Baxi MULTIFIT Flue Systems Guidance Notes
Text of Baxi MULTIFIT Flue Systems Guidance Notes
© Baxi Heating UK Ltd 2011
G U I D A N C E N OT E S
Flue Accessories & Fitting Guide
Ø 60/100 Flue Systems
Ø 80/125 Flue Systems
Ø 80/80 Twin Flue Systems
Plume Displacement Kit (Ø 60/100 Flue Systems)
READ THESE INSTRUCTIONS IN CONJUNCTION WITH THE BOILER
INSTALLATION INSTRUCTIONS BEFORE FITTING THE FLUE
Please leave these instructions with the
Installation & Servicing Instructions.
IMPORTANT NOTE: This document
will assist in the correct installati
© Baxi Heating UK Ltd 2011 • Flue systems must be constructed using only components
approved for use with the appliance and installed in
accordance with BS 5440 Part 1, any manufacturers
instructions and Part J of the Building Regulations.
• In order to meet the requirements of the Gas Safety (Installation
& Use) Regulations, provision should be made such that all flue
joints and supports can be inspected.
• The flue system should have a cont
© Baxi Heating UK Ltd 2011 A
B
K, K1
R
D
C
N
U
S
L
H
J
M
FLUE ACCESSORIES
Flue Groups
Ø60/100 Flue Systems - with Positive Fix
Ø80/125 Flue Systems
Ø80/80 Twin Flue Systems
E
G
F
A4
G
N
A
Y, Z
Key Accessory
Size
Code No
FLUE GROUP A
Concentric Flue System 60/100mm diameter
A
Telescopic Flue (Black)
315-500mm
720598701
A
Telescopic Flue (Brown)
315-500mm
720642701
A
Telescopic Flue (White)
315-500mm
720599401
A
Telescopic Flue Neta-tec &
Platinum
© Baxi Heating UK Ltd 2011 CONCENTRIC FLUE SYSTEM (60/100) ONLY - FLUE GROUP A
USE OF SUPPORTS & SECURING
Each extension and securing screws (1m, 500mm & 250mm) is
supplied with a support bracket. Additional support brackets can be
purchased separately (see Flue Accessory page overleaf). DO NOT
use brackets other than those supplied or shown in this guide.
The flue system MUST be supported AT LEAST once every metre
of actual length, and every strai
© Baxi Heating UK Ltd 2011 Y
X
NOTE: Horizontal flue pipes should always be installed with a 1.5° to 3°
fall from the terminal to allow condensate to run back to the boiler.
Push the flue deflector over the terminal end and rotate to the
optimum angle for deflecting plume. Secure the deflector to the
terminal with screw provided.
Do not direct the deflector upwards or downwards.
NOTE: A terminal guard is still required when circumstances
dictate
© Baxi Heating UK Ltd 2011 Y
X
Y
X
Y
X
C 0.5m
Total Equivalent
Length
Roof
Terminal
Roof
Terminal
A 1m
B 1m
C 0.4m
Roof
Terminal
A 0.7m
B 0.3m
This bend is equivalent to
1 metre
Total Equivalent Length =
A+B+C+1x90°Bend
All vertical and angled runs must be included,
measured from the boiler adaptor (point X) to the
joint with the flue terminal (point Y). One 93° bend
or two 135° bends can be included without
reduction of the flue length.
If furt
© Baxi Heating UK Ltd 2011 Fixing Tie
Fixing Tie
Ridge Line
Ridge Flue Terminal - Suitable for Flue Group A (60/100)
The MAXIMUM equivalent flue length when using this
terminal is 8 metres !
Special Notes
This flue terminal is designed predominantly for use in new
build situations where the roof construction allows for
ridge penetration.
In retrofit installations roofing materials will need to be
removed/replaced and the roof structure may require
© Baxi Heating UK Ltd 2011 Twin Pipe Flue System Examples
FLUE OPTIONS
The MAXIMUM total
equivalent length is stated
in the Installation &
Servicing Instructions
supplied with
each boiler.
1m Min
to
15m Max
The total equivalent
length for this example
is = 6.5 metres.
1m extension
135°bend
91.5°bend
1m
0.25m
0.5m
5
2
2
5.0m
0.5m
1.0m
AIR DUCT
No of
fittings/pipes
Sub total
Equivalent
Length Value
Equivalent Length Air Duct = 6.5m
1m extension
13