KE2 EvapOEM Quick Start Manual
Text of the manual
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.1.45
May 2019
KE2 EvapOEM pn21231
Quick Start Guide
This reference should remain on site with the installed KE2 Evap OEM controller.
Get your controller
online, & beneft from remote
monitoring, control, and text /
e-mail alarm notices.
Just a few easy steps, with
KE2 Smart Access
Pr
LL SOLENOID/COMP RELAY
BK/OR
L1
WT/R
L2
HS
GND
P/N 20996
12 AMP
20 AMP
3 AMP
OR NEUTRAL
HEATERS
thermsolutions®
R/W
BL/BK
BK
BL/BK
FROM
CONTROLLER
EC MOTOR
RELAY
NO NC
COM
TSuc
Aux3
Aux2
Aux1
TCoil
TAir
0 - 10V OUTPUT
ETHERNET
DISPLAY
DEFROST RELAY
SOLENOID
(COMPRESSOR) RELAY
FAN RELAY
Blue
Orange
Yellow
Red
Black
Empty
Red
Gr
Q.1.45 May 2019
Page 3
KE2 EvapOEM
Quick Start Guide
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Wiring Diagram - Controller without KE2 Terminal Board
NO
COM
NO
COM
NC
FAN RELAY
COMPRESSOR
RELAY
DEFROST
RELAY
COM
NO
L1
N/L2
VOUT
MOTOR
Aux3
Aux2
Aux1
TCoil
TAir
TSuc
PSI
RS-485
HS
DEFROST
HEATERS
FANS
S
LLS
NC
N
X
BLK
RED
BLK
FIEL
Q.1.45 May 2019
Page 4
KE2 EvapOEM
Quick Start Guide
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
IMPORTANT
Steps to Ensure Proper Coil Sensor Location
Installing the Sensor - The most active portion of the sensor is the first 1/2” of the probe.
The inset photo in Figure 2 shows that the sensor is positioned so that it is touch
Q.1.45 May 2019
Page 5
KE2 EvapOEM
Quick Start Guide
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Changing Setpoints
Pressing and holding the ENTER button will enter the Basic Setpoints menu.
Press ENTER button to toggle between setpoint and value.
Pressing and holding the BACK button will enter the Advanced Setpoints
menu. Press E
Quick Start Guide
Q.1.45 May 2019
Page 6
Menus and Parameters
ADVANCED Setpoints Menu
Basic (Remote) Display
KE2 Combo Display
Min
Max
Default
Description
Abbreviation
Scrolling Text
tS
tS
ROOM TEMP
-50.0 0F
90.0 0F
0.0 0F
Room Temp Setpoint - Walk-in room temp to be maintained
rFG
rF
REFRIgERANT
N/A
N/A
R-404A
Type of refrigerant used: See tabl
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.1.45 May 2019
Page 7
KE2 EvapOEM
Quick Start Guide
ADVANCED Setpoints Menu (continued)
Basic (Remote) Display
KE2 Combo Display
Min
Max
Default
Description
Abbreviation
Scrolling Text
EdF
EdF
EXTREME TEMP DIFF
0 0F
99.9 0F
20.0 0F
ADVANCED TOPIC: Call KE2 Therm for assistance
CLA
CLA
C
Quick Start Guide
Q.1.45 May 2019
Page 8
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
First Time Setup - Types of Control & KE2 Smart Access
Basic (Remote) Display
KE2 Combo Display
Description
Abbreviation
Scrolling Text
Ed
Ed
ELECTRIC DEFROST /TEV Electric Defrost w/Mechanical valve
EdE
EdE
ELECTRIC DEFROST /EEV Elec
Q.1.45 May 2019
Page 9
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
KE2 EvapOEM
Quick Start Guide
Alarm Status Menu
Basic (Remote) Display
KE2 Combo Display
Description
Abbreviation
Scrolling Text
PSA
PSA
PRESSURE SENSOR
Suction pressure sensor is shorted, open or pressure out of range
SSA
SSA
SUCTION TEMP SENSOR
Suction temperatur
© Copyright 2019 KE2 Therm Solutions, Inc., Washington, Missouri 63090
Q.1.45 May 2019
Page 10
KE2 EvapOEM
Quick Start Guide
dCL dCL
Door Switch - Door Closed
Auxiliary Input Door switch indicates door is closed
ddF ddF
Defrost Delay Fan
System Mode
At defrost, fans will continue running for several minutes, using stored cooling in the coil. Once the
coil r