SICK GRTB18SV Operating Instruction
Text of SICK GRTB18SV Operating Instruction
O P E R A T I N G I N S T R U C T I O N
GRTB18(S)V
Cylindrical photoelectric sensors
en, de, fr, pt, it, es, zh, ja, ru
O P E R A T I N G I N S T R U C T I O N S
GRTB18(S)V
Cylindrical photoelectric sensors
de
en
es
fr
it
ja
pt
ru
zh
This work is protected by copyright. Any rights derived from the copyright shall be
reserved for SICK AG. Reproduction of this document or parts of this document is only
permissible within the limits of the legal determination of Copyright Law. Any modifica‐
tion, abridgment or translation of this docu
Operating and status indicators......................................................
5
4
Mounting.............................................................................................
6
5
Electrical installation.......................
SICK GRTB18SV Read the operating instructions before commissioning.
■
Connection, mounting, and setting may only be performed by skilled per‐
son.
■
Not a safety component in accordance with the EU Machinery Directive.
■
Power supply: Class 2
Enclosure type 1
■
When commissioning, protect the device from moisture and contamination.
■
These operating instructions contain information required during the life cycle of
the sensor.
2
Intended
SICK GRTB18SV Figure 5: Long variant, connect‐
ing cable
73.4 (2.89)
49.3 (1.94)
M18x1
2
3
5
M12x1
1
4
(0.16)
12.9
(0.51)
6
8
7
M18x1
25°
4.7 (0.19)
0.6
(0.02)
Figure 6: Long variant, M12
male connector
73.3 (2.89)
49.3 (1.94)
45.3 (1.78)
4
(0.16)
12.9
(0.51)
M18x1
2
3
4
5
1
6
8
7
M18x1
25°
4.7 (0.19)
0.6
(0.02)
Figure 7: Long variant, potenti‐
ometer, connecting cabl
max. 90 Nm
Note the sensor’s maximum permissible tightening torque of 90 Nm.
Note the preferred direction of the object relative to the sensor, cf. table 1.
5
Electrical installation
The sensors must be connected in a voltage-free state (UV = 0 V). The following informa‐
tion must be observed, depending on the connection type:
–
Male connector connection: pin assignment
–
Cable: wire color
Only apply voltage/switch on the voltage supply (UV > 0 V)
Table 3: DC
PNP: Q (≤ 100 mA)
+ (L+)
Q
– (M)
+ (L+)
Q
– (M)
NPN: Q (≤ 100 mA)
+ (L+)
Q
– (M)
+ (L+)
Q
– (M)
PNP: Q (≤ 100 mA)
+ (L+)
Q
– (M)
+ (L+)
Q
– (M)
NPN: Q (≤ 100 mA)
+ (L+)
Q
– (M)
+ (L+)
Q
– (M)
6
Commissioning
1
Alignment
Align the sensor with the object. Select the position so that the red emitted light beam hits
the center of the object. You must ensure that the optical opening (front screen) of the sen‐
sor is complet
Check the application conditions: Adjust the sensing range and distance to the object or
background and the remission capability of the object according to the corresponding dia‐
gram [see figure 10] (x = sensing range, y = monitored area between the set sensing range
and background suppression as a % of the sensing range (object remission/background
remission)). Remission: 6% = black 1, 18% = gray 2, 90% = white 3 (referring to stand‐
ard white as per
SICK GRTB18SV The sensor is adjusted and ready for operation.
Figure 11: Detection
7
Troubleshooting
The Troubleshooting table indicates which measures are to be taken if the sensor stops
working.
7.1
Troubleshooting table
Table 5: Troubleshooting
LED indicator/fault pattern
Cause
Measures
Green LED does not light up
No voltage or voltage below
the limit values
Check the power supply,
check all electrical connec‐
tions (cables and plug connec‐
tions)
Green LED does
LED indicator/fault pattern
Cause
Measures
sensing range and adjust if
necessary, see figure 10,
page 9
Yellow LED lights up, no object
in the path of the beam
Distance between the sensor
and the background is too
short
Reduce the sensing range,
see figure 10
Object is in the path of the
beam, yellow LED does not
light up
Distance between the sensor
and the object is too long or
sensing range is set too short
increase the sensing range,
take note of the di
3 ... 300 mm
3 ... 100 mm
3 ... 200 mm
Sensing range max.
3 ... 300 mm1
3 ... 100 mm1
3 ... 200 mm1
Possibility of setting
Potentiometer
No possibility of
setting
No possibility of
setting
Light spot diameter/distance
7 mm / 100 mm
7 mm / 100 mm
7 mm / 100 mm
Supply voltage VS
DC 10 ... 30 V2
DC 10 ... 30 V2
DC 10 ... 30 V2
Output current Imax.
100 mA
100 mA
100 mA
Dieses Werk ist urheberrechtlich geschützt. Die dadurch begründeten Rechte bleiben
bei der Firma SICK AG. Die Vervielfältigung des Werks oder von Teilen dieses Werks ist
nur in den Grenzen der gesetzlichen Bestimmungen des Urheberrechtsgesetzes zuläs‐
sig. Jede Änderung, Kürzung oder Über
Bedien- und Anzeigeelemente........................................................
16
14
Montage.............................................................................................. 17
15
Elektronische Installation..........................................
Vor der Inbetriebnahme die Betriebsanleitung lesen.
■
Anschluss, Montage und Einstellung nur durch Fachpersonal.
■
Kein Sicherheitsbauteil gemäß EU-Maschinenrichtlinie.
■
Power supply: Class 2
Enclosure type 1
■
Gerät bei Inbetriebnahme vor Feuchte und Verunreinigung schützen.
■
Diese Betriebsanleitung enthält Informationen, die während des Lebenszyklus des
Sensors notwendig sind.
12
Bestimmungsgemäße Verwendun
Abbildung 16: Langbauform,
Anschlussleitung
73.4 (2.89)
49.3 (1.94)
M18x1
2
3
5
M12x1
1
4
(0.16)
12.9
(0.51)
6
8
7
M18x1
25°
4.7 (0.19)
0.6
(0.02)
Abbildung 17: Langbauform,
Stecker M12
73.3 (2.89)
49.3 (1.94)
45.3 (1.78)
4
(0.16)
12.9
(0.51)
M18x1
2
3
4
5
1
6
8
7
M18x1
25°
4.7 (0.19)
0.6
(0.02)
Abbildung 18: Langbauform,
Poti, Anschlussleitung
73.4 (2.89)
4