Condair Mk5 Installation And Operating Instructions Manual
Read Online
Read the Condair Mk5 Installation And Operating Instructions Manual online using the built-in PDF viewer.
Key Pages of Document
4 1.2 Notes on the installation and operating instructions 4 2 For your safety 5 3 Product overview 6 3.1 Unit types 6 3.2 Standard delivery 7 3.3� Humidification�system�overview� 8 3.4� Steam�humidifier�construction� 8 3.5 Functional description 9 4 Basic planning 10 4.1 Selecting the unit 10 4.2 Selecting the control system 13 4.3 Options 15 4.4 Accessories 16 4.4.1� Accessories�ov ...
the versions: “Visual” and “Process”.�The�various�accessories�(humidistats,�water�filter,�etc.)�are�only� described insofar as this is necessary for proper operation of the equipment. Further information on accessories can be obtained in the respective instructions. These installation and operating instructio ...
Intended use Steam�humidifiers�Condair�Mk5�are�intended�exclusively�for�direct or indirect room hu- midification or for humidification in laboratory and process applications within�the� specified�operating�conditions.�Any�other�type�of�application,�without�the�written�consent� of�your�supplier,�is�considered�as�not�conforming�with�the�intended�purpose.�The�manu- factu ...
– Visual For�direct�or�indirect�room�air�humidification�with�standard requirements for control precision. – Process For�direct�or�indirect�room�air�humidification�in�laboratory and process appli cations�where�there� are increased requirements for control precision. Basically,�the�devices�of� ...
� –�Operation�with�fully�demineralized�water�(without�lime�collector�tank) ...
� 1� Steam�humidifier 2 Electrical connections 3 Water drainage � 4� Lime�collector�tank�(only�on�units�for�operation� with untreated drinking water) 5 Filter valve (accessory “Z261”) 6 Water supply (building side) 7 Fan unit (accessory “FAN..”) 8 Condensate hose (accessory “KS10”) 9 Steam hose (accessory “Z10”) 10 Steam distribution pipe (accessory “81–...”) 3.4 S ...
9 3.5 Functional description The�Condair�Mk5�steam�humidifier�is�an�unpressurized�steam�generator.�It�operates�on�the�resistance� heating�principle�and�is�designed�for�direct�(with�fan�unit)�and�indirect�(with�steam�distribution�pipe)� room�air�humidification�in�venti�lating�and�air-conditioning�systems.�In�conjunction�with�a�“Process”�steam� distribution�pipe ...
The�selection�of�the�unit�is�reflected�in�the�type�description: 1. Application 2.� Supply�water�quality 3.� Required�maximum�steam�capacity 4. Required heating voltage 1. Application The�type�series�can�b ...
The�maximum�required�steam�capacity�is�calculated�from�the�following�formulas: V • ρ mD = • (x2 - x1) 1000 V� � mD = • (x2 - x1) 1000 • ε mD:� maximum�steam�demand�in�kg/h V: volume of supply air portion per hour in m3/h�(for�indirect�room�humidification)�or�room�volume�to� be�humidified�per�hour�in�m3/h�(for�direct�room�hum ...
Heating voltage The�Condair�Mk5�steam�humidifiers�are�available�with�various�heating�voltages.�The�maximum� achievable�steam�capacity�and�the�power�consumption�are�directly�dependent�on�the�selected� heating�voltage�(see�table). 400 V/3~ 220 V/3~ 415 V/3~ 240 V/1N~ 230 V/1N~ 200 V/3~ 50...60 Hz 50...60 Hz 50...60 Hz 50...60 Hz 50...60 Hz 50...60 Hz Condair Mk5 V ...
The various control systems – System 1: Room humidity control System 1 is suited for direct room humidification and air conditioning systems with mainly recirculated air. The humidity sensor or humidistat respectively is preferably located in the room itself�or�in�the�exhaust�air�duct. A1 humidity sensor B1 ventilation interlock B2� airflow�monitor B3� safety�humidistat B4 humidistat PII internal co ...
Supply air humidity control (humidity sensor installed in supply air duct) should be used only where room humidity control is impracticable for technical reasons.�Such�systems�always� require�a�PI-controller.�The�humidity�sensor�(A1)�is�located�in�the�supply�air�duct�after�the�steam� distribution pipe. A1 humidity sensor B1 ventilation interlock B2� airflow�monitor B ...
5...16 20...40 50...80 5...16 20...40 50...80 Interface RS232/RS485 (Interface� PCB� RS232/RS485� for� data� exchange with a building control system) RS number 1 1 1 1 1 1 Remote operating and fault indication (PCB�with�relay�con ...
5...16 20...40 50...80 5...16 20...40 50...80 Steam distribution pipe (see accessory details in chapter 4.4.2) 81-... number 1 2 1 2 Steam distribution pipe Process (see accessory details in chapter 4.4.2) Z ...
The steam distribution pipes are selected on the basis of the duct width�(for�horizontal�installation)�or� the duct height�(for�vertical�installation)�and�the�capacity�of�the�steam�humidifier. Important!�Always�select�the�longest�possible�steam�distribution�pipe�(opti�mum�humidification�dis- tance). 4.4.2 Accessory details Steam distrib ...
The�OptiSorp�steam�distribution�system�is�used�in�ventilation�ducts�where�only�a�short�humidification� distance�is�available�(see�chapter�5.3.1�for�calculation�of�humidification�distance).�Duct�dimensions� should�be�given�when�ordering.�Please�note�the�following�data�for�this: OptiSorp Number of steam connections max. steam capacity in kg/h ...
In�addition�to�the�selection�of�the�steam�humidifier,�the�accessories�and�the�options,�other�points�should� be�considered�during�planning.�Please�note�the�information�in�the�following�chapters: –� Unit�fitting�(see�chapter�5.2) –� Steam�installation�(see�chapter�5.3) –� Water�installation�(see�chapter�5.4) –� Electric�in ...
5.1 Safety instructions for mounting and installation works –� All�mounting�and�installation�work�must�be�performed�only by adequately qualified personnel.�Ascertaining�the�qualifications�is�the�customer‘s�responsibility. –� All�local�regulations�relating�to�the�execution�of�the�respective�installation�work�(Water,� steam�and�electrical�installation ...