higher rated currents may
present lower I²t.
The fuse rated current should preferably be equal to or higher than
the motor starting current in order to prevent cyclic overloads and
the tripping of the fuse in the prohibited area of the Time x Current
curve.
The proper sizing of the fuse should take into account: the local
standards for electrical installations, the starting cycle, number
of starts per hour, starting current and starting time, ambient
temperature and altitude.
For the correct sizing of the fuses, see WEG Fuse Catalog:
www.weg.net
Automation - Fuses aR and gL/gG - Type NH Blade Contact, NH
Flush End and Diametral.
Annex 1: Sizing Criteria for Ultra-Fast Fuses aR Blade Contact and
Flush End.
Annex 2: Table for aR Fuse Sizing to Protect SSW Soft-Starters
and CFW Inverters.
For the electronic supply protection of the SSW-07 must be used
fuse type D, or circuit breaker type C:
Fuse 2 A Type D or Circuit breakers 2 A Type C.
3.2.4.3 Control
Fuse
CHAPTER 3 - INSTALLATION AND CONNECTION
22
English
DANGER!
Power factor correction capacitors must never be installed at the
output of the Soft-Starter SSW-07. (U / 2T1, V / 4T2 and W / 6T3).
ATTENTION!
To ensure that the protections based on the current reading and
display operate correctly, for example the overload, the motor
nominal current must not be lower than 50 % of the nominal Soft-
Starter SSW-07 current.
NOTE!
Use the wire sizes and fuses recommended in tables 3.5, 3.6 and
3.7. The connector tightening torque is indicated in table 3.4. Use
only copper wires.
NOTE!
The Soft-Starter SSW-07 is provided with electronic protection
against motor overload. This protection must be set according to
the specific motor. When several motors are connected to the same
Soft-Starter SSW-07 use individual overload relays for each motor.
Line current of the Soft-Starter SSW-07 is equal to the motor current.
3.2.5 Soft-Starter
SSW-07
Connection to
the Motor
CHAPTER 3 - INSTALLATION AND CONNECTION
23
English
1/U1
4/U2
2/V1
5/V2
6/W2
3/W1
2/V1
5/V2
1/U1
4/U2
6/W2
3/W1
R
S
T
N
PE
R
S
T
N
PE
T
W
V
S
U
R
T
W
V
S
U
R
Figure 3.7 - Soft-Starter SSW-07 with standard connection
DANGER!
The Soft-Starter must be grounded for safety purposes (PE).
The ground connection must comply with the local regulations. Make
the ground connection to a grounding bar or to the general grounding
point (resistance ≤10 ohms).
DANGER!
The AC input for the Soft-Starter SSW-07 must have a ground
connection.
DANGER!
Do not use the neutral conductor for grounding purpose. Use
dedicated ground conductor.
ATTENTION!
Do not share the ground wiring with other equipment that operate with
high current (for examples: high voltage motors, welding machines,
etc.). When several Soft-Starters SSW-07 are used, observe the
connections in the figure 3.8.
3.2.6 Grounding
Connections
Figure 3.8 - Grounding connections for more than one Soft-Starter SSW-07
3.2.5.1 Standard
Three-Wire
Connection
BARRA DE ATERRAMENTO
INTERNA AO PAINEL
BARRA DE ATERRAMENTO
INTERNA AO PAINEL
GROUNDING BAR
INTERNAL TO THE PANEL
GROUNDING BAR
INTERNAL TO THE PANEL
CHAPTER 3 - INSTALLATION AND CONNECTION
24
English
3.2.7 Control
and Signal
Connections
EMI - Electronic Interference
The Soft-Starter SSW-07 is developed to be used in industrial
systems (Class A) according to Standard EN60947-4-2.
It’s necessary to have a distance of 0.25 m (10 in) between the
Soft- Starter SSW-07 control cables and motor cables.
Example: PLC wiring, temperature controllers, thermocouple cables, etc.
Grounding of the Motor frame
Always ground the motor frame. The Soft-Starter SSW-07 output
wiring to the motor must be installed separately from the input wiring
as well as from the control and signal wiring.
The control connections (digital inputs and relay outputs) are made
through the terminals (refer to figure 3.9).
Terminal
Description
Specifications
Torque Nm
(in lb)
A1
Electronics Supply
Voltage: 110 to 240 Vac (-15 % to +10 %)
(models from 17 A to 200 A)
110 to 130 Vac or 208 to 240 Vac
(-15 % to 10 %) (models from 255 A
to 412 A).
0.5 (4.5)
A2
Grounding
Only for the 255 to 412 A models
Terminal
Factory Default
Specifications
DI1
Starts/Stops Motor
3 isolated digital inputs
Voltage: 110 to 240 Vac (-15 % to +10 %)
Current: 2 mA Max.
DI2
Fault reset
DI3
Fault reset
13
Relay 1 output - Operation
Contact capacity:
Voltage: 250 Vac
Current: 1 A
14/23
Relay common point
24
Relay 2 output - Full voltage
Table 3.9 - Description of the control connector pins
Figure 3.9 - Control terminals of the Soft-Starter SSW-07
NOTE!
It is recommended to use shielded cables for the Dix inputs when
using long cables (above 30 m) in noisy environments. The metallic
shield and A2 must be grounded.
CHAPTER 3 - INSTALLATION AND CONNECTION
25
English
3.3 RECOMMENDED
SET-UPS
Some recommended set-ups are shown here and they can be
completely or partly used.
The main warning notes for all the recommended set-ups are
shown below and are described in the schemes by their respective
numbers.
NOTES!
The use of fuses or circuit breakers at the input circuit is
necessary for the entire installation protection. It is not necessary
to use ultra-fast fuses for the SSW-07 operation; however, their
use is recommended for the soft-starter complete protection.
The transformer “T1” is optional and must be used when there
is a difference between the line voltage and the electronic power
voltage.
In case that damage at the SSW-07 Soft-Starter power circuit
keeps the motor running (e.g., shorted thyristors), the motor
protection is obtained with the use of the power isolating
contactor (K1) or circuit breaker (Q1).
Start push-button.
Stop push-button.
Start/Stop switch. Bear in mind that when using two-wire digital
input command (normally open switch with retention), in case
of a power interruption, upon return of power, the motor will be
started immediately if the switch remains closed.
In case of maintenance of the Soft-Starter SSW-07 or the motor
it is necessary to remove the input fuses or disconnect the power
supply to ensure the complete equipment disconnection from
the power supply.
The emergency stop can be used by disconnecting the
electronics power supply.
Undervoltage release for the Q1 power isolation circuit breaker.
2
3
4
5
6
7
8
9
1
CHAPTER 3 - INSTALLATION AND CONNECTION
26
English
3.3.1 Recommended
Set-up with
Command
via Two-wire
Digital Inputs
and Isolation
Contactor
Figure 3.10 - Recommended set-up with commands via two-wire digital inputs
and isolation contactor
3.3.2 Recommended
Set-up with
Command
via Three-
wire Digital
Inputs and
Circuit- Breaker
Refer to notes in item 3.3.
NOTE!
It’s necessary to program the digital input DI2 for the three-wire
command function. Refer to item 4.10.
NOTE!
The RL1 shall be set to the “No fault” function. Refer to item 4.12.
Figure 3.11 - Recommended set-up with commands via three-wire digital
inputs and a circuit-breaker
Refer to notes in item 3.3.
24
14 23
13
DI3
RL1
RL2
T1
PE
R
S
T
K1
K1
DI2
DI1
A2
A1
M
3~
R S T
U V W
R
S
T
PE
M
3~
R S T
U V W
T1
Q1
24
14 23
13
DI3
RL1
RL2
DI2
DI1
A2
A1
Q1
CHAPTER 3 - INSTALLATION AND CONNECTION
27
English
3.3.3 Recommended
Set-up with
Command
via Two-wire
Digital Inputs
and Direction of
Rotation
Figure 3.12 - Recommended Set-up with Command via Two-wire Digital
Inputs and Direction of Rotation
NOTE!
To program the parameters shown above, is necessary the use of
keypad or serial communication. See the Programming Manual for
more information.
24
14 23
13
DI3
RL1
RL2
T1
PE
R
S
T
K1
K2
K2
K1
DI2
DI1
A2
A1
M
3~
R S T
U V W
P220 = 1
P230 = 1
P263 = 1 (DI1 = Start/Stop two
wires)
P265 = 4 (DI3 = Rotation
Direction)
P277 = 4 (RL1 = FWD/REV - K1)
P278 = 4 (RL2 = FWD/REV - K2)
P620 = 0 (RST phase sequence
= Inactive)
Refer to notes in item 3.3.
CHAPTER 3 - INSTALLATION AND CONNECTION
28
English
3.3.4 Recommended
Set-up with
Command via
Two-wires Digital
Inputs and DC-
Braking
Figure 3.13 - Recommended Set-up with Command via Two-wires Digital
Inputs and DC-Braking
NOTE!
To program the parameters shown above, is necessary the use of
keypad or serial communication. See the Programming Manual for
more information.
P220 = 1
P230 = 1
P263 = 1 (DI1 = Start/Stop two
wires)
P265 = 5 (DI3 = Brake Off)
P277 = 1 (RL1 = Running)
P278 = 5 (RL2 = DC-Braking)
P501 ≥ 1 (DC Braking Time ≥ 1s)
24
14 23
13
DI3
RL1
RL2
T1
PE
R
S
T
K1
K2
K2
K1
DI2
DI1
A2
A1
M
3~
R S T
U V W
Refer to notes in item 3.3.
CHAPTER 3 - INSTALLATION AND CONNECTION
29
English
3.3.5 Symbols
Electrical connection between
two signals
Fuse
Connection terminals
Thyristor/SCR
Relay or contactor coil
M
3~
Three-phase motor
Normally open contact (NO)
Transformer
Indicator light
N.O Contact (with retention)
Circuit-breaker
(opens under load)
Normally closed (NC)
push-button
Resistor
Normally open (NO)
push-button
Capacitor
Circuit-breaker with
undervoltage release
SETTING THE SSW-07
This chapter describes how to make the necessary settings for the
correct functioning of the SSW-07.
DIP Switch Control
Type Setting
Figure 4.1 - Control type setting
Select the type of starting control that best adapts to the application.
Voltage Ramp Starting:
This is the most commonly used method. Very easy to program
and set.
The Soft-Starter SSW-07 imposes the voltage applied to the motor.
Generally applied to loads with a lower initial torque or a square
torque.
This kind of control can be used as an initial working test.
Current Limit Starting:
The maximum current level is maintained during the start, being set
according to the application necessities.
Generally applied to loads with a higher initial torque or a constant
torque.
This kind of control is used to adapt the start to the capacity limits
of the supply network.
NOTES!
1. The Current Ramp control type, is only programmed using keypad
or serial communication. See the Programming Manual for more
details.
2. To program the control type in Pump control, see the Programming
Manual or item 5.1.4.
4.1 CONTROL
TYPE SETTING
CHAPTER 4 - SETTING THE SSW-07
31
English
4.2 KICK START
4.3 INITIAL
VOLTAGE
SETTING
Kick Start Enabling
DIP Switch
Figure 4.2 - Kick Start enabling
Soft-Starter SSW-07 offers a Kick Start function for loads that
present a large initial resistance to movement.
This function is enabled through the Kick Start DIP Switch. The
duration of the voltage pulse is set through the trimpot Kick Start
Time.
The voltage pulse applied is of 80 % Un during the programmed
trimpot Kick Start Time.
NOTE!
Use this function only for specific applications and where necessary.
Set the initial voltage to a value that the motor starts to run as soon
as the start command is given to the SSW-07.
The dot indicates
the factory default
setting
Initial Voltage
Setting Trimpot
Figure 4.3 - Initial voltage setting
CHAPTER 4 - SETTING THE SSW-07
32
English
4.4 CURRENT LIMIT
SETTING
NOTE!
The Initial Voltage trimpot has an initial voltage setting function only
when the kind of control is programmed to start with a voltage ramp.
This setting defines the maximum limit of the current during motor
starting in percentage of the nominal current of the Soft-Starter.
If the current limit is reached during the start of the motor, Soft-
Starter SSW-07 will maintain the current at this limit until the motor
reaches nominal speed.
If the current limit is not reached, the motor will start immediately.
The current limitation should be set to a level that the motor
acceleration can be observed, otherwise the motor will not start.
Current Limit
Setting Trimpot
Figure 4.4 - Current limit setting
NOTES!
If at the end of the acceleration ramp (set at the Trimpot Acceleration
Time), full voltage is not reached, a start timeout Fault will be shown.
This fault is indicated through the Fault LED flashing twice with the
Ready LED on.
The trimpot Current Limit has a Current Limit setting function only
when the kind of control is programmed to start with a Current Limit.
CHAPTER 4 - SETTING THE SSW-07
33
English
4.6 DECELERATION
RAMP TIME
SETTING
When Soft-Starter SSW-07 is programmed to Voltage Ramp control,
this is the voltage increment ramp time.
When Soft-Starter SSW-07 is programmed to Current Limit control,
this time is used as the maximum starting time, working as a
protection against blocked rotors.
Acceleration Ramp
Time Setting Trimpot
Figure 4.5 - Acceleration ramp time setting
NOTE!
The programmed acceleration time is not the exact motor
acceleration time, but the time of the voltage ramp or the maximum
starting time. The motor acceleration time depends on the motor
characteristics and the load.
Please consider that in cases where the relation of the SSW-07
current and the motor nominal current is 1.00, the maximum time
that the SSW-07 can work with 3 x In is 30 seconds.
Enables and sets the time of voltage decrease.
This setting should be used only for the deceleration of pumps to
reduce the water hammer. This setting must be made to achieve
the best pump performance.
NOTE!
This function is used to lengthen the normal deceleration time of a
load and not to force a lower time than that imposed by the load itself.
4.5 ACCELERATION
RAMP TIME
SETTING
CHAPTER 4 - SETTING THE SSW-07
34
English
4.7 MOTOR
CURRENT
SETTING
Deceleration Ramp
Time Setting Trimpot
Figure 4.6 - Deceleration ramp time setting
This setting defines the ratio of the SSW-07 current and the motor
current. The value of the setting is very important since it defines
the protection of the motor driven by the SSW-07. The setting of
this function interferes directly in the following motor protections:
-Overload;
-Overcurrent;
-Stall;
-Phase loss.
Calculation Example:
SSW-07 Used: 30 A
Motor Used: 25 A
Trimpot for the Motor Current Setting
Motor Current Setting = I motor
I SSW-07
Motor Current Setting = 25 A
30 A
Motor Current Setting = 0.833
Therefore it must be set at 83 %
CHAPTER 4 - SETTING THE SSW-07
35
English
4.8 MOTOR
ELECTRONIC
OVERLOAD
PROTECTION
Motor Current
Setting Trimpot
Figure 4.7 - Motor current setting
The motor electronic overload protection simulates the heating and
cooling of the motor, also known as thermal image. This simulation
uses as input data the True rms current.
When the thermal image passes the limit, the overload protection
trips and turns the motor off.
The adjustment of the thermal class is based on the motor locked
rotor current and locked rotor time. With this data it is possible to
find a point in the figure to determine, which thermal class protects
the motor. Please refer to figure 4.8 for cold stall time or to figure
4.9 for hot stall time. The thermal classes below the point protect
the motor.
CHAPTER 4 - SETTING THE SSW-07
36
English
Time t(s)
10000
1000
100
10
1
S.F.=1,15 1x 2x 3x 4x 5x 6x 7x 8x 9x 10x
Class 30
Class 25
Class 20
Class 15
Class 10
Class 5
x In motor
current
S.F.=1 1x 2x 3x 4x 5x 6x 7x 8x 9x
Figure 4.8 - Thermal classes of motor protection in cold condition
Time t(s)
1000
100
10
1
1x 2x 3x 4x 5x 6x 7x 8x 9x S.F.=1
Class 30
Class 25
Class 20
Class 15
Class 10
Class 5
x In motor
Current
0.1
Figure 4.9 - Motor protection thermal classes in hot condition at 100 % ln
CHAPTER 4 - SETTING THE SSW-07
37
English
Overload Protection
Enabling DIP Swicth
Thermal class adjustment DIP Switches
Figure 4.10 - Overload protection Enabling and Adjustment
NOTES!
Adjust the motor current according to chapter 4.7 for the correct
function of the overload protection;
This protection is based on Three Phase IP55 Standard WEG
motors. If your motor is different, we recommend to adjusting a
lower thermal class. For more details refer to chapter 5.2;
When SSW-07 is without the electronic supply voltage (A1 and
A2), the thermal image is saved internally. When the supply (A1
and A2) is reestablished, the thermal image returns to the value
prior to the electronic supply loss;
The RESET of the electronic overload protection can be set to
manual function (man). In this case the RESET must be made
via digital input 2 (DI2) or through the RESET key. If the RESET
setting is automatic (auto), the fault condition will automatically
be reset after the cooling time;
The thermal image is set to zero, when the overload protection
is disabled.
CHAPTER 4 - SETTING THE SSW-07
38
English
4.9 RESET
4.10 DI2 DIGITAL
INPUT SETTING
A fault condition can be reset using the RESET key at the front of
the SSW-07 or through a push-button (0.5 seconds) at DI3 (digital
input for RESET). Another way to reset the SSW-07 is by switching
Off/On the electronic power supply (A1 and A2).
NOTE!
The SSW-07 also allows for the possibility of automatic RESET by
enabling this function through the DIP Switch (auto):
Automatic RESET occurs after 15 minutes in the following
conditions:
-Overcurrent;
-Phase loss;
-Stall;
-Overcurrent before By-pass;
-Frequency out of range;
-Contact of the internal By-pass relay is open;
-Power control supply undervoltage;
-External fault.
For incorrect phase sequence there is no automatic RESET.
For electronic overload of the motor there is a specific algorithm
for the automatic RESET time.
In the factory default, the DI2 digital input has its function programmed
for the reset of faults. DI2 can also be programmed to work as a
three wire control.
The three wire control allows the Soft-Starter to be commanded
through two digital inputs, DI1 as an ON input and DI2 as an OFF
input. This allows for the direct placement of two push buttons.
Refer to item 3.3.2.
To change the DI2 digital input, follow the instructions below:
1. To enter in programming mode, maintain the reset key at the
front of the SSW-07 pressed for 5 seconds. Maintain the reset
key pressed during programming;
2. When in programming mode, two LEDs will turn on (overcurrent
and phase loss), indicating that DI2 is programmed for fault Reset.
When three LEDs turn on (overcurrent, phase loss and phase
sequence), it indicates that the DI2 is programmed for three wire
commands;
3. To change the programming to three wire commands, move the
overcurrent DIP Switch and return to the previous position. The
three LEDs will turn on, indicating that DI2 is programmed for
three wire commands;
4. To change the DI2 programming to fault Reset, move the Kick
Start DIP Switch and return to the previous position. Two LEDs
will turn on, indicating that the DI2 is programmed for fault Reset;
5. Programming is concluded when the reset key is released.
CHAPTER 4 - SETTING THE SSW-07
39
English
4.12 RELAY
OUTPUT RL1
PROGRAMMING
4.11 OUTPUT RELAY
OPERATION
�The relay of the Operation Function closes its N.O. contact
(13-14/23) every time the SSW-07 receives the enable command.
This contact is only opened at the end of the deceleration ramp
(when it is set via trimpot) or when the SSW-07 receives the
disable command.
�The relay of the Full Voltage Function closes the N.O. contacts
(14/23-24) every time the SSW-07 applies 100 % of the voltage to
the driven motor. This contact opens when the SSW-07 receives
the disable command.
(Motor Voltage)
UN
Operation Function
(13- 14/23)
Full Voltage Function
(14/23-24)
100 %
Relay on
t
t
t
Figure 4.11 - Output relay operation
In the factory default programming, the relay output RL1 has its
function programmed for “Operation”. RL1 (13/14) can be also be
programmed for the “No Fault” function. This function allows the
installation of a circuit breaker with an undervoltage release at the
SSW-07 input. Refer to figure 3.3.2. In order to change the relay
output RL1 programming follow these instructions:
1. To enter in programming mode keep the reset key, at the SSW-07
front cover, pressed during 5 seconds, keeping it also pressed
throughout the programming;
2. When in the programming mode two LEDs turn on (Overcurrent
and Phase Loss), indicating that DI2 is programmed for Error
Reset. If three LEDs turn on (Overcurrent, Phase Loss and Phase
Sequence), it indicates that DI2 is programmed for three-wire
command. If the Overload LED turns on, then the RL1 function
is “No Fault”, otherwise the function is “Operation”;
3. To modify the RL1 function change the Overload DIP Switch
and put it back in the previous position. The Overload LED will
indicate the new programmed function:
- Overload LED off: Operation function;
- Overload LED on: No Fault function.
PROGRAMMING INFORMATION AND SUGGESTIONS
This chapter helps the user to set the types of starting controls
according to their applications.
ATTENTION!
Suggestions and important notes for each type of starting control.
ATTENTION!
To know the correct programming of the parameters, have your
load data on hand and use the WEG (Soft-Starter) Dimensioning
Software available at WEG’s home page (http://www.weg.net).
If you are unable to use the software mentioned above, you can
follow some practical concepts described in this chapter.
Shown below are some characteristic curves with current and
starting torque behavior according to some kinds of control.
Current
Torque
T/Tn
I/In
Tn
Current
Torque
I/In
T/Tn
Tn
Figure 5.1 - Characteristic curves of torque and current in a direct on-line start
and by voltage ramp
CHAPTER 5 - PROGRAMMING INFORMATION AND SUGGESTIONS
41
English
5.1.1 Voltage Ramp
Starting
Current
Torque
T/Tn
Tn
I/In
Figure 5.2 - Characteristic curves of torque and current in a
current limitation start
1) Set the value of the initial voltage to a low value;
2) When a load is applied to the motor, set the initial voltage to a
value that makes the motor rotate smoothly from the instant it is
started.
3) Set the acceleration time with the necessary start time, initially
with short times, 10 to 15 seconds, and afterwards try to find the
best starting condition for the used load.
100 %Un
Start
U(V)
Disable
Voltage Ramp
Enable
t(s)
0
Figure 5.3 - Voltage ramp starting
NOTES!
With long starting times, or when the motor is without a load,
vibration can occur during the start of the motor, therefore lower
the starting time;
If faults occur during the start, check all the connections from the
Soft-Starter to the supply network, motor connections, supply
network voltage levels, fuses and circuit breakers.
CHAPTER 5 - PROGRAMMING INFORMATION AND SUGGESTIONS
42
English
5.1.2 Current Limit
Starting
1) To start with a current limitation it is necessary to start with a load.
Initial test without load can be done with a voltage ramp;
2) Set the acceleration time with the necessary starting time, initially
with short times, 20 to 25 seconds. This time will be used as the
stall time in case the motor does not start;
3) Set the current limit according to the conditions that your electric
installation allows, as well as to the values that supply enough
torque to start the motor. It can initially be programmed with values
between 2x and 3x the nominal current of the motor (ln of the motor).
I(A)
Start
I Limitation
I Nominal
Maximum Time
Current Limitation
0
t(s)
Enable
Disable
Figure 5.4 - Current limit starting
NOTES!
If the current limit is not reached during the start, the motor will
start immediately;
Very low Current Limit values do not provide sufficient torque to
start the motor. Always keep the motor rotating once it is started.
For loads that need a higher initial starting torque, the Kick Start
function can be used;
If faults occur during the start, check all the connections from the
Soft-Starter to the supply network, motor connections, supply
network voltage levels, fuses and circuit breakers.
1) To start with pump control a load is necessary. No-load tests can
be done with voltage ramp;
2) The starting parameters setting depend mainly on the types of
hydraulic installations. Thus we recommend optimizing factory
settings, if possible.
3) Check if the motor rotation direction is an indicated on the pump
frame. If not, connect the phase sequence as indicated at P620;
Figure 5.5 - Direction of rotation of a hydraulic centrifugal pump
5.1.3 Starting with
Pump Control
(P202 = 2)
CHAPTER 5 - PROGRAMMING INFORMATION AND SUGGESTIONS
43
English
4) Set the initial voltage - P101 – so the motor starts smoothly as
soon as it is enabled.
5) Set the acceleration time according to the application, and, that
the motor is able to start the load smoothly, but the required
acceleration is not exceeded. If acceleration times are set too
long, this may result in vibration or harmful motor overheating;
6) To check the correct starting process, always use a manometer
in the hydraulic installation. Pressure increase should not result
in sudden oscillations. Thus the pressure increase should be as
linear as possible;
Enable
0
100%Un
Start
Pump Control
P102
P101
U(V)
Figure 5.6 - Manometer showing pressure increase
7) Program the deceleration initial voltage (P103) only when no
pressure drop is detected at the deceleration begin. With this
deceleration initial voltage you can improve the linear pressure
drop during the deceleration;
8) Set the deceleration time according to the application, and,
ensuring that the pump stops smoothly within the expected
limits. The set of excessively long times may result in vibrations
or harmful motor overheating;
Pára
0
100%Un
Parada
P104
P105
t(s)
P103
U(V)
Figure 5.7 - Manometer showing the pressure drop
9) Generally, the current increases at the end of the deceleration ramp
and in this case the motor requires more torque to achieve a smooth
water flow stop. When the motor has already stopped, but is still
enabled, the current will increase too much. To prevent this condition,
set P105 to a value that as soon it stop it is also disabled;
CHAPTER 5 - PROGRAMMING INFORMATION AND SUGGESTIONS
44
English
10)Set P610 and P611 to current and time levels that prevent the
hydraulic pump from running without a load.
Disable
Enable
0
100%Un
Stop
Start
Pump Control
P104
P102
P105
t(s)
P103
P101
U(V)
Figure 5.8 - Start with pump control
NOTES!
1) If the hydraulic piping is not fitted with a manometer, the water
hammer can be noted at the pressure relief valves;
2) Please, consider that sudden line voltage drops results in motor
torque drops. Thus, ensure that the power supply line characteristics
are within the characteristics required for motor operation;
3) If errors are detected during the motor start, check all connections
of the Soft-Starter to the power line, the motor connections, the
voltage levels of the power line, the fuses, circuit-breakers and
disconnecting switches.
Is recommended program the control type in pump control using
keypad or serial communication, see the Programming Manual
for more details. In special cases, when is not available keypad or
serial communication, is also possible to program the control type
in pump control following these instructions:
1) To enter in programming mode, keep the reset key at the SSW-07
front cover pressed during 5 seconds, keeping it also pressed
throughout the programming;
2) When in the programming mode, LEDs will turn on indicating the
actual parameterization. See item 4.10 and 4.12;
3) To modify the control type, change the Stall DIP Switch and put
it back in the previous position. The Stall LED will indicate the
new programmed control type:
- LED Stall off: P219=0. Control type defined through Voltage
Ramp/Current Limit DIP Switch.
- LED Stall on: P219=2. Control type in Pump Control and
parameterization through Trimpots and DIP Switches.
5.1.4 Programming
the control type
in pump control
CHAPTER 5 - PROGRAMMING INFORMATION AND SUGGESTIONS
45
English
For each application exists a range of thermal classes, which might
be set. The overload protection should not trip during normal starting.
Therefore it is necessary to know the starting time and current, to
determine the minimum thermal class. The maximum thermal class
depends on the motor limit.
Determine the minimum thermal class:
1) Initially start at the standard thermal class, sometimes, but without
the motor overheating;
2) Determine the correct starting time and find an average of the
current using a multimeter with a current probe to measure it; A
current average can be found for any type of starting control;
For example:
Starting an 80 A motor using a voltage ramp. The current starts at
100 A and goes to 300 A, returning afterwards to the nominal value
in 20 seconds.
(100 A + 300 A)/2 = 200 A
200 A/80 A = 2.5 x ln of the motor
Therefore: 2.5 x ln @ 20 seconds.
Motor
Current
P102
Accel Time
Initial Voltage
P101
U(V)
Start
100 % Un
300 A
t(s)
20 s
0
100 A
Enable
Figure 5.9 - Typical current curve during a voltage ramp start
3) Use this time to find the minimum class necessary to start the
motor in cold condition. In the item 4.8 Motor Electronic Overload
Protection it is possible to check the thermal class curves of the
motor in cold condition.
5.2 PROTECTIONS
AND
PROGRAMMING
5.2.1 Suggestion on
How to Program
the Thermal
Class
CHAPTER 5 - PROGRAMMING INFORMATION AND SUGGESTIONS
46
English
2.5 x ln of the
motor
t(s)
20 s
0
xln
15
10
5
Cold
F.S.=1
Figure 5.10 - Checking the minimum class of curves in cold condition
Therefore the minimum class necessary to start the cold motor is
Class 10. Class 5 will trip during starting.
NOTE!
If the motor must start in the hot condition, class 10 will trip during
the second start. In the case a higher thermal class must be set.
Determine the maximum thermal class:
To correctly program the Thermal Class that will protect your motor it
is essential to have in hand the motor locked rotor current and locked
rotor time. This information is available in the motor manufacturer’s
catalogue. Put these values into figure 4.8, in case of the cold stall
time or into figure 4.9, in case of hot stall time.
For example:
Stall Current = 6,6 x ln
Hot Stall Time = 6s
6.6 x ln of the
motor
t(s)
6 s
0
xln
30
Hot
25
20
Figure 5.11 - Checking the maximum class of curves in hot condition
Class 25 is the highest class that protects the motor.
CHAPTER 5 - PROGRAMMING INFORMATION AND SUGGESTIONS
47
English
NOTE!
Remember that this protection has as a standard the Three Phase
IP55 Standard WEG Motor, therefore if your motor is different, then
do not program the thermal class to its maximum, instead, program
it near its minimum thermal class to start.
Example of how setting the thermal class:
Motor data:
Power: 50 hp
Voltage: 380 V
Nominal Current (ln): 71 A
Service Factor (S.F.): 1.00
lp/ln: 6.6
Stall time: 12 s in hot condition
Speed: 1770 rpm
Motor + load starting data:
Starting by Voltage Ramp, starting current average:
3 x the nominal current of the motor during 17 s (3 x ln @ 17 s).
1) In the graph, figure 4.8 in cold condition, one can see the minimum
Thermal Class that will allow the start with a reduced voltage:
For 3 x ln of the motor @17 s, the next highest is adopted: Class 10.
2) In the graph, figure 4.9 in hot condition, one can see the maximum
Thermal Class that the motor can stand due to the stall time in hot
condition:
For 6.6 x ln of the motor @ 12 s, the next lowest is adopted. Class 30.
One now knows that Thermal Class 10 allows a start and Thermal
Class 30 is the maximum limit. Thus, a Thermal Class between the
two should be adopted, according to the quantity of starts per hour
and the interval of time between Off/On procedures the motor.
The closer to Class 10, the more protected the motor will be, the
fewer the starts per hour and the greater the interval of time must
be between Off/On procedures the motor.
The closer to Class 30, the closer it gets to the maximum limit of the
motor, thus there can be more starts per hour and lower intervals of
time between Off/On procedures the motor.
When the Service Factor (S.F.) is different from 1.00 and if there is
the need to use it in the application, this must be considered in the
setting of the overload protection. To avoid tripping of the overload
protection, when the service factor is used, the nominal motor current
set at the SSW-07 must be readjusted. If an acessorie with parameter
access is used, the service factor can be set directly in the P406,
avoiding the readjustment of the nominal currrent.
5.2.2 Service Factor
CHAPTER 5 - PROGRAMMING INFORMATION AND SUGGESTIONS
48
English
Example of readjustment of the nominal current:
ISSW-07 = 30 A
IMOTOR = 25 A
S. F. = 1.15
Setting of the Motor Current = IMOTOR x S.F. / ISSW-07 = 25 A x 1.15 /
30 A = 96 %
ATTENTION!
The increased motor current has direct impact on the maximum
thermal class, that protects the motor, even if the S.F. parameter is
set.
Determine the maximum thermal class, considering the service
factor:
Stall Current = 6.6 x ln
Hot Stall Time = 6 s
Service Factor = 1.15
Before the maximum thermal class is verified in figure 4.9, the stall
current must be divided by the service factor.
Stall Current / S.F. = 6.6 / 1.15 = 5.74
5.74 x In of the motor
t(s)
6 s
0
xln
25
Hot
20
15
Figure 5.12 - Checking of the maximum thermal class, considering the S.F.
Class 20 is the highest class that protects the motor, if the service
factor is used.
6.1 FAULTS AND
POSSIBLE
CAUSES
SOLUTION AND TROUBLESHOOTING
When an error is detected, the Soft-Starter is blocked (disabled)
and the LED’s indicate this error by means of intermittent flashes.
In order that the Soft-Starter operates normally again after an error
trip, it is necessary to reset it. This procedure is performed in the
following ways:
Disconnecting and reapplying the AC power (power-on RESET);
Pressing the “RESET” key in the SSW-07 front panel (RESET
key);
Automatically by the automatic RESET. Enable this function via
DIP Switch (auto);
Via digital input DI2 or DI3.
Protection
Description and
Fault Display
Activation Description
Probable Causes
Reset
Phase loss or
Undercurrent
E03
(LED Phase
Loss)
Flashing
At starting: It occurs when there
is no voltage in the power supply
terminals (R/1L1, S/3L2 and
T/5L3) or when the motor is
disconnected.
With the motor running: It trips
when the current stays below the
programmed value longer than
the programmed time.
Referring to the nominal motor
current.
When the parameters are set with
the factory default values, then
this protection trips after elapsing
1 second with phase loss either at
the input or at the output (motor).
It trips when the current circulating
through the SSW-07 is less than
20 % of the value adjusted at the
Motor Current trimpot.
In hydraulic pump applications, it may
be running with no load.
Phase loss in the three-phase
network.
Short-circuit or fault at the thyristor or
By-pass.
Motor not connected.
Motor connection is incorrect
Loose contact in the connections.
Starting problems with the input
contactor.
Input fuses are blown.
Incorrect programming of the Motor
Current trimpot.
Motor current consumption lower
than required for phase loss
protection to work.
Power-on.
Reset key.
Auto-reset.
DIx.
Over
temperature
in the power
section
E04
(LED Fault)
Flashes once
(LED Ready)
On
When the heatsink temperature
is superior to the limit.
Also trips when the temperature
sensor is not connected.
When the time limits given by
the time x temperature curves of
SCR protection are exceeded.
Shaft load too high.
Elevated number of successive
starts.
Internal temperature sensor not
connected.
Starting cycle requires ventilation kit
(models from 45 A to 200 A).
Power-on.
Reset key.
Auto-reset.
DIx.
Table 6.1 - Faults and possible causes
CHAPTER 6
CHAPTER 6 - SOLUTION AND TROUBLESHOOTING
50
English
Protection
Description and
Fault Display
Activation Description
Probable Causes
Reset
Electronic
motor overload
E05
(LED Overload)
Flashing
When the times given by the
programmed thermal class
curves exceed the limit.
Incorrect setting of the "Motor
Current" trimpot (motor current set).
The set value is too low for the motor
being used.
Starting sequence greater than
allowed.
Programmed thermal class too low.
Time between Off/On procedures
lower than that permitted by the
motor power refrigeration time.
Load on the motor shaft too high.
Thermal protection value saved when
the control is turned off and brought
back when turned back on.
Power-on.
Reset key.
Auto-reset.
DIx.
Short circuit in
the SSW power
E19
(Fault LED)
Flashes 7 times
(Ready LED)
is off
When the current value in one of
the phases is above 30%
of the Soft-Starter rated current
with the motor stopped, that is,
without the Run command.
Short circuit in some thyristor or relay
of internal by-pass.
External short circuit in parallel with
the Soft-Starter power.
Defect in the current analog reading.
Power –on
Manual Reset
Reset key.
DIx.
Start timeout
during current
limit starting
E62
(LED Fault)
Flashes twice
(LED Ready)
On
When the starting time is
longer than the time set in the
acceleration ramp trimpot. Active
only with current limit starting.
Programmed time for the acceleration
ramp inferior to what is needed.
Value of the programmed current
limitation too low.
Motor locked, rotor blocked.
Power-on.
Reset key.
Auto-reset.
DIx.
Stall
E63
(LED Stall)
Flashing
Activates before full voltage, if
the current is greater than twice
the nominal motor current.
Programmed acceleration ramp time
lower than the actual acceleration time.
Motor shaft is locked
The transformer that supplies the
motor can be saturating and taking too
much time to recover from the starting
current.
Power-on.
Reset key.
Auto-reset.
DIx.
Overcurrent
E66
(LED
Overcurrent)
Flashing
It is only monitored when the
SSW-07 is at full voltage. When
the parameters are set with
the factory default values this
protection trips when the motor
current exceeds 2 times the
value adjusted in the trimpot
(Motor Current) for a time longer
than 1 second.
Momentary motor overload.
Motor shaft is locked, rotor blocked.
Power-on.
Reset key.
Auto-reset.
DIx.
Incorrect phase
sequence
E67
(LED Phase
Seq.)
Flashing
When the sequence of
synchronism signals
interruptions does not follow the
RST sequence.
Network phase sequence inverted at
the input.
May have been changed in another
place of the supply network.
Motor connection is incorrect.
Power-on.
Reset key.
DIx.
Table 6.1 - Faults and possible causes (cont.)
CHAPTER 6 - SOLUTION AND TROUBLESHOOTING
51
English
Protection
Description and
Fault Display
Activation Description
Probable Causes
Reset
Undervoltage
in the control
supply
E70
(LED Fault)
Flashes twice
(LED Ready)
Off
Activates when the control
supply voltage is lower than 93
Vac.
Electronics supply lower than the
minimum value.
Electronics power supply with loose
contact.
Electronics power supply fuse blown.
Power-on.
Reset key.
Auto-reset.
DIx.
Internal
By-pass relay
contact Open
E71
(LED Fault)
Flashes 3 times
(LED Ready)
Off
When there is a fault with the
internal By-pass relay contacts
at full voltage.
Loose contact in the starting cables
of the Internal By-pass relays.
Defective By-pass relay contacts due
to an overload.
Incorrect electronic supply voltage,
only for SSW-07 models 255-412 A.
Power-on.
Reset key.
Auto-reset.
DIx.
Overcurrent
before the
By-pass
E72
(LED Fault)
Flashes 4 times
(LED Ready)
Off
Activates before the closing
of the By-pass if the current is
greater than:
37.5 A for the models up to 30 A;
200 A for the models from
45 to 85 A;
260 A for the model of 130 A;
400 A for the models from
171 and 200 A.
824 for the models from 255 A to
412 A.
The time programmed for the
acceleration ramp is shorter than the
actual acceleration time.
Nominal motor current higher than
the current that can be supported by
the Soft-Starter.
Motor shaft is locked, rotor blocked.
Power-on.
Reset key.
Auto-reset.
DIx.
Frequency out
of tolerance
E75
(LED Fault)
Flashes once
(LED Ready)
Off
When the limit is higher or lower
than the limits of 45 to 66 Hz.
The line frequency is out of range.
When the Soft-Starter + motor are
being supplied by a generator that
is not supporting the full load or the
start of the motor.
Power-on.
Reset key.
Auto-reset.
DIx.
Closed By-pass
contact or
shorted SCR’s
E77
(Fault LED)
flashes 6 times
(Ready LED) is
off
When the SSW-07 does not
detect voltage difference
between the input and output
at the moment the motor is
switched off.
Bad contact in the bypass cables.
By-Pass contacts are welded.
Short-circuited thyristor.
Input and output external short-
circuit.
Disconnected motor.
Power-on.
Reset key.
DIx.
Table 6.1 - Faults and possible causes (cont.)
CHAPTER 6 - SOLUTION AND TROUBLESHOOTING
52
English
6.2 TROUBLESHOOTING
NOTES:
In the case of E04 (over temperature), it is necessary to wait a little
before resetting, in order to cool down.
In the case of E05 (motor overload), it is necessary to wait a little
before resetting, in order to cool down.
Problem
Points to check
Corrective action
Motor does not run
Wrong wiring
Check all the power and command connections.
For example:
The DIx digital inputs programmed as enabling or
external fault must be connected to AC supply.
Wrong programming
Check if the parameters are with the correct values
for the application.
Fault
Check if the Soft-Starter is not blocked to a detected
fault condition.
Motor does not reach
nominal speed
Motor stall
Increase the current limit level with the control to limit
the current (refer to table 6.1).
Motor rotation oscillates
(fluctuates)
Loose connections
Switch the Soft-Starter and the power supply off and
tighten all the connections.
Check all the internal connections of the Soft-Starter
to make sure they are well connected.
Motor rotation:
Too high or too low
Motor nameplate data
Check if the motor used is in accordance to the
application.
LEDs off
Check the power supply
voltage of the control
board (A1 and A2)
Nominal values must be inside the following limits:
Umin. = 93.5 Vac
Umax.= 264 Vac
Vibration during
acceleration
Soft-Starter Settings
Reduce the acceleration ramp time.
Table 6.2 - Solving the most frequent problems
NOTE!
When contacting WEG for service or technical assistance, please
have the following data on hand:
Model of the Soft-Starter;
Serial number, production date and hardware revision present in
the identification label of the product (refer to item 2.3);
Installed software version (refer to item 2.3);
Application and programming data.
For explanations, training or service, please contact WEG
Automação Service Department.
CHAPTER 6 - SOLUTION AND TROUBLESHOOTING
53
English
6.3 PREVENTIVE
MAINTENANCE
WARNING!
Always disconnect the general power supply before touching any
electric component associated to the Soft-Starter SSW-07.
Do not apply any high voltage tests on
the Soft-Starter SSW-07!
If necessary, consult the manufacturer.
Do not use megometers to test thyristors.
Periodic inspections of Soft-Starters SSW-07 and installations
are necessary to avoid operating problems due to unfavorable
environmental conditions like high temperature, moisture, dust,
vibrations or due to the aging of the components.
When the SSW-07 Soft-Starter is stored for a long period of time, it
is recommended that it be energized for 1 hour, each year.
Component
Abnormality
Corrective Action
Terminals, Connectors
Loose screws
Tightening(1)
Loose connectors
Fans / Ventilation Systems
Dirty fans
Cleaning(1)
Abnormal noise
Substitute fan
Fan always off
Abnormal vibration
Dust in the air filters
Cleaning or substitution(2)
Power Module / Power
Connections
Accumulated dust, oil, moisture, etc.
Cleaning(1)
Screws with loose connections
Tightening(1)
Table 6.3 - Periodic inspections after putting into use
(1) Every six months.
(2) Twice a month.
OPTIONS AND ACCESSORIES
This chapter describes the optional devices that can be used with
Soft-Starter SSW-07.
Optional Description
WEG Part Number
Plug-in Local Keypad
10935572
Remote Keypad Kit (Cable not included)
10935649
Remote Keypad + RS-485 Kit (Cable not included)
12368331
1 m SSW-07 - Remote HMI Connection Cable
10050268
2 m SSW-07 - Remote HMI Connection Cable
10190951
3 m SSW-07 - Remote HMI Connection Cable
10211478
5 m SSW-07 - Remote HMI Connection Cable
10211479
7,5 m SSW-07 - Remote HMI Connection Cable
10050302
10 m SSW-07 - Remote HMI Connection Cable
10191029
Plug-in Kit for DeviceNet Communication
10935681
Plug-in Kit for RS-232 Communication
10935578
3 m RS-232 Connection Cable
10050328
10 m RS-232 Connection Cable
10191117
Plug-in Kit for RS-485 Communication
10935573
Ventilation Kit for Size 2 (Currents from 45 to 85 A)
10935650
Ventilation Kit for Size 3 (Currents from 130 to 200 A)
10935559
IP20 Kit for Size 3 (Currents from 130 to 200 A)
10935651
Size 4 IP20 kit (255 to 412 A current)
11059230
Plug-in Kit for Motor PTC
10935663
SuperDrive G2 Kit
10945062
Table 7.1 - Optional description
The purpose of the IP20 KIT is to protect the user from the contact
with the live parts of the Soft-Starter.
382,50mm
383 mm
(15.1 in)
Figure 7.1 - IP20 kit size 3
483.50mm
484 mm
(19.1 in)
Figure 7.2 - IP20 kit size 4
7.1 IP20 KIT
This chapter describes the electric and mechanical technical
characteristics of the Soft-Starter SSW-07 line.
SSW-07
Model
Motor voltage
220/230 V
Motor voltage
380/400 V
Motor voltage
440/460 V
Motor voltage
575 V
(Hp)
(kW)
(Hp)
(kW)
(Hp)
(kW)
(Hp)
(kW)
17 A
5
3.7
7.5
5.5
10
7.5
15
11
24 A
7.5
5.5
10
7.5
15
11
20
15
30 A
10
7.5
15
11
20
15
25
18.5
45 A
15
11
25
18.5
30
22
40
30
61 A
20
15
30
22
40
30
50
37
85 A
30
22
50
37
60
45
75
55
130 A
50
37
75
55
100
75
125
90
171 A
60
45
100
75
125
90
150
110
200 A
75
55
100
75
150
110
200
150
255 A
100
75
150
110
200
150
250
185
312 A
125
90
175
130
250
185
300
225
365 A
150
110
200
150
300
225
350
260
412 A
150
110
250
185
350
260
400
300
Table 8.1 - Powers and currents according to UL508
SSW-07
Model
Motor
voltage
220/230 V
Motor
voltage
380/400 V
Motor
voltage
440/460 V
Motor
voltage
525 V
Motor
voltage
575 V
(Hp)
(kW)
(Hp)
(kW)
(Hp)
(kW)
(Hp)
(kW)
(Hp)
(kW)
17 A
6
4.5
10
7.5
12.5
9.2
15
11
15
11
24 A
7.5
5.5
15
11
15
11
20
15
20
15
30 A
10
7.5
20
15
20
15
25
18.5
30
22
45 A
15
11
30
22
30
22
40
30
40
30
61 A
20
15
40
30
50
37
50
37
60
45
85 A
30
22
60
40
60
45
75
55
75
55
130 A
50
37
75
55
100
75
125
90
125
90
171 A
60
45
125
90
125
90
150
110
175
132
200 A
75
55
125
90
150
110
200
150
200
150
255 A
100
75
175
132
200
150
250
185
250
185
312 A
125
90
200
150
250
185
300
220
300
225
365 A
150
110
250
185
300
225
350
260
400
300
412 A
150
110
300
220
350
260
440
315
450
330
Table 8.2 - Powers and currents for WEG motors
NOTE!
The maximum powers indicated in table 8.1 are based on 3 x nominal
current of Soft-Starter SSW-07 during 30 s and 10 starts per hour
(3xIn @ 30 s).
8.1 NOMINAL POWERS AND CURRENTS ACCORDING TO UL508
8.2 NOMINAL POWERS AND CURRENTS FOR STANDARD IP55, IV POLE WEG
MOTOR
CHAPTER 8 - TECHNICAL CHARACTERISTICS
English
8.4 ELECTRONICS AND PROGRAMMING DATA
8.3 POWER DATA
Power Supply
Power Voltage (R/1L1, S/3L2, T/5L3) (220 to 575) Vac (-15 % to +10 %), or
(187 to 632) Vac
Frequency
(50 to 60) Hz (±10 %), or (45 to 66) Hz
Capacity
Maximum number of starts per hour
(without ventilation)
10 (1 every 6 minutes; models from 17 A to 30 A)
3 (1 every 20 minutes; models from 45 A to 200 A)
10 (1 every 6 minutes; models from 255 A to 412 A)
Maximum number of starts per hour
with optional ventilation Kit
10 (1 every 6 minutes; models from 45 A to 200 A)
Start cycle
3 x In of the SSW-07 during 30 seconds
Thyristors (SCRs)
Reverse voltage with 1600 V maximum peak
Overvoltage category
III (UL508/EN61010)
Power Supply
Control voltage
Connector (A1, A2)
(110 to 240) Vac (-15 % to +10 %), models from 17 A to 200 A
(110 to 130) Vac or (208 to 240) Vac (-15 % to +10 %) (models
from 255 A to 412 A)
Frequency
(50 to 60) Hz (±10 %), or (45 to 66) Hz
Consumption
15 VA models from 17 A to 200 A
60 VA continuos
800 VA additional during By-pass closing (models from 255 A
to 412 A).
Control
Method
Voltage ramp;
Current limitation.
Inputs
Digitals
3 Isolated digital inputs;
Minimum upper level: 93 Vac;
Maximum lower level: 10 Vac;
Maximum voltage: 264 Vac;
Input current: 1.47 mA @ 220 V;
Programmable functions.
Outputs
Relay
2 relays with NO contacts, 240 Vac, 1 A, and programmable
functions.
Safety
Protections
Overcurrent;
Phase loss;
Inverted phase sequence;
Heatsink overtemperature;
Motor overload;
External fault;
Open By-pass contact;
Closed By-pass contact;
Overcurrent before By-pass;
Stall;
Frequency out of range;
Electronic supply undervoltage.
Instrucciones de Seguridad
1.1 Avisos de Seguridad en el Manual .....................................59
1.2 Avisos de Seguridad en el Producto ..................................59
1.3 Recomendaciones Preliminares .........................................59
CAPÍTULO 2
Informaciones Generales
2.1 A Respecto del Manual .......................................................61
2.2 A Respecto del Arrancador Suave SSW-07 .......................61
2.3 Etiqueta de Identificación del Arrancador Suave SSW-07 .62
2.4 Recibimiento y Almacenado ...............................................65
CAPÍTULO 3
Instalación y Conexión
3.1 Instalación Mecánica ..........................................................66
3.1.1 Condiciones Ambientales ............................................66
3.1.2 Dimensiones del Arrancador Suave SSW-07 ..............66
3.1.3 Posicionamiento/Fijación ............................................67
3.1.3.1 Montaje en Tablero ..............................................68
3.1.3.2 Montaje en Superficie .........................................69
3.2 Instalación Eléctrica ............................................................69
3.2.1 Terminales de Potencia ...............................................70
3.2.2 Ubicación de las Conexiones de Potencia,
Puesta a Tierra y Control .............................................71
3.2.3 Cables de Potencia y de Puesta a Tierra Propuestos ...72
3.2.4 Conexiones de la Red de Alimentación al Arrancador
Suave SSW-07 ............................................................72
3.2.4.1 Capacidad de Cortocircuito, Fusibles and
Disyuntores – UL .................................................73
3.2.4.2 Fusibles y Disyuntores de Entrada - IEC ............75
3.2.4.3 Fusible de la Electrónica .....................................76
3.2.5 Conexiones del Arrancador Suave SSW-07 al Motor ..76
3.2.5.1 Conexión Padrón del Arrancador Suave
SSW-07 al Motor con Tres Cables ......................77
3.2.6 Conexiones de Puesta a Tierra ...................................77
3.2.7 Conexiones de Señal y Control ...................................78
3.3 Accionamientos Propuestos ...............................................79
3.3.1 Accionamiento Propuesto con Comando por
Entradas Digitales a Dos Cables y Contactor
de Aislamiento de la Potencia ......................................81
3.3.2 Accionamiento Propuesto con Comando por
Entradas Digitales a Tres Cables y Disyuntor de
Aislamiento de la Potencia ..........................................81
3.3.3 Accionamiento Propuesto con Comando por Entradas
digitales y Cambio del Sentido de Giro ........................82
3.3.4 Accionamiento Propuesto con Comando por Entradas
digitales y Frenado CC ................................................83
3.3.5 Simbologia ...................................................................84
Como Ajustar el SSW-07
4.1 Ajuste del Tipo de Control ..................................................85
4.2 Kick Start ............................................................................86
4.3 Ajuste de la Tensión Inicial .................................................86
4.4 Ajuste del Limite de Corriente ............................................87
4.5 Ajuste del Tiempo de la Rampa de Aceleración .................88
4.6 Ajuste del Tiempo de la Rampa de Desaceleración ...........88
4.7 Ajuste de Corriente del Motor .............................................89
4.8 Protección de Sobrecarga Electrónica del Motor ...............90
4.9 Reset ................................................................................92
4.10 Programación de la Entrada Digital DI2 ...........................93
4.11 Funcionamiento de las Salidas a Relé .............................94
4.12 Programación de la Salida a Relé RL1 .............................94
CAPÍTULO 5
Informaciones y Sugerencias de Programación
5.1 Aplicaciones y Programación .............................................95
5.1.1 Arranque con Rampa de Tensión ................................96
5.1.2 Arranque con Limitación de Corriente .........................97
5.1.3 Arranque con Control de Bombas (P202 = 2) .............97
5.1.4 Programación del tipo de control para control
de bombas ...................................................................99
5.2 Protecciones y Programación ...........................................100
5.2.1 Sugerencia de como Programar la Clase Térmica ....100
5.2.2 Factor de Servicio ......................................................103
CAPÍTULO 6
Solución y Prevención de Fallos
6.1 Errores y Posibles Causas ...............................................104
6.2 Solución de los Problemas más Frecuentes ....................107
6.3 Mantenimiento Preventivo ................................................108
CAPÍTULO 7
Dispositivos Opcionales
7.1 Kit IP20 .............................................................................109
CAPÍTULO 8
Características Técnicas
8.1 Potencias y Corrientes Nominales Conforme UL508 .......110
8.2 Potencias y Corrientes Nominales Conforme Motores WEG,
Estándar, IP55, IV Polos ...................................................110
8.3 Datos de la Potencia ........................................................111
8.4 Datos de la Electronica y Programación ..........................111
INSTRUCCIONES DE SEGURIDAD
Este manual contiene las informaciones necesarias para el uso
correcto del Arrancador Suave SSW-07.
Fue desarrollado para ser utilizado por personas con entrenamiento
o calificación técnica adecuada para operar este tipo de
equipamiento.
En el texto serán utilizados los siguientes avisos de seguridad:
¡PELIGRO!
No considerar los procedimientos recomendados en este aviso
puede llevar a la muerte, daños físicos graves y daños materiales
considerables.
¡ATENCIÓN!
No considerar los procedimientos recomendados en este aviso
puede llevar a daños materiales.
¡NOTA!
El texto objetiva suministrar informaciones importantes para la
correcta comprensión y buen funcionamiento del producto.
Los siguientes símbolos estãn fijados al producto, sirviendo como
aviso de seguridad:
Tensiones elevadas presentes.
Componentes sensibles a descargas electrostáticas.
No tocarlos.
Conexión obligatoria puesta a tierra de protección (PE).
¡PELIGRO!
Solamente personas con calificación adecuada y familiaridad
con el Arrancador Suave SSW-07 y equipamientos asociados
deben planear o implementar la instalación, arranque, operación
y mantenimiento de este equipamiento.
Estas personas deben seguir todas las instrucciones de seguridad
contenidas en este manual y/o definidas por las normas locales.
No seguir las instrucciones de seguridad puede resultar en risco
de vida y/o daños en el equipamiento.
1.2 AVISOS DE
SEGURIDAD EN
EL PRODUCTO
1.1 AVISOS DE
SEGURIDAD EN
EL MANUAL
CAPÍTULO 1
1.3 RECOMENDACIONES
PRELIMINARES
CAPÍTULO 1 - INSTRUCCIONES DE SEGURIDAD
60
Español
¡NOTA!
Para los propósitos de este manual, personas calificadas son
aquellas entrenadas de forma a que estén aptas para:
1. Instalar, hacer la puesta a tierra, energizar y operar el SSW-07
de acuerdo con este manual y los procedimientos legales de
seguridad vigentes;
2. Utilizar los equipamientos de protección de acuerdo con las
normas establecidas;
3. Prestar servicios de primeros socorros.
¡PELIGRO!
Siempre desconecte la alimentación general antes de cambiar
cualquier componente eléctrico asociado al Arrancador Suave SSW-
07.
Altas tensiones pueden estar presente mismo después de la
desconexión de la alimentación. Aguarde por lo menos 3 minutos
para la descarga completa de los condensadores (capacitores).
Siempre conecte el disipador del equipamiento a tierra de protección
(PE), en el punto adecuado para esto.
¡ATENCIÓN!
Las tarjetas electrónicas poseen componentes sensibles a las
descargas electrostáticas. No toque directamente sobre los
componentes o conectores. Caso necesario, tocar antes en el
disipador metálico puesta a tierra o utilice pulsera antiestática
adecuada.
No ejecute ninguna prueba de tensión aplicada al Arrancador Suave SSW-07!
Caso sea necesario consultar el fabricante.
¡NOTA!
Arrancadores Suaves SSW-07 pueden interferir en otros
equipamientos electrónicos. Cumpra los cuidados recomendados
en el capítulo 3 (Instalación) para minimizar estos efectos.
¡NOTA!
Leer completamente este manual antes de instalar o operar el
Arrancador Suave SSW-07.
¡ATENCIÓN!
En operación, los sistemas de energía eléctrica, como
transformadores, convertidores, motores y cables utilizados,
generan campos electromagnéticos (CEM). De esta forma, existe
riesgo para las personas portadoras de marcapasos o de implantes,
que permanezcan en las cercanías inmediatas de tales sistemas.
Por lo tanto, es necesario que dichas personas se mantengan a
una distancia de un mínimo de 2 m de estos equipos.
Este manual describe la instalación del Arrancador Suave, como
proceder la puesta en marcha, las principales características
técnicas y como identificar y corregir los problemas más comunes.
Los manuales descriptos a seguir deben ser consultados para
obtener mayores informaciones, referentes a las funciones,
accesorios y condiciones de funcionamiento:
�Manual de Programación, con descripción detallada de los
parámetros y sus funciones;
�Manual de Comunicación RS-232 / RS-485.
�Manual de Comunicación DeviceNet.
Estos manuales son suministrados en formato electrónico (en CD),
en conjunto con el Arrancador Suave. También se puede obtner
estos manuales en la pagina Web de la WEG (www.weg.net).
El Arrancador Suave SSW-07 es un producto de alto desempeño
lo cual permite el control del arranque de motores de inducción
trifásicos. De esta forma, se evitan golpes mecánicos en la carga
y surtos de corrientes en la red de alimentación.
para Ajustes
Tampa para
Trifásica
Opcionais Plug-In
Ajustes e Habilitar as
Proteções
DIP Swith para
Trimpots
Ajustes da
LED's para Indicação
DIP Switch para
Entrada de Alimentação
Reset (DI2 e DI3)
de Status da SSW-07
Classe Termica
Alimentação da Eletrônica
(A1 e A2)
Comanda Aciona/Desaciona
Motor (DI1) e
Saída para Motor
Saida a Relé
(13,14/23 e 24)
DIP Switch para
Ajuste y Habilitar las
Protecciones
LEDs para Indicación
de Status del SSW-07
Tapa para
Opcionales Plug-in
Salida a Relé
(13,14/23 y 24)
Salida para el Motor
“Trimpots”
para Ajuste
Entrada de
Alimentación Trifásica
Alimentación de la
Electrónica (A1 y A2).
Comando Acciona /
Desacciona Motor (DI1) y
Reset (DI2 y DI3)
DIP Switch para
Ajuste de la
Clase Térmica
Figura 2.1 - Vista frontal del SSW-07
2.1 A RESPECTO
DEL MANUAL
CAPÍTULO 2
2.2 A RESPECTO
DEL
ARRANCADOR
SUAVE SSW-07
CAPÍTULO 2 - INFORMACIONES GENERALES
Español
Alimentación Trifásica
de la Potencia
Alimentación de
la Electrónica
Entradas Digitales
Programables
Salidas Digitales
Programables
"Digital Signal
Processor - DSP"
Motor Trifásico
PE
R
S
T
A1
A2
Dl2
Dl3
13
14/23
24
Dl1
3 x
2 x
RL1
RL2
U
V
W
Figura 2.2 - Diagrama de bloques del Arrancador Suave SSW-07
2.3 ETIQUETA DE IDENTIFICACIÓN DEL ARRANCADOR SUAVE SSW-07
Figura 2.3 - Etiqueta de identificación del Arrancador Suave SSW-07
Modelo del SSW-07
Datos de la entrada
(tensión, nº de fases,
corriente, frecuencia)
Datos de la alimentación de
control (tensión, frecuencia)
Número de serie
Versión del
“Software”
Fecha de fabricación
(14 corresponde a
semana y H a año)
Ítem de stock
WEG
CAPÍTULO 2 - INFORMACIONES GENERALES
Español
Posición de la etiqueta de identificación en el Arrancador Suave
SSW-07:
Figura 2.4 - Ubicación de las etiquetas
X
VISTA FRONTAL
VISTA DE X
VISTA FRONTAL
VISTA DE X
CAPÍTULO 2 - INFORMACIONES GENERALES
Español
COMO ESPECIFICAR EL MODELO DEL SSW-07
¡NOTA!
Los campos opcionales (S o O) definen si el Arrancador Suave SSW-07 será en la versión estándar o se tendrá opcionales. Si fuera
estándar, aquí termina el código.
Colocar también siempre la letra Z en el fin.
Por ejemplo:
EXSSW070017T5SZ = Arrancador Suave SSW-07 de 17 A entrada trifásica 220-575 Vca con manual en inglés, español y portugués.
Si tuviera opcionales, los campos deberán sierren rellenados en la secuencia correcta hasta el código ser finalizado con la letra Z .
El producto estándar, para efecto de este código, es proyectado en:
Grado de protección IP20 de 17 A a 85 A y IP00 de 130 A a 412 A.
(1) Solamente para los modelos 130 A hasta 412 A.
(2) Somente para los modelos de 255 A hasta 412 A.
EX
SSW-07
0017
T
5
S
_ _
_ _
_ _
Z
Mercado
BR = Brasil
EX =
Exportación
Arrancador
Suave
WEG serie
SSW-07
Corriente nominal
del SSW-07
0017 = 17 A
0024 = 24 A
0030 = 30 A
0045 = 45 A
0061 = 61 A
0085 = 85 A
0130 = 130 A
0171 = 171 A
0200 = 200 A
0255 = 255 A
0312 = 312 A
0365 = 365 A
0412 = 412 A
Alimentación
Trifásica
220-575 Vca
Opcionales:
S = Estándar
O = con
opcionales
Grado de
Protección
En blanco =
Estándar
IP = IP20 (1)
Hardware
Especial
En blanco =
Estándar
H1 = Alimentación
de la electrónica:
110 a 130 VAC (2)
H2 = Alimentación
de la electrónica:
208 a 240 VAC (2)
Software
Especial
En blanco =
Estándar
S1 =
Software
Especial
Fin del
Código
CAPÍTULO 2 - INFORMACIONES GENERALES
Español
El Arrancador Suave SSW-07 es suministrado empaquetado en
caja de cartón. En la parte externa de este embalaje existe una
etiqueta de identificación que es la misma fijada en el Arrancador
Suave SSW-07.
Para abrir la embalaje:
1- Colóquelo sobre una mesa;
2- Abra la embalaje;
3- Retire el Arrancador Suave.
Verifique se:
La etiqueta de identificación del Arrancador Suave SSW-07
corresponde al modelo comprado;
Ocurrencia de daños durante el transporte. Caso fuera detectado
algún problema, contacte inmediatamente la transportadora;
Si el Arrancador Suave SSW-07 no fuera luego instalado,
mantenerlo dentro del embalaje cerrado y almacenado en un
lugar limpio y seco con temperatura entre -25 °C y 65 °C. 1 hora
en -40 °C es permitido.
Modelo
SSW-07
Altura
H
mm
(in)
Anchura
L
mm
(in)
Profundidad
P
mm
(in)
Volumen
cm3
(in3)
Peso
kg
(lb)
17 A
24 A
30 A
221
(8.70)
180
(7.09)
145
(5.71)
5768
(352.2)
1.65
(3.64)
45 A
61 A
85 A
260
(10.24)
198
(7.80)
245
(9.65)
12613
(770.8)
3.82
(8.42)
130 A
171 A
200 A
356
(14.02)
273
(10.75)
295
(11.61)
28670
(1750)
8.36
(18.43)
255 A
312 A
365 A
412 A
415
(16.34)
265
(10.43)
320
(12.6)
35192
(2147)
12.8
(28.2)
Tabla 2.1 - Dimensiones de la embalaje en mm (in)
Figura 2.5 - Dimensiones de la embalaje
2.4 RECIBIMIENTO
Y
ALMACENADO
INSTALACIÓN Y CONEXIÓN
Este capítulo describe los procedimientos de instalación eléctrica
y mecánica del Arrancador Suave SSW-07. Las orientaciones y
sugerencias deben ser seguidas para la búsqueda del correcto
funcionamiento del Arrancador Suave SSW-07.
La ubicación de los Arrancadores Suaves SSW-07 es factor
determinante para la obtención de un funcionamiento correcto y
una vida normal de sus componentes.
Evitar:
�Exposición directa a los rayos solares, lluvia, humedad excesiva
o niebla salina;
�Gases o líquidos explosivos o corrosivos;
�Vibración excesiva, polvo o partícula metálicas y/o aceites
suspensos en el aire.
Condiciones Ambientales Permitidas:
Temperatura: 0 ºC a 55 ºC - condiciones nominales.
Humedad relativa del aire: 5 % a 90 % sin condensación.
Altitud máxima: 1000 m arriba del nivel del mar - condiciones
nominales.
De 1000 m a 4000 m arriba del nivel del mar - reducción de la
corriente de 1 % para cada 100 m arriba de los 1000 m.
De 2000 m a 4000 m arriba del nivel del mar - reducción de la
tensión de 1.1 % para cada 100 m arriba de los 2000 m.
Grado de contaminación: 2 (conforme UL508).
Normalmente, solamente polución no conductiva. La condensación
no debe causar conducción en las partículas contenidas en el
aire.
La figura 3.1, en sistema con la tabla 3.1, trae las dimensiones
externas de los agujeros para fijación del Arrancador Suave SSW-07.
C
A
B
D
P
H
L
A
L
P
C
D
B
H
Figura 3.1 - Dimensional de la SSW-07
3.1 INSTALACIÓN
MECÁNICA
CAPÍTULO 3
3.1.2 Dimensiones
del Arrancador
Suave SSW-07
3.1.1 Condiciones
Ambientales
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
Tabla 3.1 - Datos para la instalación con dimensiones en mm (in)
* IP20 con Kit opcional.
Para la instalación del Arrancador Suave SSW-07 se debe dejar
en el mínimo los espacios libres al rededor del Arrancador Suave
conforme la figura 3.2 presentada a seguir. Las dimensiones de
cada espacio libre están disponibles en la tabla 3.2.
Modelo SSW-07
A
mm
(in)
B
mm
(in)
C
mm
(in)
17 A
24 A
30 A
50
(2)
50
(2)
30
(1.2)
45 A
61 A
85 A
80
(3.2)
80
(3.2)
30
(1.2)
130 A
171 A
200 A
100
(4)
100
(4)
30
(1.2)
255 A
312 A
365 A
412 A
150
(6)
150
(6)
30
(1.2)
Tabla 3.2 - Espacios libres recomendados
Instalar el Arrancador Suave SSW-07 en la posición vertical de
acuerdo con las siguientes recomendaciones:
1) Instalar en superficie razonablemente plana;
2) No colocar componentes sensibles al calor luego arriba del
Arrancador Suave SSW-07.
¡ATENCIÓN!
Si montar un Arrancador Suave SSW-07 arriba del otro, usar la
distancia mínima A + B y desviar del Arrancador Suave superior el
aire caliente que viene del Arrancador Suave inferior.
3.1.3 Posicionamiento/
Fijación
Modelo
SSW-07
Alt.
H
mm
(in)
Anch.
L
mm
(in)
Profund
P
mm
(in)
A
mm
(in)
B
mm
(in)
C
mm
(in)
D
mm
(in)
Tornillo
p/
Fijación
Peso
kg
(lb)
Grado de
Protección
17 A
24 A
30 A
162
(6.38)
95
(3.74)
157
(6.18)
85
(3.35)
120
(4.72)
5
(0.20)
4
(0.16)
M4
1.3
(2.9)
IP20
45 A
61 A
85 A
208
(8.19)
144
(5.67)
203
(7.99)
132
(5.2)
148
(5.83)
6
(0.24)
3.4
(0.13)
M4
3.3
(7.28)
IP20
130 A
171 A
200 A
276
(10.9)
223
(8.78)
220
(8.66)
208
(8.19)
210
(8.27)
7.5
(0.3)
5
(0.2)
M5
7.6
(16.8)
IP00 *
255 A
312 A
365 A
412 A
331
(13.0)
227
(8.94)
242
(9.53)
200
(7.87)
280
(11.0)
15
(0.59)
9
(0.35)
M8
11.5
(25.4)
IP00 *
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
Para los Arrancadores Suaves SSW-07 instaladas dentro de tablero
o de cajas metálicas cerradas, proveer extractor adecuada para que
la temperatura quede dentro del rango permitido. Mirar potencias
nominales disipadas en la tabla 3.3.
3.1.3.1 Montaje en
Tablero
Tabla 3.3 - Potencias disipadas para dimensionado del ventilador del tablero
Figura 3.2 - Espacios libres para la ventilación
¡ATENCIÓN!
Prever conduíntes o electroductos independientes para la
separación física de los cables conductores de la señal, de control
y de la potencia (mirar ítem 3.2 - Instalación Eléctrica).
C
SAIDA
FLUXO DE AR
B
A
ENTRADA
FLUXO DE AR
Entrada
Flujo del Aire
Salida
Flujo del Aire
A
B
C
Modelo
SSW-07
Potencia disipada
en la electrónica
(W)
Potencia media
disipada con
10 partidas / hora
3 x In @ 30s
(W)
Potencia media
total disipada con
10 partidas / hora
3 x In @ 30s
(W)
17 A
12
15.3
27.3
24 A
12
21.6
33.6
30 A
12
27
39
45 A
12
41
53
61 A
12
55
67
85 A
12
77
89
130 A
12
117
129
171 A
12
154
166
200 A
12
180
192
255 A
12
230
242
312 A
12
281
293
365 A
12
329
341
412 A
12
371
383
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
La figura 3.3 presenta la instalación del Arrancador Suave SSW-07
en la superficie de una placa de montaje.
3.1.3.2 Montaje en
Superficie
Figura 3.3 - Procedimiento de instalación del SSW-07 en superficie
3.2 INSTALACIÓN
ELÉCTRICA
¡PELIGRO!
El Arrancador Suave SSW-07 no puede ser utilizado como
mecanismo para parada de emergencia.
¡PELIGRO!
Certifíquese que la red de alimentación está desconectada antes
de iniciar las conexiones.
¡ATENCIÓN
Las informaciones a seguir pueden ser usadas como guía para
se obtener una instalación correcta. Siga también las normas de
instalación eléctricas aplicables.
¡ATENCIÓN
Si en la primera energización no se utiliza un contactor o un disyuntor
de aislamiento de la potencia con bobina de mínima tensión,
energice primero la electrónica, ajuste los trimpots necesarios para
poner el SSW-07 en funcionamiento y solamente después energice
la potencia.
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
Los bornes de conexión de potencia cambian de mecánicas y
configuraciones dependiendo del modelo del Arrancador Suave
SSW-07, como se puede observar en las figuras 3.5 y 3.6.
Terminales:
R / 1L1, S / 3L2 y T / 5L3: Red de alimentación de la potencia.
U / 2T1, V / 4T2 y W / 6T3: Conexión para el motor.
3.2.1 Terminales de
Potencia
Figura 3.4 - Conexiones de potencia y de puesta a tierra para conexión padrón
Red
Seccionadora
Fusibles
R
S
T
R/1L1 S/3L2 T/5L3
U/2T1 V/4T2 W/6T3 PE
PE
PE
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
Modelo SSW-07
Mecánica
Red / Motor
Puesta a Tierra
Tornillo /
Terminal
Torque (Par)
(Nm)
Tornillo
Torque (Par)
(Nm)
17 A
24 A
30 A
MEC-01
Terminal
3
(27)
M4
(5/32”)
4.5
(40)
45 A
61 A
85 A
MEC-02
Terminal
5.5
(49)
M5
(3/16”)
6
(53)
130 A
171 A
200 A
MEC-03
M8
(5/16”)
19
(168)
M6
(1/4”)
8.3
(73)
255 A
312 A
365 A
412 A
MEC-04
M10
(3/8”)
37
(328)
Borne
0.5
(4.5)
Figura 3.5 - Terminales de potencia
Modelos de 17 A a 85 A
Modelos de 130 A a 412 A
Tabla 3.4 - Máximo torque (par) en los terminales de conexión de la potencia
3.2.2 Ubicación de las Conexiones de Potencia, Puesta a Tierra y Control
Figura 3.6 - Ubicación de las conexiones de potencia, puesta a tierra y control
BORNE DE SAIDA
POTENCIA
BORNE DE ENTRADA
POTENCIA
BORNE DE ENTRADA
POTENCIA
BORNE DE SAIDA
POTENCIA
Terminal de Salida
de Potencia
Terminal de Entrada
de Potencia
Terminal de Salida
Potencia
Terminal de Entrada
de Potencia
R/1L1
S/3L2
T/5L3
U/2T1
V/4T2
W/6T3
Dimensiones en mm(in).
ATERRAM EN TO
ATERRAM EN TO
ATERRAM EN TO
C O N TRO LE
C O N TRO LE
C O N TRO LE
C O N TRO LE
ATERRAM EN TO
62.8
(2.48)
36.3
(1.43)
84,8
(3.34)
13.3
(0.52)
114
(4.48)
148
(5.81)
56.3
(2.22)
60.5
(2.38)
22.7
(0.89)
39.7
(1.56)
25.1
(0.99)
197
(7.75)
32.7
(1.29)
14.8
(0.59)
14.8
(0.59)
33.0
(1.30)
39.0
(1.54)
39.0
(1.54)
48.2
(1.90)
63.0
(2.48)
75.5
(2.97)
75.5
(2.97)
63.0
(2.48)
Terminal de Puesta a Tierra
Control
Control
Control
Control
Terminal de Puesta a Tierra
Terminal de Puesta a Tierra
R/1L1 S/3L2 T/5L3
Terminal de Puesta a Tierra
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
Las especificaciones descriptas en la tabla 3.5 son validas
solamente para las siguientes condiciones:
�Cables de Cobre con aislamiento de PVC 70 ºC, temperatura
ambiente de 40 ºC, instalados en canaletas agujeradas y no
amontonadas (aglomeradas);
�Barramiento de cobre nudo o plateado con cantos (esquina)
arredondeados de 1 mm de rayo, temperatura 80 ºC y temperatura
ambiente de 40 ºC.
¡NOTA !
Para el correcto dimensionado de los cableados llevar en cuenta las
condiciones de la instalación y la máxima caída de tensión permitida.
Modelo
SSW-07
Cable de
Potencia
(mm2)
Cable de
Puesta a la
Tierra (mm2)
17 A
4
4
24 A
6
6
30 A
6
6
45 A
10
6
61 A
16
10
85 A
25
10
130 A
50
25
171 A
70
35
200 A
95
50
255 A
120
2,5
312 A
185
2,5
365 A
240
2,5
412 A
300
2,5
Tabla 3.5 - Especificaciones de las espesuras mínimas de los cableados
¡PELIGRO!
La tensión de red debe ser compatible con el rango de tensión del
Arrancador Suave SSW-07.
¡PELIGRO!
Prever un equipamiento para seccionar la alimentación del
Arrancador Suave SSW-07. Este debe seccionar la red de
alimentación para el Arrancador Suave SSW-07 cuando necesario
(por ejemplo: durante trabajos de mantenimiento).
Si una llave aislada o contactor fuera inserido en la alimentación
del motor nunca opérelos con el motor girando o con el Arrancador
Suave SSW-07 habilitado.
3.2.3 Cables de
Potencia y de
Puesta a Tierra
Propuestos
3.2.4 Conexiones
de la Red de
Alimentación
al Arrancador
Suave SSW-07
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
¡ATENCIÓN!
El control de sobretensión en la red que alimenta el Arrancador
Suave debe ser hecho a través de protectores de sobretensión con
tensión de actuación de 680 Vca (conexión fase fase) y capacidad de
absorción de energía de 40 joules (modelos de 17 A hasta 200 A) y 80
joules (modelos de 255 A hasta 412 A).
¡NOTA!
Utilizar en el mínimo las espesuras de cableados y los fusibles
recomendados en las tablas 3.5 y 3.7. El torque (par) de apierto
del el conector es indicado en la tabla 3.4. Use cableado de cobre
(70 ºC) solamente.
La tabla 3.6 presenta la capacidad de cortocircuito, Standard Fault,
de la fuente de alimentación (Arms simétricos), a la cual la SSW-07
puede ser instalado, desde que esté protegida a través de fusibles
y disyuntores, utilizados en las pruebas de la UL.
SSW-07
Modelo
Corriente
Nominal
Corriente del
Cortocircuito
≤ 600V
Disyuntor
(CB) - UL489
cualquier
MCCB
Fusible Ultrarrápido
Ferraz Shawmut/
Mersen
Flush End Contacts
Fusible Ultrarrápido
Cooper Bussmann
Bolted Contacts
17 A
17 A
5 kA
< 30A
6.6URD30TTF0050
170M2611
24 A
24 A
5 kA
< 40A
6.6URD30TTF0080
170M1366
30 A
30 A
5 kA
< 40A
6.6URD30TTF0080
170M1366
45 A
45 A
5 kA
< 150A
6.6URD30TTF0100
170M1367
61 A
61 A
5 kA
< 150A
6.6URD30TTF0125
170M1368
85 A
85 A
10 kA
< 150A
6.6URD30TTF0200
170M1370
130 A
130 A
10 kA
< 225A
6.6URD31TTF0325
170M1372
171 A
171 A
10 kA
< 250A
6.6URD32TTF0450
170M3170
200 A
200 A
10 kA
< 250A
6.6URD32TTF0500
170M3171
255 A
255 A
18 kA
< 400A
6.6URD32TTF0400
170M5158
312 A
312 A
18 kA
< 400A
6.6URD33TTF0500
170M3171
365 A
365 A
18 kA
< 600A
6.6URD33TTF0550
170M5161
412 A
412 A
18 kA
< 600A
6.6URD33TTF0700
170M6161
Tabla 3.6 - Capacidad de cortocircuito – UL Standard Fault
Los fusibles de la tabla 3.6, utilizados en las pruebas de la UL de la
SSW-07, son del tipo ultrarrápido (aR), los cuales también reducen
el riesgo de quema de los SCRs por transitorios de sobre corriente.
La tabla 3.7 presenta la capacidad de cortocircuito, High Fault, de la
fuente de alimentación (Arms simétricos), a cual la SSW-07 puede
ser instalado dentro del tablero cerrado, desde que esté protegida
a través de disyuntores, utilizados en las pruebas de la UL.
3.2.4.1 Capacidad de
Cortocircuito,
Fusibles and
Disyuntores – UL
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
SSW-07
Modelo
Corriente
Nominal
Corriente del
Cortocircuito
≤ 480V
Disyuntor
(DIVQ)
Corriente del
Cortocircuito
≤ 600V
Disyuntor
(DIVQ)
Minimas
Dimensiones del
Panel (AxAxP)
(mm)
17 A
17 A
65 kA
WEG ACW125W-FTU25-3 o
UBW225H-FTU30-3A o
HFD3030L
18 kA
UBW225H-FTU40-
3A o HFD3040L
800
600
300
24 A
24 A
65 kA
WEG ACW125W-FTU30-3
18 kA
UBW225H-FTU40-
3A o HFD3040L
800
600
300
30 A
30 A
65 kA
WEG ACW125W-FTU40-3
18 kA
UBW225H-FTU40-
3A o HFD3040L
800
600
300
45 A
45 A
65 kA
WEG ACW125W-FTU60-3
o UBW225H-FTU150-3A o
HFD3150L
18 kA
UBW225H-FTU40-
3A o HFD3040L
800
600
300
61 A
61 A
65 kA
WEG ACW125W-FTU60-3
o UBW225H-FTU150-3A o
HFD3150L
18 kA
UBW225H-FTU150-
3A o HFD3150L
800
600
300
85 A
85 A
65 kA
WEG ACW125W-FTU60-3
o UBW225H-FTU150-3A o
HFD3150L
18 kA
UBW225H-FTU150-
3A o HFD3150L
800
600
300
130 A
130 A
65 kA
WEG ACW250W-FTU250-3
o UBW225H-FTU225-3A o
HFD3225L
18 kA
UBW225H-FTU150-
3A o HFD3150L
800
600
300
171 A
171 A
65 kA
WEG ACW250W-FTU250-3 o
UBW250H-FTU250-3A
o HJD3250
30 kA
UBW225H-FTU225-
3A o HFD3225L
800
600
300
200 A
200 A
65 kA
WEG ACW250W-FTU250-3 o
UBW250H-FTU250-3A
o HJD3250
30 kA
UBW250L-FTU250-
3A o JDC3250
800
600
300
255 A
255 A
65 kA
WEG ACW400W-FTU400-3
o UBW400H-FTU400-3A o
HKD3400
30 kA
UBW250L-FTU250-
3A o JDC3250
1000
600
400
312 A
312 A
65 kA
WEG ACW400W-FTU400-3
o UBW400H-FTU400-3A o
HKD3400
30 kA
UBW400H-FTU400-
3A o HKD3400
1000
600
400
365 A
365 A
65 kA
WEG ACW800W-FTU800-3 o
UBW600H-FTU600-3A
o HLD3600
42 kA
UBW400H-FTU400-
3A o HKD3400
1000
600
400
412 A
382 A
65 kA
WEG ACW800W-FTU800-3 o
UBW600H-FTU600-3A
o HLD3600
42 kA
UBW600L-FTU600-
3A o LDC3600
1000
600
400
Tabla 3.7 - Capacidad de cortocircuito – UL High Fault
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
3.2.4.2 Fusibles y
Disyuntores
de Entrada –
IEC
Fusibles del tipo ultrarrápido (aR), fusibles normales o disyuntores:
Para Coordinación Tipo 1, pueden ser utilizados fusibles normales
o disyuntores, de acuerdo con la IEC 60947-4-2, que protegerán la
instalación contra cortocircuito, no obstante, los SCRs no quedarán
protegidos, disyuntores tabla 3.6 y tabla 3.7.
Para Coordinación Tipo 2, los fusibles a ser utilizados en la entrada
deberán ser para protección de semiconductores, tipo ultrarrápido
(aR), de acuerdo con la IEC 60947-4-2. Los cuales reducen el riesgo
de quema de los SCRs por transientes de sobrecorriente.
SSW-07
Modelo
I²t del SCR
(A²s)
FNH aR
Blade Contacts
17 A
720
FNH1-63-K-A
24 A
4000
FNH00-80-K-A
30 A
4000
FNH00-100-K-A
45 A
8000
FNH00-125-K-A
61 A
10500
FNH00-160-K-A
85 A
51200
FNH00-250-K-A
130 A
97000
FNH1-400-K-A
171 A
168000
FNH2-500-K-A
200 A
245000
FNH2-630-K-A
255 A
90000
FNH3-500-K-A
312 A
238000
FNH3-710-K-A
365 A
238000
FNH3-710-K-A
412 A
320000
2 x FNH3-500-K-A
Tabla 3.8 - I²t del SCR y fusibles aR Weg
Fusibles tipo ultrarrápido (aR), con l2t menor o igual a 75 % del valor
del SCR indicado (A2s) en la tabla 3.8.
¡NOTA!
El máximo I2t del fusible de las SSWs varía de acuerdo con la forma
constructiva del tiristor utilizado, por ese motivo, las corrientes
nominales mayores pueden presentar I2t menores.
La corriente nominal del fusible debe, preferentemente, ser
igual o mayor que la corriente de arranque del motor, para evitar
sobrecargas cíclicas y la actuación del fusible en la región prohibida
de la curva Tiempo x Corriente.
El correcto dimensionamiento del fusible debe tomar en consideración:
las normas locales de instalaciones eléctricas, el ciclo de arranques,
la cantidad de arranques por hora, la corriente de arranque y el
tiempo de arranque, la temperatura ambiente y la altitud.
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
3.2.5 Conexiones
del Arrancador
Suave SSW-07
al Motor
Para el correcto dimensionamiento de los fusibles, ver el Catálogo
de fusibles de WEG:
www.weg.net
Automatización - Fusibles aR y gL/gG - Tipo NH Contacto Cuchilla,
NH Flush End y Diametral.
Anexo 1: Criterios de Dimensionamiento Fusibles Ultrarrápidos aR
Contacto Cuchilla y Flush End.
Anexo 2: Tablas de Dimensionamiento de Fusibles aR para
Protección de Soft-Starters SSW y Convertidores CFW.
Para la protección de los componentes electrónicos del SSW-07
debe utilizarse fusible tipo D, o mini disyuntor tipo C:
Fusible 2 A Tipo D o Disyuntor 2 A Tipo C.
¡PELIGRO!
Capacitores de corrección del factor de potencia nunca podrán
ser instalados en la salida del Arrancador Suave SSW-07
(U/2T1, V/4T2 y W/6T3).
¡ATENCIÓN!
Para las protecciones basadas en la lectura y indicación de corriente
funcionen correctamente, por ejemplo la sobrecarga, la corriente
nominal del motor no deberá ser inferior a 50 % de la corriente
nominal del Arrancador Suave SSW-07.
3.2.4.3 Fusible de la
Electrónica
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
3.2.6 Conexiones de
Puesta a Tierra
3.2.5.1 Conexión
Padrón del
Arrancador
Suave
SSW-07 al
Motor con
Tres Cables
¡NOTA!
Utilizar en el mínimo las espesuras de cableados y fusibles
recomendados en las tablas 3.5, 3.6 y 3.7. El torque (par) de apierto
del conector es indicado en la tabla 3.4. Use solamente cableado
de cobre.
¡NOTA!
El Arrancador Suave SSW-07 posee protección electrónica de
sobrecarga del motor, que debe ser ajustada de acuerdo con el
motor específico. Cuando diversos motores fueren conectados
al mismo Arrancador Suave SSW-07, utilice relés de sobrecarga
individuales para cada motor.
Corriente de línea del Arrancador Suave SSW-07 igual a la corriente
del motor.
1/U1
4/U2
2/V1
5/V2
6/W2
3/W1
2/V1
5/V2
1/U1
4/U2
6/W2
3/W1
R
S
T
N
PE
R
S
T
N
PE
T
W
V
S
U
R
T
W
V
S
U
R
Figura 3.7 - Arrancador Suave SSW-07 con conexión padrón
¡PELIGRO!
Los Arrancadores Suaves SSW-07 deben ser obligatoriamente
puestos a tierra de protección (PE).
La conexión de puesta a tierra debe seguir las normativas locales.
Conéctelo a una barra de aterramiento especifica o al punto de puesta
a la tierra especifico o al punto de aterramiento general (resistencia
≤ 10 ohms).
¡PELIGRO!
La red que alimenta el Arrancador Suave SSW-07 debe ser
solidamente puesta a tierra.
¡PELIGRO!
Para poner a tierra no utilice el conductor neutro y si un conductor
específico.
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
3.2.7 Conexiones de
Señal y Control
¡ATENCIÓN!
No compartir el cableado de puesta a tierra con otros equipamientos
que operen con altas corrientes (ej.: motores de alta potencia,
máquinas de soldadura, etc). Cuando varios Arrancadores Suaves
SSW-07 fueren utilizados, observar las conexiones en la figura 3.8.
BARRA DE ATERRAMENTO
INTERNA AO PAINEL
BARRA DE ATERRAMENTO
INTERNA AO PAINEL
BARRA DE PUESTA A TIERRA
INTERNA AL TABLERO.
BARRA DE PUESTA A TIERRA
INTERNA AL TABLERO.
Figura 3.8 - Conexiones de puesta a tierra para más de un Arrancador Suave
SSW-07
EMI - Interferencia Electromagnética
El Arrancador Suave SSW-07 es desarrollado para ser utilizado
en sistemas industriales (Categoría A), conforme la normativa
EN60947-4-2. Es necesario desplazar los equipamientos y cableados
sensibles en 0,25 m del Arrancador Suave SSW-07 y de los cableados
entre Arrancador Suave SSW-07 y motor. Ejemplo: Cableado de
PLCs, controladores de temperatura, cables de termopar, etc.
Puesta a Tierra de la Carcasa del Motor
El cableado de salida del Arrancador Suave SSW-07 para el motor
debe ser instalado separado del cableado de entrada de la red, bien
como del cableado de control y de la señal.
Las conexiones de control (entradas digitales y salidas a relé) son
hechas a través de los terminales (mirar posicionamiento en la
figura 3.9).
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
Terminal
Descripción
Especificación
Torque
Nm (Par)
A1
Alimentación de la Electrónica
Tensión: 110 Vca a 240 Vca (-15 % a +10 %)
(modelos de 17 A hasta 200 A),
110 Vca a 130 Vca o 208 a 240 Vca
(-15 % a +10 %) (modelos de 255 A hasta 412 A)
0,5
A2
Puesta a Tierra
Solamente para los modelos 255 A hasta 412 A
Terminal
Padrón de Fábrica
Especificación
DI1
Acciona / Desaciona el motor
3 entradas digitales aisladas
Tensión 110 Vca a 240 Vca
(-15 % a +10 %)
Corriente: 2 mA Máx.
DI2
Reset de Errores
DI3
Reset de Errores
13
Salida a relé - Operación
Capacidad de los contactos:
Tensión: 250 Vca
Corriente: 1 A
14/23
Punto Común de los relés
24
Salida relé 2 – Tensión Plena
Tabla 3.9 - Descripción de los terminales de los conectores de control
Figura 3.9 - Terminales de control de la SSW-07
¡NOTA!
Para cables con gran longitud (arriba de los 30 m) en las DIx en
ambientes ruidosos es recomendable el uso de cables blindados.
El blindaje y el A2 deben ser puestos a tierra.
Aquí son presentados algunos accionamientos propuestos, los
cuales pueden ser usados por entero o en parte para implementar
el accionamiento deseado.
Las principales notas de advertencia, para todos los accionamientos
sugestivos, son presentados abajo y están relacionadas con los
proyectos a través de los suyos respectivos números:
3.3 ACCIONA-
MIENTOS
PROPUESTOS
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
¡NOTAS!
Para la protección de toda la instalación eléctrica es necesaria
la utilización de fusibles o disyuntores en el circuito de entrada.
No es necesaria la utilización de fusibles ultra rápidos para el
funcionamiento del Arrancador Suave SSW-07, sin embargo
su utilización es recomendada para la completa protección del
Arrancador Suave.
El transformador “T1” es opcional y debe ser utilizado cuando
ocurrir diferencia entre la tensión de la red de alimentación y
la tensión de alimentación de la electrónica.
Caso ocurran daños en el circuito de potencia del Arrancador
Suave SSW-07 que mantengan el motor accionado (por
ejemplo: cortocircuito en los tiristores), la protección del motor
es obtenida con la utilización del contactor (K1) o del disyuntor
(Q1) de aislamiento de potencia.
Botonera Acciona.
Botonera Desacciona.
Llave acciona/desacciona, recuerdas que al utilizar comando
por entrada digital a dos cables (llave normalmente abierta con
retención) caso ocurra falta de energía eléctrica, al regresar, el
motor será accionado inmediatamente si la llave permanecer
cerrada.
En caso de mantenimiento, en el Arrancador Suave SSW-07
o en el motor, es necesario retirar los fusibles de entrada o
seccionar la entrada de alimentación para garantizar la completa
desconexión del equipamiento de la red de alimentación.
La emergencia puede ser utilizada cortándose la alimentación
de la electrónica.
Bobina de mínima tensión del disyuntor de aislamiento de la
potencia Q1.
2
3
4
5
6
7
8
9
1
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
3.3.1 Accionamiento
Propuesto
con Comando
por Entradas
Digitales a
Dos Cables y
Contactor de
Aislamiento de
la Potencia
Figura 3.10 - Accionamiento propuesto con comando por entradas digitales a
dos cables y contactor de aislamiento de la potencia
3.3.2 Accionamiento
Propuesto
con Comando
por Entradas
Digitales a
Tres Cables y
Disyuntor de
Aislamiento de
la Potencia
¡NOTA!
Es necesario programar la entrada digital DI2 para la función
comando a 3 cables. Mirar ítem 4.10.
¡NOTA!
El RL1 precisa ser programado para la función “sin error”. Mirar
ítem 4.12.
Figura 3.11 - Accionamiento propuesto con comando por entradas digitales a
tres cables y disyuntor de aislamiento de la potencia
Mirar notas en el ítem 3.3.
24
14 23
13
DI3
RL1
RL2
T1
PE
R
S
T
K1
K1
DI2
DI1
A2
A1
M
3~
R S T
U V W
Mirar notas en el ítem 3.3.
R
S
T
PE
M
3~
R S T
U V W
T1
Q1
24
14 23
13
DI3
RL1
RL2
DI2
DI1
A2
A1
Q1
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
3.3.3 Accionamiento
Propuesto
con Comando
por Entradas
digitales y
Cambio del
Sentido de Giro
Figura 3.12 - Accionamiento Propuesto con Comando por Entradas digitales
y Cambio del Sentido de Giro
¡NOTA!
Para efectuar la programación de los parámetros citados encima,
es necesario el uso de HMI o comunicación serial. Ver manual de
programación.
24
14 23
13
DI3
RL1
RL2
T1
PE
R
S
T
K1
K2
K2
K1
DI2
DI1
A2
A1
M
3~
R S T
U V W
P220 = 1
P230 = 1
P263 = 1 (DI1 = Start/Stop
dos cables)
P265 = 4 (DI3 = Sentido de
giro)
P277 = 4 (RL1 = Sentido de
giro K1)
P278 = 4 (RL2 = Sentido de
giro K2)
P620 = 0 (Secuencia de fase
RST = Inactiva)
Mirar notas en el ítem 3.3.
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
3.3.4 Accionamiento
Propuesto
con Comando
por Entradas
digitales y
Frenado CC
Figura 3.13 - Accionamiento Propuesto con Comando por Entradas digitales
y Frenado CC
¡NOTA!
Para efectuar la programación de los parámetros citados encima,
es necesario el uso de HMI o comunicación serial. Ver manual de
programación.
P220 = 1
P230 = 1
P263 = 1 (DI1 = Start/Stop
dos cables)
P265 = 5 (DI3 = Sin frenado)
P277 = 1 (RL1 = En
funcionamiento)
P278 = 5 (RL2 = Frenado
CC)
P501 ≥ 1 (Tiempo de
Frenado ≥ 1s)
24
14 23
13
DI3
RL1
RL2
T1
PE
R
S
T
K1
K2
K2
K1
DI2
DI1
A2
A1
M
3~
R S T
U V W
Mirar notas en el ítem 3.3.
CAPÍTULO 3 - INSTALACIÓN Y CONEXIÓN
Español
3.3.5 Simbología
Conexión eléctrica entre dos
señales
Fusible
Terminal para conexión
Tiristor/SCR
Bobina relé, contactor
M
3~
Motor trifásico
Contacto normalmente abierto
Transformador
Señalero
Llave N.A. (con retención)
Seccionadora o Disyuntor
(abertura bajo carga)
Botonera push-botton
normalmente cerrada
Resistor
Botonera push-botton
normalmente abierta
Capacitor
Disyuntor con bobina de
mínima tensión
COMO AJUSTAR EL SSW-07
Este capítulo describe los procedimientos necesarios para el
correcto funcionamiento del Arrancador Suave SSW-07.
"DIP Switch" de Ajuste
del Tipo de Control
Figura 4.1 - Ajuste del tipo de control
Seleccionar el tipo de control de arranque que mejor se adapta a
su aplicación.
Arranque con rampa de tensión:
Este es el método más utilizado. Muy fácil de programar y ajustar.
El Arrancador Suave SSW-07 impone la tensión aplicada al motor.
Generalmente aplicado a cargas con torque (par) inicial más bajo
o torque (par) cuadrático.
Este tipo de control puede ser usado como un teste inicial de
funcionamiento.
Arranque con Limitación de Corriente:
El máximo nivel de corriente es mantenido durante el arranque y es
ajustado de acuerdo con las necesidades de la aplicación.
Generalmente aplicado a cargas con torque (par) inicial más alto
o torque (par) constante.
Este tipo de control es utilizado para adecuar el arranque a los
límites de capacidad de la red de alimentación.
¡NOTAS!
1. Para programar el tipo de control en Rampa de Corriente es
necesario utilizar HMI o comunicación serial. Ver manual de
programación.
2. Para programar el tipo de control en Control de bombas. Ver
manual de programación o ítem 5.1.4.
4.1 AJUSTE DEL
TIPO DE
CONTROL
CAPÍTULO 4 - COMO AJUSTAR EL SSW-07
Español
4.2 KICK START
4.3 AJUSTE DE
LA TENSIÓN
INICIAL
“DIP Switch” de Habilitación
del Kick Start
Figura 4.2 - Habilitación del Kick Start
El Arrancador Suave SSW-07 posibilita la utilización de un pulso de
torque (par) en el arranque para cargas que presentan una grande
resistencia inicial al movimiento.
Esta función es habilitada a través de la “DIP Switch” Kick Start. El
tiempo de duración del pulso de tensión es ajustable a través del
trimpot Kick Start Time.
El pulso de tensión aplicado es de 80 % Un durante el tiempo
programado en el Kick Start Time.
¡NOTA!
Utilizar esta función solamente para aplicaciones específicas donde
ocurra la necesidad.
Ajustar el valor de la tensión inicial para el valor en que empiece
a girar el motor accionado por el SSW-07, tan luego el Arrancador
Suave reciba el comando de acciona.
El punto indica el
ajuste padrón de
fábrica
Trimpot de Ajuste
de la Tensión Inicial
Figura 4.3 - Ajuste de la tensión inicial
CAPÍTULO 4 - COMO AJUSTAR EL SSW-07
Español
4.4 AJUSTE DEL
LIMITE DE
CORRIENTE
¡NOTA!
El trimpot Inicial Voltage posee la función de ajuste de la Tensión
Inicial solamente cuando el tipo de control estuviera programado
para arranque con rampa de tensión.
Este ajuste define el valor límite máximo de corriente durante
el arranque del motor en porcentual de la corriente nominal del
Arrancador Suave.
Si el límite es alcanzado durante el arranque del motor, el Arrancador
Suave SSW-07 irá mantener la corriente en ese limite hasta el motor
alcanzar el final del arranque.
Si el límite de corriente no es alcanzado el motor irá arrancar
inmediatamente.
La limitación de corriente debe ser ajustada para un nivel donde se
pueda observar la aceleración del motor, caso contrario el motor
no irá arrancar.
Trimpot de Ajuste del
Límite de Corriente
Figura 4.4 - Ajuste del límite de corriente
¡NOTAS!
Si en el final del tiempo de rampa de aceleración (ajustado en
el Trimpot Accel Time), no es alcanzado la tensión plena, habrá
la actuación del Error de Excesso de Tiempo de Limitación de
Corriente. Este error es indicado a través del LED Fault parpadeando
2 veces con el LED Ready acceso.
El trimpot Current Limit posee la función de ajuste del Limite de
Corriente solamente cuando el tipo de control esta programado
para arranque con Limitación de Corriente.
Cuando el Arrancador Suave SSW-07 se encuentra programado
CAPÍTULO 4 - COMO AJUSTAR EL SSW-07
Español
4.5 AJUSTE DEL
TIEMPO DE
LA RAMPA DE
ACELERACIÓN
4.6 AJUSTE DEL
TIEMPO DE
LA RAMPA DE
DESACELE-
RACIÓN
con control de Rampa de Tensión, este es el tiempo de la rampa
de incremento de tensión.
Cuando el Arrancador Suave SSW-07 se encuentra programado
con control de Límite de Corriente, este tiempo actúa como tiempo
máximo de arranque, actuando como una protección contra rotor
bloqueado.
Trimpot de Ajuste de
Tiempo de la Rampa
de Aceleración
Figura 4.5 - Ajuste del tiempo de la rampa de aceleración
¡NOTA!
El tiempo de aceleración programado no es el tiempo exacto de
aceleración del motor, pero sí el tiempo de la rampa de tensión o el
tiempo máximo para el arranque. El tiempo de aceleración del motor
dependerá de las características del motor y también de la carga.
Tomar cuidado para que en los casos en que la relación de corriente
de la SSW-07 y de la Corriente nominal del motor es 1,00 el tiempo
máximo que el SSW-07 puede funcionar con 3x In del SSW-07 es
de 30 segundos.
Habilita y ajusta el tiempo de la rampa de decremento de tensión.
Este ajuste debe ser utilizado solamente en desaceleración de
bombas para amenizar el “Golpe de Ariete”. Este ajuste debe ser
hecho para conseguir el mejor resultado práctico.
¡NOTA!
Esta función es utilizada para aumentar el tiempo de desaceleración
normal de una carga y no para forzar un tiempo menor que el
impuesto por la propia carga.
CAPÍTULO 4 - COMO AJUSTAR EL SSW-07
Español
4.7 AJUSTE DE
CORRIENTE
DEL MOTOR
Trimpot de Ajuste del
Tiempo de la Rampa
de Desaceleración
Figura 4.6 - Ajuste del tiempo de la rampa de desaceleración
Este ajuste irá definir la relación de corriente del Arrancador Suave
SSW-07 y del motor por elle accionado. Este valor es de extrema
importancia, pues es elle quien irá definir las protecciones del motor
accionado por el SSW-07.
El ajuste de esta función interfiere directamente en las siguientes
protecciones del motor:
- Sobrecarga;
- Sobrecorriente;
- Rotor bloqueado;
- Falta de fase.
Ejemplo de Cálculo:
SSW-07 utilizada: 30 A
Motor utilizado: 25 A
Trimpot de Ajuste de la Corriente del Motor
Ajuste de la Corriente del Motor = lMotor
lSSW-07
Ajuste de la Corriente del Motor = 25 A
30 A
Ajuste de la Corriente del Motor = 0,833
Por lo tanto debe ser ajustado en 83 %
CAPÍTULO 4 - COMO AJUSTAR EL SSW-07
Español
4.8 PROTECCIÓN DE
SOBRECARGA
ELECTRÓNICA
DEL MOTOR
Trimpot de Ajuste de
la Corriente del Motor
Figura 4.7 - Ajuste de la corriente del motor
La protección de sobrecarga electrónica del motor haz la simulación
del calentamiento y del enfriamiento del motor, llamada de imagen
térmica.
Esa simulación usa como dato de entrada el valor de corriente eficaz
verdadera (True rms).
Cuando el valor de la imagem térmica pasara del limite, el error de
sobrecarga se dispara y desconecta el motor.
El ajuste de la clase térmica es basado en la corriente de rotor
bloqueado y en el tiempo de rotor bloqueado del motor. A partir
de estos datos, es posible encontrar el punto en el gráfico para
determinar cuales clases térmicas protegen el motor. Si el dato de
tiempo de rotor bloqueado fuera a frío, utilice la figura 4.8; caso el
tiempo de rotor bloqueado fuera a caliente, utilice la figura 4.9. Las
clases térmicas abajo del punto encontrado protegen el motor.
CAPÍTULO 4 - COMO AJUSTAR EL SSW-07
Español
Tiempo t(s)
10000
1000
100
10
1
F.S.=1,15 1x 2x 3x 4x 5x 6x 7x 8x 9x 10x
Clase 30
Clase 25
Clase 20
Clase 15
Clase 10
Clase 5
Corriente
x In del
motor
F.S.=1 1x 2x 3x 4x 5x 6x 7x 8x 9x
Figura 4.8 - Clases térmicas de protección del motor a frío
Tiempo t(s)
1000
100
10
1
1x 2x 3x 4x 5x 6x 7x 8x 9x F.S.=1
Clase 30
Clase 25
Clase 20
Clase 15
Clase 10
Clase 5
Corriente
x In del
motor
0.1
Figura 4.9 - Clases térmicas de protección del motor a caliente con 100 % In
CAPÍTULO 4 - COMO AJUSTAR EL SSW-07
Español
DIP Switch de
Habilitación de
la Protección de
Sobrecarga
DIP Switch de ajuste
del clase térmica
Figura 4.10 - Habilitación e ajuste del protección de sobrecarga
¡NOTAS!
Cuando el SSW-07 se queda sin tensión de alimentación
en la electrónica (A1 y A2), la imagen térmica es guardada
internamente. Al retornar la alimentación (A1 y A2) el valor de la
imagen térmica retorna al valor anterior a la falta de alimentación
de la electrónica;
El RESET de la protección de sobrecarga electrónica puede ser
ajustado para la función manual (man), en este caso se debe
hacer el RESET vía entrada digital 2 (DI2) o através del botón
de RESET. Si el ajuste del RESET se encuentra ajustado para
automático (auto), la condición de error es automáticamente
reseteada después de transcurrido el tiempo de enfriamiento;
Al desactivar la protección de sobrecarga electrónica, la imagen
térmica es puesta a cero.
Para el perfecto funcionamiento de la protección de sobrecarga,
ajuste la corriente del motor conforme el capítulo 4.7.
Esta protección utiliza como estándar el Motor Trifásico IP55
Standard WEG. Caso el motor sa diferente, recomendamos
ajustar una clase térmica menor. Para más detalles ver 5.2.
Una condición de error puede ser reseteada a través del botón
de RESET en el frontal del SSW-07, o a través de una botonera
pulsante (0,5 segundos) en la DI3 (entrada digital para RESET).
Otro modo para efectuar el RESET en el SSW-07, es desconectar
y conectar nuevamente la tensión de alimentación de la electrónica
(en los terminales A1 y A2).
4.9 RESET
CAPÍTULO 4 - COMO AJUSTAR EL SSW-07
Español
4.10 PROGRAMACIÓN
DE LA ENTRADA
DIGITAL DI2
¡NOTAS!
En el SSW-07 existe la posibilidad de RESET automático, bastando
habilitar esta función vía DIP Switch (auto):
El tiempo para ocurrir el RESET automático después de la
ocurrencia del error es de 15 minutos para las siguientes
condiciones:
- Sobrecorriente;
- Falta de fase;
- Rotor bloqueado;
- Sobrecorriente antes del By-Pass;
- Frecuencia fuera de la tolerancia;
- Contacto del relé de By-Pass interno abierto;
- Subtensión en la alimentación de la electrónica;
- Error externo.
Para secuencia de fase incorrecta no existe RESET automático;
Para sobrecarga electrónica del motor existe un algoritmo
específico para tiempo de RESET automático.
En la programación padrón de fábrica, la entrada digital DI2 tiene
la suya función programada para reset de errores. La DI2 puede
ser también programada para funcionar con control a tres cables.
El control a tres cables posibilita que el Arrancador Suave sea
comandado a través de dos entradas digitales. DI1 como entrada
de acciona y DI2 como entrada de desacciona. Pudiendo así colocar
directamente una botonera de dos teclas. Mirar ítem 3.3.2.
Para modificar la programación de la entrada digital DI2, seguir las
siguientes instrucciones:
1. Para entrar en el modo de programación, mantener presionada
la tecla reset en la parte frontal del SSW-07 por 5 segundos.
Mantener la tecla de reset presionada durante la programación;
2. Cuando estuviera en el modo programación, encenderá dos
LEDs (sobrecorriente y falta de fase), señalizando que la DI2
esta programada para Reset de errores.
Encendiendo tres LEDs (sobrecorriente, falta de fase y secuencia
de fase), señaliza que la DI2 esta programada para comandos
a tres cables;
3. Para modificar la programación para comandos a tres cables,
mover la “DIP Switch” de sobrecorriente y volver para la posición
anterior. Encenderá los tres LEDs, señalizando que la DI2 esta
programada para comandos a tres cables;
4. Para modificar la programación de la DI2 para Reset de errores,
mover la “DIP Switch” de Kick Start y volver para la posición
anterior. Encenderá los dos LEDs, señalizando que la DI2 esta
programada para Reset de errores;
5. Al desaccionar la tecla de Reset, la programación estará
concluida.
CAPÍTULO 4 - COMO AJUSTAR EL SSW-07
Español
4.11 FUNCIONA-
MIENTO DE LAS
SALIDAS A RELÉ
4.12 PROGRAMACIÓN
DE LA SALIDA A
RELÉ RL1
�El relé para la Función de Operación cierra el suyo contacto
NA. (13-14/23), siempre que el SSW-07 recibir un comando de
acciona, este contacto solamente es abierto en la final de la
rampa de desaceleración (cuando esta se encuentra ajustada
vía trimpot), o cuando el SSW-07 recibir el comando para
desacciona;
�El relé para la función Tensión Plena cierra el suyo contacto NA.
(14/23-24) siempre que el SSW-07 se encuentra con 100 % de
la tensión aplicada al motor por elle accionado, este contacto es
abierto cuando el SSW-07 recibir el comando para desaccionar;
(Tensión en el Motor)
UN
Función de Operación
(13-14/23)
Función de Tensión Plena
(14/23-24)
100%
Relé
Activado
t
t
t
Figura 4.11 - Funcionamiento de las salidas a relé
En la programación padrón de fábrica, la salida a relé RL1 tiene
su función programada para “Operación”. El RL1 (13/14) puede
ser programado también para funcionar “Sin Error”. Esta función
posibilita la instalación de un disyuntor con bobina de mínima tensión
en la entrada del Arrancador Suave SSW-07. Mirar ítem 3.3.2.
Para modificar la programación de la salida a relé RL1, seguir las
siguientes instrucciones:
1. Para entrar en el modo de programación, mantener presionada
la tecla reset en la parte frontal del SSW-07 por 5 segundos.
Manteniéndola presionada durante la programación;
2. Cuando en Arrancador Suave SSW-07 se encuentra en el modo
de programación, encenderá dos LEDs (sobrecorriente y falta
de fase), indicando que la DI2 está programada para reset de
errores.
Encendido 3 LEDs (sobrecorriente, falta de fase y secuencia de
fase), se indica que la DI2 está programada para comandos a
tres cables. Si el LED Overload se encender, la función del RL1
es “Sin Error”, caso contrario la función es “Operación”;
3. Para modificar la programación del relé RL1 es necesario mover
el “DIP switch” de “overload” y volver para la posición anterior. El
LED “overload” indica la nueva programación del RL1.
- LED Overload apagado:
Función de Operación;
- LED Overload encendido:
Función Sin Error.
5.1 APLICACIONES Y
PROGRAMACIÓN
INFORMACIONES Y SUGERENCIAS DE
PROGRAMACIÓN
Este capítulo auxilia el usuario a ajustar y a programar los tipos de
control de arranque de acuerdo con la aplicación.
¡ATENCIÓN!
Sugerencias y notas importantes para cada tipo de control de
arranque.
¡ATENCIÓN!
Para saber la correcta programación de los parámetros tenga en
manos los datos de su carga y utilice el “Software” de Dimensionado
WEG para Arrancadores Suaves disponible en la página de Internet
(http://www.weg.net).
Caso no se consiga utilizar este software se pueden seguir algunos
conceptos prácticos descriptos en este capítulo.
A seguir son presentadas las curvas características con el
comportamiento de la corriente y del torque (par) de arranque
conforme algunos tipos de control.
Corriente
Torque (Par)
C/Cn
I/In
Cn
0
25
50
75
100 % rpm
Corriente
Torque (Par)
I/In
Cn
0
25
50
75
100 % rpm
C/Cn
Cn
Figura 5.1 - Curvas características de torque (par) y de corriente en un
arranque directo y por rampa de tensión
CAPÍTULO 5 - INFORMACIONES Y SUGERENCIAS DE PROGRAMACIÓN
Español
5.1.1 Arranque con
Rampa de
Tensión
I/In
Torque (Par)
Corriente
C/Cn
Cn
0
25
50
75
100 % rpm
Figura 5.2 - Curvas características de torque (par) y de corriente en un
arranque con limitación de corriente
1) Ajustar el valor de la tensión inicial para un valor bajo;
2) Cuando fuera colocada carga en el motor, ajustar la tensión inicial
para un valor que haga el motor girar suavemente a partir del
instante que fuera accionado;
3) Ajustar el tiempo de aceleración con el tiempo necesario para
el arranque, inicialmente con tiempos cortos, 10 a 15 segundos,
después intente encontrar la mejor condición de arranque para
la suya carga.
100 %Un
Arranque
U(V)
Para
Rampa de Tensión
Gira
t(s)
0
Figura 5.3 - Arranque con rampa de tensión
¡NOTAS!
Con largos tiempos de arranque, o el motor sin carga, pueden
ocurrir vibraciones durante el arranque del motor, por lo tanto
disminuya el tiempo de arranque;
Caso ocurran errores durante el arranque, revise todas las
conexiones del Arrancador Suave a la red de alimentación,
conexiones del motor, niveles de las tensiones de la red de
alimentación, fusibles, disyuntores y seccionadoras.
CAPÍTULO 5 - INFORMACIONES Y SUGERENCIAS DE PROGRAMACIÓN
Español
5.1.2 Arranque con
Limitación de
Corriente
5.1.3 Arranque
con Control
de Bombas
(P202 = 2)
1) Para arrancar con limitación de corriente se debe arrancar con
carga, testes a vació pueden ser hechos con rampa de tensión;
2) Ajustar el tiempo de aceleración con el tiempo necesario para el
arranque, inicialmente con tiempos cortos, 20 a 25 s. Ese tiempo será
utilizado como tiempo de rotor bloqueado caso el motor no arranque;
3) Ajustar el Limite de Corriente de acuerdo con las condiciones
que su instalación eléctrica permita y también a valores que
suministren el torque (par) suficiente para arrancar el motor.
Inicialmente puede ser programado con valores entre 2x a 3x
de la corriente nominal del motor (In del motor).
I(A)
Arranque
I Limitación
I Nominal
Tiempo Máximo
Gira
Para
Limitación de Corriente
0
t(s)
Figura 5.4 - Arranque con límite de corriente constante
¡NOTAS!
Si el límite de corriente no fuera alcanzado durante el arranque,
el motor irá arrancar inmediatamente;
Valores muy bajos de Límite de Corriente no proporcionan
torque (par) suficiente para arrancar el motor. Mantenga el motor
siempre girando a partir del instante que fuera accionado;
Para cargas que necesiten de un torque (par) inicial de arranque
más elevado, se puede utilizar la función “Kick Start”;
Caso ocurran errores durante el arranque, revise todas
las conexiones del Arrancador Suave SSW-07 a la red de
alimentación, conexiones del motor, niveles de las tensiones de
la red de alimentación, fusibles, disyuntores y seccionadoras.
1) Para arrancar con control de bombas se debe arrancar con carga,
testes en vacío pueden ser hechos con rampa de tensión;
2) Los ajustes de los parámetros de arranque dependen mucho de
los tipos de instalaciones hidráulicas, por tanto, siempre es útil
optimizar los valores padrones de fábrica;
3) Verificar el correcto sentido de giro del motor, indicado en la carcaza
de la bomba. Caso necesario utilice la secuencia de fase P620;
Figura 5.5 - Sentido de giro en una bomba hidráulica centrífuga
CAPÍTULO 5 - INFORMACIONES Y SUGERENCIAS DE PROGRAMACIÓN
Español
4) Ajustar el valor de la Tensión Inicial P101 para un valor que
haga el motor girar suavemente a partir del instante que fuera
accionado;
5) Ajustar el valor del tiempo de aceleración suficiente para la
aplicación, o sea, que torne el arranque de la bomba suave
sin exceder el necesario. Tiempos largos programados para el
arranque pueden ocasionar vibraciones o sobre calentamientos
desnecesarios al motor;
6) Utilice siempre un manómetro en la instalación hidráulica para
verificar el perfecto funcionamiento del arranque. El aumento de
la presión no debe presentar oscilaciones bruscas y debe ser el
más lineal posible;
Gira
0
100%Un
Arranque
Control de
Bombas
P102
P101
U(V)
Figura 5.6 - Manómetro presentando el aumento de la presión
7) Programar la tensión inicial de desaceleración solo cuando fuera
observado que, lo instante inicial de la desaceleración, no ocurre
la disminución de la presión. Con el auxilio del tensión inicial de
desaceleración, se puede mejorar la linealidad de la queda de
la presión en la desaceleración;
8) Ajustar el valor del tiempo de desaceleración suficiente para la
aplicación, o sea, que torne la parada de la bomba suave más
que no exceda el necesario. Tiempos largos programados para
la parada pueden ocasionar vibraciones o sobre calentamientos
desnecesario al motor;
Para
0
100%Un
Parada
P104
P105
t(s)
P103
U(V)
Figura 5.7 - Manómetro presentando la caída de la presión
CAPÍTULO 5 - INFORMACIONES Y SUGERENCIAS DE PROGRAMACIÓN
Español
9) En el final de la rampa de desaceleración es común que la
corriente aumente, en este instante el motor necesita de más par
(torque) para mantener el flujo de agua parando suavemente.
Pero si el motor es parado y continua accionado, la corriente irá
aumentar mucho, para prevenir esto aumentar el valor de P105
hasta el valor ideal en el momento que el motor pare de girar y
es desaccionado;
10)Programe P610 y P611 con niveles de corrientes y tiempos que
pueden proteger su bomba hidráulica de trabajar en vacío.
Para
Gira
0
100%Un
Parada
Arranque
Control de Bombas
P104
P102
P105
t(s)
P103
P101
U(V)
Figura 5.8 - Partida con control de bombas
¡NOTAS!
1) Si no hubiera manómetros de observación en las tuberías
hidráulicas, los golpes de Arietes pueden ser observados a través
de las válvulas de alivio de presión;
2) Recordar que caídas bruscas de tensión en la red de alimentación
provocan caídas de par (torque) en el motor, por tanto mantenga
las características de su red eléctrica dentro de los limites
permitidos por su motor;
3) Caso ocurran errores durante el arranque, revise todas las
conexiones del Arrancador Suave a la red de alimentación,
conexiones del motor, niveles de las tensiones de la red de
alimentación, fusibles, disyuntores y seccionadoras.
Es indicado programar el tipo de control para control de bombas,
usando HMI o comunicación serial, ver Manual de Programación.
En casos especiales, donde no está disponible HMI o comunicación
serial, también es posible programar el tipo de control para control
de bombas obedeciendo las siguientes instrucciones:
1) Para entrar en el modo programación, mantener presionada la
tecla reset en la parte frontal de la SSW-07 por 5 segundos.
Manteniéndola presionada durante la programación;
2) Cuando esté en modo programación, se encenderán LEDs
indicando la actual programación. Ver ítem 4.10 y 4.12;
5.1.4 Programación del
tipo de control
para control de
bombas