Gemu GEMU 1242 Operating Instructions Manual
Read Online
Read the Gemu GEMU 1242 Operating Instructions Manual online using the built-in PDF viewer.
Text of the manual
Electrical position indicator
Operating instructions
EN
4009951
4009951
further information
webcode: GW-1242
All rights including copyrights or industrial property rights are expressly reserved.
Keep the document for future reference.
© GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG
12.04.2019
www.gemu-group.com
2 / 32
GEMÜ 1242
DeviceNet
General information ...................................................
4
1.1
Information .........................................................
4
1.2
Symbols used .....................................................
4
1.3
Definition of terms .............................................
4
1.4
Warning notes ....................................................
4
2
Safety information ....................................................
6
3
Product description ...................................................
7
4
Correct use ................................................................
9
5
Order data ................................................................. 11
6
Technical data ........................................................... 12
7
Dimensions ............................................................... 13
8
Manufacturer's information ....................................... 14
8.1
Delivery ............................................................... 14
8.2
Packaging ........................................................... 14
8.3
Transport ............................................................ 14
8.4
Storage ............................................................... 14
9
Assembly and installation ......................................... 14
9.5
Assembling and installing the electrical posi-
tion indicator ...................................................... 17
10 Electrical connection ................................................. 19
10.1
Potential equalisation – special function X and
Y .......................................................................... 19
10.2
DeviceNet, ordering option Fieldbus, code DN . 20
11 Programming the end positions ................................. 22
11.1
On-site end position programming ................... 22
11.2
End position programming via DeviceNet ........ 22
12 Specific data - DeviceNet .......................................... 23
12.1
Inputs .................................................................. 23
12.2
Outputs ............................................................... 23
12.3
Parameter ........................................................... 24
13 Error clearance .......................................................... 26
14 Inspection and servicing ............................................ 27
15 Disassembly ............................................................. 27
16 Disposal .................................................................... 27
17 Returns ..................................................................... 27
18 Declaration of conformity according to 2014/30/EU
(EMC Directive) ......................................................... 28
19 Declaration of conformity in accordance with
2014/34/EU (ATEX) ................................................... 29
GEMÜ 1242
DeviceNet
www.gemu-group.com
3 / 32
4 / 32
GEMÜ 1242
DeviceNet
General information
1
General information
1.1
Information
–
The descriptions and instructions apply to the standard versions. For special versions not described in this document
the basic information contained herein applies in combination with any additional special documentation.
–
Correct installation, operation, maintenance and repair work ensure faultless operation of the product.
–
Should there be any doubts or misunderstandings, the German version is the authoritative document.
–
Contact us at the address on the last page for staff training information.
1.2
Symbols used
The following symbols are used in this document:
Symbol
Meaning
●
Tasks to be performed
Response(s) to tasks
–
Lists
The following LED symbols are used in the documentation:
Symbol
LED conditions
Off
Lit (on)
Flashing
1.3
Definition of terms
Speed-AP
Speed Assembly and Programming, particularly user-friendly quick assembly, setting and initialisation of electrical position in-
dicators, combi switchboxes and controllers.
1.4
Warning notes
Wherever possible, warning notes are organised according to the following scheme:
SIGNAL WORD
Symbol for
the specific
danger
Type and source of the danger
Possible consequences of non-observance
Measures for avoiding danger
Warning notes are always marked with a signal word and sometimes also with a symbol for the specific danger.
The following signal words and danger levels are used:
DANGER
Imminent danger!
▶Non-observance can cause death or severe injury.
WARNING
Potentially dangerous situation!
▶Non-observance can cause death or severe injury.
5 / 32
GEMÜ 1242
DeviceNet
CAUTION
Potentially dangerous situation!
▶Non-observance can cause moderate to light injury.
NOTICE
Potentially dangerous situation!
▶Non-observance can cause damage to property.
The following symbols for the specific dangers can be used within a warning note:
Symbol
Meaning
Danger from potentially explosive atmosphere
General information
6 / 32
GEMÜ 1242
DeviceNet
Safety information
2
Safety information
The safety information in this document refers only to an individual product. Potentially dangerous conditions can arise in
combination with other plant components, which need to be considered on the basis of a risk analysis. The operator is re-
sponsible for the production of the risk analysis and for compliance with the resulting precautionary measures and regional
safety regulations.
The document contains fundamental safety information that must be observed during commissioning, operation and mainten-
ance. Non-compliance with these instructions may cause:
–
Personal hazard due to electrical, mechanical and chemical effects.
–
Hazard to nearby equipment.
–
Failure of important functions.
–
Hazard to the environment due to the leakage of dangerous materials.
The safety information does not take into account:
–
Unexpected incidents and events, which may occur during installation, operation and maintenance.
–
Local safety regulations which must be adhered to by the operator and by any additional installation personnel.
Prior to commissioning:
1. Transport and store the product correctly.
2. Do not paint the bolts and plastic parts of the product.
3. Carry out installation and commissioning using trained personnel.
4. Provide adequate training for installation and operating personnel.
5. Ensure that the contents of the document have been fully understood by the responsible personnel.
6. Define the areas of responsibility.
7. Observe the safety data sheets.
8. Observe the safety regulations for the media used.
During operation:
9. Keep this document available at the place of use.
10. Observe the safety information.
11. Operate the product in accordance with this document.
12. Operate the product in accordance with the specifications.
13. Maintain the product correctly.
14. Do not carry out any maintenance work and repairs not described in this document without consulting the manufacturer
first.
In cases of uncertainty:
15. Consult the nearest GEMÜ sales office.
7 / 32
GEMÜ 1242
DeviceNet
3
Product description
3.1
Construction
1
2
4
3
5
Item
Name
Materials
1
Housing cover - standard version:
PC
2
Housing base
Anodised aluminium or SS
3
Electrical connection
SS, PP
4
Adapter piece
SS
5
Mounting kit, valve specific
SS
Seals
EPDM and NBR
Product description
8 / 32
GEMÜ 1242
DeviceNet
Product description
3.2
LED displays
3.2.1 Status LEDs
As well as the electrical position feedback and error analysis a visual signal is emitted by LEDs that can be seen from above.
LED
Colour
Function
Standard 1)
Inversed 2)
CLOSED
green
orange
Process valve in CLOSED
position
ERROR
red
red
Error
OPEN
orange
green
Process valve in OPEN
position
MNS
green
green
Communication existing
red
red
Communication error
High visibility LED
green
orange
Process valve in CLOSED
position
orange
green
Process valve in OPEN
position
green / orange
green / orange
Programming mode
1)
Option
Code 00: Without
2)
Option
Code 40: Inversed LED feedback
For order codes see chapter "Order data"
3.2.2 LED conditions
Function
CLOSED
ERROR
OPEN
High visibility LED
Valve in OPEN position
Valve in CLOSED position
Programming mode
OPEN / CLOSED flash alternately
flashes alternately
LED conditions
lit (on)
~
irrelevant
flashes
off
3.3
Description
The GEMÜ 1242 electrical position indicator is suitable for mounting to pneumatically operated linear actuators. Secure con-
nection to valve spindle means reliable feedback signal. Intelligent microprocessor controlled functions make commissioning
and support during operation easier. The current position of the valve is displayed via high visibility LEDs and fed back via
electrical signals. The GEMÜ 1242 has been specially designed for valves with a stroke of 2 to 46 mm.
3.4
Function
The GEMÜ 1242 electrical position indicator is suitable for mounting to pneumatically operated linear actuators. Secure con-
nection to valve spindle means reliable feedback signal. Intelligent microprocessor controlled functions make commissioning
and support during operation easier. The current position of the valve is displayed via high visibility LEDs and fed back via
electrical signals. The GEMÜ 1242 has been specially designed for valves with a stroke of 2 to 46 mm.
9 / 32
GEMÜ 1242
DeviceNet
4
Correct use
DANGER
Danger of explosion
▶Danger of death or severe injury.
●
Only use the product in potentially explosive zones confirmed in the declaration of conformity.
WARNING
Improper use of the product!
▶Risk of severe injury or death.
▶Manufacturer liability and guarantee will be void.
●
Only use the product in accordance with the operating conditions specified in the contract documentation and this docu-
ment.
The GEMÜ 1242 is designed to be fitted to a GEMÜ valve in order to detect the position of linear actuators optically and elec-
trically. The product has a microprocessor controlled intelligent position sensor as well as an analogue travel sensor system
(potentiometer) and is connected in a force-locking way with the actuator spindle by means of a mounting kit (spring, operat-
ing bush). The valve end positions and the integrated travel sensor can be controlled via the electrical connections.
4.1
Product without special function X or Y
The product is not intended for use in potentially explosive areas.
4.2
Product with special function Y
The product with special function Y is UL/CSA certified and protected against explosion in accordance with ISA 12.12.01 (see
"Technical data").
The product with special function Y can be connected to switches, power supplies, PLC outputs and PLC inputs.
The energy supply must be equipped with a switch or an overcurrent protective device in the system. The switch or overcur-
rent protective device must be placed in a suitable and accessible position and also labelled as an isolating device for the
product with special function Y.
The product user is responsible for providing connections that comply with standards, a locking mechanism, cable compatibil-
ity and warning signs.
Suitable locking clips must be used to secure the circular connectors against becoming unintentionally loose or being
loosened without the use of tools
Installation, operation and servicing must only be carried out by qualified trained personnel.
Do not repair the device yourself if it is faulty. Instead, replace it with an equivalent new device. Repairs must only be carried
out by the manufacturer!
The device must only be used if its materials are resistant against mechanical and/or chemical influences or corrosion under
the respective operating conditions to such a sufficient degree that the explosion protection is not impaired or nullified.
Correct use
10 / 32
GEMÜ 1242
DeviceNet
Correct use
4.3
Product with special function X
The product with the special version X order option is intended for use in potentially explosive areas of zone 2 with gases,
mists or vapours and zone 22 with combustible dusts in accordance with EU directive 2014/34/EU (ATEX).
The product has the following explosion protection marking:
Gas:
II 3G Ex ec nC IIC T4 Gc X
Dust:
II 3D Ex tc IIIC T 80 °C Dc X
Type examination certificate: IBExU18ATEXB008 X
The product has been developed in compliance with the following harmonised standards:
–
DIN EN 60079-0:2012+A11:2013
–
DIN EN 60079-7:2015
–
DIN EN 60079-15:2010
–
DIN EN 60079-31:2014
Use of the product is permissible in the following ambient temperature ranges: 0 to +60 °C
For use in potentially explosive areas, the following conditions or operation limits must be observed:
Index X is applied to the ATEX marking.
The following special conditions must be complied with:
1. Connection cables and connectors must be protected from damage.
2. Layers of dust > 5 mm must be removed.
3. Warning label "Danger from electrostatic build-up".
4. Warning label "Do not disconnect when live".
The order data provide an overview of standard configurations.
Please check the availability before ordering. Other configurations available on request.
Note: A valve specific mounting kit is required for assembly. For designing the mounting kit, the valve type, nominal size, con-
trol function and actuator size must be stated.
Order codes
1 Type
Code
Electrical position indicator
1242
2 Fieldbus
Code
Without, 24 V version, with IO-Link
000
AS-Interface, 31 slaves, 4I/4O
A2
AS-Interface, 62 slaves, 4I/3O
A3
AS-Interface, 62 slaves, 8I/8O
A4
DeviceNet
DN
3 Accessory
Code
Accessory
Z
4 Housing material
Code
Stainless steel base, PC cover
07
Aluminium base, PC cover
14
5 Function
Code
Position feedback Open / Closed
00
6 Electrical connection
Code
M12 plug, 5-pin
01
M12 plug, 8-pin
02
7 Option
Code
Without
00
Inversed LED feedback
40
8 Switch
Code
Electronics
E0
9 Connection diagram
Code
M12 plug, 5-pin
01
M12 plug, 8-pin
02
10 Special version
Code
Without
NEC 500 and UL/CSA approval
Y
ATEX (2014/34/EU)
X
Order example
Order option
Code
Description
1 Type
1242
Electrical position indicator
2 Fieldbus
DN
DeviceNet
3 Accessory
Z
Accessory
4 Housing material
14
Aluminium base, PC cover
5 Function
00
Position feedback Open / Closed
6 Electrical connection
01
M12 plug, 5-pin
7 Option
00
Without
8 Switch
E0
Electronics
9 Connection diagram
01
M12 plug, 5-pin
10 Special version
Without
Order data
www.gemu-group.com
11 / 32
GEMÜ 1242
DeviceNet
www.gemu-group.com
11 / 32
GEMÜ 1242
DeviceNet
12 / 32
GEMÜ 1242
DeviceNet
Technical data
6
Technical data
6.1
Temperature
Ambient temperature:
0 to 60 °C
Storage temperature:
0 to 40 °C
6.2
Product compliance
EMC Directive:
2014/30/EU
DeviceNet
Interference emission
EN 61000-6-3
Interference resistance
EN 61000-6-2
Explosion protection:
ATEX (2014/34/EU), order code special version X
NEC 500 (ISA 12.12.01), order code for special version Y
ATEX marking:
Gas:
II 3G Ex ec nC IIC T4 Gc X
Dust:
II 3D Ex tc IIIC T 80 °C Dc X
Type examination certificate: IBExU18ATEXB008 X
NEC marking:
Class I, Division II, Groups C & D, T4
6.3
Mechanical data
Installation position:
Optional
Weight:
320 g (aluminium version)
600 g (stainless steel version)
Protection class:
IP 67
IP NEMA 4X (UL 61010-1, UL 50E), only available as special version code Y
IP64, only as special version code X
Travel sensor:
Minimum stroke:
2 mm
Maximum stroke:
46 mm
Hysteresis:
0.2 mm
Accuracy:
0.2 Full Scale
6.4
Electrical data
Supply voltage Uv:
11 to 25 V DC
Duty cycle:
Continuous duty
Reverse battery
protection:
yes
Current consumption:
typically 30 mA
Electrical connection
type:
1 x 5-pin M12 plug (A-coded)
13 / 32
GEMÜ 1242
DeviceNet
Switching characteristic:
100%
0%
td1
td1
td1
td2
td1
ta
t/ms
t/ms
t/ms
Stroke %
Switch point "Open"
Switching hysteresis
Switching hysteresis
Switching output "Open"
Switch point "Closed"
active
inactive
active
inactive
Switching output "Closed"
td1: Signal delay
td2: Signal delay
ta: Signal interval
Switch points: The data in percent refer to the programmed stroke, before each end position
Switch points:
Default setting switch point CLOSED
12 %
Default setting switch point OPEN
25 %
Min. switch point CLOSED
0.8 mm
Min. switch point OPEN
0.5 mm
If the percentage switch points dependent on the programmed stroke are smaller than the per-
missible min. switch points, the min. switch points apply automatically.
Electrical protection
class:
III
7
Dimensions
98
Ø57
X
13
16,6
47
WAF 20 for mounting kit M12x1,
x = 9 mm
WAF 24 for mounting kit M16x1,
x = 11 mm
dependent on valve used
Dimensions in mm
Dimensions
14 / 32
GEMÜ 1242
DeviceNet
Manufacturer's information
8
Manufacturer's information
8.1
Delivery
●
Check that all parts are present and check for any damage immediately upon receipt.
The product's performance is tested at the factory. The scope of delivery is apparent from the dispatch documents and the
design from the order number.
8.2
Packaging
The product is packed in a cardboard box which can be recycled as paper.
8.3
Transport
1. Only transport the product by suitable means. Do not drop. Handle carefully.
2. After the installation dispose of transport packing material according to relevant local or national disposal regulations /
environmental protection laws.
8.4
Storage
1. Store the product free from dust and moisture in its original packaging.
2. Avoid UV rays and direct sunlight.
3. Do not exceed the maximum storage temperature (see chapter "Technical data").
4. Do not store solvents, chemicals, acids, fuels or similar fluids in the same room as GEMÜ products and their spare parts.
9
Assembly and installation
NOTICE
●
Observe the data on the product labels, product documentation and the EC type examination certificate.
●
Connect cable carefully, do not damage individual wires.
●
Prepare the wire ends when connecting several cables or fine-wired cables.
●
Always attach wire end ferrule stops using pinch tools to achieve consistent quality.
●
Tighten all clamping points, even the ones not being used.
1. Observe the national regulations and provisions.
2. Observe the installer provisions.
3. Protect M12 plugs against electrostatic build-up.
4. Protect M12 plugs against damage.
5. Lay cables securely and protect them from damage.
6. Differential voltage for two intrinsically safe electric circuits: Maximum 30 V.
7. Connect open wire ends in a junction box with protection class IP20 and higher or outside the EX area.
15 / 32
GEMÜ 1242
DeviceNet
9.1
Preparations for assembly to the valve
1. Move the actuator A into zero position (actuator vented).
2. Remove optical position indicator 2 and / or protective cap 1 from the actuator top.
A
1
2
9.2
Mounting kit assembly
Item
Name
Item
Name
1
Spindle
7
Flange plate
2
Spring
8
Screws
3
Operating bush
9
Pressure disc*
4
Distance piece
10
O-ring*
5
O-ring
11
O-ring*
6
Adapter
* Included depending on version.
CAUTION
Pretensioned spring!
▶Damage to the device.
●
Slowly release the tension in the spring.
CAUTION
Do not scratch the spindle!
▶A damaged spindle surface may cause failure of the travel sensor.
1
4
1
2
3
1. Pull out the spindle 1.
2. Align the indentation of the distance piece 4 to the spring and push it over the
spindle 1 using the spring 2 and fix it in place using the operating bush 3.
Assembly and installation
16 / 32
GEMÜ 1242
DeviceNet
Assembly and installation
5
6
3. Tighten the operating bush 3 by turning it
clockwise.
4. Affix the O-ring 5 and the adapter 6.
7
8
5. Attach the flange plate 7
6. Screw the flange plate on tight using screws 8.
–
Push in the spindle until it pushes against the spring and then slowly release the pressure on the spring.
NOTICE
▶For some valves (e.g. GEMÜ 650 and GEMÜ 687) it is necessary to fit a pressure disc between the threaded adapter and
the actuator head. This is included in the required mounting kits, sometimes with an additional O-ring (only GEMÜ 650
with normally open and double-acting control function – code 2+3).
▶If the pressure disc does not have a groove for a seal, this will already be inserted in the groove provided at the adapter
opening of the actuator head (e.g. GEMÜ 687 with normally open control function – code 2).
9
6
11
10
Insert the O-ring 11 (if included) into the corresponding groove
on the adapter 6.
If included: Push the pressure disc 9 over the adapter 6 and
insert the O-ring 10 in the intended groove of the pressure
disc.
17 / 32
GEMÜ 1242
DeviceNet
9.3
Assembling the adapter (linear actuator)
With some mounting kits it is necessary to install an adapter as well. This adapter is enclosed with the required mounting kits.
Valves with a normally open and double acting control function (code 2+3) also include additional O-rings (1+2).
1
3
2
1. Move the actuator to the closed position.
2. Place O-rings 1 and 2 into adapter 3.
3. Screw adapter 3 into the actuator opening as far as it will go and tighten.
9.4
Assembling the stroke limiter (linear actuator)
5
5
4
3
2
1
6
8
9
7.1
7.2
Option1
Option2
1. Screw distance piece 5 onto/into actuator spindle
6.
2. Move the actuator to the closed position.
3. Insert the O-ring 7.1 in the stroke limiter 1.
4. Insert the O-ring 7.2 in the washer 4.
5. Screw stroke limiter 1 with nut 2, seal 3 and washer
4 into the actuator opening.
6. Set stroke limiter 1 to the required stroke.
7. Make sure that the minimum stroke is reached.
8. Secure stroke limiter 1 with nut 2.
Key
1
Stroke limiter
7.1 1)
7.2 1)
O-ring
2
Nut
8
Protective cap
3 1)
Seal
9
Position indicator
4 1)
Disc
10
Operating bush
5 2)
Distance piece
11
Spindle
6
Actuator spindle
12
Travel sensor
1)
Only available for valves with the NO and DA control functions.
2)
Only included in required mounting kits. The design depends on the valve.
9.5
Assembling and installing the electrical position indicator
DANGER
Danger of explosion
▶Danger of death or severe injury.
●
Do not use the product as a step or foothold.
●
Prior to commissioning, ensure that the cover is fully closed and that the housing and the O-ring are not
damaged.
Assembly and installation
18 / 32
GEMÜ 1242
DeviceNet
Assembly and installation
1. Move the actuator to the open position.
2. Place the product as far as it will go into the actuator opening, insert adapter 3 (see chapter 9.3) or stroke limiter 1 (see
chapter 9.4) and screw in clockwise against the initial spring tension.
3. Use the spanner flat of the travel sensor to tighten the product.
4. Turn the housing clockwise to align the pneumatic or electrical connections.
CAUTION
Incorrect installation of the product.
▶Damage to the housing.
●
Only tighten the product using the spanner flats provided for this purpose.
5. The product with mounting kit is fully assembled.
6. The product with mounting kit and adapter is fully assembled.
19 / 32
GEMÜ 1242
DeviceNet
7. The product with mounting kit and stroke limiter is fully assembled.
10 Electrical connection
10.1 Potential equalisation – special function X and Y
Connecting the potential equalisation device
1. Use a screw M4x6 to attach the potential equalisation device to the electrical position indicator.
ð Potential equalisation for metal housings in potentially explosive areas: Minimum 4 mm².
2. Secure the connection against working itself loose.
Electrical connection
20 / 32
GEMÜ 1242
DeviceNet
Electrical connection
10.2 DeviceNet, ordering option Fieldbus, code DN
DANGER
Danger of explosion!
▶Risk of injury or death!
●
Do not connect or disconnect the device until the power has been switched off or the area has been classi-
fied as non-hazardous.
●
The standard version of the product (without special function X or Y) must not be used in potentially explos-
ive zones.
DANGER
Danger of explosion due to sparking
▶Risk of severe injury or death.
●
Never disconnect the connection cables when live.
10.2.1 Net topology - DeviceNet system
To avoid malfunction the trunk cable is fitted with resistors on both sides. The drop cables do not require bus ends.
V+
V-
CAN_H
120 Ω
1/4 W
CAN_L
Shield
Protective
earth
Protective
earth
Drop cable
120 Ω
1/4 W
Trunk cable
Maximum cable length
Baud rate [kBaud]
Trunk cable
Drop cable
Thick cable
Thin cable
Max. cable length per
drop cable
Max. drop cable accu-
mulated length
125
500 m
100 m
6 m
156 m
250
250 m
100 m
6 m
78 m
500
100 m
100 m
6 m
39 m
21 / 32
GEMÜ 1242
DeviceNet
10.2.2 Pin assignment
1
4
3
2
5
Pin
Signal name
1
Shield
2
V+
3
V-
4
CAN_H
5
CAN_L
10.2.3 Electrical connection
1. Connect the product in accordance with the pin assignment.
For electrical connection, we recommend the M12 connectors for EX areas from IFM, series EVCxxA.
The M12 plugs may only be assembled, connected and commissioned by trained personnel. The trained personnel must have
expertise in types of ignition protection, and regulations and provisions for operating media in EX areas.
2. Securely lay the connection cables or ensure sufficient tension relief.
3. Refer to the technical data and cable gland documentation for details of the wire cross sections.
4. Protect the product and the cables from damage.
5. Only clean the product with an anti-static or damp cloth.
6. Only operate the product when it is fully assembled.
Electrical connection
22 / 32
GEMÜ 1242
DeviceNet
Programming the end positions
11 Programming the end positions
The end positions must be programmed under the following conditions:
–
Retrofitting an electrical position indicator
–
Replacing the actuator
–
Replacing the diaphragm
If electrical position indicators have been fitted to the process valve at the factory, the end positions will already have been
programmed.
The end positions can be programmed as follows:
–
On-site programming
–
Communication interface
When programming via the communication interface, automatic programming is recommended.
11.1 On-site end position programming
1
1. Connect supply voltage.
2. Briefly (>100 ms) hold a magnet (e.g. 1242000ZMA) to the position marked PROG 1 on the housing cover.
ð OPEN and CLOSED LEDs flash alternately
ð High visibility LED flashes alternately green / orange
3. Open valve until end position is reached.
4. Close valve until end position is reached.
5. Programming mode is automatically terminated if the valve does not move for 5 seconds.
ð The end positions are set.
11.2 End position programming via DeviceNet
Automatic programming mode:
1. Briefly (>100 ms) set output bit 6 = 1. (automatic programming mode)
2. Set output bit 6 = 0.
3. Open valve until end position is reached.
4. Close valve until end position is reached.
5. Programming mode is automatically terminated if the valve does not move for 5 seconds.
ð The end positions are set.
Manual programming mode:
6. Set output bit 5 =1. (manual programming mode)
7. Open valve until end position is reached.
8. Close valve until end position is reached.
9. Set output bit 5 = 0. (electrical position indicator in normal operation)
ð The end positions are set.
23 / 32
GEMÜ 1242
DeviceNet
12 Specific data - DeviceNet
Communication modes:
Function, Polling, Change of state, Cyclic, Bit strobe
Identity
Class
Inst.
Attr.
Function
Value
1h
1h
1h
Vendor ID
869
2h
Product Type
43
3h
Product Code
1242
4h
Rev.
2.2 1)
5h
Status
Device status according to DeviceNet specifications
6h
Series No.
Continuous serial number
7h
Name
1242 DN position indicator
1)
Use EDS file in accordance with revision status of the device
Note: Download EDS files from www.gemu-group.com
12.1 Inputs
Bit
Default
Designation
Function
Logic
0, 1
not used
2
0
Programmingmode Operating mode
0 = normal operation
1 = programming mode
3
0
Position Closed
CLOSED position
0 = process valve not in CLOSED position
1 = process valve in CLOSED position
4
0
Position Open
OPEN position
0 = process valve not in OPEN position
1 = process valve in OPEN position
5
0
Calibrationmode
Calibration mode
0 = normal operation
1 = calibration mode
6
0
Global warnings
Warning
0 = warning not active
1 = warning active
7
0
Global errors
Error
0 = error not active
1 = error active
As seen from the DeviceNet master, Class 64h, Inst. 1h, Attr. 1h
12.2 Outputs
Bit
Default
Designation
Function
Logic
0 … 2 not used
3
0
Location function
Location function
0 = location function not active
1 = location function active
4
not used
5
0
Manual
programming
Manual programming mode
0 = manual programming mode not
active
1 = manual programming mode active
6
0
Automatic
programming
Automatic programming mode:
0 = automatic programming mode not
active
1 = automatic programming mode active
7
not used
As seen from the DeviceNet master, Class 64h, Inst. 1h, Attr. 1h
Specific data - DeviceNet
24 / 32
GEMÜ 1242
DeviceNet
Specific data - DeviceNet
12.3 Parameter
Class
Inst.
Attr.
Parameter
Lengt
h
Data
type
Ac-
cess
Stand-
ard
value
Value range
Fh
1h
1h
Inversion of LED colours
1 byte
Boolean
Get/Set 0
0 = standard
1 = inversed
Fh
2h
1h
Inversion of signals
1 byte
Boolean
Get/Set 0
0 = standard
1 = inversed
Fh
3h
1h
Function of high visibility
1 byte
USINT
Get/Set 3
0 = OFF
1 = 33 %
2 = 66 %
3 = 100 %
4 = Closed 100%; Open OFF
5 = Closed OFF; Open 100%
Fh
4h
1h
On site programming
1 byte
Boolean
Get/Set 0
0 = enabled
1 = disabled
Fh
5h
1h
Switch Point OPEN request
1 byte
USINT
Get/Set 25
3 % – 97 %
Fh
6h
1h
Switch Point OPEN real
1 byte
USINT
Get
0
Display of values 0 % – 100 %
Fh
7h
1h
Switch Point CLOSED request
1 byte
USINT
Get/Set 12
3 % – 97 %
Fh
8h
1h
Switch Point CLOSED real
1 byte
USINT
Get
0
Display of values 0 % – 100 %
Fh
9h
1h
Alarm stroke reduction OPEN
1 byte
USINT
Get/Set 1
0 = disabled
1 = 25 %
2 = 50 %
3 = 75 %
Fh
Ah
1h
Alarm stroke reduction
CLOSED
1 byte
USINT
Get/Set 1
0 = disabled
1 = 25 %
2 = 50 %
3 = 75 %
Fh
Bh
1h
Alarm opening time
1 byte
USINT
Get/Set 0
0 - 255 (0 = off)
Fh
Ch
1h
Alarm closing time
1 byte
USINT
Get/Set 0
0 - 255 (0 = off)
Fh
Fh
1h
Programmed position OPEN
2 byte
UINT
Get
0
Display of numerical values 0 -
4092
Fh
10h
1h
Programmed position CLOSED 2 byte
UINT
Get
0
Display of numerical values 0 -
4092
Fh
11h
1h
Programmed stroke
2 byte
UINT
Get
0
Display of numerical values 0 -
4092
Fh
12h
1h
Last position OPEN
2 byte
UINT
Get
0
Display of numerical values 0 -
4092
Fh
13h
1h
Last position CLOSED
2 byte
UINT
Get
0
Display of numerical values 0 -
4092
Fh
14h
1h
Last stroke
2 byte
UINT
Get
0
Display of numerical values 0 -
4092
Fh
15h
1h
Valve position
2 byte
UINT
Get
0
Display of numerical values 0 -
4092
Fh
16h
1h
Sensor error
1 byte
USINT
Get
0
0 = Sensor OK
1 = Sensor error position
closed
2 = Sensor error position open
25 / 32
GEMÜ 1242
DeviceNet
Class
Inst.
Attr.
Parameter
Lengt
h
Data
type
Ac-
cess
Stand-
ard
value
Value range
Fh
17h
1h
Programming error
1 byte
USINT
Get
1
0 = Programming OK
1 = not calibrated
2 = no stroke
3 = stroke < min. stroke
4 = Sensor error position
closed
5 = Sensor error position open
6 = Sensor error position
closed + open
Fh
19h
1h
Internal error
1 byte
USINT
Get
0
0 = Device OK
1 = un-valid crc-check
2 = un-valid serial number
3 = Memory error
Fh
1Ah
1h
Stroke reduction warning
1 byte
USINT
Get
0
0 = Stroke OK
1 = Stroke reduction position
closed
2 = Stroke reduction position
open
3 = Stroke reduction position
closed + open
Fh
1Bh
1h
Valve cycles user
4 byte
UDINT
Get/Set 0
Resettable to 0,
display of numerical values 0 -
429496729
Fh
1Ch
1h
Valve cycles total
4 byte
UDINT
Get
0
Display of numerical values 0 -
429496729
Specific data - DeviceNet
13 Error clearance
13.1 LED error message
Function
CLOSED
ERROR
OPEN
Programming error
No stroke
Stroke < min. stroke
After sensor error
OPEN / CLOSED flash alternately
Sensor error
OPEN position
CLOSED position
Pneumatic fault
OPEN position
CLOSED position
Mid position
Supply voltage too low
Internal error
OPEN / CLOSED flash simultaneously
13.2 Error clearance
Error
Error cause
Error clearance
Programming error no stroke
No mounting kit available
Check the mounting kit, re-programme
Process valve faulty
Replace process valve, re-programme
Programming error stroke < min. stroke
Minimum stroke was not reached (e.g.
due to stroke limiter)
Ensure minimum stroke, re-programme
Shut off diaphragm compressed too
much (diaphragm size 8)
Ensure correct compression of the shut
off diaphragm, re-programme
Programming error after sensor error
The sensor range was exceeded during
the programming procedure. Currently
the process valve is in the valid sensor
range.
Check the mounting kit, re-programme.
Note the maximum stroke (see
"Technical data")
Sensor error CLOSED or OPEN position
Sensor limit exceeded
Check the mounting kit, re-programme.
Note the maximum stroke (see
"Technical data")
Sensor error CLOSED position
Sensor limit in CLOSED position
exceeded
Check the mounting kit, re-programme.
Note the maximum stroke (see
"Technical data")
Supply voltage too low
Supply voltage < 18 V DC
Ensure supply voltage (see "Technical
data")
Internal error
Memory error
Re-programme
The spring locks during installation
Mounting kit too long
Contact GEMÜ
Error clearance
www.gemu-group.com
26 / 32
GEMÜ 1242
DeviceNet
27 / 32
GEMÜ 1242
DeviceNet
14 Inspection and servicing
NOTICE
Exceptional maintenance work!
▶Damage to the GEMÜ product.
●
Any maintenance work and repairs not described in these operating instructions must not be performed without consult-
ing the manufacturer first.
The operator must carry out regular visual examination of the products depending on the operating conditions and the poten-
tial danger in order to prevent leakage and damage.
1. Have servicing and maintenance work performed by trained personnel.
2. Wear appropriate protective gear as specified in plant operator's guidelines.
3. Shut off plant or plant component.
4. Secure plant or plant component against recommissioning.
5. Depressurize the plant or plant component.
6. Actuate products which are always in the same position four times a year.
7. Carry out inspection and servicing for products in the potentially explosive area to DIN EN 60079-17.
14.1 Spare parts
No spare parts are available for this product. If it is faulty, please return it to GEMÜ for repair.
14.2 Cleaning the product
DANGER
Danger of explosion due to electrostatic build-up
▶Danger of death or severe injury.
●
Only clean the product with an anti-static or damp cloth.
–
Do not clean the product with a high pressure cleaning device.
15 Disassembly
1. Disassemble in reverse order to assembly.
2. Unscrew the electrical wiring.
3. Disassemble the product. Observe warning notes and safety information.
16 Disposal
1. Pay attention to adhered residual material and gas diffusion from penetrated media.
2. Dispose of all parts in accordance with the disposal regulations/environmental protection laws.
17 Returns
Legal regulations for the protection of the environment and personnel require that the completed and signed return delivery
note is included with the dispatch documents. Returned goods can be processed only when this note is completed. If no return
delivery note is included with the product, GEMÜ cannot process credits or repair work but will dispose of the goods at the op-
erator's expense.
1. Clean the product.
2. Request a return delivery note from GEMÜ.
3. Complete the return delivery note.
4. Send the product with a completed return delivery note to GEMÜ.
Returns
18 Declaration of conformity according to 2014/30/EU (EMC Directive)
EU Declaration of Conformity
according to 2014/30/EU (EMC Directive)
We,
GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG
Fritz-Müller-Straße 6-8
74653 Ingelfingen-Criesbach, Germany
declare that the product listed below complies with the safety requirements of the EMC Directive 2014/30/EU.
Description of the product:
GEMÜ 1242
Technical standards used:
–
Interference resistance:
24 V DC, IO-Link, DeviceNet: EN 61000-6-2
AS-Interface: acc. to AS-Interface Spec. 3.0
–
Interference emission:
24 V DC, IO-Link, DeviceNet: EN 61000-6-3
AS-Interface: acc. to AS-Interface Spec. 3.0
Ingelfingen-Criesbach 29-05-2018
Joachim Brien
Head of Technical Department
www.gemu-group.com
28 / 32
GEMÜ 1242
DeviceNet
Declaration of conformity according to 2014/30/EU (EMC Directive)
19 Declaration of conformity in accordance with 2014/34/EU (ATEX)
EU Declaration of Conformity
in accordance with 2014/34/EU (ATEX)
We,
GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG
Fritz-Müller-Straße 6-8
74653 Ingelfingen-Criesbach, Germany
declare that the product listed below complies with the requirements of directive 2014/34/EU for intended use in potentially
explosive areas.
Description of the product:
Electrical position indicator GEMÜ 1242
Explosion protection marking:
Gas:
II 3G Ex ec nC IIC T4 Gc X
Dust:
II 3D Ex tc IIIC T 80 °C Dc X
Type examination certificate: IBExU18ATEXB008 X
Explanations:
For special conditions or operation limits see chapter "Correct use" in the operating
instructions.
The Essential Safety and Health Requirements are met by compliance with the standards listed below that are applicable for
the above mentioned product:
–
DIN EN 60079-0:2012+A11:2013
–
DIN EN 60079-7:2015
–
DIN EN 60079-15:2010
–
DIN EN 60079-31:2014
Ingelfingen-Criesbach 29-05-2018
Joachim Brien
Head of Technical Department
GEMÜ 1242
DeviceNet
www.gemu-group.com
29 / 32
Declaration of conformity in accordance with 2014/34/EU (ATEX)
GEMÜ Gebr. Müller Apparatebau GmbH & Co. KG
Fritz-Müller-Straße 6-8, 74653 Ingelfingen-Criesbach,
Germany
Tel. +49 (0)7940 123-0 · [email protected]
www.gemu-group.com
Subject to alteration
04.2019 | 88585870